The document provides technical specifications for the Amps X 10 Bus - UT2MV01A07, including details on current ratings, time delays, and protection settings. It specifies the FLA (Full Load Amps) as 262.4 Amps and includes information on various circuit protection devices and their settings. Additionally, it mentions the CT (Current Transformer) ratios and the inrush current for the associated transformer.

Uploaded by

j77965265
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
13 views1 page

Teste CCO

The document provides technical specifications for the Amps X 10 Bus - UT2MV01A07, including details on current ratings, time delays, and protection settings. It specifies the FLA (Full Load Amps) as 262.4 Amps and includes information on various circuit protection devices and their settings. Additionally, it mentions the CT (Current Transformer) ratios and the inrush current for the associated transformer.

Uploaded by

j77965265
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

Amps X 10 Bus - UT2MV01A07 (Nom. kV=6,6, Plot Ref.

kV=6,6)
,5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
1K 1K
TR - UT1-TA04-T01-TSA1 R - UT2MV01A06 - P
FLA - Other 65 OC1
500 500
262,432 Amps Schweitzer
751A
300 LOAD 01 CT Ratio 2000:5 300
FLA C2 - IEC Cls B Very Inverse
262,4 Amps Pickup = 6,62 (0,5 - 16 Sec - 5A)
Time Dial = 1
3x = 6,75 s, 5x = 3,38 s, 8x = 1,93 s
100 TR - UT1-TA04-T01-TSA1 Inst = 15,44 (0,5 - 96 Sec - 5A) 100

Withstand Time Delay = 0,6 s


OCR
50 50
R - UT2MV01A06
30 30

o
OCR
10 10 R-UT2MV01A07

5 5

Seconds
Seconds

3 3

R-UT2MV01A07 - P
1 OC1 1

Schweitzer Bus - UT2MV01A07


751A
,5 CT Ratio 50:5 ,5

C2 - IEC Cls B Very Inverse


,3 Pickup = 1,2 (0,5 - 16 Sec - 5A) ,3
Time Dial = 0,22 ∆ 0,5 s
3x = 1,49 s, 5x = 0,743 s, 8x = 0,424 s CBL-UT2-MV01A07-TRSA1
Inst = 13 (0,5 - 96 Sec - 5A)
Time Delay = 0,1 s
,1 ,1

,05 ,05
TR - UT1-TA04-T01-TSA1
Inrush
,03 ,03

R - UT2MV01A06 - 3P
32,804kA @ 6,6kV
(Sym)
TR - UT1-TA04-T01-TSA1
,01 ,01 100 kVA
,5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K

Amps X 10 Bus - UT2MV01A07 (Nom. kV=6,6, Plot Ref. kV=6,6)


ETAP Star 22.5.0C

BUS-UT1-TA04-T01-TSA1-BT

LOAD 01
100 kVA