Adaptive Instantaneous Overcurrent: A Case Studied in A Real Brazilian System
Adaptive Instantaneous Overcurrent: A Case Studied in A Real Brazilian System
   Abstract—Recently, a large number of small generator plants               coordination shall to be executed. The traditional coordination
have been building on Brazil as reflex of governmental invest-               of power system protection studied, is a difficult and hart task
ments on renewable power source. As known, modifications on                  [1]. Some authors have been proposing techniques to optimize
power supply may have succeeded by a revision on coordination
protection system settings. However, this task is still make in              the process of coordination, reducing the protection engineers
many companies using archaic methods. In other hand, re-                     effort [2], [3], [4], [5]. However, most of these techniques do
searchers have been shown that an efficient and fast method may              not have a good computational performance.
be used to determine the new relays settings, this techniques was               To guarantee reliable system operation is necessary esti-
called adaptive protection. In this paper, frequency estimation              mating the fundamental power frequency [6]. Several meth-
was used to determine modifications on power supply plant in
a real Brazilian system, and these modification on the system                ods have been proposed and, most of them perform well
was used to the adaptive overcurrent protection block determine              when the signal is not distorted by harmonics or noises. In
the update on relays settings. The application of the methods                distribution systems due to the dynamic load, this system
of frequency estimation to the adaptive overcurrent protection               suffers high disturbs and it is usually not balanced, this
presented good results and improvements on the protection of                 causes high problems in frequency estimation [6]. Recently,
the electric system.
                                                                             a new protection philosophy propos that relay settings have
  Index Terms—Adaptive protection, overcurrent protection, fre-              be updated automatically following topological or operational
quency estimation, distributed generation, protection, islanding.            modifications [7], [8]. This technique was called adaptive
                                                                             protection.
                                                                                In distribution systems the main protection applied is the
                         I. I NTRODUCTION                                    overcurrent function [10]. On traditional protection techniques,
       N actual Power Electric System (PES) scenario, modi-                  network modifications were not considers on coordination
O      fications on topology and operational network are fre-
quently. In electric distribution systems changes have been
                                                                             studies, such as: blinding of protection and false trip are
                                                                             frequent [9]. Adaptive protection scheme (APS) provides relay
verified in lot of cases, such as: add new consumers to the                  settings based on operational conditions. In other words, relay
grid, contingence condition, and more recently, connection of                settings suit up to operational conditions.
small power generators.                                                         In this paper, an adaptive protection scheme is proposed to
   In Brazil, generally are used renewable energy sources, such              determine instantaneous overcurrent relay setting. The adap-
as: energy based on sugar cane bagasse, wind energy and solar                tive overcurrent protection will monitor system modifications
or photovoltaic energy all these known as green energy.                      done from the estimation of the fundamental frequency. For
   Actually, with the connection of distributed generation (DG)              this reason, frequency estimation algorithms have to be robust
in the PES, the system has suffered big changes and dynamic                  and reliable because frequency estimation is used in the
situations in the operation. During the operation of the system              protection.
can occur islanding situation of the DG and the parameters,                     The frequency of the power system has an important role
such as: voltage, current and frequency can suffer changes.                  in monitoring and control the operational status of the grid or
   Generally, the modification on the PES impact in the per-                 in DG systems. For reliable operation of the smart grid, it is
formance and reliability of the grid. However, the protection                essential to estimate the power system frequency accurately
scheme should also include all these changes and update the                  [6]. For this reason, many algorithms are presented for funda-
relay setting. So, for each network change, a new setting for                mental frequency estimation applied in electric power systems,
                                                                             for example: zero crossing method [11], [12], adjustment of
  —————————————————————–
  This work was supported by CAPES (Coordenação de Aperfeiçoamento        points to a pure sinusoidal waveform (APPSW) [13], hybrid
de Pessoal de Nı́vel Superior) and CNPq (Conselho Nacional de Desenvolvi-    method [14], [15], discrete Fourier transform method (DFT)
mento Cientı́fico e Tecnológico).                                           [16].
  F. C. Souza Jr, H. S. Sanca and B. A. Souza are with the
Department of Electrical Engineering/COPELE, Federal University of              In this paper, three methods of fundamental frequency esti-
Campina Grande, Campus Univesitário Bodocongó, Campina Grande,             mation applied in distribution systems in islanding operation
PB, CEP:58.429-900, Brazil. E-mail: francisco.junior@ee.ufcg.edu.br, huil-   of DG were evaluated for adaptive overcurrent protection, such
man.sanca@ee.ufcg.edu.br, benemar@dee.ufcg.edu.br.
  F. B. Costa is with School of Science and Technology, Federal University   as: (i) Zero crossing, (ii) curve fitting and (iii) hybrid method.
of Rio Grande do Norte, Campus Univesitário Lagoa Nova, Natal - RN,         Using a distribute architecture composed for three centers
CEP:59.078-970, Brazil. E-mail: flaviocosta@ect.ufrn.br.                     [4], [17], proposed method was available in a real Brazilian
   Presented at the International Conference on Power Systems Transients
                                                                             sub-transmission system, owned by Eletrobrás Distributer of
(IPST’2015) in Cavtat, Croatia on June 15-18, 2015.                          Alagoas (EDAL).
                                                                                                                                 2
   Adaptive protection system was built using ATP/MODELS           determining of the overcurrent relays. This choice was made
[18], [19]. The three centers that make up the APS system          because protective device would have not need high processing
were: substation control center (SCC), control operational         power. As indicated in [26], the adaptive protections system
center (COC) and the Inteligent Electric Device (IED). SCC         can be implemented using digital signal processor, such as:
center performs monitoring and topological/perational detec-       DSP or FPGA chips. Finally, forming the third center, the
tion. COC center is responsible to execute all mathematic          IED does traditional digital relays and also proposes adaptive
operations to determine a new instantaneous instantaneous          task.
overcurrent relay settings. IED has the same architecture as
proposed on literature [20], [21] with one difference, relay
                                                                                                                      SCC
parameters do not loaded on device, it is provided from COC
center, through a communication channel.
                                                                                                   COC
   Results showed that in some cases, traditional protection
scheme does not provide a correct performance when topo-
logic modification occurred. In some cases yet miscoordination
was verified. However, when the proposed APS was apply, in
all cases protection devices concerned a good performance
for network, including when topological and/or operational
                                                                           Power Electric
modifications occurred.                                                       System
   Strictly, an uninterrupted voltage and current phasor transfer     communication channel to receives adjustments settings that
from COC to the relays would result in the necessity of a             are provided using an online method by COC.
very fast communication channel. For this fact, decides for a
duplication on COC for a relays similar architecture describes
in [21], i.e., all steps blocks responsible for the tasks until the    III. D ESCRIPTION    OF METHODS APPLIED IN THIS WORK
phasor estimation are present as on the relays devices as in                         FOR FREQUENCY ESTIMATION
the COC. Fig. 3 shown the COC operation architecture.
   According to Fig. 3 presents the system must be able to              In this section, the description of many methods applied
operate with current and voltage signals in more than one             in this work for the fundamental frequency estimation is
point of the grid. This necessity is due to the fact that             presented.
the determination of the equivalent network depends on the
knowledge of such signals at various points in the system.
   Despite having the same structure of digital relays, COC           A. Method based on signal zero-crossings
dont need made phasor estimation for all samples. The win-
                                                                         This algorithm is based on the measurement of the time
dowing process continues to be done without interruption,
but the following steps: phasor estimation, calculation of            interval between two zero-crossings of the sampled signal.
                                                                      The exact time of the zero-crossing is obtained by linear
the equivalent network and protective devices adjustments
                                                                      interpolation between two consecutive samples of different
settings, are only performed if the SCC detected any change
                                                                      sign [13] is given by:
in the electrical network.
   The setting adjustments of adaptive protection devices are
extremely dependent of phasor estimation and network equiva-                                     tk−1 Vk − tk Vk−1
                                                                                         tzc =                     ,               (1)
lents routine. According [9] network equivalent determination                                       Vk − Vk−1
must be obtained using probabilistic relationships between
voltage and current. Through routines oriented tests was              were k denotes the instant of the sample that follows the zero
verified a shorter error value of equivalent network routines         crossing; and k − 1 denotes the instant the sample before the
when a minimum 40 samples/cicle of voltage and current are            zero crossing, (Vk , Vk−1 ) and (tk , tk−1 ) are the voltage and
used. As IED and COC uses 16 samples/cycle, sets equivalent           time in the instant (k) and (k − 1) respectively.
network determinations routine to use the triple samples hate            During the time interval between two zero-crossings, it is
value, i.e., the mathematics calculation will be realized once        possible to assume that the frequency value is equal to the last
every three complete cycles of samples on phasor estimation.          calculated value. The frequency in the instant (k) is calculate
   After determination of new adjustments settings, these pa-         by:
rameters will be transferee to IEDs thought communication
channel.                                                                                                1
                                                                                    fk =                                ,          (2)
                                                                                           2 ∗ (tzcnext − tzcprevious )
C. Inteligent Electric Device (IED)
                                                                      were fk denotes the fundamental frequency, in Hz, calculated
   A lot of paper on technical literature suggest a relay model
                                                                      in the instant k by zero-crossing; tzcnext denotes the time
to most kind of analysis on the PES [20], [21], [27]. However,
                                                                      of the next zero-crossing; tzcprevious denotes the time of the
actually there is no defined a model that provide the adaptive
                                                                      previous zero-crossing.
protection techniques implementation. For this reason, a new
relay model it is necessary to effectuate adaptive tasks.
   [17] describes a device with adaptive characteristics. Ho-
wever, proposed relay model needs a high processing per-              B. Adjustment of points to a pure sinusoidal waveform method
formance, this fact makes the proposal commercially non-                 This method was applied in [13], in this method is used
viable. Furthermore, the IED will concentrate all adaptive            trigonometric relations to find the frequency value. The
protection tasks. This fact should be strenuously avoided since       method based on three consecutive samples (Vk−2 , Vk−1 , Vk ),
the probability of failure in the system would increase rather.       spaced by a time interval △t, was used. In such conditions,
   So, an adaptive protective device may have, beyond the             the pure sinusoidal wave fulfils the following relationship is
functions of any protective device, the possibility of adjust-        given by:
ment settings change with no stop analysis of voltage and
current process. Actually, most recent relay have a logic
                                                                                                         Vk−2 + Vk
control process that use digital switch equipments, such as                            cos(2πf △t) =               .               (3)
                                                                                                           2Vk−1
circuit breakers, status to change relay adjustments settings
[28]. However, to do this process an offline step is necessary.
                                                                         The frequency (f), is obtained for voltage calculated in the
   To torn possible this characteristic, a new step was add
                                                                      instant (k) and the time interval ∆t is given by:
to the basic relay model proposed in [21]. This step will be
responsible to automaticly relay setting permute.                                                               
   In Fig. 4, the proposed device model was presented. As                                            Vk−2 + Vk         1
                                                                                    fk = cos−1                            .        (4)
can seen in Fig. 4, on the new relay model there is a                                                  2Vk−1         2π△t
                                                                                                                                                                                                                  4
                                                                        *        *
                                           vL , v C                   vL , v C                    vLd , vCd                        VLd , VCd
                                                      Analog                            A/D
                                            iL , iC    Filter
                                                                            *
                                                                       iL , iC
                                                                                 *
                                                                                                    iLd , iCd          Buffer      ILd , ICd
                                                                                      Conversor
                                                                                                                                                                 ^ ,V
                                                                                                                                                                 V  ^
                                                                                                                                                                  C  L
ADAPTIVE RELAY
                                                                                         *
                                       v                  v                            v                          vd                           Vd
                                           Auxiliary             Analogical                    A/D                                                       Phasor
                                                          i        Filter               i*                        id       Buffer              Id
                                       i   PTs e CTs                                         Conversor                                                 Estimation
                                                                                                                                                                                  From COC
                                                              Circuit-breakers status         Digital
                                                                                              Inputs
                                                                                                                                                           ^ ^
                                                                                                                                                           V I
                                                                   To SCC
                                                                                              Digital                      Relay                                               Relay
                                                                                                                                                       Comparison
                                                                                              Outputs                      logic                                              Settings
                                                      Open circuit-breakers flag
C. Combined frequency estimation technique: hybrid method                                                                where: (k) represents the sample number; f rk denotes the
   This method was presented by [15], [14] and combines                                                                  value of frequency estimated by the APPSW algorithm; f0k
two traditionally techniques. The method combines the zero-                                                              denotes the value of frequency estimated by the zero-crossing
crossings method and the APPSW method. If T2 is the time                                                                 algorithm; and fk denotes the final output of the frequency
length of the latest tree cycles. The precision of the zero-                                                             estimation algorithm. Results obtained from simulation studies
crossings is corrupted by effect of noise and harmonics and                                                              indicate that an appropriate value for T h2 is 0.05 Hz [15].
for minimize this problem is can use the average of the
frequencies of the last three cycles of the signal, given by:                                                                           IV. A DAPTIVE I NSTANTANEOUS OVERCURRENT
                                                                                                                            Instantaneous overcurrent setting is most frequently defined
                                     3                                                                                   by pick-up current unit [1] . However, some authors have been
                                f2 =    .                                                               (5)
                                     T2                                                                                  shown that, also distance protection, instantaneous overcurrent
   The equation (5), this equation provides greater immunity                                                             relays may act based on local fault where short-circuit current
to signal distortions. However, is less sensitive to frequency                                                           was equal to pick-up current setting [10].
variations, for this reason is used f1 (frequency obtained by                                                               To obtain the reach of directional instantaneous overcurrent
zero-crossing in one cycle) or f2 (frequency obtained by zero-                                                           relay settings, [25] propose the following equation:
crossing in tree cycles), given by:                                                                                                                                               ZLT − ZS × (k1 − 1)
                                                                                                                                                                 h =                                  ,         (9)
                                                                                                                                                                                       k1 × ZLT
                          If |f2 − f1 | < T h1 ,
                          then : f0 = f2 ,                                                              (6)              where:
                          else : f0 = f1 ,                                                                                 ZLT - line impedance,
                                                                                                                           ZS - equivalent impedance,
where f0 denotes the final value estimated by the sample count                                                             k1 - reliable coefficient.
and interpolate method; and T h1 denotes a threshold value                                                                 In this paper, system equivalent impedance in an online
equal to the maximum error due to noise and harmonic effects                                                             method based on [9], was obtained. To estimate system
in (5) and the value used is 0.01Hz [15].                                                                                Thevenin equivalent circuit, load voltage and current samples
   The second method APPSW have the same problem that                                                                    are required.
the zero-crossing. The specified conditions are as follows:
                                                                                                                                                                                     V. C ASE           STUDY
               f rk−1 + f rk−2 + f rk−3
          If                            − f rk < T h2 ,                                                                     To evaluate the proposed method, a real Brazilian sub-
                           3
                                                                                                                         transmittion system was used. This network composes part
                            then : fk = f rk ,                                                          (7)              of the EDAL system and has 11 buses and 20 lines. The total
                                                                                                                         installed load has 242.6 MW and 107 MVAr. According to
                            else : fk = f0k ,                                                           (8)              Fig. 5, two units of DG were connected on the grid by CPC
                                                                                                                                                                                                                                                                                                                                                                                                                                                                                  5
                                                                                                                                                                                                                                                                   PCA                        CPC
                                                                                                                                                                                                                                                                                                                                                    DG
TBM
MCO-CHESF
                                                                                                                              MCO-CHESF                                                                                                                                                                                                       CTO
                                                                                                                                                                                                                PNO
CZA
BBE
PJA
DG
and CZA bus. CPC and CZA generators supply about 40% of                                                                                                                                                                the main generator greater than when some DG is get out.
total load system.                                                                                                                                                                                                     However, to relay R3, near CPC and CZA buses, greater
   Four cases were analysed on this paper. On the first, any                                                                                                                                                           value was obtained. This occurs because the contribution of
generation was connected on the grid, so all installed load                                                                                                                                                            main generator for fault near R3 is less than when no DG
was supplied by main generator. In second scenario, CPC                                                                                                                                                                is connected. In Fig. 7 reach of instantaneous directional
and CZA DG were on the grid, and on the following cases,                                                                                                                                                               overcurrent is present with all DG are connected on the grid.
generators were disconnected at network, one by one. In each
case, a stream of three relays was coordinated using adaptive
                                                                                                                                                                                                                                                        72.5                                           Instantaneous Reach (% of LT)        62
                                                                                                                                                                                                                        Instantaneous Reach (% of LT)
technique proposed. 64
   • R3 - PNO-CTO
                                                                                                                                                                                                                       Fig. 7. Reach of instantaneous directional overcurrent unit when CPC and
   The first relays (R1) may protect a line with only 500 m.                                                                                                                                                           CZA distributed generator it is on the grid.
On the second protective device (R2), the line protected has
10,34 km and, R3 relay acts on a line with 3,014 km.
                                                                                                                                       h (R2)                                                               h (R3)
                                21
                                                              h (R1)
                                                                                                    60.5                                                                51.5
                                                                                                                                                                                                                       For the R3 relay, near CPC bus, was verified that a large
                                20.5                                                                      60                                                                     51                                    variation on Thevenin equivalent system. In addiction to this
                                20                                                                       59.5                                                           50.5                                           variation, reach of overcurrent instantaneous unit was verified,
                                19.5                                                                      59                                                                     50                                    see Fig. 8.
                                19                                                                   58.5                                                               49.5
                                     0   50    100      150        200                                   0      50     100       150       200                              0         50      100     150      200
                                              Time (ms)                                                              Time (ms)                                                              Time (ms)                                                   71.9                                                                                60.62                                                                                           55
                                                                                                                                                                                                                       Instantaneous Reach (% of LT)
D. Out of CZA distributed generator                                                                                                                                                                          [7] S. HOROWITZ, A. PHADKE, and J. THORP, “Adaptive transmission
                                                                                                                                                                                                                 system relaying,” Power Delivery, IEEE Transactions on, vol. 3, no. 4,
   CZA contribute with about 40% of total DG of the system.                                                                                                                                                      pp. 1436–1445, Oct 1988.
However, this generator plant is located on an important                                                                                                                                                     [8] G. D. ROCKEFELLER, C. WAGNER, J. LINDERS, K. HICKS, and
                                                                                                                                                                                                                 D. RIZI, “Adaptive transmission relaying concepts for improved per-
region. The effect of CZA DG may provide a change on the                                                                                                                                                         formance,” Power Delivery, IEEE Transactions on, vol. 3, no. 4, pp.
direction current seen by R3 relay.                                                                                                                                                                              1446–1458, Oct 1988.
   Because of this characteristic a little modification in relation                                                                                                                                          [9] M. OJAGHI, Z. SUDI, and J. FAIZ, “Implementation of full adaptive
                                                                                                                                                                                                                 technique to optimal coordination of overcurrent relays,” Power Deliv-
of CPC out of the grid, the reach of instantaneous directional                                                                                                                                                   ery, IEEE Transactions on, vol. 28, no. 1, pp. 235–244, Jan 2013.
overcurrent unit were observed as shown in Fig. 9.                                                                                                                                                          [10] P. M. ANDERON, Power System Protection. Piscataway, NJ - USA:
                                                                                                                                                                                                                 IEEE Press Series on Power Engineering, 1999.
                                72                                                                   60.6                                 Instantaneous Reach (% of LT)   55                                [11] M. M. BegoviC, P. M. DjuriC, S. Dunlap, and A. G. Phadke, “Frequancy
                                                                     Instantaneous Reach (% of LT)
Instantaneous Reach (% of LT)
                                                          h (R1)                                                               h (R2)                                     50
                           71.5
                                                                                                     60.5
                                                                                                                                                                          45
                                                                                                                                                                                                 h (R3)          tracking in power networks in the presence of harmonics,” IEEE
                                                                                                     60.4
                                                                                                     60.3
                                                                                                                                                                          40                                     Transactions on Power Delivery, vol. 8, no. 2, pp. 480–486, Apr. 1993.
                                71
                                                                                                     60.2
                                                                                                                                                                          35                                [12] D. W. P. Thomas and M. S. Woolfson, “Evaluation of frequency tracking
                                                                                                                                                                          30
                           70.5                                                                      60.1
                                                                                                                                                                          25                                     methods,” IEEE Transactions on Power Delivery, vol. 3, no. 3, pp. 367–
                                70
                                                                                                      60                                                                  20                                     371, Jul. 2001.
                                                                                                     59.9                                                                 15
                           69.5                                                                      59.8                                                                 10
                                                                                                                                                                                                            [13] E. Sorrentino and R. Carvalho, “Performance of three algorithms for
                               0     50    100      150        200                                       0    50    100      150    200                                     0   50    100      150    200
                                          Time (ms)                                                                Time (ms)                                                         Time (ms)                   frequency measurement under transient conditions,” Electric Power
                                           (a)                                                                      (b)                                                                (c )                      System Research, vol. 80, pp. 1191–1196, Mar. 2010.
                                                                                                                                                                                                            [14] R. A. Zadeh, A. Ghosh, G. Ledwich, and F. Zare, “Online estimation
Fig. 9. Reach of instantaneous directional overcurrent unit when CZA                                                                                                                                             of distorted power system signal parameters,” Generation, Transmission
distributed generator get out of the grid.                                                                                                                                                                       and Distribution, IET, vol. 4, no. 6, pp. 746–755, Feb. 2010.
                                                                                                                                                                                                            [15] R. Aghazadeh, H. Lesani, M. Sanaye-Pasand, and B. Ganji, “New
                                                                                                                                                                                                                 technique for frequency and amplitude estimation of power system
                                                                                                                                                                                                                 signals,” Generation, Transmission and Distribution, IET, vol. 152,
                                                                                                                                                                                                                 no. 3, pp. 435–440, May. 2005.
                                                                                         VI. C ONCLUSION                                                                                                    [16] J. Ren, S. Member, and M. Kezunovic, “Real-time power system
                                                                                                                                                                                                                 frequency and phasors estimation using recursive wavelet transform,”
   This paper presented an adaptive overcurrent protection                                                                                                                                                       IEEE Transactions on Power Delivery, vol. 26, no. 3, pp. 1392–1402,
technique based on monitoring of the variation of the funda-                                                                                                                                                     Jul. 2011.
mental frequency, to obtain instantaneous overcurrent unit of                                                                                                                                               [17] F. SOUZA Jr. and B. SOUZA, “Adaptive overcurrent adjustment set-
                                                                                                                                                                                                                 tings: A case study using rtds,” in Innovative Smart Grid Technologies
relays based on frequency estimation for identify modifications                                                                                                                                                  Latin America (ISGT LA), 2013 IEEE PES Conference On, 2013, pp.
on the grid topology. The possible of an online Thevenin                                                                                                                                                         1–5.
system estimation given to the system a characteristic of                                                                                                                                                   [18] ATP - Alternative Transient Program, Leuven EMTP Center, Herverlee,
                                                                                                                                                                                                                 Belgium, 1987.
really adaptive protection scheme. As result of this really                                                                                                                                                 [19] L. Dube, Models in ATP: Language Manual, 1996.
adaptive scheme, offline step dont necessary as some paper                                                                                                                                                  [20] E. I. SCHWEITZER and A. ALIAGA, “Digital programmable time-
listed previously.                                                                                                                                                                                               parameter relay offers versatility and accuracy,” Power Apparatus and
                                                                                                                                                                                                                 Systems, IEEE Transactions on, vol. PAS-99, no. 1, pp. 152–157, 1980.
   The use of frequency estimation as indication of changes on                                                                                                                                              [21] S. G. A. PEREZ, “Modeling relays for power system protection studies,”
the network is a good option to do it. The fast results provided                                                                                                                                                 Ph.D. dissertation, University of Saskatchewan - Canad, 2006.
by this technique allow an update on instantaneous overcurrent                                                                                                                                              [22] B. H. ADAMIAK, M. and J. BRIGHT, “Feasibility of adaptive protec-
                                                                                                                                                                                                                 tion and control,” Power Delivery, IEEE Transactions on, vol. 8, no. 3,
unit with less than two samples in relation of modification act.                                                                                                                                                 pp. 975–983, 1993.
   In addition in all analysed cases coordination was obtained                                                                                                                                              [23] Z. LI, W. TONG, F. LI, and S. FENG, “Study on adaptive protection
for all relays of the grid. This fact shows that the adaptive                                                                                                                                                    system of power supply and distribution line,” in Power System Tech-
                                                                                                                                                                                                                 nology, 2006. PowerCon 2006. International Conference on, oct. 2006,
protection is really feasible in real system and may provide                                                                                                                                                     pp. 1 –6.
improvements in the operation of the protection power system.                                                                                                                                               [24] J. CHEN, S. CHEN, and Y. YANG, “Study on adaptive protection relay
                                                                                                                                                                                                                 system based on multi-agetn,” in Machine Learning and Cybernetics,
                                                                                                                                                                                                                 2005. Proceedings of 2005 International Conference on, vol. 1, Agosto
                                                                                                            R EFERENCES                                                                                          2005, pp. 114 –118.
                                                                                                                                                                                                            [25] H. YI, H. XUEHAO, and Z. GONGXIA, “A new adaptive current
                       [1] C. R. MASON, The Art and Science of Protective Relaying, first                                                                                                                        protection scheme of distribution networks with distributed generation,”
                           edition ed. Wiley, January 1956.                                                                                                                                                      in Sustainable Power Generation and Supply, 2009. SUPERGEN ’09.
                       [2] A. Y. ABDELAZIZ, H. E. A. TALLAT, A. I. NOSSEIR, and A. H.                                                                                                                            International Conference on, Abril 2009, pp. 1 –5.
                           AMMAR, “An adaptive protection scheme for optimal coordination of                                                                                                                [26] H. CHEUNG, A. HAMLYN, L. YANG, WANG, C. YANG, and
                           overcurrent relays,” Eletric Power System Research, vol. 61, pp. 1–9,                                                                                                                 R. CHEUNG, “Dsp-based adaptive protection for feeders with dis-
                           Maio 2001.                                                                                                                                                                            tributed generations,” in Power Engineering, 2007 Large Engineering
                       [3] A. H. A. A.-D. M. M. R. RAZAVI, F. and H. TORKAMAN, “A new                                                                                                                            Systems Conference on, oct. 2007, pp. 49 –53.
                           comprehensive genetic algorithm method for optimal evercurrent relays                                                                                                            [27] C. HOR, K. KANGVANSAIEHOL, P. CROSSLEY, and A. SHAFIU,
                           coordination,” Elect. Power Energy Syst. Res., pp. 713–720, 2007.                                                                                                                     “Relay models for protection studies,” in Power Tech Conference Pro-
                       [4] A. A. CHVEZ, J. L. GUARDADO, D. SEBASTIN, and E. MELGOZA,                                                                                                                             ceedings, 2003 IEEE Bologna, vol. 4, June 2003, pp. 8 pp. Vol.4–.
                           “Distance protection coordination using search methods,” IEEE Latin                                                                                                              [28] SEL-411L Protection and Automation System, Protection Manual.
                           America Transcations, vol. 6, no. 1, pp. 51–58, Maro 2008.
                       [5] N. OLIVEIRA, F. SOUZA Jr., and B. A. SOUZA, “Automao da
                           coordenao da proteo de sobrecorrente em sistemas eltricos de distribuio
                           utilizando algoritmos genticos,” in Transmission and Distribution Con-
                           ference and Exposition: Latin America (T&D-LA), 2010 IEEE/PES,
                           2010.
                       [6] J. K. Hwang and P. N. Markham, “Power system frequency estimation
                           by reduction of noise using three digital filters,” IEEE Transactions on
                           Instrumentation and Measurement, vol. 63, no. 2, pp. 402–409, Feb.
                           2014.