3.6 Peripheral devices
3.6.1 System Wire Arrangement
Please follow the specific
Power power supply requirement
supply shown in this manual.
FUSE/ NFB
There may be an inrush
Fuse/NFB current during power up.
Magnetic contactor
Please refer to 3.7.1 and
select the correct fuse /NFB.
Please do not use a Magnetic
Input AC Line Reactor
Magnetic contactor as the I/O switch of
contactor the inverter, as it will reduce
the operating life cycle of the
inverter.
AC line reactor should be
Input AC installed to improve the input
EMI filter Line Reactor power factor. The wiring
distance should be less than
10m. Please refer to 3.7.6.
Braking resistor
R/L1 S/L2 T/L3 +/P Zero-phase reactors are used
B
B
to reduce radio noise especially
R
P1 U when audio equipment installed
E
PR Zero-phase near the inverter. Effective for
-/N Reactor noise reduction on both the
Braking unit input and output sides. The
U/T1 V/T2 W/T3 frequency band effective range
is from 1MHz to 10 MHz.
Please refer to 3.7.5.
Zero- phase Reactor Used to reduce
EMI filter electromagnetic interference.
Braking unit Used to reduce stopping time
Output AC Line Reactor of the motor.
Motor surge voltage
amplitudes depending on
Output AC motor cable length. The output
Line Reactor AC line reactor is necessary to
Motor install on the inverter output
side. Please refer to 3.7.6.
INVERTER INTRODUCTION 30
Arrangement of control terminal
3.7 Terminal wire arrangement
SINK
SOURCE
SW1
0-10V
4~20mA
SW3
0-10V
0-20mA
SW2
Note: 1: All series includes built-in braking units, please connect braking resistor between + / P, PR.
2: All series inclides built-in RFI filters to suppress electromagnetic interference, but if you need to comply with CE
regulations, please refer to the relevant instructions in the manual for installation.
3: In order to improve the braking ability during deceleration, the frame C / D external braking unit can be connected
between (+ / P)-(-N). For details, please refer to Section 3.7.1.
4: When adding a DC reactor on C / D frame inverter, jumper between + / P and P1 must be removed. For the selection
of reactor, refer to section 3.6.4.
5. Do not short the 10, SD, SE, 5, and PC terminals to each other.
6. Please refer to section 5.3.9 for HDO wiring.
INVERTER INTRODUCTION 35
Arrangement of control terminal
6. If the distance between the inverter and motor is long, please use thick wires, make sure wire voltage drop is
under 2V (wire length below 500 meters).
7. Use "insulation crimp sleeve " for power supply side and load side connection.
8. After cutting off terminal power, high voltage still exist between (+/P) and (-/N) in short period of time. Within 10
minutes, do not touch terminals to avoid electric shock.
3.7.3 Ground
For safety and to reduce noise, the grounding of the inverter must be well grounded. To avoid electric shocks
and fire accident, the external metal ground wire of the equipment should be short and thick, and should be connected
to specific grounding terminals on the inverter. If several inverters are placed together, all inverters must be
connected to the common ground. Please refer to the following diagrams and ensure that no loop is formed between
grounding terminals.
Best Average Poor
3.7.4 RFI filter
SE3 series inverters are equipped with built-in RFI filters. These filters are effective in reducing electromagnetic
interference, but to meet CE standard, please refer to section 3.5.4 for installation and wiring.
Frame A/B
*1. Frame A:SE3-043-0.4~1.5K、SE3-023-0.4~1.5K、SE3-021-0.4~0.75K
*2. Frame B:SE3-043-2.2~3.7K、SE3-023-2.2~3.7K、SE3-021-1.5~2.2K
Frame A Frame B
INVERTER INTRODUCTION 39
Arrangement of control terminal
Note: 1. Screwdriver, use small slotted screwdriver (the tip thickness: 0.4mm/tip width: 2.5mm).
2. If the screwdriver tip width is too narrow, it may cause terminal damage.
3. Please alignment terminals by pressing down with the slotted screwdriver, head sliding may cause damage
or injury accident inverter.
4. Installation, wire arrangement, dismounting and maintenance can only be done by qualified electrical
professional personnel.
5. Please follow the wire arrangement notice. If installation is not done by above steps, and inverter is
damaged, our company will not undertake any legal responsibility. In case there is any question on the wire
arrangement, please feel free to contact us.
Toggle switch
SINK 0-10V 4-20mA
SOURCE 0-20mA 0-10V
SW1 SW2 SW3
Switch Switch
Explanation Remarks
number state
* Select sink input mode Please refer to section 3.7.5 control logic
SW1
Select source input mode switch.
* Output 0~10V voltage from terminal AM Also requires setting 02-45,
SW2
Output 0~20mA/4~20mA current from terminal AM please refer to section 5.3.10.
* Input 4~20mA current signal into terminal 4-5 Also requires setting 02-20,
SW3
Input 0~10V voltage signal into terminal 4-5 please refer to section 5.3.6.
Note: 1. The state with “*” is the default state of switch.
2. The parts in black stand for switch handle.
INVERTER INTRODUCTION 44
Component name of keypad (PU302)
4. BASIC OPERATION
4.1 Component name of keypad (PU302)
(a) (b) (c) (d)
(f)
(e)
(k)
(g)
(j) (i) (h)
NO. Operation parts Name Content
PU: On when in PU operation mode, flickers in H1~H5
(a) PU Operation mode indicator
operation mode.
(b) MON Keypad status indicator MON: On to indicate the monitoring mode
(c) RUN RUN indicator On when running
(d) PLC PLC function indicator On when in PLC mode
Hz: On when monitoring frequency.
Hz A A: On when monitoring output current.
(e) Monitoring indicator
V V: On when monitoring output voltage by default. Can be set
by 00-07(P.161)to monitor different values.
Shows the frequency, parameter number, and parameter
(f) 8.8.8.8.8. Monitor (5-digit LED)
value, etc.
Stops the operation.
(g) STOP/RESET button
Resets the inverter when alarm.
Long press writes parameter value, frequency, etc.
(h) SET button
Press to read the parameter.Enter into the next menu.
(i) MODE button Switches to different modes
FWD: Starts forward rotation.
(j) FWD button REV button
REV: Starts reverse rotation.
Clockwise rotation increase values or can switch options
(k) M Setting dial Counter clockwise rotation decrease value or can switch
options
PRIMARY OPERATION46