SKYLINE ELECTRICALS
# 1-112-566, 4th Floor, Sai Boda's Nilayam, Maharshi Marg, Near Shilpa Park, Kondapur,
Hyderabad - 500 084
FINAL COMMISSIONING TEST FORM
PROJECT : M/s. Genpact India Private Limited Phase-2 Hafeezpet Hyderabad
PACKAGE : SITC OF ELECTRICAL DESCRIPTION OF DISTRIBUTION BOARDS
WORKS EQUIPMENT/WORK
REVISIONS ITEM : UPS DB-1
DATE 21.02.2020 LOCATION : SECOND FLOOR - ELECTRICAL ROOM
Sl.No ITEM DESCRIPTION CHECKED BY
SKYLINE REMARKS
1 DB installation as per dawing with line & level. √
2 MCB, ELCB,RCBO,DB etc.,make as per approved list of makes. √
3 Rating of Components as per drawing. √
4 Incomer and Outgoing Cable are as per schedule. √
5 Check for vents and paint damage. √
6 Check hinges / Closure of doors. √
7 Glanding and terminations of cables. √
8 Body earthing of Distribution Board. √
9 Dressing of wire inside DB. √
10 Termination in MCB, ELCB,RCBO etc.,properly done. √
11 Neutral terminals as required as per drawing and tightness of
terminals. √
12 Earthing as required as per drawing and tightness of terminals √
13 Crimping of cable lugs done properly. √
14 Inside and outside DB is cleaned properly. √
VOLTAGE READING IN VOLTS
RY YB BR RN YN BN RE YE BE NE
397 398 397 230 229 230 230 230 229 0.4
REMARKS / COMMENTS
NAME : NAME : Siddu
SIGNTURE : SIGNTURE :
FOR FOR SKYLINE ELECTRICALS
SKYLINE ELECTRICALS
# 1-112-566, 4th Floor, Sai Boda's Nilayam, Maharshi Marg, Near Shilpa Park, Kondapur,
Hyderabad - 500 084
FINAL COMMISSIONING TEST FORM
PROJECT : M/s. Genpact India Private Limited Phase-2 Hafeezpet Hyderabad
PACKAGE : SITC OF ELECTRICAL DESCRIPTION OF DISTRIBUTION BOARDS
WORKS EQUIPMENT/WORK
REVISIONS ITEM : UPS DB-2
DATE 21.02.2020 LOCATION : SECOND FLOOR - ELECTRICAL ROOM
Sl.No ITEM DESCRIPTION CHECKED BY
SKYLINE REMARKS
1 DB installation as per dawing with line & level. √
2 MCB, ELCB,RCBO,DB etc.,make as per approved list of makes. √
3 Rating of Components as per drawing. √
4 Incomer and Outgoing Cable are as per schedule. √
5 Check for vents and paint damage. √
6 Check hinges / Closure of doors. √
7 Glanding and terminations of cables. √
8 Body earthing of Distribution Board. √
9 Dressing of wire inside DB. √
10 Termination in MCB, ELCB,RCBO etc.,properly done. √
11 Neutral terminals as required as per drawing and tightness of
terminals. √
12 Earthing as required as per drawing and tightness of terminals √
13 Crimping of cable lugs done properly. √
14 Inside and outside DB is cleaned properly. √
VOLTAGE READING IN VOLTS
RY YB BR RN YN BN RE YE BE NE
397 397 398 229 229 230 230 230 229 0.4
REMARKS / COMMENTS
NAME : NAME : Siddu
SIGNTURE : SIGNTURE :
FOR FOR SKYLINE ELECTRICALS
SKYLINE ELECTRICALS
# 1-112-566, 4th Floor, Sai Boda's Nilayam, Maharshi Marg, Near Shilpa Park, Kondapur,
Hyderabad - 500 084
FINAL COMMISSIONING TEST FORM
PROJECT : M/s. Genpact India Private Limited Phase-2 Hafeezpet Hyderabad
PACKAGE : SITC OF ELECTRICAL DESCRIPTION OF DISTRIBUTION BOARDS
WORKS EQUIPMENT/WORK
REVISIONS ITEM : UPS DB-3
DATE 21.02.2020 LOCATION : SECOND FLOOR - ELECTRICAL ROOM
Sl.No ITEM DESCRIPTION CHECKED BY
SKYLINE REMARKS
1 DB installation as per dawing with line & level. √
2 MCB, ELCB,RCBO,DB etc.,make as per approved list of makes. √
3 Rating of Components as per drawing. √
4 Incomer and Outgoing Cable are as per schedule. √
5 Check for vents and paint damage. √
6 Check hinges / Closure of doors. √
7 Glanding and terminations of cables. √
8 Body earthing of Distribution Board. √
9 Dressing of wire inside DB. √
10 Termination in MCB, ELCB,RCBO etc.,properly done. √
11 Neutral terminals as required as per drawing and tightness of
terminals. √
12 Earthing as required as per drawing and tightness of terminals √
13 Crimping of cable lugs done properly. √
14 Inside and outside DB is cleaned properly. √
VOLTAGE READING IN VOLTS
RY YB BR RN YN BN RE YE BE NE
397 398 398 229 229 230 229 230 229 0.4
REMARKS / COMMENTS
NAME : NAME : Siddu
SIGNTURE : SIGNTURE :
FOR FOR SKYLINE ELECTRICALS
SKYLINE ELECTRICALS
# 1-112-566, 4th Floor, Sai Boda's Nilayam, Maharshi Marg, Near Shilpa Park, Kondapur,
Hyderabad - 500 084
FINAL COMMISSIONING TEST FORM
PROJECT : M/s. Genpact India Private Limited Phase-2 Hafeezpet Hyderabad
PACKAGE : SITC OF ELECTRICAL DESCRIPTION OF DISTRIBUTION BOARDS
WORKS EQUIPMENT/WORK
REVISIONS ITEM : UPS DB-4
DATE 21.02.2020 LOCATION : SECOND FLOOR - ELECTRICAL ROOM
Sl.No ITEM DESCRIPTION CHECKED BY
SKYLINE REMARKS
1 DB installation as per dawing with line & level. √
2 MCB, ELCB,RCBO,DB etc.,make as per approved list of makes. √
3 Rating of Components as per drawing. √
4 Incomer and Outgoing Cable are as per schedule. √
5 Check for vents and paint damage. √
6 Check hinges / Closure of doors. √
7 Glanding and terminations of cables. √
8 Body earthing of Distribution Board. √
9 Dressing of wire inside DB. √
10 Termination in MCB, ELCB,RCBO etc.,properly done. √
11 Neutral terminals as required as per drawing and tightness of
terminals. √
12 Earthing as required as per drawing and tightness of terminals √
13 Crimping of cable lugs done properly. √
14 Inside and outside DB is cleaned properly. √
VOLTAGE READING IN VOLTS
RY YB BR RN YN BN RE YE BE NE
397 398 397 229 229 230 230 230 229 0.4
REMARKS / COMMENTS
NAME : NAME : Siddu
SIGNTURE : SIGNTURE :
FOR FOR SKYLINE ELECTRICALS
SKYLINE ELECTRICALS
# 1-112-566, 4th Floor, Sai Boda's Nilayam, Maharshi Marg, Near Shilpa Park, Kondapur,
Hyderabad - 500 084
FINAL COMMISSIONING TEST FORM
PROJECT : M/s. Genpact India Private Limited Phase-2 Hafeezpet Hyderabad
PACKAGE : SITC OF ELECTRICAL DESCRIPTION OF DISTRIBUTION BOARDS
WORKS EQUIPMENT/WORK
REVISIONS ITEM : UPS DB-5
DATE 21.02.2020 LOCATION : SECOND FLOOR - ELECTRICAL ROOM
Sl.No ITEM DESCRIPTION CHECKED BY
SKYLINE REMARKS
1 DB installation as per dawing with line & level. √
2 MCB, ELCB,RCBO,DB etc.,make as per approved list of makes. √
3 Rating of Components as per drawing. √
4 Incomer and Outgoing Cable are as per schedule. √
5 Check for vents and paint damage. √
6 Check hinges / Closure of doors. √
7 Glanding and terminations of cables. √
8 Body earthing of Distribution Board. √
9 Dressing of wire inside DB. √
10 Termination in MCB, ELCB,RCBO etc.,properly done. √
11 Neutral terminals as required as per drawing and tightness of
terminals. √
12 Earthing as required as per drawing and tightness of terminals √
13 Crimping of cable lugs done properly. √
14 Inside and outside DB is cleaned properly. √
VOLTAGE READING IN VOLTS
RY YB BR RN YN BN RE YE BE NE
398 397 398 230 229 239 230 230 229 0.4
REMARKS / COMMENTS
NAME : NAME : Siddu
SIGNTURE : SIGNTURE :
FOR FOR SKYLINE ELECTRICALS