FP0H Upgrade Tool Operation Manual

- Applicable models:
FP0H C32T/P
FP0H C32ET/EP

Panasonic Industrial Devices SUNX Co.,Ltd.


Table of contents

Table of contents

1. How to Operate FP0H Upgrade Tool ................................ 1-1

1.1 How to Activate Upgrade Tool ............................................................... 1-2

1.2 Advance Preparation for Upgrade Tool.................................................. 1-3

1.3 Communication Settings/Upgrade Mode Select ..................................... 1-5

1.4 Upgrade Mode Check ............................................................................ 1-8

1.5 Upgrade ................................................................................................ 1-9

1.6 Finish................................................................................................... 1-11

2. List of Error Messages .................................................... 2-12

2.1 Solution for Each Error Message ......................................................... 2-14

ii
1
How to Operate FP0H Upgrade
Tool
Table of contents

1.1 How to Activate Upgrade Tool


 How to start
1. Unzip the file (FP0H_Vxxxx_en.zip) downloaded to a PC into a desired area.
The following four files and one folder will be decompressed.
File name Content
Fp0h_Vxxxx_VupTool.exe : Upgrade tool startup module
Fp0h_Vxxxx_Vup.dll : Upgrade tool FP0H DLL file
Fp0h_V1_en.dll : Resource DLL file
Fp0h_V1_Manual_en.pdf : Operation Manual PDF file
Fp0h_EDS : FP0H EDS File folder

2. Execute the upgrade tool startup module (Fp0h_Vxxxx_VupTool.exe).

1.2 The upgrade tool will be activated.

1-2
Table of contents

1.2 Advance Preparation for Upgrade Tool


 Advance preparation
1. Confirming applicable models: Confirm if the FP0H you use is the applicable model
for this tool.
- Applicable models: FP0H C32T/P
FP0H C32ET/EP
2. Open the cover and change the switch on the FP0H to PROG. mode.

3. Turn on the power to the FP0H and connect the USB cable to a PC. *

* Do not connect more than one FP0H to one PC.


System requirements: OS (WindowsXP SP3, Vista SP2, Windows7 SP1 or later, Windows8,
Windows10)
4. When FPWIN GR7 is active, set it to offline.

1-3
Table of contents

 Advance preparation (Continuation of the above section)

After confirming the advance preparation (1 to 4), click the "Next" button.

Description of functions
Confirm in advance on this screen.

- Update program version: Indicates the update version made with this application.
The update version varies according to a provided update tool. (Screen sample: Ver.3.03)
When the version of the FP0H you use is the same, it is not necessary to update it.
- See here for the list of supported models and manuals.: This manual is displayed.

"Abort" button: Aborts and exits this application.


"Next" button: Goes to 1.3 Communication Settings/Upgrade Mode Select

1-4
Table of contents

1.3 Communication Settings/Upgrade Mode Select


 Communication settings/Upgrade mode select

Description of functions
The USB port setting and switching to the upgrade mode is made on this screen.
After selecting a USB port and the mode selection button, click the "Next" button.
- Communication settings
Select the USB port connected with the FP0H. *1, 2.
*1. When the USB port is automatically selected in the initial display, the USB port is
recognized correctly, so the selection is not necessary.
(When more than one FP0H is connected, make only one connection available by turning off
the power to the rest of the FP0H units or remove the cables.)
*2. When the USB is not selected in the initial display;
As the FP0H is not recognized, reinsert the USB cable after turning on the power, and
press the "Update" button. (The USB port will be redisplayed.)
- Upgrade mode select
Compare the LED display on the FP0H to the screen, and select the operation mode.
Normal mode: PROG. is on.  To Upgrade mode select *3
Upgrade mode: RUN and PROG. flashes alternately.  Upgrade
*3. Note: The FP0H may be locked if "Normal mode" is selected in the upgrade mode. (In
this case, the FP0H must be rebooted.)

1-5
Table of contents

 Communication settings/Upgrade mode select (Continuation of the above section)


By clicking "Next" when "Normal mode" is selected, the connected PLC model and the
version of the update program will be displayed.

When clicking "Cancel";


Returns to 1.3 Communication Settings/Upgrade Mode Select.
When clicking "OK";
Starts switching to the upgrade mode.

1-6
Table of contents

 Communication settings/Upgrade mode select (Continuation of the above section)


By clicking "Next" when "Normal mode" is selected, changing the mode to the upgrade
mode will start.
(After a short time, the screen will change to "Upgrade mode confirmation screen".)

(The screen will change after a short time.)

Goes to 1.4 Upgrade Mode Check.

1-7
Table of contents

1.4 Upgrade Mode Check


 Upgrade mode check

Description of functions
Check if the mode has been changed from normal mode to upgrade mode on this screen.
After checking that the LED display on the FP0H flashes just like the animation on the screen,
check the checkbox and click the "Next" button.
- Upgrade mode select confirmation (After check)

Goes to 1.5 Upgrade.

1-8
Table of contents

1.5 Upgrade
 Upgrade

Description of functions
Confirm the current program version and execute the upgrade on this screen.
When selecting the upgrade mode in Communication settings/Upgrade mode select, the
current model and program version is not displayed.
(Display example: C32ET/C32EP Ver.1.00  Ver.1.10)
After the confirmation, click the "Next" button.

 Confirmation of starting the upgrade.

Confirm the message and click the "Yes" button. *


* The subsequent operation cannot be aborted. (Proceed with the operation carefully.)

Goes to Upgrade (Start to End)

1-9
Table of contents

 Upgrade (Start to End)

The screen message changes as follows according to the progress.


(1) "Version will be upgraded. Do not turn off the power during updating."
 (Waiting for starting the upgrade)
(2) "Update data is being transferred. Please do not turn off the power and wait."
 (FP0H is transferring data.)
(3) "Firmware is being rewritten. Please do not turn off the power and wait."
 (FP0H is rewriting the firmware.)
(4) "Upgrade verification in progress"
 (FP0H is waiting for reboot and confirming the version.)
Completed.

Click the "OK" button to go to 1.6 Finish.

1-10
Table of contents

1.6 Finish
 Finish

Description of functions
The upgrade operation has been completed. Click the "Finish" button to finish the operation.

For upgrade another FP0H, click the "Back to Beginning" button.


Goes to 1.2 Advance Preparation.

1-11
Table of contents

2
2 List of Error Messages

2-12
Table of contents

List of error and warning messages

Error title name Screen Cause


1) Connection error Communication USB connection
settings/Upgrade error
mode select
2) Connection error Communication USB is being used.
settings/Upgrade
mode select
3) Version upgrade not supported Communication Unsupported model
settings/Upgrade
mode select
4) Latest version Communication The latest version
settings/Upgrade already installed.
mode select
5) Failed in changing the upgrade mode Communication Communication
settings/Upgrade failure
mode select
6) Operation mode is incorrect Communication RUN mode
settings/Upgrade
mode select
7) Upgrade failed Upgrade Writing error
8) FP0H cannot be detected Upgrade USB reconnection
error
9) FP0H multiple units connection error Communication Multiple FP0H
settings/Upgrade connections
mode select
10) RUN mode select confirmation Communication RUN mode
settings/Upgrade
mode select
11) Upgrade data error None (At the initial Data error
startup)
12) Upgrade confirmed Communication Confirmation of
settings/Upgrade update target
mode select

2-13
Table of contents

2.1 Solution for Each Error Message


1) Error message (Connection error)

Solution
- Check if the USB port settings are correct. (Select the correct USB port.)
- Check if the USB and power supply connection cables are securely inserted.
- Check if the FP0H is powered on.
- Check if the connected PLC type is FP0H.

2) Error message (Connection error)

Solution
- The USB port is used by another communication software (FPWIN GR/GR7/Pro or
HyperTerminal).
- Set it to offline or exit it.

2-14
Table of contents

3) Error message (Version upgrade not supported)

Solution
- The model used is not applicable for this tool. Use a supported model.

4) Warning message (Latest version)

Solution: None (The latest version has been already installed.)

5) Error message (Failed in changing the upgrade mode.)

Solution
- Turn off the power to the FP0H and retry the upgrade from the beginning.

2-15
Table of contents

6) Error message (Operation mode is incorrect.)

Solution
- Change the switch on the FP0H to PROG.

7) Error message (Upgrade failed)

Solution
Turn off the power to the FP0H and retry the upgrade from the beginning.

8) FP0H cannot be detected.

Solution
- Reinsert the USB cable and click the "Retry" button.

2-16
Table of contents

9) FP0H multiple units connection error

Solution
- Turn off the power to the FP0H units not to be upgraded, or remove the USB cables.

10) RUN mode select confirmation

Solution
- Click the "Yes" button. (The mode will be automatically changed to the PROG. mode in the
software.)
- When the switch is changed manually, click the "No" button to proceed.

11) Upgrade data error

Solution
Please contact your dealer regarding upgrade data errors.

2-17
Table of contents

12) Upgrade confirmed

Solution)
 Confirm the version of the update program of FP0H.