Eyz 291: Router, Novanet291: Features

The EYZ 291 novaNet291 router is designed for efficient communication within the SAUTER novaNet system, allowing for configuration and remote access via RS-232 interface. It features a 1 MB buffer, supports various communication devices, and operates under specific ambient conditions. The device is suitable for mounting on a DIN rail and complies with relevant EMC directives.

Uploaded by

ghared saleh
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
26 views4 pages

Eyz 291: Router, Novanet291: Features

The EYZ 291 novaNet291 router is designed for efficient communication within the SAUTER novaNet system, allowing for configuration and remote access via RS-232 interface. It features a 1 MB buffer, supports various communication devices, and operates under specific ambient conditions. The device is suitable for mounting on a DIN rail and complies with relevant EMC directives.

Uploaded by

ghared saleh
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

Product data sheet 96.

691

EYZ 291: Router, novaNet291

How energy efficiency is improved


SAUTER novaNet communication, technology that has proven itself thousands of times over

Features
• Part of the EY-modulo 2 and EY3600 system family
• Bus access device for novaNet system bus with RS-232 interface
• For configuring EY-modulo 2 and EY3600 stations with SAUTER CASE applications
• For management-level software and all SAUTER novaPro visualisations and novaNet OPC servers
• Direct communication from novaNet stations to PC with a serial connection EYZ291F001
• Remote access with router function via RS-232 modem
• Remote monitoring in routel mode via RS-232 modem (i.e. automatic uploading of events)
• Communication using two-wire novaNet system bus
• Communication with RS-232-compatible pairs of devices (dial-up modem, ISDN adaptor, electronic
surge protector, OWG converter, wireless modem etc.)
• 1 MB buffer for separating the time characteristics of novaNet and RS-232 interface

Technical data
Power supply
Power supply 230 V~, 50/60 Hz
Max. current consumption 10 VA

Ambient conditions
Operating temperature 0...45 °C (32...113 °F)
Storage and transport temperature –25...70 °C (–13...158 °F)
Humidity 10…90% rh, no condensation

Interfaces and communication


COM port (DTE) DB9 plug
novaNet 1 × a/b terminal, 1 × RJ-11 socket
DIP switch 4 (baud rate, router/routel function)

Construction
Weight 0.99 kg (2.2 lb)

Standards and directives


Type of protection IP 20 (EN 60529)
CE conformity as per EMC directive 2004/108/EC EN 61000-6-1, EN 61000-6-2,
EN 61000-6-3, EN 61000-6-4

Overview of types
Type Description
EYZ291F001 novaNet router

Accessories
Type Description
0367862001 novaNet291 or moduNet292 automation station 1.5 m (4.9 ft)
0367862002 novaNet291 or moduNet292 automation station 2.9 m (9.5 ft)
0367862003 novaNet291 or moduNet292 automation station 6.0 m (19.7 ft)

ion

Additional informat
Fitting instructions MV 505463

Description of operation
Configuration of EY3600 and EY-modulo 2 stations via RS-232 interface. Access unit for SAUT-
ER novaPro visualisation and novaNet OPC-Server management level software.
The novaNet EYZ291F001 router is used to connect the EY3600 novaNet to a (notebook) PC via the
COM interface. The connection is either directly to the PC COM interface or via a dial-up modem as

Right of amendment reserved © 2015 Fr. Sauter AG 5.1 1/4


Product data sheet 96.691

regards every other switched or unswitched RS232-compatible device pair (ISDN adaptor, line driver,
converter for optical fibres, dedicated line modem, wireless modem etc.). The novaNet router has 1
MB buffer memory for de-coupling the time characteristic of the novaNet and the RS232 interface.
The functionality in the dial-up mode comprises the selection from above (remote access/router
mode) and the selection from below (remote monitoring/routel mode, i.e. automatic reporting of rele-
vant events).

Intended use
This product is only suitable for the purpose intended by the manufacturer, as described in the “De-
scription of operation” section.
All related product documents must also be adhered to. Changing or converting the product is not ad-
missible.

Engineering notes
• The EYZ291F001 novaNet router is designed for mounting on a DIN EN 50022 top-hat rail, as well
as for portable use or as a tabletop device.
• The EYZ291F001 version is powered with 230 V~ and the EYZ291F005 version with 115 V~.
• On the back there are a socket for the mains power supply (3-pin P+N+E lead required) and power
switch, a DB9 plug for the RS-232 connection, 1 DIL switch for selecting router or routel mode, 3
DIL switches for selecting the baud rate (19200, 38400, 57600) as well as an RJ-11 socket and a
plug-in screw terminal for connecting to the novaNet.

DIL switches

on (switch down = on)


1 2 3 4
Routel
19200
38400
57600

Switch 1 = On (switch down) switches the novaNet291 to routel mode.


The baud rate of the COM interface is selected by setting the corresponding DIL switches (38400
baud recommended). If no baud rate switch is set, a speed of 9600 baud is selected.

Disposal
When disposing of the product, observe the currently applicable local laws.
More information on materials can be found in the Declaration on materials and the environment for
this product.

Dimension drawing
DIN-3F 35 mm
EN 50022 - 35x7,5/35x15 45
( 1 .7 7 "
)
1 5 3 (6 ")
242 (9.53")
176 (6.93")

no va N R ec ei ve

t
no va N S en d
et Fa ul
et
et

DCD
no va N

DSR
Po w er

2/4 5.1 Right of amendment reserved © 2015 Fr. Sauter AG


Product data sheet 96.691

Connection diagram
DB9 Male
EYZ 291
OFF a b 1 DCD (IN)
ON
1 2 3 4 2 RD (IN)
3 TD (OUT)

Routel
19200
38400
57600
1 2 3 4 5 123456
novaNet 4 DTR (OUT)
5 GND
6 7 8 9
6 DSR (IN)
Baud DB9 RJ11 6/6 7 RTS (OUT)
ON/OFF
8 CTS (IN)
RS232 novaNet 9 RI (IN)
EYZ 291 F001
230 V~, 10 VA (SI1=T80 mA/ 250 V~)
EYZ 291 F005
115 V~, 10 VA (SI1=T160 mA/ 250 V~) B06705a

Wiring
Note:
The pin assignment of the RS-232 plug is defined according to DTE (data terminal equipment), which
means crossover cables must be used for connection to a PC (=DTE).
• The crossover should be as shown below.
• Not all null modem cables are suitable.
• A non-crossover cable (supplied with the modem) is used for connection with the modem.

EYZ 291 novaNet Modem Modem EYZ 291 novaNet

DB9 - DB9 DB9 - DB9


PC 1 DCD DCD 1 EYZ 291 Modem DCD DCD EYZ 291
(DTE) (DTE) 1 1
RD RD (DCE) (DTE)
2 2 RD RD
2 2
TD TD
3 3 TD TD
3 3
DTR DTR
4 4 DTR DTR
4 4
DB9 GND GND DB9 DB9
Male 5 5 GND GND DB9
Male Female 5 5
Male
DSR DSR
6 6 DSR DSR
6 6
RTS RTS
7 7 RB RB
7 7
CTS CTS
8 8 CTS CTS
8 8
9 RI RI 9 RI RI
9 9

DB25 - DB9
DB25 - DB9
PC DCD EYZ 291
1 1 Modem DCD EYZ 291
(DTE) (DTE) 1 1
2
TD RD
2
(DCE) (DTE)
TD RD
2 2
RD TD
3 3 RD TD
3 3
RTS DTR
4 4 RTS DTR
4 4
DB25 CTS GND DB9
Male 5 5 DB25 CTS GND DB9
Male Female 5 5
DSR DSR Male
6 6 DSR DSR
6 6
GND RTS
7 7 GND RTS
7 7
DCD CTS
8 8 DCD CTS
. 8 8
. RI .
9 . RI
. 9
DTR .
20 DTR
. 20
. .
. 22 RI
. .
.

For connection to the AS via RJ-11/RJ-12 cable, use the accessories listed above.
The PC address is set using the EY3600 software. The address range reserved for the management
level PC with router is from 31744 and 31999, the range for a management level with routel is from
32512 to 32767. See manual 7000991.001.

Right of amendment reserved © 2015 Fr. Sauter AG 5.1 3/4


Product data sheet 96.691

Application
• Clip-on PC: Access to AS network with computers without an ISA slot (notebooks).
• Remote access (router mode): Access from PC to the novaNet via all types of connected or non-
connected networks, by intermediary connection of two DCEs (e.g. modem access via telephone
network or access via ISDN TA, fibreoptic converter, COM server, CATV modem, wireless modem
etc.).
• Remote monitoring (routel mode): Remote units report significant events (configured using no-
vaPro32) via a connected network to a central operating station.

Remote monitoring topology (routel mode)

novaPro32

M M EYZ 291

M EYZ 291

M EYZ 291

LED indicator and diagnostics


Power Green Mains power present
novaNet Receive Yellow Flashes irregularly when telegrams are in circulation on the novaNet
novaNet Send Yellow Flashes when the novaNet-Router sends telegrams to the AS.
novaNet Fault Red / yellow Indicates novaNet faults, e.g.:
Earth fault (each pole)
DC or AC external voltage
> 50% of AS have no power supply.
(LED red when: a < 3.74 V, a > 8.88 V, b < 1.11 V, b > 6.22 V)
DSR Green The modem or PC connected to the router is operational (DTR crossed).
DCD Green “Connected” (online) message from a connected modem.

Fr. Sauter AG
Im Surinam 55
CH-4016 Basel
Tel. +41 61 - 695 55 55
www.sauter-controls.com

4/4 5.1 Right of amendment reserved © 2015 Fr. Sauter AG