Installation instructions
AS-i module
UK
AC2267
07 / 2010
7390851 / 00
Function and features
• AS-i profile S-7.A.7
• maximum number of modules per master: 62
• AS-Interface version 3.0
• external PELV voltage supply for inputs
• the slave AC2267 can only be operated in conjunction with a version 3.0
master (master profile M4)
Operating and display elements
25 105
114
35,5
LEDs
1: addressing socket
2: Combicon plug with screw terminals (optional)
Mounting
Mount the module onto a 35 mm rail or fasten it onto a mounting device.
Technical data
You can download the data sheet from the Internet if required (www.ifm.com).
2
Addressing
At the factory the address is set to 0.
Addressing with the addressing unit AC1154
When mounted and wired the module can be addressed by connecting the
addressing cable (E70213) to the implemented addressing socket.
Do not remove the addressing plug while live.
Electrical connection UK
Disconnect power! Connect the sensors and actuators with the terminals.
The sensors must be supplied with external PELV voltage.
The device shall be supplied from an isolating transformer having a secondary
Listed fuse rated as noted in the following table.
Overcurrent protection
Control-circuit wire size Maximum protective device rating
AWG (mm2) Ampere
26 (0.13) 1
24 (0.20) 2
22 (0.32) 3
20 (0.52) 5
18 (0.82) 7
16 (1.3) 10
3
Connection
A+: AS-i +
A-: AS-i -
I+: sensor supply +24 V
I-: sensor supply 0 V
external sensor supply for sensors /
E+:
actuators LEDs 1
external sensor supply for sensors /
E-:
actuators ADR
I1 ... I4: switching inputs sensors 1...4 LEDs 2
O1 ...O3: switching outputs actuators 1...4
O-: switching output actuator 0 V
LEDs 1: switching status indication sensor inputs O- O- O- O-
LEDs 2: AS-i, FAULT, AUX O1 O2 O3 O4
A+ A- E+ E-
LEDs 3: switching status indication actuator outputs
ADR addressing socket
Operation
Check the safe functioning of the unit. Display by LEDs:
• LED green (AS-i): voltage supply via the AS-i network o.k.
• LED green (AUX): external voltage supply o.k.
• LED yellow: input/output switched
• LED red is lit (FAULT): AS-i communication error, e. g. slave address 0
• LED red flashing (FAULT): peripheral error, e.g. no auxiliairy voltage