DOL 534 - DOL 539: Climate Controller User Manual
DOL 534 - DOL 539: Climate Controller User Manual
Climate Controller
User Manual
In case of an operating error or inappropriate use, ventilation systems can result in production
losses or cause loss of lives among livestock.
We recommend that ventilation systems should be mounted, operated and serviced only by
trained staff and that a separate emergency opening unit and an alarm system be installed as well
as maintained and tested at regular intervals, according to terms and conditions of sale and deliv-
ery.
Installation, servicing and troubleshooting of all electrical equipment must be carried out by quali-
fied personnel in compliance with the applicable national and international standard EN 60204-1
and any other EU standards that are applicable in Europe.
The installation of a power supply isolator is required for each motor and power supply to facilitate
voltage-free work on the electrical equipment. The power supply isolator is not included.
Note
• All rights belong to SKOV A/S. No part of this manual may be reproduced in any manner whatsoever without
the expressed written permission of SKOV A/S in each case.
• All reasonable efforts have been made to ensure the accuracy of the information contained in this manual.
Should any mistakes or imprecise information occur in spite of this, SKOV A/S would appreciate being noti-
fied thereof.
• Irrespective of the above, SKOV A/S shall not accept any liability with regard to loss or damage caused or
alleged to be caused by reliance on any information contained herein.
• Copyright by SKOV A/S.
User Manual 3
DOL 534 • DOL 539
1 Guidelines ....................................................................................................................................................... 7
3 Operating instructions................................................................................................................................... 9
3.1 Operation .................................................................................................................................... 9
3.2 Daily use ................................................................................................................................... 10
3.3 TrustMe ..................................................................................................................................... 11
3.4 Activity log................................................................................................................................ 11
3.5 Pages ........................................................................................................................................ 13
3.5.1 Selecting default pages.............................................................................................................. 13
3.5.2 Page types ................................................................................................................................. 13
3.5.2.1 Daily view................................................................................................................................... 13
3.5.2.2 House view ................................................................................................................................ 15
3.5.2.3 Program overview ...................................................................................................................... 16
3.5.2.4 Ventilation view .......................................................................................................................... 17
3.5.3 Creating pages........................................................................................................................... 18
3.5.3.1 Simplifying settings in 2 zone houses ........................................................................................ 20
3.5.4 Edit pages .................................................................................................................................. 20
3.6 Settings..................................................................................................................................... 21
3.7 Search in menus ...................................................................................................................... 22
3.8 Selection of language.............................................................................................................. 23
3.9 Password .................................................................................................................................. 23
4 Climate .......................................................................................................................................................... 25
4.1 Automatic climate control....................................................................................................... 25
4.2 Temperature ............................................................................................................................. 26
4.3 Humidity.................................................................................................................................... 26
4.3.1 Humidification ............................................................................................................................ 28
4.3.2 Humidity control mode ............................................................................................................... 29
4.3.2.1 Humidity ventilation.................................................................................................................... 29
4.3.2.2 Temperature reduction............................................................................................................... 30
4.3.2.3 Humidity heat ............................................................................................................................. 31
4.3.3 Intelligent humidity control - at high outside temperature and outside humidity ........................ 32
4.3.4 Humidity settings........................................................................................................................ 33
4.3.4.1 Adaptive humidity ventilation ..................................................................................................... 33
4.3.4.2 Adaptive humidity heat............................................................................................................... 33
4.4 CO2............................................................................................................................................ 33
4.5 NH3............................................................................................................................................ 34
4.6 Pressure.................................................................................................................................... 35
4.7 Heat recovery unit.................................................................................................................... 35
4.8 Ventilation................................................................................................................................. 37
4.8.1 Adaptive ventilation control ........................................................................................................ 38
4.8.2 Parking of fans ........................................................................................................................... 38
4.8.3 Ventilation settings..................................................................................................................... 39
4.8.4 Ventilation status........................................................................................................................ 39
4.8.4.1 Cycle timer at minimum air intake.............................................................................................. 40
4.8.5 Zone controlled inlet................................................................................................................... 40
4.8.6 Inlet de-ice ................................................................................................................................. 41
4.9 Side cooling.............................................................................................................................. 42
4.9.1 Nozzle cleaning.......................................................................................................................... 43
4.9.2 Start cooling ............................................................................................................................... 43
4.9.2.1 Side cooling start based on ventilation level .............................................................................. 43
4.9.2.1.1 Cooling priority ........................................................................................................................... 44
4.9.2.1.2 Cooling potential ........................................................................................................................ 45
User Manual
DOL 534 • DOL 539
5 Management ................................................................................................................................................. 60
5.1 House data................................................................................................................................ 60
5.1.1 House status Active house - Empty house ................................................................................ 60
5.1.2 Settings ...................................................................................................................................... 61
5.1.2.1 Preheating by day number......................................................................................................... 62
5.1.3 Settings ...................................................................................................................................... 62
5.1.3.1 Preheating by day number......................................................................................................... 63
5.2 History curves .......................................................................................................................... 63
5.3 Batch curves ............................................................................................................................ 63
5.3.1 Setting curves ............................................................................................................................ 64
5.4 In-between functions ............................................................................................................... 65
5.4.1 Empty house .............................................................................................................................. 66
5.4.2 Settings ...................................................................................................................................... 67
5.4.3 Preheating.................................................................................................................................. 67
5.4.4 Temperature surveillance .......................................................................................................... 68
5.5 Ventilation boost...................................................................................................................... 68
5.6 Equipment status..................................................................................................................... 70
5.7 Catching.................................................................................................................................... 70
5.8 Auxiliary sensors ..................................................................................................................... 71
5.9 Consumption............................................................................................................................ 71
6 Alarms ........................................................................................................................................................... 72
6.1 Stopping an alarm signal ........................................................................................................ 72
6.2 Alarm test ................................................................................................................................. 73
6.3 Power failure alarm.................................................................................................................. 73
6.4 Alarm settings .......................................................................................................................... 73
6.4.1 Master/Client alarms .................................................................................................................. 73
6.4.2 Temperature alarms................................................................................................................... 73
6.4.3 Humidity alarm ........................................................................................................................... 75
6.4.4 Inlet and outlet alarm ................................................................................................................. 75
6.4.5 Sensor alarm.............................................................................................................................. 76
6.4.6 Tunnel cooling sensor alarm...................................................................................................... 76
6.4.7 Pressure sensor......................................................................................................................... 76
6.4.8 Auxiliary sensor and CO2 alarm ................................................................................................ 77
6.4.9 NH3 alarm.................................................................................................................................. 77
User Manual
DOL 534 • DOL 539
User Manual
DOL 534 • DOL 539
1 Guidelines
This user manual deals with the daily operation of the house controller. The manual provides the fundamental
knowledge about the functions of the controller that is required to ensure optimum use of it.
Some functions are optional and only used in specific set-ups of the house controller. These func-
tions are shown with an optional icon.
If a function is not used, e.g. 24-hour clock, it is not shown in the user menus of the controller. The manual may
therefore contain sections that are not relevant to the specific setup of your controller. See also the Technical
Manual or, if necessary, contact service or your dealer.
This manual's Operating Instructions consists of a general introduction, which describes briefly how to operate
the house controller.
This is followed by descriptions of the controller functions.
User Manual 7
DOL 534 • DOL 539
2 Product description
DOL 53X is a series of one-house controllers specifically designed for poultry houses. The controller series in-
cludes several variants. Each of them meets the different requirements for climate and production control in
connection with the production forms and geographical climatic conditions.
• DOL 534 climate controller
• DOL 535 production controller
• DOL 539 climate and production controller (obtained by combining DOL 534 and DOL 535)
The controller is operated via a large touch display with graphical views of the ventilation status, icons and
curves, among other things. The pages shown in the display may be adapted in accordance with the user re-
quirements so that the most frequently used working procedures are easily accessible. In addition, a wide range
of functions such as 24-hour clock, light, water meter, and extra - sensor are named by the user, so the func-
tions are easier to recognize in menus and alarms.
Along with two USB ports, DOL 53X provides two LAN ports for connection of the management program Far-
mOnline.
8 User Manual
DOL 534 • DOL 539
3 Operating instructions
3.1 Operation
The climate and production controller is operated by means of the touch display.
The view in the display is called a page. You can scroll both up/down and right/left to see the entire page.
C D E
B F
A G
H
J
I
User Manual 9
DOL 534 • DOL 539
You can take a step back in menus by pressing the button with
the arrow pointing left in the left corner.
10 User Manual
DOL 534 • DOL 539
3.3 TrustMe
TrustMe information is meant to give a better understanding of how the controller is working.
For selected control areas the following is described:
• the current status.
• the reason for the current adjustment.
• what the next step in adjustment will be.
The information is available from pages with cards with the icon
in the right corner.
Press the card to see how the controller is currently working.
Press the icon in the left corner to close the window again.
The TrustMe information can also be added as a card to a
page. See also Creating pages [} 18].
User Manual 11
DOL 534 • DOL 539
C D
12 User Manual
DOL 534 • DOL 539
3.5 Pages
A page is a user-defined display of selected values, graphs and settings. Pages therefore provide quick access
to reading and operation.
We recommend that you create a number of pages to show exactly the functions and values used in the individ-
ual house and that cover the needs of the daily user.
A B C D
A Temperature
The house controller displays the current inside temperature.
User Manual 13
DOL 534 • DOL 539
Click on or to adjust the inside temperature to the required temperature in the house.
Adjustment: +/- 0.5 oC
Next possible adjustment: in two hours.
B Humidity
The controller displays the current air humidity.
Click on or to adjust the humidity to the required air humidity in the house.
Adjustment: +/- 5%
Next possible adjustment: in 24 hours.
C Air quality
The controller displays the current minimum ventilation in the house.
14 User Manual
DOL 534 • DOL 539
User Manual 15
DOL 534 • DOL 539
D
B
A
16 User Manual
DOL 534 • DOL 539
User Manual 17
DOL 534 • DOL 539
Select the content you want on the page (views in top cards
and/or key values in cards).
To layout the columns as you want or to group cards, you can
also insert Empty cards.
18 User Manual
DOL 534 • DOL 539
A Press the one of the tools to edit headlines or card content, to move or delete the cards.
Edit
Move
Delete
B When a tool is selected, the icons on the cards change to reflect the tool.
C Add more cards.
D Finish the setup by pressing Confirm.
When editing cards, several cards can be joined together, for example you can join Temperature with Tempera-
ture setpoint.
First select the editing tool and click on the key value you
want to add setpoints to.
Select Key value 2 and select the key value to be displayed.
Select Key value 3, if required and select the key value to be
displayed.
If the values are also displayed as graphs, the graphs can also
be shown in the card.
To the right in the menu a preview of the card is shown.
You can add up to two key values to a status view. For exam-
ple, you can join:
Temperature + Temperature setpoint
Humidity + Humidity setpoint
Ventilation + Minimum ventilation/animal
Heating + Heat offset
Feed consumption + Add feed
Provided that the functions are supported by the controller.
User Manual 19
DOL 534 • DOL 539
20 User Manual
DOL 534 • DOL 539
3.6 Settings
The settings menu is opened by pressing Overview and then Settings .
The menu is divided into the following sub-menus: Climate, Production, Management, Alarm settings, Techni-
cal and General.
The display will show the menu that was last opened.
The menu opens to the left and settings are made to the right.
Activating/deactivating functions
Functions can be activated and deactivated by means of the
toggle button.
Scroll up/down
If the page or menu is higher than the display, you can scroll
up/down.
The possibility to scroll is shown by the arrows in the display.
You can scroll by pressing the arrows or letting your finger slide
across the display.
Scroll right/left
If the page or menu is wider than the display, you can scroll
right/left.
The option of scrolling right/left can be seen by the shadow in
the first column in the menu.
You can scroll by letting your finger slide across the display.
User Manual 21
DOL 534 • DOL 539
The result is shown under the search field to the left on the
screen. The path for the individual menus is also shown, for ex-
ample: Climate | Ventilation | Information.
22 User Manual
DOL 534 • DOL 539
3.9 Password
This section is only relevant to houses where the Password function is activated.
The controller can be protected against unauthorized operation with the use of passwords. This function can be
activated in the menu | Management | Use password.
In order to gain access to changing a setting, you must enter a password that corresponds to the user level
where the relevant function is located (Daily, Advanced and Service).
Enter the code.
After entering the password, the controller can be operated at
the corresponding user level. After 10 minutes without opera-
tion, the user is automatically logged off.
User Manual 23
DOL 534 • DOL 539
Activate the function Use password for technical menu only to make the controller require the Service
password only when the user wants to change settings in the menus Installation, Calibration and Ser-
vice.
You can change the password for each of the three user levels in the menu | Management | Password.
In order to gain access to changing a password, you must first enter the valid password.
User level Gives access to Factory-set code
Daily view Entering the number of animals
(without login) Fine-tuning of temperature, humidity and air quality
Daily Daily: 1111
Changing of set values
Advanced Daily + advanced: 2222
Changing of curves and alarm settings
Set the house controller in manual mode
Service Daily + advanced + service: 3333
Changing of settings under Technical menu
24 User Manual
DOL 534 • DOL 539
4 Climate
4.1 Automatic climate control
The controller automatically regulates and monitors a large number of factors that are important for the climate
in the house - e.g. air change and temperature. It can regulate very precisely and maintain the required temper-
ature and humidity level in the house.
Fresh air in
With correct setup of the house controller, the daily user of the house should only exceptionally need to make
manual changes to the settings.
User Manual 25
DOL 534 • DOL 539
4.2 Temperature
The controller adjusts the inside temperature according to the Temperature setpoint.
When the inside temperature is too high, the controller increases the ventilation level to supply more fresh air.
When the temperature is too low, the controller reduces the ventilation level to keep the heat in the house; the
heating level is increased if needed.
Ventilation
- air change
- air speed
Heating
Cooling
The most important temperature values can be seen and adjusted on the page types Daily view, Climate and
House view. See also Daily view [} 13] and House view [} 15].
The following sections describe the functions and setting options available in the temperature menu.
It is possible to search for functions via the search function in the Settings menu. See section
Search in menus [} 22].
4.3 Humidity
This section is relevant only to houses with a humidity sensor.
The air humidity in the house is important both for the indoor climate and for the well-being of the animals. In re-
lation to air humidity the regulation must ensure a suitable level - neither too high nor too low.
When the animals are young, it is especially important to avoid a very high humidity level (> 80%) in order to
limit pathogens in the environment. A very low humidity level (<40%) can dry out the house, but also the ani-
mals.
In relation to animal welfare, it is generally more important to keep the correct inside temperature than to keep
the humidity within a precise level. Therefore, the house controller regulates for humidity only when the temper-
ature control allows it.
26 User Manual
DOL 534 • DOL 539
Note that a combination of a high inside temperature and high air humidity (>85%) can be life-threatening
to the animals.
Ventilation
- air change
Heating
Cooling
Humidity is supplied to the housing air partly from the animals, feed, drinking water and litter, and partly from the
cooling and humidification functions.
Basically, the humidity of the house can be regulated by either increasing or decreasing the ventilation level or
by increasing or decreasing the heat supply. The house controller has several humidity control principles, which
you can choose from depending on what suits the house in question. See section Humidity control mode
[} 29].
The most important humidity values can be seen and adjusted on the page types Daily view, Climate and House
view. See also section Daily view and House view.
Adaptive control
From the factory the control is set to adaptive control. This means that the house controller constantly adapts
the regulation to the current conditions. Thus, there is less need for the user to make manual changes to set-
tings.
The following sections describe the functions and setting options available in the humidity menu.
It is possible to search for functions via the search function in the Settings menu. See section
Search in menus [} 22].
Climate | Humidity
Current humidity Display of current humidity level.
Humidity ventilation Display of how much is being ventilated due to humidity.
Outside humidity Current outside humidity level.
Humidity setpoint Setting the upper air humidity limit.
If you need to adjust the humidity, it is recommended to change it 3% and wait 3-4
days. Then assess whether further adjustment is necessary.
Humidity control mode Selecting type of humidity control. See also the section Humidity control mode
[} 29].
Humidity control status Display of the current humidity control. See section Intelligent humidity control -
at high outside temperature and outside humidity [} 32].
User Manual 27
DOL 534 • DOL 539
4.3.1 Humidification
Humidification increases the air humidity of the house by supplying atomized water to the air. It is important to
maintain a certain air humidity, among other things to prevent dehydration of the animals’ mucous membranes.
The house controller increases humidification as long as the air humidity is below the humidification setpoint.
During batch production, the house controller can automatically regulate the humidification in relation to the age
of the animals by adjusting the batch curve. See also the section Batch curves.
Climate | Humidity
Humidification require- Display of current humidification requirement.
ment
Humidification setpoint Setting of lower air humidity limit.
Can be set to a maximum of 5% below Humidity setpoint.
Humidification last day Setting of the day number when the house controller deactivates humidification.
The house controller thus humidifies only at the start of the batch, until the natural
humidity level in the house has reached the desired level.
28 User Manual
DOL 534 • DOL 539
Humidification/ventilation %
Humidification
Ventilation
Air humidity %
1. Humidification setpoint 2. Humidity setpoint
Figure 1: 1. Decreasing air humidity. The air humidity is below Humidification setpoint. The house controller starts the humid-
ification. 2. Increasing air humidity The air humidity is above humidity setpoint. The house controller increases the ventila-
tion.
Temperature
Temperature drop 1 °C
ON OFF Humidification
Figure 2: Decreasing temperature: Humidification will be disconnected if the inside temperature is 1° C below Temperature
setpoint. Humidification could otherwise make the inside temperature drop further.
If the temperature falls so much that the relative air humidity reaches 100%, the water vapor will start to con-
dense (dew point).
These general principles can be exploited by choosing the humidity control mode that best suits the require-
ments of the animals and the individual house (geographical location).
The house controller has 3 primary humidity control modes, each of which takes its own area into account.
User Manual 29
DOL 534 • DOL 539
When the house controller has been set to control humidity according to the humidity heat principle, it will re-
duce a too high humidity level by gradually increasing the ventilation. The increased air change will make the in-
side temperature fall. To maintain the temperature of heating temperature, the heating system will gradually
supply more heating.
Humidity ventilation makes it possible to keep the house air humidity at the set humidity.
Ventilation %
2. Increased ventilation
Minimum ventilation
Air humidity %
1. Humidity setpoint
Figure 3: Humidity ventilation: 1. The air humidity exceeds humidity setpoint. 2. The house controller increases ventilation. 3.
Increase up to maximum humidity ventilation (35%).
Maximum humidity ventilation can be set with a batch curve in the menu Management | Batch curves | Cli-
mate. This especially relevant to livestock houses with limited heating capacity where you would prefer a lower
degree of humidity ventilation at the start of a batch when the animals are small.
30 User Manual
DOL 534 • DOL 539
The humidity control process is the same as for heat supply until the point at which ventilation is reduced to min-
imum ventilation. Without heat supply, the inside temperature could continue to drop below the Heat setpoint.
Inside temperature
2. Temperature setpoint
Air humidity
1. Humidity setpoint
Figure 4: Humidity control with temperature reduction
The house controller will lower the set temperature by 1° C each time the air humidity exceeds the humidity set-
point by 5 %.
Heating costs
Check the heat consumption at regular intervals when using the principle of humidity heating to regulate
the house humidity. Settings for heating and humidity control should be checked to avoid excessive heat-
ing costs.
User Manual 31
DOL 534 • DOL 539
The intelligent humidity control takes over when the following conditions are met:
1. High inside humidity (higher than Humidity setpoint)
2. High outside humidity (exceeds the limit for Outside humidity)
3. High outside temperature (higher than the Temperature setpoint of 6°C)
32 User Manual
DOL 534 • DOL 539
4.4 CO2
This section is relevant only to houses with a CO2 sensor.
Using a CO2 sensor, you can monitor the current CO2 level in the livestock house and use it as an indicator of
the air quality.
The feature either increases or lowers the minimum ventilation and the current ventilation level, depending on
the atmospheric CO2 content. i.e., if it was higher or lower than the set CO2.
The following sections describe the functions and setting options available in the CO2 menu.
It is possible to search for functions via the search function in the Settings menu. See section
Search in menus [} 22].
Climate | CO2
Current CO2 Current CO2 level.
CO2 setpoint Upper limit of CO2 in the air.
When the CO2 content in the air exceeds the CO2 setpoint, the function increases
the ventilation. The controller reduces the minimum ventilation if the CO2 level in the
livestock house is below the CO2 setpoint.
User Manual 33
DOL 534 • DOL 539
CO2 minimum ventilation Current ventilation requirement (a percentage of the capacity of the ventilation sys-
tem) to keep the CO2 level below the CO2 setpoint.
Use CO2 minimum venti- You can connect and disconnect the CO2 minimum ventilation function that is active
lation when the minimum ventilation is active.
4.5 NH3
This section is relevant only to houses with a NH3 sensor.
By using a NH3 sensor, the current NH3 level (ammonia) in the house can be monitored and used as an indica-
tor of the air quality.
This function increases the ventilation and the current ventilation level depending on the air’s NH3 content, that
is if it is higher than the NH3 setpoint. Ventilation due to NH3 can, however, not exceed 25% of the ventilation.
The following sections describe the functions and setting options available in the NH3 menu.
It is possible to search for functions via the search function in the Settings menu. See section
Search in menus [} 22].
Climate | NH3
Current NH3 Current NH3 level.
NH3 ventilation Current ventilation requirement (a percentage of the capacity of the ventilation sys-
tem) to keep the NH3 level below the NH3 setpoint.
NH3 setpoint The upper limit of NH3 in the air.
When the NH3 in the air exceeds the NH3 setpoint, the function increases the venti-
lation.
Apply NH3 ventilation You can connect and disconnect the NH3 ventilation function.
If the inside temperature drops below the heating setpoint, the climate controller will gradually reduce the NH3
ventilation.
34 User Manual
DOL 534 • DOL 539
4.6 Pressure
This section is relevant only to houses with pressure control.
By means of a pressure sensor, the house controller can control the pressure level in the house. On the basis of
the sensor measurements, the climate controller controls the opening of the flaps; this way, it maintains the re-
quired pressure level in the house.
The following sections describe the functions and setting options available in the pressure menu.
It is possible to search for functions via the search function in the Settings menu. See section
Search in menus [} 22].
Climate | Pressure
Pressure Display of the current pressure level in the house.
Pressure setpoint Setting of the pressure level.
Active in side mode Connection and disconnection of pressure control at side ventilation.
Active in tunnel mode Connection and disconnection of pressure control at tunnel ventilation.
Pressure inlet require- Percentage indication of how much the flaps must be open to maintain Pressure
ment setpoint.
The heat recovery unit can be controlled as an integrated part of the house ventilation system. It is used to re-
cover heat in the low ventilation area for a number of days at the beginning of a batch. When a higher air output
is needed than the capacity of the heat recovery unit, the ordinary ventilation system will gradually take over.
The heat recovery unit has two fans. One of the fans removes warm, humid air from the house. The other fan
draws fresh, preheated air into the house.
Cooled/humid air
Outside
Air inlet
Preheated, dry air
Figure 5: Example of heat recovery unit principle.
User Manual 35
DOL 534 • DOL 539
The following sections describe the functions and setting options available in the heat recovery unit menu.
It is possible to search for functions via the search function in the Settings menu. See section
Search in menus [} 22].
Temperature
Disconnected
Deactivate
Connected - below temperature setpoint
Day number
Figure 6: Heat recovery unit – low and high outside temperature limits
Anti-icing function
Anti-ice View of whether the function is active or not.
36 User Manual
DOL 534 • DOL 539
When the anti-ice function is active, the air inlet of the heat recovery unit alternately
turns on and off to prevent ice from forming in the unit.
Anti ice active at outside Setting the outside temperature which activates the anti-ice function.
temperature below
Anti-ice sensor View of current temperature at the anti-ice sensor. The sensor value is not used for
controlling the anti-ice function.
Activate heat Connection and disconnection of an external heat source in connection with the
heat recovery unit.
Cleaning program
Cleaning programs When the heat recovery unit used has a built-in cleaning system, the house con-
troller can run up to three cleaning programs per 24 hours.
Setting of number of cleaning programs per 24 hours.
Setting the start and stop times for the cleaning programs.
Info Status views of the heat recovery unit's individual parts.
4.8 Ventilation
The house ventilation consists of air inlets and air outlets. Apart from supplying fresh air to the the house, venti-
lation is to remove humidity and excess heat, if any.
The controller continuously adjusts the ventilation according to a calculation of the ventilation requirement.
Thus, the controller will increase or limit ventilation according to whether the inside temperature and air humidity
are too high or too low.
Temperature
Humidity
The most important ventilation values such as minimum ventilation and ventilation requirement can be set up to
be viewed and adjusted on a page.
User Manual 37
DOL 534 • DOL 539
The following sections describe the functions and setting options available in the ventilation menu.
It is possible to search for functions via the search function in the Settings menu. See section
Search in menus [} 22].
We recommend that you only use parking for fans that are not actually in use. Otherwise, the ventilation control
cannot automatically adapt to the changed ventilation capacity.
If you need to switch MultiStep often between parked and active, it is an advantage to create a page with short-
cuts for the function. See also section Creating pages [} 18].
If fans are parked and ventilation has been running at maximum for 5 minutes, the controller will give a soft
alarm to make you aware that you should activate the fans again.
Parking of fans must not be used as safety breaker in case of servicing the fan.
38 User Manual
DOL 534 • DOL 539
Be aware that if you park all tunnel fans in a Combi-Tunnel system, the controller can still switch to tunnel
regulation of the ventilation - but without actually being able to use the tunnel fans.
This can be catastrophic for the animals.
Climate | Ventilation
Minimum ventilation The lower limit for how little is ventilated in relation to the air requirement of the
animals.
The minimum ventilation function supplies the exact amount of air to the house, which ensures an acceptable
air quality. The function is particularly relevant in periods with cold weather when it is not necessary to ventilate
to keep down the inside temperature.
The controller calculates the necessary minimum ventilation according to the animals’ need for fresh air.
The animals' fresh air requirement varies according to the type of animal and weight. You must indicate the re-
quirement as cubic meters per hour (m3/h) per animal. You can find the correct figure in the technical literature
or ask your consultant if in doubt.
Note that the correct number of animals must be set in the menu Management | Animals.
Reduced minimum ventilation
In houses where a high minimum ventilation is required to avoid high CO2 and ammonia levels, it may be rele-
vant to use the Reduced minimum ventilation function. This function allows the minimum ventilation to follow the
outside temperature.
Climate | Ventilation
Maximum ventilation Upper limit for how much of the system's capacity the controller can activate.
Maximum ventilation sets a limit to how much of the capacity of the ventilation system (in percentage) the con-
troller can activate. 100% ventilation corresponds to the animals’ calculated requirement, while ventilation utiliz-
ing the total system capacity may reach e.g. 160% (see also the section on extra ventilation).
The function can be relevant to use during very high outside temperatures. Ventilation utilizing the total system
capacity would make the inside temperature exceed the required temperature, as large amounts of warm air is
added. The function can also prevent young animals from being exposed to a level of ventilation which they do
not tolerate.
When you want to disregard the function, you should set the Maximum ventilation to the maximum value (fac-
tory setting 300 %). By doing so you ensure that there is not actually a limit on how much of the ventilation sys-
tem's capacity can be used.
User Manual 39
DOL 534 • DOL 539
The air outlet in the house consists of partly one or several stepless exhaust units, partly groups of ON/OFF ex-
haust units. The stepless exhaust unit is variable, as the controller can adjust motor performance and flap open-
ing of the fan, while the fans in the other exhaust units are either on or off.
The ventilation system connects the stepless exhaust unit first. When the ventilation requirement exceeds the
capacity of the stepless exhaust unit, a group of the other exhaust units are connected and the stepless exhaust
unit decreases its output simultaneously. This way, the controller ensures stepless transition from one ventila-
tion level (MultiStep) to the next. If the ventilation requirement increases further, the stepless exhaust unit will
perform up to its maximum until it reduces its output when the next group of ON/OFF exhaust units is con-
nected.
All exhaust units in the the house bear a sign showing if it is a stepless or an ON/OFF exhaust unit. The latter
are numbered according to which MultiStep they belong. This way, it is possible to recognize the individual ex-
haust units and compare their actual output with the status that you can read in the Ventilation menu. This is
particularly relevant in connection with fault finding.
Shutter position
The flap position is a percentage indication of how much the flaps of both air inlet and air outlet are open. If you
are in doubt about the actual ventilation output, you can compare the reading of the Ventilation status in the
ventilation menu with the output that you can actually observe in the house. The percentage indications are rele-
vant particularly in connection with troubleshooting.
40 User Manual
DOL 534 • DOL 539
In order to neutralize possible temperature differences in very large one-zone houses, the air inlets can be
grouped in up to six zones. Each group is adjusted according to its own temperature sensor and the air inlets
are adjusted according to the temperature measured by the climate controller in that particular zone.
Zone 3
Zone 2
Zone 1
Zone 6
Zone 5
Zone 4
De-icing is a function that changes the regulation of ventilation at low outside temperatures to cycle time in order
to avoid ice formation in the air inlet.
The house controller activates de-icing when the outside temperature falls below the setting for Outside temper-
ature below.
OFF
Outside temperature below Outside temperature
- 10°C
Figure 9: Activation of de-icing
User Manual 41
DOL 534 • DOL 539
Cooling is used in houses where ventilation alone cannot reduce the inside temperature sufficiently.
Cooling has the advantage over ventilation in that it can bring the inside temperature down below the outside
temperature. On the other hand, cooling will also increase the air humidity in the house.
MAX
Temperature
The combination of a high inside temperature and high air humidity can be life-threatening to the
animals. As cooling makes the house humidity increase, the controller automatically disconnects
cooling when the house humidity exceeds Humidity to stop side cooling (normally 75-85%, fac-
tory setting: 85 %).
The following sections describe the functions and setting options available in the side cooling menu.
It is possible to search for functions via the search function in the Settings menu. See section
Search in menus [} 22].
42 User Manual
DOL 534 • DOL 539
Humidity to stop side The air humidity percentage that makes the controller stop the cooling function.
cooling Furthermore, a humidity limit can be set for the tunnel cooling.
Cooling is gradually removed 10 % before humidity limit
Cooling
Temp. setpoint
+ addition Start cooling offset
Temperature
With this setting the climate controller will continuously calculate the ventilation level at which the side cooling
must start.
The calculations are based on the current outside humidity and outside temperature and indicate a so-called
cooling potential. Also, see section Cooling potential [} 45].
User Manual 43
DOL 534 • DOL 539
Required ventilation to Displays the calculated ventilation level at which cooling will start (in percent of
start cooling: Maximum ventilation). Maximum ventilation is either determined as batch curve or
set in the menu Technical | Service | Settings | Climate | Air output.
Temperature °C
Temperature setpoint
Minimum cooling
Time
Figure 11: To maintain the required inside temperature, cooling starts before the ventilation level has reached Maximum
ventilation. When cooling can no longer maintain the temperature, the ventilation is increased again.
Lower limit
Ventilation (%)
Maximum ventilation
Minimum priority
Medium priority
Maximum priority
Figure 12: The higher the cooling potential, the higher priority of early cooling start.
Minimum:
Used in areas where the temperature is primarily maintained by means of ventilation and where the cooling po-
tential is low.
At a cooling potential of 15 °C, cooling will, for example, start at 80 % of the maximum ventilation.
Medium:
44 User Manual
DOL 534 • DOL 539
Factory setting. Usually the factory setting should not be changed. It may be necessary to change the cooling
priority, if the adjustment takes place too slowly or too quickly.
At a cooling potential of 15 °C, cooling will, for example, start at 70 % of the maximum ventilation.
Maximum:
Used in areas where the temperature is primarily maintained by means of cooling and where the cooling poten-
tial is high.
At a cooling potential of 15 °C, cooling will, for example, start at 60 % of the maximum ventilation.
In general there is a higher cooling potential in hot areas than in cold areas. Furthermore, there will usually be a
very high cooling potential in areas with very low humidity.
Figure 13: The lower the outside humidity, the higher the cooling potential.
A rule of thumb states that for each 5 % increase in air humidity, the temperature drops by 1 °C.
4.10 Tunnel
This section is relevant only to houses with tunnel ventilation.
Tunnel ventilation is used at high temperatures. The air is let in through a tunnel opening at one end of the live-
stock house, and the air is exhausted through a number of wall fans at the other end of the house. This makes
the air move quickly in a lengthwise direction in the the house and the air therefore feels cooler.
Temperature
The tunnel ventilation cannot be activated until both the outside and inside temperatures are sufficiently high.
User Manual 45
DOL 534 • DOL 539
The following sections describe the functions and setting options available in the tunnel menu.
It is possible to search for functions via the search function in the Settings menu. See section
Search in menus [} 22].
46 User Manual
DOL 534 • DOL 539
Force tunnel exit It is possible to force the ventilation from the tunnel to side mode. This may be de-
sirable in the case of mechanical failure or repair thereof.
Tunnel outside tempera- Lower outdoor temperature limit for activation of tunnel ventilation. The limit is set
ture limit in the batch curve by the name of the Chill curve – outside temp. (only combi-tun-
nel)
Min.vent. Per animal The lower limit for how little is ventilated relative to the air requirement of the ani-
mals (m3/h per animal).
User Manual 47
DOL 534 • DOL 539
Side
Tunnel with cycle timer
The controller calculates which inside temperature is required in order to activate tunnel mode (only combi-tun-
nel).
• To make the change to tunnel at a lower inside temperature you must reduce the chill factor.
• To make the change to tunnel at a higher inside temperature you must increase the chill factor.
48 User Manual
DOL 534 • DOL 539
Cooling is used in houses where ventilation alone cannot reduce the inside temperature sufficiently. Cooling has
the advantage over ventilation in that it can bring the inside temperature down below the outside temperature.
On the other hand, cooling will also increase the air humidity in the house.
Temperature
The combination of a high inside temperature and high air humidity can be life-threatening to the
animals. As cooling makes the house humidity increase, the controller automatically disconnects
cooling when the house humidity exceeds Humidity to stop tunnel cooling (normally 75-85%,
factory setting: 85 %).
The following sections describe the functions and setting options available in the tunnel cooling menu.
It is possible to search for functions via the search function in the Settings menu. See section
Search in menus [} 22].
User Manual 49
DOL 534 • DOL 539
See sections Tunnel cooling start based on a fixed air speed [} 50], Tunnel cool-
ing start based on an adapted air speed [} 50] and Tunnel cooling start based on
inside temperature [} 52].
With this setting, the controller will continuously calculate at which air speed the tunnel cooling should start.
50 User Manual
DOL 534 • DOL 539
The calculations are based on the current outside humidity and outside temperature and indicate a so-called
cooling potential. Also, see section Cooling potential [} 53].
Upper limit
Lower limit
Figure 16: In areas with low outside humidity and great cooling potential, the cooling can start at a lower air speed. Con-
versely, in areas with low cooling potential, you would wait as long as possible to start the cooling so that it starts at maxi-
mum air speed.
User Manual 51
DOL 534 • DOL 539
Temperature (°C)
Measured temperature
Experienced temperature
Cooling (%)
Max. cooling
Min. cooling
Figure 17: The cooling starts already at low air speed to maintain the required inside temperature. When the cooling cannot
maintain the temperature, the air speed is increased again.
Humidity to stop tunnel Setting the percentage of air humidity that makes the controller stop the tunnel
cooling cooling.
Humidity to restart tunnel View of the calculated air humidity where the tunnel cooling starts again. This
cooling would be 3% below the humidity limit.
52 User Manual
DOL 534 • DOL 539
In general there is a higher cooling potential in hot areas than in cold areas. Furthermore, there will usually be a
very high cooling potential in areas with very low humidity.
Figure 18: The lower the outside humidity, the higher the cooling potential.
A rule of thumb states that for each 5 % increase in air humidity, the temperature drops by 1 °C.
A stir fan is typically used to improve air circulation inside the house and thus provide a more uniform tempera-
ture in the house. Depending on the type, location and connection method, however, it can be used for many
different purposes.
24-hour clock
Temperature
Heating
User Manual 53
DOL 534 • DOL 539
Temperature
Start time: 14:00 hh:mm
Stop time: 16:00 hh:mm
ON time: 00:05:00
hh:mm:ss
OFF time: 00:05:00
hh:mm:ss
Time
Figure 19: 24-hour clock control
54 User Manual
DOL 534 • DOL 539
1 temperature sensor
Start temperature offset Setting an offset to Temperature setpoint. The stir fan is activated when the inside
temperature exceeds Temperature setpoint + Start temperature offset.
At high temperatures, a stir fan can be used to create the experience of cooling
via air speed.
Stop temperature natural Setting of the temperature where the stir fan stops.
Stop temperature side / In livestock houses that also have side/tunnel ventilation.
tunnel
Display of the temperature where the stir fan stops at side and tunnel ventilation.
Differential temperature
Temperature difference Setting the temperature difference between the 2 sensors. The stir fan is activated
activation when the temperature difference exceeds the setting.
In case of temperature differences in the house, a stir fan can be used to compen-
sate for temperature differences between colder and warmer areas.
Temperature °C
ON time/OFF time
05:00 min:sec
Start temperature offset 4 °C
Temperature setpoint
Time
Figure 20: Relay-controlled stir fan (ON/OFF) controlled by temperature
User Manual 55
DOL 534 • DOL 539
Temperature sensor se- Selecting which temperature sensor to use for the control.
lection
Start temperature offset At high temperatures, a stir fan can be used to create the experience of cooling
via air speed.
Setting an offset to Temperature setpoint. The offset can be set as a positive or
negative value.
Positive value: The stir fan starts at an excess temperature to Temperature set-
point. E.g. 15 °C +5 °C = 20 °C.
Negative value: The stir fan starts at a temperature below Temperature setpoint.
E.g. 15 °C -5 °C = 10 °C.
Stop temperature natural Setting the temperature that stops the stir fan at natural ventilation.
Stop temperature side / In livestock houses that also have side/tunnel ventilation.
tunnel
Display of the temperature where the stir fan stops at side and tunnel ventilation.
Variable temperature Setting an inside temperature range where the stir fan will run between minimum
range and maximum speed.
Activate override control Manual activation of the stir fan. It will run at the speed set in Override speed.
Remember to deactivate the function again.
Override speed Setting the speed that the stir fan must run at when in manual mode.
Minimum speed 0 %
Maximum speed 100 %
Temperature °C
Temperature setpoint 20 °C
Start temperature offset
Figure 21: 0-10 V controlled stir fan with a positive Start temperature offset.
56 User Manual
DOL 534 • DOL 539
Speed %
Reversed Normal
Temperature °C
Temperature setpoint 20 °C
Reverse temperature offset
Figure 22: 0-10 V-controlled stir fan with reverse relay
User Manual 57
DOL 534 • DOL 539
Stop delay
Control: With heater
Heat
Start delay
Stir fan
Start delay
Control: After heating
ON time
Time
Figure 23: Control with heater
58 User Manual
DOL 534 • DOL 539
The average values are only shown when selected in the menu | Installation | Manual installation |
Climate | Sensors | Weather station.
| Climate status
TEMPERATURE USER OFFSETS
HEAT USER OFFSETS
VETILATION USER OFFSETS
OTHER USER OFFSETS
CONTROL PRINCIPLES
User Manual 59
DOL 534 • DOL 539
5 Management
5.1 House data
5.1.1 House status Active house - Empty house
The controller has 2 different modes of operation, one for when there are animals in the house and one for
when the house is empty.
With animals in the house – Active house. Control takes place according to the automatic settings and day pro-
grams, the day number counts upwards and all alarms are active.
Without animals in the house – Empty house. Control takes place according to the in-between settings Empty
house. Only active alarms are alarms for CAN communication and temperature surveillance for Empty house.
Active house
It may be an advantage to change the status to Active house the day before stocking the animals. This way the
controller has time to adapt the climate to the needs of the animals and to feed in the house.
The day number then switches to day 0, and the controller operates in accordance with the automatic settings.
Empty house
The status should not be changed to Empty house until the house has been depopulated.
Then the controller disconnects the adjustment and controls according to the in-between function Empty house.
This function protects the animals in case a house is set to Empty house by mistake.
If the house is to be completely closed, the settings of the in-between function Empty house must be reset. See
the section Empty house [} 66].
When the house status is changed to Initiate batch stop, the controller resets all changes made in curves and
settings.
60 User Manual
DOL 534 • DOL 539
The function Change status can also be added as a card to a page, see the section Edit pages [} 20] for
information about setting up pages.
5.1.2 Settings
Management | House data
Status Reading status (Active house/ Empty house).
Change status Changing the house status by entering a unique code, which is shown in the dis-
play.
Stocked animals Setting the number of animals (only DOL 534).
Adjust date and time Setting of current date and time.
Correct setting of the clock is important, both as regards several control functions
and as regards the registration of alarms. Thus, all programs in the controller use
both date and time and day number.
The clock will not stop in the event of a power failure.
Summer and winter time
There is no automatic adaptation in relation to summer and winter time, as some
animal types are very sensitive to changes in their circadian rhythm. If you want the
controller to follow the local time for summer and winter time, you must therefore
manually change the time setting by +/- 1 hour.
Day number Setting of day number. The at midnight the day number counts up 1 for every 24
hours that pass after the house has been set to active house.
Select whether the day number should show the time since batch start or actual age
of the animals. When the actual age of the animals is required, the day number
must be adjusted until it matches the life expectancy.
Day number can be set as low as -9 so the climate and production controller can
control the preheating of the house prior to the animals being stocked.
Week number Display of current week number.
Week 0: Day 0 – 6
Week 1: Day 7 – 13
.
.
Week 15: Day 105 – 111
Week 16: Day 112 - 118
Week day Display of week day.
Start at day Setting of the day on which the batch shall start.
House name Setting of house name.
When the house controller is integrated in a LAN network, it is important that each
livestock house has a unique name. The house name is transferred through the net-
work and the livestock house should therefore be identifiable based on the name.
Set up a plan for the naming of all controllers connected to the network.
Service Access activated Information that the climate and production controller is being remotely controlled
via the farm management program FarmOnline Explorer.
User Manual 61
DOL 534 • DOL 539
5.1.3 Settings
Management | House data
Status Reading status (Active house/ Empty house).
Change status Changing the house status by entering a unique code, which is shown in the dis-
play.
Stocked animals Setting the number of animals (only DOL 534).
Adjust date and time Setting of current date and time.
Correct setting of the clock is important, both as regards several control functions
and as regards the registration of alarms. Thus, all programs in the controller use
both date and time and day number.
The clock will not stop in the event of a power failure.
Summer and winter time
There is no automatic adaptation in relation to summer and winter time, as some
animal types are very sensitive to changes in their circadian rhythm. If you want the
controller to follow the local time for summer and winter time, you must therefore
manually change the time setting by +/- 1 hour.
Day number Setting of day number. The at midnight the day number counts up 1 for every 24
hours that pass after the house has been set to active house.
Select whether the day number should show the time since batch start or actual age
of the animals. When the actual age of the animals is required, the day number
must be adjusted until it matches the life expectancy.
Day number can be set as low as -9 so the climate and production controller can
control the preheating of the house prior to the animals being stocked.
Week number Display of current week number.
Week 0: Day 0 – 6
Week 1: Day 7 – 13
.
.
Week 15: Day 105 – 111
Week 16: Day 112 - 118
Week day Display of week day.
Start at day Setting of the day on which the batch shall start.
House name Setting of house name.
When the house controller is integrated in a LAN network, it is important that each
livestock house has a unique name. The house name is transferred through the net-
work and the livestock house should therefore be identifiable based on the name.
Set up a plan for the naming of all controllers connected to the network.
62 User Manual
DOL 534 • DOL 539
Service Access activated Information that the climate and production controller is being remotely controlled
via the farm management program FarmOnline Explorer.
Together with other information, the curve settings form the basis of the controller’s calculation of climate regu-
lation.
User Manual 63
DOL 534 • DOL 539
Humidity
Days
Figure 24: Curve for air humidity
It is generally the case for the curve functions that the house controller automatically displaces the rest of a
curve sequence in parallel when you change the associated setting in the course of a flock.
Changes in settings can be seen in the menu Climate | Climate status.
64 User Manual
DOL 534 • DOL 539
Status
The climate controller can activate the in-between functions
only when the status is Empty house (in the menu Manage-
ment/ House data/ Status).
The menu is only visible when status is Empty house.
When the time for an in-between function is up, the controller
will again regulate according to the settings for Empty house.
Animals stocked
Animals stocked
Empty house
Empty house
Active house
Active house
In-between
In-between
functions
functions
Day 0
Cleaning
Heating
Management
Delivery
Cleaning
Heating
Batch 1 Batch 2
Figure 25: In-between function at batch production
Day no.
At
Temperature surveillance
Soaking 24:00 h
Ventilation closed
Empty house
Ventilation
Washing 01:00 h
Ventilation
Drying 06:00 h
Ventilation
Heating
Disinfection 24:00 h
Ventilation shut off
Temperature control
Preheating
Ventilation shut off
Heater
User Manual 65
DOL 534 • DOL 539
Program sequence
With time control, each in-between function can be set to start
at a specified time. It is thus possible to set a total sequence for
the in-between functions.
Soaking
Soaking will soak the house with water to loosen dust and dirt. This will not only reduce the amount of dust dur-
ing the subsequent cleaning but also make cleaning easier.
In soaking mode, stop ventilation to maintain the humidity in the house. Set the soaking system to run at inter-
vals (Cycle time) for a number of minutes (ON-time) during the total period (soaking time) which the soaking
process is to last.
Washing
While washing the house manually, ventilation must run again to start changing the air in the house.
Drying
Drying is a combination of ventilation and heat supply. The more heat is supplied to the the house, the faster it
dries.
Heating can be supplied as room heating or floor heating.
A desired temperature is set when room heating is used.
When floor heating is used, the percentage the floor heating system will operate at must be set. The floor heat-
ing stops when the inside temperature exceeds the temperature that has been set.
Disinfection
Disinfection is carried out manually by adding disinfectant to the water.
A certain temperature must be maintained in the house during disinfection in order for the disinfectant to have
optimal effect (often over 20 °C).
The house controller shuts off the ventilation system and supplies heat as needed to maintain the correct tem-
perature for disinfection.
Heating can be supplied as room heating or floor heating.
A desired temperature is set when room heating is used.
When floor heating is used, the percentage the floor heating system will operate at must be set. The floor heat-
ing stops when the inside temperature exceeds the temperature that has been set.
66 User Manual
DOL 534 • DOL 539
When status is Empty house, all alarm functions - except temperature surveillance at empty
house - are disconnected. See also the section Temperature surveillance [} 68].
When batch status is Empty house, the house controller disables all automatic regulations and
operates according to the settings in the Empty house in-between function.
5.4.2 Settings
Management | In-between functions
The house is Menu for selection of in-between function
Roof inlet flap Setting of flap position for the roof inlets (roof).
Roof inlet fan Setting of speed control for the roof inlets (roof).
Re-circulation inlet Setting of recirculation fan for the roof inlets (roof).
Side inlet Setting the flap opening for side air inlet.
Tunnel inlet Setting of the tunnel opening (tunnel).
Ventilation Setting the percentage of nominal ventilation.
When the house is in Empty house, this function is typically used to open a number
of ON/OFF air outlets.
Air outlet 1 flap Setting the flap opening for air outlet.
When the house is in Empty house, this function is typically used to open the step-
less flap.
Air outlet fan speed Setting of speed control for air outlet.
When the the house is in Empty house, this function is typically used to turn off the
stepless fan.
Soaking time Setting the active period for soaking.
Cycle time Setting the intervals in which the soaking system is active.
ON time Setting the active period for soaking.
Washing time Setting the active period for washing.
Heating Setting the heating in connection with the Drying function.
Drying time Setting the active period for drying.
Disinfection time Setting the active period for disinfection.
Temperature Setting of the temperature it needs to be in the house during disinfection.
5.4.3 Preheating
Preheating ensures that the inside temperature does not fall be-
low the set temperature when batch status is empty house for a
longer period of time.
Thus, the function can also be used to protect the house
against frost.
Heating can be supplied as room heating or floor heating.
User Manual 67
DOL 534 • DOL 539
Inside temperature
Preheating setpoint
Preheating at stop
Day number
68 User Manual
DOL 534 • DOL 539
Ventilation boost is a function to improve the air quality in the house, the function can reduce CO2 and NH3 as
well as the amount of dust in the air. This is achieved by activating the function once or several times during the
day.
The air quality is improved by increasing the ventilation and activating an environment system which humidifies
the livestock housing with water (added oil is an option). This reduces the amount of dust and gas in the air in
the livestock housing. When the ventilation boost function starts, the climate controller gradually adjusts the cli-
mate to the settings of the function and then gradually reverts to the regular setting.
You can activate/deactivate the function's day program, which can have up to 8 active periods. You can also ac-
tivate the function manually if you enter the house outside one of the set periods. If you activate the function
manually there is no start adaption time, but the climate controller will still gradually revert to the regular set-
tings.
The function is not active when the house is set to Empty house.
Minimum ventilation
Adaption period
Time
You must set the day program's periods for when the function must be active. Furthermore, you must adjust
Temperature adjustment with the degrees by which the inside temperature must fall and Ventilation addition
with the percentile by which Minimum ventilation must rise.
User Manual 69
DOL 534 • DOL 539
When the function starts and stops, the temperature will be adjusted within the specified period. To achieve the
full effect, the start time may be set to approx. 30 minutes before you wish to enter the livestock house.
Set:
• Number of periods per day (1-8)
• Time for start
• Time for stop
Press the field in the column Start to change the start time.
Press the field in the column End to change the stop time.
Press Add activity for a new period and then set the start and
stop time.
The blocks on the time line shows when and how long ventila-
tion boost is active.
Press to delete a period.
The function operates in the same way every day. When Batch
status is Empty house, the function is disconnected.
5.7 Catching
The catching function is designed to alter the air change in the house in connection with all or some of the ani-
mals leaving the house. The ventilation status will change to Catching and adapt its settings. When it changes
back, the ventilation returns to half the ventilation requirement that was just before the function started and dis-
play restoring information. The function also modifies the feeding program, light control and alarms.
Management | Catching
Catching Connection and disconnection of the function. (with display operation)
Catching ready Setting the date and time that the user can activate the function.
Catching start Displaying the time when catching was activated. Only visible when the function is
active.
Catching stop Display of the time when the function is to stop (using the Auto stop catching after).
If the catching lasts for longer than expected, the stop time can however be
changed. Only visible when the function is active.
Allow catching start pe- Setting the time period when the user can activate the function. (only push button
riod and key)
Auto stop catching after Setting the maximum period that Catching can be active.
Air inlet Setting how much the air inlets must be open in percent during catching.
Roof inlet Setting roof inlet, flap, fan and stir fan in percent during catching.
Stepless Setting how much the air outlets must be open in percent during catching.
70 User Manual
DOL 534 • DOL 539
MultiSteps Selecting which MultiStep should be active during Catching. For example, you can
control the desired direction of the airflow, by only activating the MultiSteps at one
end of the house.
Light control Select if activating catching should change the light control.
Stop feed system Select if activating catching should stop the feed system.
Stop feed weigher be- Setting the time period. The time period should correspond to the time it takes for
fore feed system is the animals to eat the feed which is distributed in the system.
stopped
Stop feed mixing before Setting the time period. The time period should correspond to the time that the ani-
feed weigher is stopped mals should only have one type of feed.
Type of feed when feed Selection of the last type of feed to be used before the feeding system is stopped.
mixing is stopped
Optional:
Stop feed mixture Stop feed Stop Catching starts Time limit Optional:
(non-wheat) weigher feeding Key activated Manual start of feeding
The Auxiliary sensors menu gives you a quick overview of the registrations of the house controller from the aux-
iliary sensors. The auxiliary sensors have no influence on the regulation.
The climate controller registers the content of CO2, NH3, O2 and humidity in the house air, as well as pressure
and temperature. You can also connect air speed and wind direction sensors that can measure the wind direc-
tion and air speed outside the the house.
The display of the auxiliary sensors menu depends on which types of auxiliary sensors you install.
5.9 Consumption
Management | Consumption
The menu shows the energy consumption in the house. The contents of the menu depend on the type and the
setup of the controller.
User Manual 71
DOL 534 • DOL 539
6 Alarms
Alarms only work when the status is Active house.
The only exceptions are alarm test and alarms for CAN communication and temperature surveil-
lance for Empty house.
The controller will also activate an alarm signal, which you can
choose to maintain.
The alarm signal will thus continue to sound until you acknowl-
edge the alarm. This also applies even if the situation that trig-
gered the alarm has stopped
Alarms maintained:
YES: The signal continues after the alarm situation has ceased.
NO: The signal stops after the alarm situation has ceased.
72 User Manual
DOL 534 • DOL 539
The user is always responsible for ensuring that all alarm settings are correct.
Connection lost to Client Select the alarm type Hard, Soft or Disabled.
Connection lost to Master Select the alarm type Hard, Soft or Disabled.
User Manual 73
DOL 534 • DOL 539
Low temperature limit Alarm for excessively low temperature in relation to the Temperature setpoint.
Temperature
Low temperature limit with In FreeRange houses, the alarm limit is lowered with this setting when the pop-
FreeRange holes are open.
Example Heating installed but not active in FreeRange
Temperature setpoint 19 °C
Heat offset: -2 °C
Low temp. limit with FreeRange: -5 °C
When not in FreeRange mode, the heating is set to 17°C
Alarm is triggered at 12°C
When the pop-holes close, the alarm limits will return to the general tempera-
ture alarm limits within 30 minutes
Summer Alarm at 20 °C and The function has a varying alarm limit that monitors changes in the high out-
30 °C Outside side temperature. When the temperature rises, the alarm limit will also rise.
When the temperature rises, the alarm limit will also rise. It will thus postpone
the time when the high temperature alarm is triggered.
The house controller only triggers the alarm if the inside temperature also ex-
ceeds the high temperature alarm.
74 User Manual
DOL 534 • DOL 539
Temperature
Outside temperature
High temperature limit
Time
Absolute high temperature The alarm for absolute high temperature is triggered by an actual temperature,
such as 32° C. The house controller triggers the absolute high temperature
alarm when the inside temperature exceeds this setpoint.
The absolute high temperature alarm is set as a temperature curve.
Temperature difference in The alarm is active at tunnel ventilation where ventilation is regulated accord-
tunnel Front/Rear ing to an average value of the front and rear temperatures. The house con-
troller generates an alarm when the temperature difference between the front
(Two zones)
and the rear zones exceeds the set number of degrees.
User Manual 75
DOL 534 • DOL 539
Tunnel cooling temperature Alarm for when the inside temperature exceeds the outside temperature. This
indicates an error in tunnel opening.
76 User Manual
DOL 534 • DOL 539
Pressure sensor With the function Sensor alarm delay you can postpone the alarm signal so that
the alarm is not triggered by transient changes of the pressure level in the house,
e.g. when a door is opened.
The controller activates an alarm when the pressure in the house drops below or
exceeds the settings of Pressure high limit/ Pressure low limit.
User Manual 77
DOL 534 • DOL 539
6.4.14 Catching
Catching
Catching key error Alarm that the catching is not completed within the set period.
After creating the alarm, see the menu | Installation | Show connection for information about where to
connect the extra equipment.
Low alarm Possible equipment failure. The equipment may be disconnected by mistake.
Alarm due to missing current consumption. For example, MultiStep/stepless may
be activated and the power consumption too low, if the emergency stop at the fan
is activated.
High alarm The equipment shows signs of wear.
Alarm due to excessive current consumption.
78 User Manual
DOL 534 • DOL 539
ON alarm The equipment is active, but should not be in relation to the controller's regulation.
Alarming due to current consumption, which should not be there. For example,
MultiStep/stepless may be activated and the power consumption too high, if there
is an emerging defect in the fan.
Alarms are only triggered when a limit has been exceeded for 5 minutes.
The alarms are set up to match the connected monitoring equipment. This is done in the menu Alarm settings |
Equipment status.
Select the alarm type Hard, Soft or Disabled.
Set voltage ranges for Low alarm, High alarm and ON alarm.
First read the current consumption during normal operation to
get an indication of the voltage ranges.
It may be an advantage to disconnect absolute high humidity in houses that are placed in areas with very high
outside air humidity and in situations when a technical sensor error emerges.
Temperature controlled emergency opening is only triggered when the inside temperature exceeds the tempera-
ture setpoint for emergency opening (Emergency opening setpoint). You can read off the setpoint as an actual
temperature figure on the house controller’s display. The emergency opening is also triggered in the event of
power failure.
User Manual 79
DOL 534 • DOL 539
Be careful not to set the Battery voltage limit too low, as this will actually deactivate the alarm.
Whether an inside temperature sensor error should trigger the emergency inlet depends on the general climate
conditions. If it is very hot, you could profit from using the function. However, if it is cold, you should consider the
necessity of using it and whether the animals will suffer.
The emergency Inlet has its own temperature setting Emergency Inlet, where the number of degrees are en-
tered for the Temperature setpoint and any Comfort temperature.
This setting makes it possible to open the air intake during a hot season where the air intake, under normal con-
ditions, is not activated by the normal high temperature alarm limit.
80 User Manual
DOL 534 • DOL 539
7 Maintenance instructions
The house controller requires no maintenance to function correctly.
You should test the alarm system every week.
Use only original spare parts.
Note that the service life of the house controller will be extended if it stays connected all the time, as this will
keep it dry and free from condensation.
7.1 Cleaning
Clean the product with a cloth that has been wrung out almost dry in water and avoid using:
• high-pressure cleaner
• solvents
• corrosive/caustic agents
7.2 Recycling/Disposal
It must be possible for customers to deliver the products to local collection sites/recycling stations in accordance
with local instructions. The recycling station will then arrange for further transport to a certified plant for reuse,
recovery and recycling.
User Manual 81
611821 • 2022-09-30 • en-US • Made in Denmark