Heat Load

The document contains HVAC estimates for three different job sites, detailing solar gain, heat gain, and various calculations for air conditioning requirements. Each job includes specifics such as size, estimated cooling loads, and internal heat gains from people and equipment. The calculations are aimed at determining the necessary cooling capacity for summer conditions.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
56 views10 pages

Heat Load

The document contains HVAC estimates for three different job sites, detailing solar gain, heat gain, and various calculations for air conditioning requirements. Each job includes specifics such as size, estimated cooling loads, and internal heat gains from people and equipment. The calculations are aimed at determining the necessary cooling capacity for summer conditions.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
You are on page 1/ 10

JOB NAME: mourya DATE: 6/6/2019 Rev: 0

SPACE FOR: comfort ac Estimated By: ACE


SIZE: 1203 Sq ft 12632 Cu ft Estimate for: SUMMER
SOLAR GAIN GLASS HEAT GAIN CONDITION DB (°F) WB (°F) % RH DP (°F) GR/LB
ITEM Area Sun Gain Factor Btu/hour OUTSIDE 96 78 45 - 120.87
(Sq ft) (Btu/h.sq ft) ROOM 73.4 61.12 61.18
N - Glass 0 14 0.56 0 DIFFERENCE 22.6 XXXX XXXX XXXX 59.69
NE - Glass 601.125 12 0.56 4040 N - Wall
E - Glass 0 12 0.56 0 OUTSIDE AIR (VENTILATION) NE - Wall
SE - Glass 0 12 0.56 0 40 People X 15 CFM/Person 600 E - Wall
S - Glass 0 12 0.56 0 12632 Cu ft X 1 Air change per hour 211 SE - Wall
SW - Glass 0 100 0.56 0 CFM VENTILATION 600 S - Wall
W - Glass 0 164 0.56 0 SW - Wall
NW - Glass 84 130 0.56 6115 EFF. SENSIBLE HEAT FACTOR (ESHF) = 0.82 W - Wall
Sky light 0 Indicated ADP = 49.7 °F NW - Wall
SOLAR & TRANS. GAIN WALLS & ROOF Selected ADP = 49.7 °F
ITEM Area Eq. temp. diff. U Dehum. temp rise = 20.15 °F
(Sq ft) (°F) (Btu/h.sq ft) DEHUMIDIFIED CFM = 3044
N - Wall 0 8.6 0.36 0
NE - Wall 0 14.6 0.36 0
E - Wall 48 22.6 0.36 391
SE - Wall 0 22.6 0.36 0
S - Wall 367.5 20.6 0.36 2725
SW - Wall 0 18.6 0.36 0
W - Wall 0 16.6 0.36 0
NW - Wall 0 10.6 0.36 0
Roof Sun 1203 39.6 0.12 5717
Roof Shaded 31 0 NOTES
TRANS. GAIN EXCEPT WALLS & ROOF Occupancy = 40 Nos
ITEM Area Temp. diff. U Lighting = 1.25 W/Sq ft
(Sq ft) (°F) (Btu/h.sq ft) Eq. Load = 0.3 KW
All Glass 685.125 22.6 1.13 17497 Height = 10.5 FT
Partition 546 17.6 0.32 3075 Fresh Air= 15.0 Cfm per person
Ceiling 0 17.6 0.32 0 = 1.0 Air changes per hour
Floor 0 17.6 0.38 0 Internal Heat - People
INTERNAL HEAT GAIN Sensible Heat = 280
People 40 Nos X 280 11200 Latent Heat = 270
Light 1504 W X 1 3.41 5128
Eq. Load 300 W X 3.41 1023 billing machine 200 w
ROOM SENSIBLE HEAT (RSH) 56911 tv 100 w
Supply duct heat Supply duct Heat gain from 4 2276
gain + leak. loss + fan HP(%) 300 0.3 kw
Safety factor (%) 8.5 4837 EQUIPMENT TO BE SELECTED = 9.82TR/3044CFM
OUTSIDE AIR
CFM °F BF FACTOR
600 22.6 0.15 1.08 2197
EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 66221
LATENT HEAT
People 40 Nos X 270
ROOM LATENT HEAT (RLH) 10800
Supply duct leakage loss + Safety factor % 5.0 540
OUTSIDE AIR
CFM GR/LB BF FACTOR
600 59.69 0.15 0.68 3653
EFFECTIVE ROOM LATENT HEAT (ERLH) 14993
EFFECTIVE ROOM TOTAL HEAT (ERTH) 81214
OUTSIDE AIR HEAT (SENSIBLE) CHECK FIGURES
CFM °F 1 - BF FACTOR Btu/h/ Sq ft = 97.9
600 22.6 0.85 1.08 12448 CFM / Sq ft = 2.53
OUTSIDE AIR HEAT (LATENT) Sq ft / TR = 123
CFM GR/LB 1 - BF FACTOR CFM/ TR = 310
600 59.69 0.85 0.68 20700
HEAT SUB TOTAL 114363
Return duct heat HP Pump + Dehum. & Pipe 3.0 3431
gain & leak. loss + loss (%)

TR 9.82 GRAND TOTAL HEAT 117794


gross(w+g) only glass only wall
0 0 0
601.125 601.125 0
48.09 0 48.09
0 0 0
367.5 0 367.5
0 0 0
0 0 0
84 84 0

DBT RH
75 50% ESHF 0.84 0.82 0.78
ADP 52 51.33333 50
0.333333
73.4

72 50% ESHF 0.88 0.82 0.81


ADP 50 48.285 48
0.285714

75 51.33333

73.4 49.7

72 48.285
JOB NAME: THEOREMS DATE: 6/6/2019 Rev: 0
SPACE FOR: comfort ac Estimated By: ACE
SIZE: 2199.2364 Sq ft 26391 Cu ft Estimate for: SUMMER
SOLAR GAIN GLASS HEAT GAIN CONDITION DB (°F) WB (°F) % RH DP (°F) GR/LB
ITEM Area Sun Gain Factor Btu/hour OUTSIDE 96 78 45 - 120.87
(Sq ft) (Btu/h.sq ft) ROOM 73.4 61.12 61.18
N - Glass 106.272 14 0.56 833 DIFFERENCE 22.6 XXXX XXXX XXXX 59.69
NE - Glass 0 12 0.56 0 N - Wall
E - Glass 105.165 12 0.56 707 OUTSIDE AIR (VENTILATION) NE - Wall
SE - Glass 0 12 0.56 0 25 People X 15 CFM/Person 375 E - Wall
S - Glass 34.686 12 0.56 233 26391 Cu ft X 1 Air change per hour 440 SE - Wall
SW - Glass 0 100 0.56 0 CFM VENTILATION 440 S - Wall
W - Glass 70.11 164 0.56 6439 SW - Wall
NW - Glass 0 130 0.56 0 EFF. SENSIBLE HEAT FACTOR (ESHF) = 0.90 W - Wall
Sky light 0 Indicated ADP = 51.9 °F NW - Wall
SOLAR & TRANS. GAIN WALLS & ROOF Selected ADP = 51.9 °F
ITEM Area Eq. temp. diff. U Dehum. temp rise = 18.28 °F
(Sq ft) (°F) (Btu/h.sq ft) DEHUMIDIFIED CFM = 3611
N - Wall 354.20064 8.6 0.36 1097
NE - Wall 0 14.6 0.36 0
E - Wall 401 22.6 0.36 3259
SE - Wall 0 22.6 0.36 0
S - Wall 262.482 20.6 0.36 1947
SW - Wall 0 18.6 0.36 0
W - Wall 285.7044 16.6 0.36 1707
NW - Wall 0 10.6 0.36 0
Roof Sun 39.6 0.12 0
Roof Shaded 31 0 NOTES
TRANS. GAIN EXCEPT WALLS & ROOF Occupancy = 25 Nos
ITEM Area Temp. diff. U Lighting = 1.00 W/Sq ft
(Sq ft) (°F) (Btu/h.sq ft) Eq. Load = 4.8 KW
All Glass 316.233 22.6 1.13 8076 Height = 12.0 FT
Partition 1023.36 17.6 0.32 5764 Fresh Air= 15.0 Cfm per person
Ceiling 0 17.6 0.32 0 = 1.0 Air changes per hour
Floor 0 17.6 0.38 0 Internal Heat - People
INTERNAL HEAT GAIN Sensible Heat = 245
People 25 Nos X 245 6125 Latent Heat = 205
Light 2199 W X 1.25 3.41 9374 EQUIPMENT NO'S DISSI TOTAL
Eq. Load 4800 W X 3.41 16368 SYSTEM 19 200 3800 WATTS
ROOM SENSIBLE HEAT (RSH) 61929 PRINTER 1 1000 1000
Supply duct heat Supply duct Heat gain from 4 2477
gain + leak. loss + fan HP(%) 4800 WATTS 4.8 KW
Safety factor (%) 8.5 5264 EQUIPMENT TO BE SELECTED = 8.9TR/3611CFM
OUTSIDE AIR
CFM °F BF FACTOR
440 22.6 0.15 1.08 1610
EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 71280
LATENT HEAT
People 25 Nos X 205
ROOM LATENT HEAT (RLH) 5125
Supply duct leakage loss + Safety factor % 5.0 256
OUTSIDE AIR
CFM GR/LB BF FACTOR
440 59.69 0.15 0.68 2678
EFFECTIVE ROOM LATENT HEAT (ERLH) 8059
EFFECTIVE ROOM TOTAL HEAT (ERTH) 79339
OUTSIDE AIR HEAT (SENSIBLE) CHECK FIGURES
CFM °F 1 - BF FACTOR Btu/h/ Sq ft = 48.5
440 22.6 0.85 1.08 9125 CFM / Sq ft = 1.64
OUTSIDE AIR HEAT (LATENT) Sq ft / TR = 247
CFM GR/LB 1 - BF FACTOR CFM/ TR = 406
440 59.69 0.85 0.68 15175
HEAT SUB TOTAL 103640
Return duct heat HP Pump + Dehum. & Pipe 3.0 3109
gain & leak. loss + loss (%)

TR 8.90 GRAND TOTAL HEAT 106749


gross(w+g) only glass only wall
460.4726 106.272 354.2006
0 0 0
505.776 105.165 400.611
0 0 0
297.168 34.686 262.482
0 0 0
355.8144 70.11 285.7044
0 0 0

DBT RH
75 50% ESHF 0.92 0.9 0.84
ADP 54 53.5 52
0.25
73.4

72 50% ESHF 0.92 0.9 0.88


ADP 51 50.5 50

75 53.5

73.4 51.9

72 50.5
JOB NAME: JUST DIAL DATE: 6/6/2019 Rev: 0
SPACE FOR: comfort ac Estimated By: ACE
SIZE: 3078.436 Sq ft 36941 Cu ft Estimate for: SUMMER
SOLAR GAIN GLASS HEAT GAIN CONDITION DB (°F) WB (°F) % RH DP (°F) GR/LB
ITEM Area Sun Gain Factor Btu/hour OUTSIDE 96 78 45 - 120.87
(Sq ft) (Btu/h.sq ft) ROOM 73.4 61.12 61.18
N - Glass 0 14 0.56 0 DIFFERENCE 22.6 XXXX XXXX XXXX 59.69
NE - Glass 454.88352 12 0.56 3057 N - Wall
E - Glass 0 12 0.56 0 OUTSIDE AIR (VENTILATION) NE - Wall
SE - Glass 168.92 12 0.56 1135 110 People X 15 CFM/Person 1650 E - Wall
S - Glass 0 12 0.56 0 36941 Cu ft X 1 Air change per hour 616 SE - Wall
SW - Glass 0 100 0.56 0 CFM VENTILATION 1650 S - Wall
W - Glass 0 164 0.56 0 SW - Wall
NW - Glass 0 130 0.56 0 EFF. SENSIBLE HEAT FACTOR (ESHF) = 0.86 W - Wall
Sky light 0 Indicated ADP = 51.9 °F NW - Wall
SOLAR & TRANS. GAIN WALLS & ROOF Selected ADP = 51.9 °F
ITEM Area Eq. temp. diff. U Dehum. temp rise = 18.28 °F
(Sq ft) (°F) (Btu/h.sq ft) DEHUMIDIFIED CFM = 10200
N - Wall 0 8.6 0.36 0
NE - Wall 64.5504 14.6 0.36 339
E - Wall 0 22.6 0.36 0
SE - Wall 536.37184 22.6 0.36 4364
S - Wall 0 20.6 0.36 0
SW - Wall 482.27808 18.6 0.36 3229
W - Wall 0 16.6 0.36 0
NW - Wall 211.3632 10.6 0.36 807
Roof Sun 39.6 0.12 0
Roof Shaded 31 0 NOTES
TRANS. GAIN EXCEPT WALLS & ROOF Occupancy = 110 Nos
ITEM Area Temp. diff. U Lighting = 1.25 W/Sq ft
(Sq ft) (°F) (Btu/h.sq ft) Eq. Load = 22.0 KW
All Glass 623.80352 22.6 1.13 15931 Height = 12.0 FT
Partition 1023.36 17.6 0.32 5764 Fresh Air= 15.0 Cfm per person
Ceiling 0 17.6 0.32 0 = 1.0 Air changes per hour
Floor 3078.436 17.6 0.38 20589 Internal Heat - People
INTERNAL HEAT GAIN Sensible Heat = 245
People 110 Nos X 245 26950 Latent Heat = 205
Light 3848 W X 1.25 3.41 16402 EQUIPMENT NO'S DISSI TOTAL
Eq. Load 22000 W X 3.41 75020 SYSTEM 105 200 21000 WATTS
ROOM SENSIBLE HEAT (RSH) 173586 PRINTER 1 1000 1000
Supply duct heat Supply duct Heat gain from 4 6943
gain + leak. loss + fan HP(%) 22000 WATTS 22 KW
Safety factor (%) 8.5 14755 EQUIPMENT TO BE SELECTED = 8.9TR/3611CFM
OUTSIDE AIR
CFM °F BF FACTOR
1650 22.6 0.15 1.08 6041
EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 201325
LATENT HEAT
People 110 Nos X 205
ROOM LATENT HEAT (RLH) 22550
Supply duct leakage loss + Safety factor % 5.0 1128
OUTSIDE AIR
CFM GR/LB BF FACTOR
1650 59.69 0.15 0.68 10046
EFFECTIVE ROOM LATENT HEAT (ERLH) 33723
EFFECTIVE ROOM TOTAL HEAT (ERTH) 235049
OUTSIDE AIR HEAT (SENSIBLE) CHECK FIGURES
CFM °F 1 - BF FACTOR Btu/h/ Sq ft = 109.1
1650 22.6 0.85 1.08 34232 CFM / Sq ft = 3.31
OUTSIDE AIR HEAT (LATENT) Sq ft / TR = 110
CFM GR/LB 1 - BF FACTOR CFM/ TR = 364
1650 59.69 0.85 0.68 56926
HEAT SUB TOTAL 326207
Return duct heat HP Pump + Dehum. & Pipe 3.0 9786
gain & leak. loss + loss (%)

TR 28.00 GRAND TOTAL HEAT 335994


gross(w+g) only glass only wall
0 0 0
519.4339 454.8835 64.5504
0 0 0
705.2918 168.92 536.3718
0 0 0
482.2781 0 482.2781
0 0 0
211.3632 0 211.3632

DBT RH
75 50% ESHF 0.92 0.9 0.84
ADP 54 53.5 52
0.25
73.4

72 50% ESHF 0.92 0.9 0.88


ADP 51 50.5 50

75 53.5

73.4 51.9

72 50.5
JOB NAME: ATALANTIC DATE: 6/6/2019 Rev: 0
SPACE FOR: comfort ac Estimated By: ACE
SIZE: 4052 Sq ft 48624 Cu ft Estimate for: SUMMER
SOLAR GAIN GLASS HEAT GAIN CONDITION DB (°F) WB (°F) % RH DP (°F) GR/LB
ITEM Area Sun Gain Factor Btu/hour OUTSIDE 92 82 28 - 149.8
(Sq ft) (Btu/h.sq ft) ROOM 71.6 59.64 57.4
N - Glass 0 14 0.56 0 DIFFERENCE 20.4 XXXX XXXX XXXX 92.4
NE - Glass 0 12 0.56 0 N - Wall
E - Glass 220.5 12 0.56 1482 OUTSIDE AIR (VENTILATION) NE - Wall
SE - Glass 0 12 0.56 0 90 People X 15 CFM/Person 1350 E - Wall
S - Glass 0 12 0.56 0 48624 Cu ft X 1 Air change per hour 810 SE - Wall
SW - Glass 0 100 0.56 0 CFM VENTILATION 1350 S - Wall
W - Glass 220.5 164 0.56 20251 SW - Wall
NW - Glass 0 130 0.56 0 EFF. SENSIBLE HEAT FACTOR (ESHF) = 0.89 W - Wall
Sky light 0 Indicated ADP = 50.25 °F NW - Wall
SOLAR & TRANS. GAIN WALLS & ROOF Selected ADP = 50.25 °F
ITEM Area Eq. temp. diff. U Dehum. temp rise = 18.15 °F
(Sq ft) (°F) (Btu/h.sq ft) DEHUMIDIFIED CFM = 12863
N - Wall 0 6.4 0.36 0
NE - Wall 0 12.4 0.36 0
E - Wall 902 20.4 0.36 6621
SE - Wall 0 20.4 0.36 0
S - Wall 0 18.4 0.36 0
SW - Wall 0 16.4 0.36 0
W - Wall 901.5 14.4 0.36 4673
NW - Wall 0 8.4 0.36 0
Roof Sun 37.4 0.12 0
Roof Shaded 31 0 NOTES
TRANS. GAIN EXCEPT WALLS & ROOF Occupancy = 90 Nos
ITEM Area Temp. diff. U Lighting = 1.25 W/Sq ft
(Sq ft) (°F) (Btu/h.sq ft) Eq. Load = 24.8 KW
All Glass 441 20.4 1.13 10166 Height = 12.0 FT
Partition 1023.36 15.4 0.32 5043 Fresh Air= 15.0 Cfm per person
Ceiling 4052 15.4 0.32 19968 = 1.0 Air changes per hour
Floor 4052 15.4 0.38 23712 Internal Heat - People
INTERNAL HEAT GAIN Sensible Heat = 245
People 90 Nos X 245 22050 Latent Heat = 205
Light 5065 W X 1.25 3.41 21590 EQUIPMENT NO'S DISSI TOTAL
Eq. Load 24800 W X 3.41 84568 SYSTEM 80 300 24000 WATTS
ROOM SENSIBLE HEAT (RSH) 220124 PRINTER 4 200 800
Supply duct heat Supply duct Heat gain from 4 8805
gain + leak. loss + fan HP(%) 24800 WATTS 24.8 KW
Safety factor (%) 8.5 18711 EQUIPMENT TO BE SELECTED = 32.75TR/12863CFM
OUTSIDE AIR
CFM °F BF FACTOR
1350 20.4 0.15 1.08 4461
EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 252101
LATENT HEAT
People 90 Nos X 205
ROOM LATENT HEAT (RLH) 18450
Supply duct leakage loss + Safety factor % 5.0 923
OUTSIDE AIR
CFM GR/LB BF FACTOR
1350 92.4 0.15 0.68 12723
EFFECTIVE ROOM LATENT HEAT (ERLH) 32096
EFFECTIVE ROOM TOTAL HEAT (ERTH) 284197
OUTSIDE AIR HEAT (SENSIBLE) CHECK FIGURES
CFM °F 1 - BF FACTOR Btu/h/ Sq ft = 97.0
1350 20.4 0.85 1.08 25282 CFM / Sq ft = 3.17
OUTSIDE AIR HEAT (LATENT) Sq ft / TR = 124
CFM GR/LB 1 - BF FACTOR CFM/ TR = 393
1350 92.4 0.85 0.68 72100
HEAT SUB TOTAL 381578
Return duct heat HP Pump + Dehum. & Pipe 3.0 11447
gain & leak. loss + loss (%)

TR 32.75 GRAND TOTAL HEAT 393025


gross(w+g) only glass only wall
0 0 0
0 0 0
1122 220.5 901.5
0 0 0
0 0 0
0 0 0
1122 220.5 901.5
0 0 0

DBT RH
75 50% ESHF 0.92 0.9 0.84
ADP 54 53.5 52
0.25
73.4

72 50% ESHF 0.92 0.89 0.88


ADP 51 50.25 50

75 53.5

73.4 51.9

72 50.5
JOB NAME: OMBR DATE: 6/8/2019 Rev: 0
SPACE FOR: comfort ac Estimated By: ACE
SIZE: 3652 Sq ft 38638 Cu ft Estimate for: SUMMER
SOLAR GAIN GLASS HEAT GAIN CONDITION DB (°F) WB (°F) % RH DP (°F) GR/LB
ITEM Area Sun Gain Factor Btu/hour OUTSIDE 96 78 45 - 116
(Sq ft) (Btu/h.sq ft) ROOM 73.4 62.5 65
N - Glass 0 14 0.56 0 DIFFERENCE 22.6 XXXX XXXX XXXX 51
NE - Glass 0 12 0.56 0 N - Wall
E - Glass 57.2 12 0.56 384 OUTSIDE AIR (VENTILATION) NE - Wall
SE - Glass 0 12 0.56 0 75 People X 15 CFM/Person 1125 E - Wall
S - Glass 346.49 12 0.56 2328 38638 Cu ft X 1 Air change per hour 644 SE - Wall
SW - Glass 0 100 0.56 0 CFM VENTILATION 1125 S - Wall
W - Glass 141.33 164 0.56 12980 SW - Wall
NW - Glass 0 130 0.56 0 EFF. SENSIBLE HEAT FACTOR (ESHF) = 0.86 W - Wall
Sky light 0 Indicated ADP = 52.4 °F NW - Wall
SOLAR & TRANS. GAIN WALLS & ROOF Selected ADP = 52.4 °F
ITEM Area Eq. temp. diff. U Dehum. temp rise = 17.85 °F
(Sq ft) (°F) (Btu/h.sq ft) DEHUMIDIFIED CFM = 6938
N - Wall 468.69 8.6 0.36 1451
NE - Wall 0 14.6 0.36 0
E - Wall 281 22.6 0.36 2286
SE - Wall 0 22.6 0.36 0
S - Wall 0 20.6 0.36 0
SW - Wall 0 18.6 0.36 0
W - Wall 700.838 16.6 0.36 4188
NW - Wall 0 10.6 0.36 0
Roof Sun 0 39.6 0.12 0
Roof Shaded 31 0 NOTES
TRANS. GAIN EXCEPT WALLS & ROOF Occupancy = 75 Nos
ITEM Area Temp. diff. U Lighting = 1.00 W/Sq ft
(Sq ft) (°F) (Btu/h.sq ft) Eq. Load = 11.1 KW
All Glass 545.02 22.6 1.13 13919 Height = 10.6 FT
Partition 1078 17.6 0.32 6071 Fresh Air= 15.0 Cfm per person
Ceiling 0 17.6 0.32 0 = 1.0 Air changes per hour
Floor 0 17.6 0.38 0 Internal Heat - People
INTERNAL HEAT GAIN Sensible Heat = 245
People 75 Nos X 245 18375 Latent Heat = 205
Light 3652 W X 1 3.41 15567 EQUIPMENT NO'S DISSI TOTAL
Eq. Load 11050 W X 3.41 37681 SYSTEM 67 150 10050 WATTS
ROOM SENSIBLE HEAT (RSH) 115230 PRINTER 1 1000 1000
Supply duct heat Supply duct Heat gain from 4 4609
gain + leak. loss + fan HP(%) 11050 WATTS 11.05 KW
Safety factor (%) 8.5 9795 EQUIPMENT TO BE SELECTED = 31.79TR/14411CFM
OUTSIDE AIR
CFM °F BF FACTOR
1125 22.6 0.15 1.08 4119
EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 133753
LATENT HEAT
People 75 Nos X 205
ROOM LATENT HEAT (RLH) 15375
Supply duct leakage loss + Safety factor % 5.0 769
OUTSIDE AIR
CFM GR/LB BF FACTOR
1125 51 0.15 0.68 5852
EFFECTIVE ROOM LATENT HEAT (ERLH) 21996
EFFECTIVE ROOM TOTAL HEAT (ERTH) 155749
OUTSIDE AIR HEAT (SENSIBLE) CHECK FIGURES
CFM °F 1 - BF FACTOR Btu/h/ Sq ft = 59.9
1125 22.6 0.85 1.08 23340 CFM / Sq ft = 1.90
OUTSIDE AIR HEAT (LATENT) Sq ft / TR = 200
CFM GR/LB 1 - BF FACTOR CFM/ TR = 381
1125 51 0.85 0.68 33163
HEAT SUB TOTAL 212252
Return duct heat HP Pump + Dehum. & Pipe 3.0 6368
gain & leak. loss + loss (%)

TR 18.22 GRAND TOTAL HEAT 218619


gross(w+g) only glass only wall
612 40 572
0 0 0
984 860 124
0 0 0
609 40 569
0 0 0
663.96 511.92 152.04
0 0 0

DBT RH
75 50% ESHF 0.92
ADP 54

73.4

72 50% ESHF 0.92


ADP 51

75 54

73.4 52.4

72 51