AP1000 Design

The steam and power conversion system of the AP1000 is designed to efficiently transfer heat from the reactor coolant to generate electrical power, utilizing two steam generators and a turbine-generator with an output of approximately 1,199,500 kW. The system incorporates various protective features, including overpressure protection, turbine overspeed protection, and erosion-corrosion monitoring to ensure safe and reliable operation. Additionally, instrumentation and monitoring systems are in place to maintain water chemistry and detect any contamination within the system.

Uploaded by

zhanggz0206
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
38 views5 pages

AP1000 Design

The steam and power conversion system of the AP1000 is designed to efficiently transfer heat from the reactor coolant to generate electrical power, utilizing two steam generators and a turbine-generator with an output of approximately 1,199,500 kW. The system incorporates various protective features, including overpressure protection, turbine overspeed protection, and erosion-corrosion monitoring to ensure safe and reliable operation. Additionally, instrumentation and monitoring systems are in place to maintain water chemistry and detect any contamination within the system.

Uploaded by

zhanggz0206
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 5

10.

Steam and Power Conversion System AP1000 Design Control Document

CHAPTER 10

STEAM AND POWER CONVERSION

10.1 Summary Description

The steam and power conversion system is designed to remove heat energy from the reactor
coolant system via the two steam generators and to convert it to electrical power in the
turbine-generator. The main condenser deaerates the condensate and transfers heat that is unusable
in the cycle to the circulating water system. The regenerative turbine cycle heats the feedwater,
and the main feedwater system returns it to the steam generators.

Table 10.1-1 gives the significant design and performance data for the major system components.
Figure 10.1-1 shows the rated heat balance for the turbine cycle process.

10.1.1 General Description

The steam generated in the two steam generators is supplied to the high-pressure turbine by the
main steam system. After expansion through the high-pressure turbine, the steam passes through
the two moisture separator/reheaters (MSRs) and is then admitted to the three low-pressure
turbines. A portion of the steam is extracted from the high- and low-pressure turbines for seven
stages of feedwater heating.

Exhaust steam from the low-pressure turbines is condensed and deaerated in the main condenser.
The heat rejected in the main condenser is removed by the circulating water system (CWS). The
condensate pumps take suction from the condenser hotwell and deliver the condensate through
four stages of low-pressure closed feedwater heaters to the fifth stage, open deaerating heater.
Condensate then flows to the suction of the steam generator feedwater booster pump and is
discharged to the suction of the main feedwater pump. The steam generator feedwater pumps
discharge the feedwater through two stages of high-pressure feedwater heating to the two steam
generators.

The turbine-generator has an output of approximately 1,199,500 kW for the Westinghouse nuclear
steam supply system (NSSS) thermal output of 3,415 MWt. The principal turbine-generator
conditions for the turbine rating are listed in Table 10.1-1. The rated system conditions for the
NSSS are listed in Table 10.1-1. The systems of the turbine cycle have been designed to meet the
maximum expected turbine generator conditions.

Instrumentation systems are designed for the normal operating conditions of the steam and
condensate systems. The systems are designed for safe and reliable control and incorporate
requirements for performance calculations and periodic heat balances. Instrumentation for the
secondary cycle is also provided to meet recommendations by the turbine supplier and
ANSI/ASME TDP-2-1985, "Recommended Practices for the Prevention of Water Damage to
Steam Turbines Used for Electric Power Generation." Design features for prevention of water
hammer in the steam generator are described in subsection 5.4.2.2. Continuous sampling
instrumentation and grab sample points are provided so that water chemistry in the secondary
cycle can be maintained within acceptable limits, as required by the nuclear steam system and

Tier 2 Material 10.1-1 Revision 19


10. Steam and Power Conversion System AP1000 Design Control Document

turbine suppliers (see subsections 9.3.4 and 10.3.5). Condenser tube/tube sheet leakage can be
identified and isolated by using condenser conductivity sampling provisions.

Criteria and bases for safety-related instrumentation for main steam isolation are discussed in
Section 7.3.

10.1.2 Protective Features

Loss of External Electrical Load and/or Turbine Trip Protection

In the event of turbine trip, steam is bypassed to the condenser via the turbine bypass valves and,
if required, to the atmosphere via the atmospheric relief valves. Steam relief permits energy
removal from the reactor coolant system. Load rejection capability is discussed in
subsections 10.3.2.3.1 and 15.2.2.

Overpressure Protection

Spring-loaded safety valves are provided on both main steam lines, in accordance with the ASME
Code, Section III. The pressure relief capacity of the safety valves is such that the energy
generated at the high-flux reactor trip setting can be dissipated through this system. The design
capacity of the main steam safety valves equals or exceeds 105 percent of the NSSS design steam
flow at an accumulation pressure not exceeding 110 percent of the main steam system design
pressure. Overpressure protection for the main steam lines is a safety-related function. The main
steam safety valves are described in subsection 10.3.2.

In addition, the shell sides of the feedwater heaters and the moisture separator/reheaters are
provided with overpressure protection in accordance with ASME Code, Section VIII, Division 1,
or equivalent standards.

Loss of Main Feedwater Flow Protection

The startup feedwater pumps provide feedwater to the steam generators for the removal of
sensible and decay heat whenever main feedwater flow is interrupted, including loss of offsite
electric power. This system is described in subsection 10.4.9.

Turbine Overspeed Protection

During normal operations, turbine overspeed protection is provided by the action of the redundant
controller of the electro-hydraulic control system. Additional protection is provided by an
overspeed protection system, which continuously monitors critical turbine parameters on a
three-channel basis. Each of the channels is independently testable under load with overspeed
protection during testing provided by the channels not being tested. If turbine speed exceeds
110 percent of rated speed, the electronic trip system causes steam supply valves to close, tripping
the unit. This system is described in subsection 10.2.2.5.

Tier 2 Material 10.1-2 Revision 19


10. Steam and Power Conversion System AP1000 Design Control Document

Turbine Missile Protection

Turbine rotor integrity minimizes the probability of generating turbine missiles and is discussed in
subsection 10.2.3. Turbine missiles are addressed in subsection 3.5.1.3. The favorable orientation
of the turbine-generator directs potential missiles away from safety-related equipment and
structures.

Radioactivity Protection

Under normal operating conditions, there are no significant radioactive contaminants present in
the steam and power conversion system. However, it is possible for the system to become
contaminated through steam generator tube leakage. In this event, radiological monitoring of the
main condenser air removal system, the steam generator blowdown system, and the main steam
lines will detect contamination and alarm high radioactivity concentrations. A discussion of the
radiological aspects of primary-to-secondary system leakage and limiting conditions for operation
is contained in Chapter 11. The steam generator blowdown system described in subsection 10.4.8
and the condensate polishing system described in subsection 10.4.6 serve to limit the radioactivity
level in the secondary cycle.

Erosion-Corrosion Protection

Erosion-corrosion resistant materials are used in steam and power conversion systems for
components exposed to single-phase or two-phase flow where significant erosion can occur.
Factors considered in the evaluation of erosion-corrosion include system piping and component
configuration and geometry, water chemistry, piping and component material, fluid temperature,
and fluid velocity. Carbon steel with only carbon and manganese alloying agents is not used for
applications subject to significant erosion-corrosion.

In addition to material selection, pipe size and layout may also be used to minimize the potential
for erosion-corrosion in systems containing water or two-phase flow. The secondary side water
chemistry (see subsection 10.3.5) uses a volatile pH adjustment chemical to maintain a
noncorrosive environment. Steam and power conversion systems are designed to facilitate
inspection and erosion-corrosion monitoring programs.

An industry-sponsored computer program developed for nuclear and fossil power plant
applications is used to evaluate the rate of wall thinning for components and piping potentially
susceptible to erosion-corrosion. The engineering models are the result of research and
development in the fields of material science, water chemistry, fluid mechanics, and corrosion
engineering. The program quantifies the benefits of piping material, system layout, and sizing
considerations used to reduce corrosion rates.

10.1.3 Combined License Information on Erosion-Corrosion Monitoring

The Combined License holder will address preparation of an erosion-corrosion monitoring


program for carbon steel portions of the steam and power conversion systems that contain water or
wet steam. This monitoring program will address industry guidelines and the requirements
included in Generic Letter 89-08.

Tier 2 Material 10.1-3 Revision 19


10. Steam and Power Conversion System AP1000 Design Control Document

Table 10.1-1

SIGNIFICANT DESIGN FEATURES AND


PERFORMANCE CHARACTERISTICS FOR MAJOR
STEAM AND POWER CONVERSION SYSTEM COMPONENTS
Nuclear Steam Supply System, Full Power Operation
Rated NSSS power (MWt) 3415
Steam generator outlet pressure (psig) 821
Steam generator inlet feedwater temperature (°F) 440
Maximum steam generator separator outlet steam moisture (%) 0.25
Steam generator outlet steam temperature (°F) 523
Quantity of steam generators 2
Flow rate per steam generator (lb/hr) 7.49 x 106

Turbine
Nominal output (kW) 1,199,500
Turbine type Tandem-compound 6-flow,
52 in. last-stage blade
Turbine elements 1 high pressure
3 low pressure
Operating speed (rpm) 1800

Tier 2 Material 10.1-4 Revision 19


10. Steam and Power Conversion System AP1000 Design Control Document

Figure 10.1-1

Rated Heat Balance

Tier 2 Material 10.1-5 Revision 19