ZTT Tla
ZTT Tla
Summary......................................................................................................................................................................
01
Execution Standards..........................................................................................................................................
02
Quality, Design and Service......................................................................................................................... 03
Type Instructions................................................................................................................................................... 05
Normal Operating Conditions.................................................................................................................... 06
Abnormal operating conditions................................................................................................................. 06
Main Specifications and Technical Parameters of 6 ~ 10kV Composite
Metal-oxide Surge Arresters........................................................................................................................ 07
Main Specifications and Technical Parameters of 35kV Composite Metal-
oxide Surge Arresters......................................................................................................................................... 08
Main Specifications and Technical Parameters of 110 ~ 220kV Composite
Metal-oxide Surge Arresters for Substation.................................................................................... 09
Main Specifications and Technical Parameters of 110 ~ 500kV Composite
without Gap Metal-oxide Surge Arresters for Transmission Line.................................. 11
Main Specifications and Technical Parameters of 110 ~ 500kV Composite
with Gap Metal-oxide Surge Arresters for Transmission Line.......................................... 13
Main Specifications and Technical Parameters of 35 ~ 500kV Porcelain
Metal-oxide Surge Arresters for Substation.................................................................................... 17
Main Specifications and Technical Parameters of 3 ~ 36kV Composite
Metal-oxide Surge Arresters for Outlet............................................................................................... 21
Main Specifications and Technical Parameters of 110 ~ 275kV Composite
Metal-oxide Surge Arresters for Outlet............................................................................................... 27
Metal oxide surge arresters Metal oxide surge arresters
02 / Execution Standards
ZTT arresters design, manufacture in full compliance with GB11032, IEC60099-4 standards.
01 / Summary
In the process of production, transmission, distribution to the load terminal of electric energy equipment used for
generation- transmission - distribution is inevitably suffered overvoltage attack. No matter where such over-voltages
comes from, the atmosphere or the interior, damage or permanent damage to the equipment may occur, which result
in power interruption and substantial economic loss. It is necessary to take appropriate protective measures. At
present, metal-oxide surge arresters are recognized as the most excellent over-voltage protection devices on a global
scope. When atmospheric over-voltage or internal over-voltage occurs to the system, the core element of the arrester
- the zinc oxide arrester keeps its resistance value at a low level. The current of kilo-amperes flows into the earth
through the resistor sheet. The residual voltage pressure at both ends of the arrester is limited below the allowable
value, thereby providing a reliable protection for the insulation of the power equipment and cutting off power-flow
current; when the arrester is running under normal voltage, due to its excellent non-linear, its resistance will be high
and the current flowing through the arrester will be only a few hundred micro amps, which limit the power loss to a
minimum.
01 02
Metal oxide surge arresters Metal oxide surge arresters
● Manufacturers have access to ISO9001 quality certification. ● New interface coupling technology to eliminate the possibility
● Products have passed independent third party laboratory type test. of product internal breakdown.
Repeated tests of Suitable coupling agent make the product’s
separation strength between the core and the silicone rubber
reaches up to at least 15kN / m, eliminating product internal
breakdown caused by interface problems.
03 04
Metal oxide surge arresters Metal oxide surge arresters
05 / Normal Operating
Conditions
—Ambient temperature: + 40℃~- 40℃;
—Altitude: ≤ 1000m;
—Maximum wind speed: ≤ 35m/s;
—Maximum ice thickness:20mm;
—illumination intensity:0.1w/cm2;
— Mains frequency: 48Hz ~ 62Hz;
Rated voltage(kV)
Design No.
e.g.:YH5WS-17/50T means this product for composite metal oxide surge arrester of distribution type,
nominal discharge current: 5kA,rated voltage: 17kV, residual voltage less than: 50kV, with disconnector.
05 06
Metal oxide surge arresters Metal oxide surge arresters
07 / Main Specifications and Technical Parameters of 6 ~ 10kV 08 / Main Specifications and Technical Parameters of 35kV
Composite Metal-oxide Surge Arresters Composite Metal-oxide Surge Arresters
System voltage level 10kV 6kV System voltage level 35kV
Type YH5WZ-17/45 YH5WS-17/50 YH5WX-17/50 YH5WR-17/46 YH2.5WD-12/30 YH5WZ-10/27 YH5WD-8/18.7 YH5WR-10/27 Type YH5WZ-51/125 YH5WZ-51/134 YH5WZ-54/142 YH5WR-51/134 YH1.5W-30/80 YH1.5W-33/90 YH5WT-42/120
Continuous operating voltage Uc(kV) 13.6 13.6 13.6 13.6 9.6 8.0 6.3 8 Continuous operating voltage Uc(kV) 40.8 40.8 43.2 40.8 24 26.4 34
1mA DC reference voltage U1mA(kV) 24 25 25 25 15 15.2 12 14.4 1mA DC reference voltage U1mA(kV) 73 73 77 73 44 49 65
Steep current impulse residual voltage(kV) 51.8 57.5 57.5 / 34.6 31 21.5 / Steep current impulse residual voltage(kV) 145 154 163 154 / / 138
Electric Electric
parameters parameters
Lightning impulse residual voltage(kV) 45 50 50 46 30 27 18.7 27 Lightning impulse residual voltage(kV) 125 134 142 134 80 90 120
Switching impulse residual voltage(kV) 38.3 42.5 42.5 35 23 23 15 21 Switching impulse residual voltage(kV) 106 114 121 114 75 84 98
Square wave impulse withstand Current(A) 150 150 150 600 400 150 600 600 Square wave impulse withstand Current(A) 400 400 400 600 600 600 600
High Current impulse withstand Current(kA) 65 65 65 100 65 65 100 100 High Current impulse withstand Current(kA) 100 100 100 100 100 100 100
Overall height H(mm) 252 252 252 240 240 252 240 240 Overall height H(mm) 684 684 684 684 684 684 684
Cree-page distance(mm) 405 405 405 390 390 405 390 390 Cree-page distance(mm) 1400 1400 1400 1400 1400 1400 1400
Structural Structural
Shed diameter Φ(mm) 100 100 100 120 120 100 120 120 Shed diameter Φ(mm) 162 162 162 162 162 162 162
parameters parameters
Weight (kg) 1.3 1.3 1.3 1.7 1.7 1.3 1.7 1.7 Weight (kg) 13 13 13 13 13 13 13
Outline Drawing Fig1 Fig1 Fig1 Fig1 Fig1 Fig1 Fig1 Fig1 Outline Drawing Fig2 Fig2 Fig2 Fig2 Fig2 Fig2 Fig2
Power
Capacitor
Protected object Substation transmission and Substation Capacitor bank Motors Substation Motors Protected object Substation Substation Substation Capacitor bank Neutral point Neutral point Electric railway
bank
distribution
through-hole
— Fig1 — — Fig2 —
07 08
Metal oxide surge arresters Metal oxide surge arresters
Steep current impulse residual voltage(kV) 291 297 314 594 628 — Fig3 —
Electric
parameters
Lightning impulse residual voltage(kV) 260 266 281 532 562
Square wave impulse withstand Current(A) 600/800 600/800 600/800 600/800 600/800
High Current impulse withstand Current(kA) 100 100 100 100 100
Pollution class Ⅳ Ⅳ Ⅳ Ⅳ Ⅳ
Structural
Shed diameter Φ(mm) 214 214 214 214 214
parameters
09 10
Metal oxide surge arresters Metal oxide surge arresters
10 / Main Specifications and Technical Parameters of 110 ~ 500kV Designated size of coupling:16
1mA DC reference voltage U1mA(kV) 140 157 292 314 442 597 630
Steep current impulse residual voltage(kV) 288 315 560 630 847 1238 1306
Electric
parameters
Lightning impulse residual voltage(kV) 250 281 500 562 760 1106 1166 — Fig5 — — Fig6 —
Square wave impulse withstand Current(A) 600 600 600/800 600/800 800/1000 1200/1800 1200/1800
High Current impulse withstand Current(kA) 100 100 100 100 100 100 100
Pollution class Ⅳ Ⅳ Ⅳ Ⅳ Ⅳ Ⅳ Ⅳ
Overall height H(mm) 1256 1256 2588 2588 2931 4307 4307
Structural
Shed diameter Φ(mm) 195 195 214 214 252 252 252
parameters
Protected object Transmission line Transmission line Transmission line Transmission line Transmission line Transmission line Transmission line
— Fig7 — — Fig8 —
11 12
Metal oxide surge arresters Metal oxide surge arresters
Line
System voltage level 110kV 220kV 330kV 500kV
1mA DC reference voltage U1mA(kV) 148 160 280 296 408 561
Steep current impulse residual voltage(kV) 331 358 628 662 817 1171
Electric
Lightning impulse residual voltage(kV) 296 320 560 592 775 1050
parameters
Square wave impulse withstand Current(A) 500/600 500/600 600/800 600/800 800/1200 1200/1800
High Current impulse withstand Current(kA) 100 100 100 100 100 100
Power-frequency discharge voltage (kV) 185 185 370 370 510 567
impulse discharge voltage (kV) 525 525 900 900 1300 1760
Structural
Shed diameter Φ(mm) 195 195 195 195 252 252
parameters Designated size of coupling:16
Protected object Transmission line Transmission line Transmission line Transmission line Transmission line Transmission line
13 14
Metal oxide surge arresters Metal oxide surge arresters
15 16
Metal oxide surge arresters Metal oxide surge arresters
Rated voltage UR(kV) 51 102 108 204 216 312 444 468
Continuous operating voltage Uc(kV) 40.8 81.6 86.4 163.2 172.8 237 324 330
1mA DC reference voltage U1mA(kV) 75 155 164 310 328 442 597 630
Steep current impulse residual voltage(kV) 154 297 314 594 628 847 1137 1198 — Fig13 —
Electric
parameters
Lightning impulse residual voltage(kV) 134 266 281 532 562 760 1015 1070
Switching impulse residual voltage(kV) 114 225 239 451 477 643 900 950
Square wave impulse withstand Current(A) 400 600/800 600/800 600/800 600/800 1000/1200 2000 2000
High Current impulse withstand Current(kA) 65 100 100 100 100 100 100 100
Pollution class Ⅳ Ⅳ Ⅳ Ⅳ Ⅳ Ⅳ Ⅳ Ⅳ
Overall height H(mm) 1007 1821 1821 3283 3283 3780 5850 5850
Cree-page distance(mm) 1285 3976 3976 7952 7952 11400 17300 17300
Structural
Shed diameter Φ(mm) 220 300 300 300 300 300 480 480
parameters
Outline Drawing Fig 13 Fig 14 Fig 14 Fig 15 Fig 15 Fig 15 Fig 16 Fig 16
Protected object Substation Substation Substation Substation Substation Substation Substation Substation
— Fig14 —
17 18
Metal oxide surge arresters Metal oxide surge arresters
860
1490
125
45 45 17.5
17.5
45
150
45
9× 18
terminal
接线盖板
plate cover plat
H
333
333
装监测器用
2× 15
To install the monitor
4× 30
— Fig15 — — Fig16 —
19 20
Metal oxide surge arresters Metal oxide surge arresters
kV(r.m.s) kV ≤ A kA
21 22
Metal oxide surge arresters Metal oxide surge arresters
— Fig20 —
— Fig23 —
— Fig21 —
— Fig22 — — Fig24 —
23 24
Metal oxide surge arresters Metal oxide surge arresters
— Fig25 — — Fig27 —
— Fig26 — — Fig28 —
25 26
Metal oxide surge arresters Metal oxide surge arresters
Steep current impulse residual voltage(kV) 296 365 410 504 670
Electric
Lightning impulse residual voltage(kV) 256 315 374 460 620
parameters
Square wave impulse withstand Current(A) 600 800 600/800 1000 1200/1500
High Current impulse withstand Current(kA) 100 100 100 100 100
Pollution class Ⅳ Ⅳ Ⅳ Ⅳ Ⅳ
Structural
Shed diameter Φ(mm) 226 226 226 214 252
parameters 4Xø13through-hole EQS
4Xø17through-hole EQS
Weight (kg) 30 35 40 70 90
Protected object Substation Substation Substation Substation Substation — Fig29 — — Fig30 — — Fig31 —
27 28