Heat Load
Heat Load
DBT RH
75 50% ESHF 0.84 0.82 0.78
ADP 52 51.33333 50
0.333333
73.4
75 51.33333
73.4 49.7
72 48.285
JOB NAME: THEOREMS DATE: 6/6/2019 Rev: 0
SPACE FOR: comfort ac Estimated By: ACE
SIZE: 2199.2364 Sq ft 26391 Cu ft Estimate for: SUMMER
SOLAR GAIN GLASS HEAT GAIN CONDITION DB (°F) WB (°F) % RH DP (°F) GR/LB
ITEM Area Sun Gain Factor Btu/hour OUTSIDE 96 78 45 - 120.87
(Sq ft) (Btu/h.sq ft) ROOM 73.4 61.12 61.18
N - Glass 106.272 14 0.56 833 DIFFERENCE 22.6 XXXX XXXX XXXX 59.69
NE - Glass 0 12 0.56 0 N - Wall
E - Glass 105.165 12 0.56 707 OUTSIDE AIR (VENTILATION) NE - Wall
SE - Glass 0 12 0.56 0 25 People X 15 CFM/Person 375 E - Wall
S - Glass 34.686 12 0.56 233 26391 Cu ft X 1 Air change per hour 440 SE - Wall
SW - Glass 0 100 0.56 0 CFM VENTILATION 440 S - Wall
W - Glass 70.11 164 0.56 6439 SW - Wall
NW - Glass 0 130 0.56 0 EFF. SENSIBLE HEAT FACTOR (ESHF) = 0.90 W - Wall
Sky light 0 Indicated ADP = 51.9 °F NW - Wall
SOLAR & TRANS. GAIN WALLS & ROOF Selected ADP = 51.9 °F
ITEM Area Eq. temp. diff. U Dehum. temp rise = 18.28 °F
(Sq ft) (°F) (Btu/h.sq ft) DEHUMIDIFIED CFM = 3611
N - Wall 354.20064 8.6 0.36 1097
NE - Wall 0 14.6 0.36 0
E - Wall 401 22.6 0.36 3259
SE - Wall 0 22.6 0.36 0
S - Wall 262.482 20.6 0.36 1947
SW - Wall 0 18.6 0.36 0
W - Wall 285.7044 16.6 0.36 1707
NW - Wall 0 10.6 0.36 0
Roof Sun 39.6 0.12 0
Roof Shaded 31 0 NOTES
TRANS. GAIN EXCEPT WALLS & ROOF Occupancy = 25 Nos
ITEM Area Temp. diff. U Lighting = 1.00 W/Sq ft
(Sq ft) (°F) (Btu/h.sq ft) Eq. Load = 4.8 KW
All Glass 316.233 22.6 1.13 8076 Height = 12.0 FT
Partition 1023.36 17.6 0.32 5764 Fresh Air= 15.0 Cfm per person
Ceiling 0 17.6 0.32 0 = 1.0 Air changes per hour
Floor 0 17.6 0.38 0 Internal Heat - People
INTERNAL HEAT GAIN Sensible Heat = 245
People 25 Nos X 245 6125 Latent Heat = 205
Light 2199 W X 1.25 3.41 9374 EQUIPMENT NO'S DISSI TOTAL
Eq. Load 4800 W X 3.41 16368 SYSTEM 19 200 3800 WATTS
ROOM SENSIBLE HEAT (RSH) 61929 PRINTER 1 1000 1000
Supply duct heat Supply duct Heat gain from 4 2477
gain + leak. loss + fan HP(%) 4800 WATTS 4.8 KW
Safety factor (%) 8.5 5264 EQUIPMENT TO BE SELECTED = 8.9TR/3611CFM
OUTSIDE AIR
CFM °F BF FACTOR
440 22.6 0.15 1.08 1610
EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 71280
LATENT HEAT
People 25 Nos X 205
ROOM LATENT HEAT (RLH) 5125
Supply duct leakage loss + Safety factor % 5.0 256
OUTSIDE AIR
CFM GR/LB BF FACTOR
440 59.69 0.15 0.68 2678
EFFECTIVE ROOM LATENT HEAT (ERLH) 8059
EFFECTIVE ROOM TOTAL HEAT (ERTH) 79339
OUTSIDE AIR HEAT (SENSIBLE) CHECK FIGURES
CFM °F 1 - BF FACTOR Btu/h/ Sq ft = 48.5
440 22.6 0.85 1.08 9125 CFM / Sq ft = 1.64
OUTSIDE AIR HEAT (LATENT) Sq ft / TR = 247
CFM GR/LB 1 - BF FACTOR CFM/ TR = 406
440 59.69 0.85 0.68 15175
HEAT SUB TOTAL 103640
Return duct heat HP Pump + Dehum. & Pipe 3.0 3109
gain & leak. loss + loss (%)
DBT RH
75 50% ESHF 0.92 0.9 0.84
ADP 54 53.5 52
0.25
73.4
75 53.5
73.4 51.9
72 50.5
JOB NAME: JUST DIAL DATE: 6/6/2019 Rev: 0
SPACE FOR: comfort ac Estimated By: ACE
SIZE: 3078.436 Sq ft 36941 Cu ft Estimate for: SUMMER
SOLAR GAIN GLASS HEAT GAIN CONDITION DB (°F) WB (°F) % RH DP (°F) GR/LB
ITEM Area Sun Gain Factor Btu/hour OUTSIDE 96 78 45 - 120.87
(Sq ft) (Btu/h.sq ft) ROOM 73.4 61.12 61.18
N - Glass 0 14 0.56 0 DIFFERENCE 22.6 XXXX XXXX XXXX 59.69
NE - Glass 454.88352 12 0.56 3057 N - Wall
E - Glass 0 12 0.56 0 OUTSIDE AIR (VENTILATION) NE - Wall
SE - Glass 168.92 12 0.56 1135 110 People X 15 CFM/Person 1650 E - Wall
S - Glass 0 12 0.56 0 36941 Cu ft X 1 Air change per hour 616 SE - Wall
SW - Glass 0 100 0.56 0 CFM VENTILATION 1650 S - Wall
W - Glass 0 164 0.56 0 SW - Wall
NW - Glass 0 130 0.56 0 EFF. SENSIBLE HEAT FACTOR (ESHF) = 0.86 W - Wall
Sky light 0 Indicated ADP = 51.9 °F NW - Wall
SOLAR & TRANS. GAIN WALLS & ROOF Selected ADP = 51.9 °F
ITEM Area Eq. temp. diff. U Dehum. temp rise = 18.28 °F
(Sq ft) (°F) (Btu/h.sq ft) DEHUMIDIFIED CFM = 10200
N - Wall 0 8.6 0.36 0
NE - Wall 64.5504 14.6 0.36 339
E - Wall 0 22.6 0.36 0
SE - Wall 536.37184 22.6 0.36 4364
S - Wall 0 20.6 0.36 0
SW - Wall 482.27808 18.6 0.36 3229
W - Wall 0 16.6 0.36 0
NW - Wall 211.3632 10.6 0.36 807
Roof Sun 39.6 0.12 0
Roof Shaded 31 0 NOTES
TRANS. GAIN EXCEPT WALLS & ROOF Occupancy = 110 Nos
ITEM Area Temp. diff. U Lighting = 1.25 W/Sq ft
(Sq ft) (°F) (Btu/h.sq ft) Eq. Load = 22.0 KW
All Glass 623.80352 22.6 1.13 15931 Height = 12.0 FT
Partition 1023.36 17.6 0.32 5764 Fresh Air= 15.0 Cfm per person
Ceiling 0 17.6 0.32 0 = 1.0 Air changes per hour
Floor 3078.436 17.6 0.38 20589 Internal Heat - People
INTERNAL HEAT GAIN Sensible Heat = 245
People 110 Nos X 245 26950 Latent Heat = 205
Light 3848 W X 1.25 3.41 16402 EQUIPMENT NO'S DISSI TOTAL
Eq. Load 22000 W X 3.41 75020 SYSTEM 105 200 21000 WATTS
ROOM SENSIBLE HEAT (RSH) 173586 PRINTER 1 1000 1000
Supply duct heat Supply duct Heat gain from 4 6943
gain + leak. loss + fan HP(%) 22000 WATTS 22 KW
Safety factor (%) 8.5 14755 EQUIPMENT TO BE SELECTED = 8.9TR/3611CFM
OUTSIDE AIR
CFM °F BF FACTOR
1650 22.6 0.15 1.08 6041
EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 201325
LATENT HEAT
People 110 Nos X 205
ROOM LATENT HEAT (RLH) 22550
Supply duct leakage loss + Safety factor % 5.0 1128
OUTSIDE AIR
CFM GR/LB BF FACTOR
1650 59.69 0.15 0.68 10046
EFFECTIVE ROOM LATENT HEAT (ERLH) 33723
EFFECTIVE ROOM TOTAL HEAT (ERTH) 235049
OUTSIDE AIR HEAT (SENSIBLE) CHECK FIGURES
CFM °F 1 - BF FACTOR Btu/h/ Sq ft = 109.1
1650 22.6 0.85 1.08 34232 CFM / Sq ft = 3.31
OUTSIDE AIR HEAT (LATENT) Sq ft / TR = 110
CFM GR/LB 1 - BF FACTOR CFM/ TR = 364
1650 59.69 0.85 0.68 56926
HEAT SUB TOTAL 326207
Return duct heat HP Pump + Dehum. & Pipe 3.0 9786
gain & leak. loss + loss (%)
DBT RH
75 50% ESHF 0.92 0.9 0.84
ADP 54 53.5 52
0.25
73.4
75 53.5
73.4 51.9
72 50.5
JOB NAME: ATALANTIC DATE: 6/6/2019 Rev: 0
SPACE FOR: comfort ac Estimated By: ACE
SIZE: 4052 Sq ft 48624 Cu ft Estimate for: SUMMER
SOLAR GAIN GLASS HEAT GAIN CONDITION DB (°F) WB (°F) % RH DP (°F) GR/LB
ITEM Area Sun Gain Factor Btu/hour OUTSIDE 92 82 28 - 149.8
(Sq ft) (Btu/h.sq ft) ROOM 71.6 59.64 57.4
N - Glass 0 14 0.56 0 DIFFERENCE 20.4 XXXX XXXX XXXX 92.4
NE - Glass 0 12 0.56 0 N - Wall
E - Glass 220.5 12 0.56 1482 OUTSIDE AIR (VENTILATION) NE - Wall
SE - Glass 0 12 0.56 0 90 People X 15 CFM/Person 1350 E - Wall
S - Glass 0 12 0.56 0 48624 Cu ft X 1 Air change per hour 810 SE - Wall
SW - Glass 0 100 0.56 0 CFM VENTILATION 1350 S - Wall
W - Glass 220.5 164 0.56 20251 SW - Wall
NW - Glass 0 130 0.56 0 EFF. SENSIBLE HEAT FACTOR (ESHF) = 0.89 W - Wall
Sky light 0 Indicated ADP = 50.25 °F NW - Wall
SOLAR & TRANS. GAIN WALLS & ROOF Selected ADP = 50.25 °F
ITEM Area Eq. temp. diff. U Dehum. temp rise = 18.15 °F
(Sq ft) (°F) (Btu/h.sq ft) DEHUMIDIFIED CFM = 12863
N - Wall 0 6.4 0.36 0
NE - Wall 0 12.4 0.36 0
E - Wall 902 20.4 0.36 6621
SE - Wall 0 20.4 0.36 0
S - Wall 0 18.4 0.36 0
SW - Wall 0 16.4 0.36 0
W - Wall 901.5 14.4 0.36 4673
NW - Wall 0 8.4 0.36 0
Roof Sun 37.4 0.12 0
Roof Shaded 31 0 NOTES
TRANS. GAIN EXCEPT WALLS & ROOF Occupancy = 90 Nos
ITEM Area Temp. diff. U Lighting = 1.25 W/Sq ft
(Sq ft) (°F) (Btu/h.sq ft) Eq. Load = 24.8 KW
All Glass 441 20.4 1.13 10166 Height = 12.0 FT
Partition 1023.36 15.4 0.32 5043 Fresh Air= 15.0 Cfm per person
Ceiling 4052 15.4 0.32 19968 = 1.0 Air changes per hour
Floor 4052 15.4 0.38 23712 Internal Heat - People
INTERNAL HEAT GAIN Sensible Heat = 245
People 90 Nos X 245 22050 Latent Heat = 205
Light 5065 W X 1.25 3.41 21590 EQUIPMENT NO'S DISSI TOTAL
Eq. Load 24800 W X 3.41 84568 SYSTEM 80 300 24000 WATTS
ROOM SENSIBLE HEAT (RSH) 220124 PRINTER 4 200 800
Supply duct heat Supply duct Heat gain from 4 8805
gain + leak. loss + fan HP(%) 24800 WATTS 24.8 KW
Safety factor (%) 8.5 18711 EQUIPMENT TO BE SELECTED = 32.75TR/12863CFM
OUTSIDE AIR
CFM °F BF FACTOR
1350 20.4 0.15 1.08 4461
EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 252101
LATENT HEAT
People 90 Nos X 205
ROOM LATENT HEAT (RLH) 18450
Supply duct leakage loss + Safety factor % 5.0 923
OUTSIDE AIR
CFM GR/LB BF FACTOR
1350 92.4 0.15 0.68 12723
EFFECTIVE ROOM LATENT HEAT (ERLH) 32096
EFFECTIVE ROOM TOTAL HEAT (ERTH) 284197
OUTSIDE AIR HEAT (SENSIBLE) CHECK FIGURES
CFM °F 1 - BF FACTOR Btu/h/ Sq ft = 97.0
1350 20.4 0.85 1.08 25282 CFM / Sq ft = 3.17
OUTSIDE AIR HEAT (LATENT) Sq ft / TR = 124
CFM GR/LB 1 - BF FACTOR CFM/ TR = 393
1350 92.4 0.85 0.68 72100
HEAT SUB TOTAL 381578
Return duct heat HP Pump + Dehum. & Pipe 3.0 11447
gain & leak. loss + loss (%)
DBT RH
75 50% ESHF 0.92 0.9 0.84
ADP 54 53.5 52
0.25
73.4
75 53.5
73.4 51.9
72 50.5
JOB NAME: OMBR DATE: 6/8/2019 Rev: 0
SPACE FOR: comfort ac Estimated By: ACE
SIZE: 3652 Sq ft 38638 Cu ft Estimate for: SUMMER
SOLAR GAIN GLASS HEAT GAIN CONDITION DB (°F) WB (°F) % RH DP (°F) GR/LB
ITEM Area Sun Gain Factor Btu/hour OUTSIDE 96 78 45 - 116
(Sq ft) (Btu/h.sq ft) ROOM 73.4 62.5 65
N - Glass 0 14 0.56 0 DIFFERENCE 22.6 XXXX XXXX XXXX 51
NE - Glass 0 12 0.56 0 N - Wall
E - Glass 57.2 12 0.56 384 OUTSIDE AIR (VENTILATION) NE - Wall
SE - Glass 0 12 0.56 0 75 People X 15 CFM/Person 1125 E - Wall
S - Glass 346.49 12 0.56 2328 38638 Cu ft X 1 Air change per hour 644 SE - Wall
SW - Glass 0 100 0.56 0 CFM VENTILATION 1125 S - Wall
W - Glass 141.33 164 0.56 12980 SW - Wall
NW - Glass 0 130 0.56 0 EFF. SENSIBLE HEAT FACTOR (ESHF) = 0.86 W - Wall
Sky light 0 Indicated ADP = 52.4 °F NW - Wall
SOLAR & TRANS. GAIN WALLS & ROOF Selected ADP = 52.4 °F
ITEM Area Eq. temp. diff. U Dehum. temp rise = 17.85 °F
(Sq ft) (°F) (Btu/h.sq ft) DEHUMIDIFIED CFM = 6938
N - Wall 468.69 8.6 0.36 1451
NE - Wall 0 14.6 0.36 0
E - Wall 281 22.6 0.36 2286
SE - Wall 0 22.6 0.36 0
S - Wall 0 20.6 0.36 0
SW - Wall 0 18.6 0.36 0
W - Wall 700.838 16.6 0.36 4188
NW - Wall 0 10.6 0.36 0
Roof Sun 0 39.6 0.12 0
Roof Shaded 31 0 NOTES
TRANS. GAIN EXCEPT WALLS & ROOF Occupancy = 75 Nos
ITEM Area Temp. diff. U Lighting = 1.00 W/Sq ft
(Sq ft) (°F) (Btu/h.sq ft) Eq. Load = 11.1 KW
All Glass 545.02 22.6 1.13 13919 Height = 10.6 FT
Partition 1078 17.6 0.32 6071 Fresh Air= 15.0 Cfm per person
Ceiling 0 17.6 0.32 0 = 1.0 Air changes per hour
Floor 0 17.6 0.38 0 Internal Heat - People
INTERNAL HEAT GAIN Sensible Heat = 245
People 75 Nos X 245 18375 Latent Heat = 205
Light 3652 W X 1 3.41 15567 EQUIPMENT NO'S DISSI TOTAL
Eq. Load 11050 W X 3.41 37681 SYSTEM 67 150 10050 WATTS
ROOM SENSIBLE HEAT (RSH) 115230 PRINTER 1 1000 1000
Supply duct heat Supply duct Heat gain from 4 4609
gain + leak. loss + fan HP(%) 11050 WATTS 11.05 KW
Safety factor (%) 8.5 9795 EQUIPMENT TO BE SELECTED = 31.79TR/14411CFM
OUTSIDE AIR
CFM °F BF FACTOR
1125 22.6 0.15 1.08 4119
EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 133753
LATENT HEAT
People 75 Nos X 205
ROOM LATENT HEAT (RLH) 15375
Supply duct leakage loss + Safety factor % 5.0 769
OUTSIDE AIR
CFM GR/LB BF FACTOR
1125 51 0.15 0.68 5852
EFFECTIVE ROOM LATENT HEAT (ERLH) 21996
EFFECTIVE ROOM TOTAL HEAT (ERTH) 155749
OUTSIDE AIR HEAT (SENSIBLE) CHECK FIGURES
CFM °F 1 - BF FACTOR Btu/h/ Sq ft = 59.9
1125 22.6 0.85 1.08 23340 CFM / Sq ft = 1.90
OUTSIDE AIR HEAT (LATENT) Sq ft / TR = 200
CFM GR/LB 1 - BF FACTOR CFM/ TR = 381
1125 51 0.85 0.68 33163
HEAT SUB TOTAL 212252
Return duct heat HP Pump + Dehum. & Pipe 3.0 6368
gain & leak. loss + loss (%)
DBT RH
75 50% ESHF 0.92
ADP 54
73.4
75 54
73.4 52.4
72 51