PD Test Report (Cable)

The document is a test report for On Line Partial Discharge Testing of HT cables conducted at IOCL Gujarat Refinery, detailing the methodology, testing equipment, and results from the 7th phase of the project. It outlines the criticality of various assets tested, recommendations for inspection based on partial discharge activity, and emphasizes the importance of continuous monitoring. The report also includes a comprehensive analysis of the testing conducted from December 6 to December 24, 2022, with a creation date of May 7, 2023.

Uploaded by

sen19subhajit
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
32 views175 pages

PD Test Report (Cable)

The document is a test report for On Line Partial Discharge Testing of HT cables conducted at IOCL Gujarat Refinery, detailing the methodology, testing equipment, and results from the 7th phase of the project. It outlines the criticality of various assets tested, recommendations for inspection based on partial discharge activity, and emphasizes the importance of continuous monitoring. The report also includes a comprehensive analysis of the testing conducted from December 6 to December 24, 2022, with a creation date of May 7, 2023.

Uploaded by

sen19subhajit
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 175

+

Test Report
For

On Line Partial Discharge Testing (7th Phase) of


HT Cables
At
GUJARAT REFINERY

IOCL GUJARAT

Document ID : RPT_IOCL_GR_CB_CM_TST_V005

Navitus Controls & Equipment Pvt. Ltd


Prepared by : Incubation-18, WEBEL HRDC Building,
P-1 Taratala Road, Kolkata– 700068

Ref : W/O No. 26807898 Dated: 06/02/21

Release Date: 7-May-23

This document is for restricted circulation. No part of this document shall be reproduced, stored in retrieval system or transmitted
in any form or by any means – recording, photocopying, electronic and mechanical without prior permission of NCEPL.
Test Report for On Line Partial Discharge Testing at IOCL Gujarat
Refinery (WO :26807898 Dated: 06/02/21)

Reference:

Purchase Order No & Date 26807898 Dated: 06/02/21

Tender No JC20ELT221

Test conducted Date 06/12/2022-24/12/2022

Test conducted by Mr. Subhajit Sen / Mr. Arindam Chatterjee

Report Creation Date 7-May-23

Report prepared by Mr. Subhajit Sen / Mr. Arindam Chatterjee


Report Reviewed by Mr. Biplab Ghosh

Customer Details:

Customer Indian Oil Corporation Limited (IOCL), Gujarat


Refinery

Testing Location Cables at various substations

Report Creation Date 7-May-23

Customer Officers/ Mr. Sumanth Banavath/ Mr. Manish Prakash/ Mr. R. R.


Engineers involved Reddy

Kind Attn. Mr. S.V. RAJESH KUMAR


Test Report for On Line Partial Discharge Testing at IOCL Gujarat
Refinery (WO :26807898 Dated: 06/02/21)

Contents
1 Executive Summary ................................................................................................... 6

2 Background & Objective ............................................................................................ 7

3 Methodology ............................................................................................................... 8
a) PD-74 ..................................................................................................................................................................... 8
b) PD-30 ..................................................................................................................................................................... 8
c) Prycam Portable ..................................................................................................................................................... 8
d) PD-13 ..................................................................................................................................................................... 8

4 Summary Report & Analysis: ..................................................................................... 7

5 Annexure-I (Detailed Analysis- Cables) ................................................................... 24

5.1 HT-101 TIE FEEDER 1A -R Phase Cables ............................................................... 24

5.2 HT-101 TIE FEEDER 1A Y Phase Cables ................................................................ 26

5.3 HT-101 TIE FEEDER 1A B Phase Cables ................................................................ 29

5.4 HT-101 SAT 4 Cables .............................................................................................. 31

5.5 HT-101 OG to 33kV Distribution Switch Board 103A ............................................. 34

5.6 HT-101 SAT-2 Cables ........................................................................................... 39

5.7 HT-101 OG to 33kV Distribution Switch Board 103B .......................................... 41

5.8 HT-101 GT 6 I/C cables ........................................................................................ 46

5.9 HT-102 TIE FEEDER 2B ....................................................................................... 53

5.10 HT-102 SAT 1 Cables ........................................................................................... 59

5.11 HT-102 OG to 33kV Distribution Switch Board 104A .......................................... 61

5.12 HT-102 SAT 3 Cables ........................................................................................... 66

5.13 HT-102 GT 5 IC Cables ........................................................................................ 68

5.14 GRE Feeder-1 ....................................................................................................... 75

5.15 SS 37 BUS -A ....................................................................................................... 76

5.16 SS-39 BUS A ........................................................................................................ 79

5.17 GRE Feeder-3 ....................................................................................................... 81

5.18 DTR-5 Cables ....................................................................................................... 82

5.19 SS-38 BUS A ........................................................................................................ 84

5.20 SS-39 Bus B ......................................................................................................... 87

5.21 SS-38 Bus B ......................................................................................................... 89

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 3 of 173


Test Report for On Line Partial Discharge Testing at IOCL Gujarat
Refinery (WO :26807898 Dated: 06/02/21)

5.22 SS37 BUS B ......................................................................................................... 92

5.23 GRE Feeder-2 ....................................................................................................... 94

5.24 DTR-6 Cables ....................................................................................................... 96

5.25 OG TO BS-VI FDR1 ............................................................................................... 98

5.26 OG TO BS-VI FDR2 ............................................................................................. 100

5.27 InterConnection-1 P5 & P16 .............................................................................. 102

5.28 InterConnection-2 P12 & P20 ............................................................................ 105

5.29 OG to CGP-1 ICT-1 R-Phase ............................................................................... 108

5.30 OG to CGP-1 ICT-1 Y-Phase ............................................................................... 110

5.31 OG to CGP-1 ICT-1 B-Phase ............................................................................... 112

5.32 OG to CGP-1 ICT-2 R-Phase ............................................................................... 113

5.33 OG to CGP-1 ICT-2 Y-Phase ............................................................................... 115

5.34 OG to CGP-1 ICT-2 B Phase ............................................................................... 117

5.35 I/C FROM TR-1 ................................................................................................... 119

5.36 GRE OG TO 33/6.6KV TR-1 ................................................................................ 122

5.37 GRE OG TO 33/6.6KV TR-2 ................................................................................ 124

5.38 GRE OG TO 33/6.6KV TR-3 ................................................................................ 126

5.39 SS 37 TR-11A Cables ......................................................................................... 128

5.40 C37 TR-11C Cables ............................................................................................ 132

5.41 C37 TR-11D Cables ............................................................................................ 136

5.42 C37 TR-11B Cables ............................................................................................ 139

5.43 SS39 OG TO DUMAD-1 FDR Cables ................................................................... 143

5.44 SS39 to DUMAD-2 FDR Cables .......................................................................... 144

5.45 SS39 Reactor-1 I/C Cables ................................................................................ 146

5.46 SS39 Reactor-1 0/G Cables ............................................................................... 148

5.47 SS39 TR-1 Cables .............................................................................................. 149

5.48 SS39 TR-2 Cables .............................................................................................. 153

5.49 38 TRP-01-01 Cables ......................................................................................... 156

5.50 38 TRP-01-02 Cables ......................................................................................... 158

5.51 38 TRP-01-03 Cables ......................................................................................... 160

5.52 38 TRP-01-04 Cables ......................................................................................... 162

5.53 38 TRP-01-05 Cables ......................................................................................... 164


RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 4 of 173
Test Report for On Line Partial Discharge Testing at IOCL Gujarat
Refinery (WO :26807898 Dated: 06/02/21)

5.54 38 TRP-01-06 Cable ........................................................................................... 165

5.55 SS61TR-61021 ................................................................................................... 166

5.56 SS61 TR-61022 .................................................................................................. 168

5.57 SS61 TR-61023 .................................................................................................. 170

5.58 SS61 TR-61024 .................................................................................................. 172

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 5 of 173


Test Report for On Line Partial Discharge Testing at IOCL Gujarat
Refinery (WO :26807898 Dated: 06/02/21)

1 Executive Summary
Background:

Navitus Controls & Equipment (P) Ltd (NCEPL) received a contract from IOCL Gujarat refinery for online partial
discharge monitoring of 33kV cables, HT transformer & motor termination box, Transformer main tank, 33kV,
11kV, 6.6kV switchgears. The contract has defined the test procedures and also mentioned the type of sensors
that are to be used for testing each of the target assets. However, NCEPL not only complied with the stated
procedures and the type of sensors specified against each type of the asset but also deployed additional
sensors to achieve better sensitivity for the tests performed. The following table describes the sensors specified
in the contract and the additional tests performed by NCEPL team for achieving higher sensitivity and data
comparison among various sensors for better accuracy.

Type of asset Tests performed as per SOW in the Additional tests Remarks
tender performed by NCEPL
Cable EMI based PD test in HF range, TeV/ Contact type acoustic
terminations & UHF at the cable terminations and testing at the
cable accessible joints. 72 hrs.Continuous terminations and
monitoring in case of high PD activity accessible joints for data
with rising trend. corroboration

Test summary& criticality analysis:

The project envisages repeated testing of the target assets based on their criticality. In the 7th Phase of the
project NCEPL tested the following assets.

 33kV cables- 214

NCEPL team has followed a proven testing methodology and has collected the On Line PD data of these target
assets for detail analysis. Depending on the outcome of the analysis, NCEPL team has classified the assets
into different categories based on their criticalities. NCEPL team has also provided specific recommendations
against each type of criticality. Recommendations provided are based upon NCEPL experience against various
types of discharges.

The progression of PD is a complex activity and depends on many factors making it almost impossible to
predict the time to failure for these PD pulses. It is through repeated testing IOCL has to determine the trend
analysis and a fast-increasing trend is what is most critical and requires immediate intervention. Hence it is
helpful to have the failure history of the target assets before any On Line PD Monitoring is performed on an
asset.

The assets with criticality ORANGE should be immediately inspected. The detailed recommendations were
provided in the detailed report later in the document. However, the criticality marked in YELLOW shall also be
inspected as per the recommendations. Failure history shall be shared for more accurate criticality assignment.

Conclusion:

NCEPL team has completed the 5th Phase of the testing and shall undertake the next phase in close
coordination with the IOCL team. Meanwhile, NCEPL urges IOCL to open the assets marked critical and look
for physical marks/ traces of PD in these assets. If found these deteriorations need to be fixed and the assets
can be re-tested after that.

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 6 of 173


Test Report for On Line Partial Discharge Testing at IOCL Gujarat
Refinery (WO :26807898 Dated: 06/02/21)

2 Background & Objective

Navitus Controls & Equipment (P) Ltd (NCEPL) received an order from M/S India Oil Corporation
Limited, Gujarat refinery for the online partial discharge testing of the following:
1. Condition assessment of HT 11/33 kV switchgears- 1200 EA
2. Localization of PD activity in 11/33kV switchgears- 100 EA
3. Online PD testing of 6.6kV switchgears- 1848 EA
4. Localization of PD activity in 6.6 kV switchgears- 50 EA
5. Online PD testing of 33 kV cables- 880 EA
6. Cables, cable joints & end termination- 360 EA
7. Diagnostic testing of HT cables- 20 EA
8. 72 hrs continuous monitoring of PD in critical cables- 10 EA
9. Online PD testing of transformer terminal box & motor terminal box- 2240 EA
10. PD monitoring of transformer main tank through UHF drain valve sensors- 10 EA
11. Diagnostic testing of transformers- 8 EA
12. Condition monitoring of HT/ LT motors- 5 EA
13. Diagnostic testing of VCBs of HT panels- 10 EA
Testing modalities were defined by IOCL in the tender as follows:
1. For 11 & 33kV switchgears, PD monitoring shall be done in UHF range using UHF sensors.
2. For PD localization, HFCT/ UHF/ Ultrasonic/ offline PD test shall be carried out for locating the PD in
the switchgear (33 kV & 11kV)
3. For 6.6 kV switchgears airborne acoustic & TeV technology shall be used for PD identification &
localization.
4. For 33kV cables, cable terminations and the whole cable shall be tested through EMI/ HFCT based
sensors & TeV or UHF sensors at the terminals.
5. Critical cables shall be subjected to 72 hrs of continuous monitoring.
6. 6.6 kV transformer terminal box & motor terminal box shall be monitored using air-borne acoustic &
TeV. PD testing has also been done using EMI based sensors for HT motors.
7. PD identification inside the transformer tank shall be done through UHF drain valve sensors.
8. Location of PD in transformers shall be done through four acoustic & one HFCT sensor technology.
NCEPL engineers used multiple On Line PD Testing equipment to ascertain the test results as per the
technology requirement guided in the work order/ tender. The equipment that were used are:-

 PD-30 (TeV & Ultrasound measurement device)


 PD 74 (Acoustic, UHF Rod & Guide Antenna, TEV, HFCT)
 Pry-CAM Portable (EMI Based Antenna/Sensor)

 PD-13 (Acoustic & HFCT based device for location analysis in switchgears

 PD-71 (UHF PD monitoring & localizing system)

 UHF drain valve sensors


 Failure history of each asset tested (if any) shall be provided by IOCL for more accurate
prediction. The failure history (or previous PD test readings) of the assets shall be mandatory
for providing recommendations after the first round of test.
 To conclude NCEPL would like to thank IOCL for giving this opportunity to undertake the On
RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 7 of 173
Test Report for On Line Partial Discharge Testing at IOCL Gujarat
Refinery (WO :26807898 Dated: 06/02/21)

Line PD Testing for their critical Cables/ Transformers & Switchgears.

3 Methodology

NCEPL deployed four partial discharge monitoring devices for comprehensive PD monitoring of the
assets listed in the work order of IOCL to NCEPL. The devices are:-
a) PD-74
b) PD-30
c) Prycam Portable
d) Prycam Grids
e) PD-13
f) PD-71

a) PD-74
PD-74 is an HFCT based Cable PD monitoring device. It has three channels viz: Acoustic channel,
High frequency channel &Ultra high frequency channel. It has the following features:-
 Real-time PD measurement with provision for Acoustic, HF & UHF range of measurements
in one single unit.
 Provision for both Wideband & Narrow band spectrum measurement &analysis.
 PRPD, 3D & PD Expert features are available in the unit itself. No requirement of laptop at
site as the unit has a well-defined HMI.
 Apart from cables it can also be used for PD measurements in GIS, AIS & HV Switchboards.

b) PD-30
The PD-30 has the following features:-
 PD-30 is a TeV& Acoustic measuring instrument.
 Data archiving capability in the acquisition unit itself. So it can be easily handled at site for
data acquisition &viewing.
 PD-30 is suitable for Cables &HT switchgear.

c) Prycam Portable
The Prycam portable is an EMI antenna based PD monitoring device. It captures PD signals in high
frequency range. The device has the following features:-
 Traffic light indication (Green/Yellow/Red) in the power cycle providing an easy
understanding of the health of the asset (Basic mode).
 PRPD, Spectrum, Pulse characteristics using waveform analysis, PRPD data filter, Pulse
count, intensity & amplitude for more refined and detailed analysis if the Traffic light is Red
(Advanced/Premium mode).
 Data saving option along with the feature for uploading the data in Prysmian cloud for data
retrieving & analysis at a later stage using any i-pad with Prycam software installed with all
the data & photographs from any location.

d) PD-13

PD-13 has the following features:-


 Four acoustic and one HF based transformer PD monitoring system.
 Four acoustic sensors are installed and dynamically moved across the transformer wall to identify
acoustic discharge (mechanical/ electrical) inside the transformer.
 HFCT installed at the transformer earth path is gives a confirmation of the presence of electrical
PD.
 PD location inside the tank can be identified.

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 8 of 173


Test Report for On Line Partial Discharge Testing at IOCL Gujarat
Refinery (WO : 26807898 Dated: 06/02/21)

4 Summary Report & Analysis:


Cables
Reading
Cable Rating Test
Sl. No. Feeder Name TeV HFCT EMI Pattern (PD/Noise) Observation
No. (kV) Point
dBmV Pattern µW mV
HT-101 CGP-2
33 HT-101 End 2 N/A N/A 75.12 External Interference
1 Cable 1 Low Critical PD
33 HT-102 End 1 N/A N/A 64.00 External Interference
33 HT-101 End 0 N/A N/A 68.03 External Interference
2 Cable 2 Low Critical PD
33 HT-102 End 2 N/A N/A 45.00 External Interference
Tie Feeder 1A R Phase
33 HT-101 End 0 N/A N/A 61.65 External Interference
3 Cable 3 Low Critical PD
33 HT-102 End 1 N/A N/A 30.00 External Interference
33 HT-101 End 0 N/A N/A 64.00 External Interference
4 Cable 4 Low Critical PD
33 HT-102 End 3 N/A N/A 34.90 External Interference
33 HT-101 End 6 N/A N/A 36.79 External Interference
5 Cable 1 Low Critical PD
33 HT-102 End 4 N/A N/A 39.87 External Interference
33 HT-101 End 2 N/A N/A 94.49 External Interference
6 Cable 2 Low Critical PD
33 HT-102 End 1 N/A N/A 89.00 External Interference
Tie Feeder 1A Y Phase
33 HT-101 End 0 N/A N/A 39.84 External Interference
7 Cable 3 Low Critical PD
33 HT-102 End 1 N/A N/A 45.00 External Interference
33 HT-101 End 1 N/A N/A 74.80 External Noise
8 Cable 4 Low Critical PD
33 HT-102 End 6 N/A N/A 65.98 External Noise
33 HT-101 End 4 N/A N/A 77.95 External Noise
9 Cable 1 Low Critical PD
33 HT-102 End 3 N/A N/A 56.00 External Noise
Tie Feeder 1A B Phase
33 HT-101 End 5 N/A N/A 77.95 External Noise
10 Cable 2 Low Critical PD
33 HT-102 End 4 N/A N/A 57.34 External Noise

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 7 of 173


Test Report for On Line Partial Discharge Testing at IOCL Gujarat
Refinery (WO : 26807898 Dated: 06/02/21)

33 HT-101 End 1 N/A N/A 74.80 External Noise


11 Cable 3 Low Critical PD
33 HT-102 End 0 N/A N/A 72.34 External Noise

33 HT-101 End 0 N/A N/A 77.95 External Noise


12 Cable 4 Low Critical PD
33 HT-102 End 0 N/A N/A 76.90 External Noise
33 SS End 2 N/A N/A 38.30 Noise
13 HT-101 SAT 4 R Phase Cable 1 Noise Low Critical PD
33 TR End 0 N/A N/A 24.00
33 SS End 1 N/A N/A 35.43 Noise
14 HT-101 SAT 4 Y Phase Cable 1 Low Critical PD
33 TR End 1 N/A N/A 21.00 Noise
33 SS End 0 N/A N/A 135.0 Surface Discharge
15 HT-101 SAT 4 B Phase Cable 1 Moderately Low Critical PD
33 TR End 2 N/A N/A 89.00 Surface Discharge
33 HT-101 End 0 N/A N/A 77.95 Noise
16 Cable 1 Low Critical PD
33 HT-103 End 1 N/A N/A 76.89 Noise
HT-101 OG to 33kV 33 HT-101 End 4 N/A N/A 62.01 Noise
17 Distribution Switch Cable 2 Noise Low Critical PD
Board 103A R Phase 33 HT-103 End 2 N/A N/A 46.00
33 HT-101 End 1 N/A N/A 36.85 Noise
18 Cable 3 Low Critical PD
33 HT-103 End 4 N/A N/A 36.00 Noise

33 HT-101 End 2 N/A N/A 60.04 Noise


19 Cable 1 Low Critical PD
33 HT-103 End 2 N/A N/A 45.00 Noise
HT-101 OG to 33kV 33 HT-101 End 1 N/A N/A 77.95 Noise
20 Distribution Switch Cable 2 Noise Low Critical PD
Board 103A Y Phase 33 HT-103 End 2 N/A N/A 71.93

33 HT-101 End 5 N/A N/A 61.65 Noise


21 Cable 3 Low Critical PD
33 HT-103 End 2 N/A N/A 65.90 Noise
33 HT-101 End 3 N/A N/A 15.80 Noise
22 Cable 1 Low Critical PD
33 HT-103 End 2 N/A N/A 21.00 Noise
HT-101 OG to 33kV 33 HT-101 End 8 N/A N/A 21.37 Noise
23 Distribution Switch Cable 2 Low Critical PD
33 HT-103 End 7 N/A N/A 24.00 Noise
Board 103A B Phase
33 HT-101 End 2 N/A N/A 21.37 Noise
24 Cable 3 Low Critical PD
33 HT-103 End 4 N/A N/A 24.00 Noise

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 8 of 173


Test Report for On Line Partial Discharge Testing at IOCL Gujarat
Refinery (WO : 26807898 Dated: 06/02/21)

33 SS End 1 N/A N/A 93.70 Noise


25 HT-101 SAT-2 R Phase Cable 1 Low Critical PD
33 TR End 2 N/A N/A 86.77 Noise
33 SS End 1 N/A N/A 54.57 Noise
26 HT-101 SAT-2 Y Phase Cable 1 Low Critical PD
33 TR End 4 N/A N/A 45.90 Noise
33 SS End 3 N/A N/A 17.39 Noise
27 HT-101 SAT-2 B Phase Cable 1 Low Critical PD
33 TR End 2 N/A N/A 12.00 Noise
33 HT-101 End 0 N/A N/A 75.12 External Interference
28 Cable 1 Low Critical PD
33 HT-103 End 2 N/A N/A 64.00 External Interference
HT-101 OG to 33kV 33 HT-101 End 1 N/A N/A 68.03 External Interference
29 Distribution Switch Cable 2 Low Critical PD
Board 103B R Phase 33 HT-103 End 2 N/A N/A 56.00 External Interference
33 HT-101 End 1 N/A N/A 61.98 External Interference
30 Cable 3 Low Critical PD
33 HT-103 End 0 N/A N/A 45.00 External Interference
33 HT-101 End 0 N/A N/A 64.00 External Interference
31 Cable 1 Low Critical PD
33 HT-103 End 2 N/A N/A 45.00 External Interference
HT-101 OG to 33kV 33 HT-101 End 1 N/A N/A 36.85 External Interference
32 Distribution Switch Cable 2 Low Critical PD
Board 103B Y Phase 33 HT-103 End 3 N/A N/A 23.99 External Interference
33 HT-101 End 1 N/A N/A 64.00 External Interference
33 Cable 3 Low Critical PD
33 HT-103 End 4 N/A N/A 45.12 External Interference
33 HT-101 End 4 N/A N/A 53.92 External Interference
34 Cable 1 Low Critical PD
33 HT-103 End 1 N/A N/A 75.12 External Interference
HT-101 OG to 33kV 33 HT-101 End 3 N/A N/A 65.34 External Interference
35 Distribution Switch Cable 2 Low Critical PD
Board 103B B Phase 33 HT-103 End 2 N/A N/A 68.03 External Interference
33 HT-101 End 7 N/A N/A 61.98 External Interference
36 Cable 3 Low Critical PD
33 HT-103 End 6 N/A N/A 49.78 External Interference
33 HT-101 End 1 N/A N/A 40.35 Noise
37 Cable 1 Low Critical PD
33 TR End 0 N/A N/A 12.00 Noise
HT-101 GT 6 I/C R 33 HT-101 End 5 N/A N/A 30.51 Noise
38 Phase Cable 2 Low Critical PD
33 TR End 1 N/A N/A 23.76 Noise
33 HT-101 End 0 N/A N/A 36.85 Noise
39 Cable 3 Low Critical PD
33 HT-102 End 3 N/A N/A 24.00 Noise

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 9 of 173


Test Report for On Line Partial Discharge Testing at IOCL Gujarat
Refinery (WO : 26807898 Dated: 06/02/21)

33 HT-101 End 2 N/A N/A 36.22 Noise


40 Cable 4 Low Critical PD
33 HT-102 End 6 N/A N/A 23.24 Noise
33 HT-101 End 3 N/A N/A 25.72 Noise
41 Cable 1 Low Critical PD
33 TR End 2 N/A N/A 30.76 Noise
33 HT-101 End 1 N/A N/A 46.36 Noise
42 Cable 2 Low Critical PD
33 TR End 2 N/A N/A 45.90 Noise
HT-101 GT 6 I/C Y
Phase 33 HT-101 End 0 N/A N/A 90.94 Noise
43 Cable 3 Low Critical PD
33 HT-102 End 9 N/A N/A 77.65 Noise
33 HT-101 End 2 N/A N/A 75.79 Noise
44 Cable 4 Low Critical PD
33 HT-102 End 3 N/A N/A 56.00 Noise
33 HT-101 End 5 N/A N/A 79.92 Noise
45 Cable 1 Low Critical PD
33 TR End 3 N/A N/A 65.00 Noise
33 HT-101 End 1 N/A N/A 73.03 Noise
46 Cable 2 Low Critical PD
HT-101 GT 6 I/C B 33 TR End 2 N/A N/A 64.98 Noise
Phase
33 HT-101 End 2 N/A N/A 63.07 Noise
47 Cable 3 Low Critical PD
33 HT-102 End 6 N/A N/A 45.00 Noise
33 HT-101 End 9 N/A N/A 73.70 Noise
48 Cable 4 Low Critical PD
33 HT-102 End 7 N/A N/A 77.00 Noise
33 HT-101 End 1 N/A N/A 64.00 Corona
49 Cable 1 Moderately Low Critical PD
33 HT-102 End 2 N/A N/A 45.90 Corona
33 HT-101 End 1 N/A N/A 175.0 External Noise
50 Cable 2 Low Critical PD
HT-102 TIE FEEDER 33 HT-102 End 1 N/A N/A 101.0 External Noise
2B R Phase 33 CGP-I End 1 N/A N/A 342.0 External Noise
51 Cable 3 Low Critical PD
33 HT-102 End 0 N/A N/A 264.0 External Noise

33 CGP-I End 1 N/A N/A 125.0 Noise


52 Cable 4 Low Critical PD
33 HT-102 End 3 N/A N/A 76.98 Noise

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 10 of 173


Test Report for On Line Partial Discharge Testing at IOCL Gujarat
Refinery (WO : 26807898 Dated: 06/02/21)

33 HT-101 End 0 N/A N/A 125.0 External Noise


53 Cable 1 External Noise Moderately Low Critical PD
33 HT-102 End 3 N/A N/A 94.55
33 HT-101 End 2 N/A N/A 245.0 External Noise
54 Cable 2 Moderately Low Critical PD
33 HT-102 End 1 N/A N/A 125.0 External Noise
HT-102 TIE FEEDER
2B Y Phase 33 CGP-I End 1 N/A N/A 175.0 External Noise
55 Cable 3 Moderately Low Critical PD
33 HT-102 End 2 N/A N/A 125.0 External Noise
Possible Minor Surface
33 CGP-I End 0 N/A N/A 65.59
56 Cable 4 Discharge Moderately Low Critical PD
33 HT-102 End 4 N/A N/A 56.77 Noise
33 HT-101 End 1 N/A N/A 64.00 External Noise
57 Cable 1 Low Critical PD
33 HT-102 End 2 N/A N/A 45.00 External Noise
33 HT-101 End 1 N/A N/A 175.0 External Noise
58 Cable 2 Moderately Low Critical PD
33 HT-102 End 3 N/A N/A 125.0 External Noise
HT-102 TIE FEEDER External Noise
33 CGP-I End 1 N/A N/A 175.0
59 2B B Phase Cable 3 Moderately Low Critical PD
33 HT-102 End 2 N/A N/A 125.0 External Noise
Possible Minor Surface
33 CGP-I End 0 N/A N/A 75.79
Discharge
60 Cable 4 Moderately Low Critical PD
Possible Minor Surface
33 HT-102 End 1 N/A N/A 65.00
Discharge

33 SS End 0 N/A N/A 88.58


61 HT-102 SAT 1 R Phase Cable 1 Noise Low Critical PD
33 TR End 1 N/A N/A 76.00
33 SS End 2 N/A N/A 46.00
62 HT-102 SAT 1 Y Phase Cable 1 Noise Low Critical PD
33 TR End 0 N/A N/A 20.32
33 SS End 3 N/A N/A 125.0
63 HT-102 SAT 1 B Phase Cable 1 Noise Low Critical PD
33 TR End 0 N/A N/A 12.40
33 HT-102 End 0 N/A N/A 58.07
64 Cable 1 Noise Low Critical PD
HT-102 OG to 33kV 33 HT-104 End 0 N/A N/A 14.56
Distribution Switch 33 HT-102 End 1 N/A N/A 28.06
65 Board 104A R Phase Cable 2 Noise Low Critical PD
33 HT-104 End 5 N/A N/A 25.35
66 Cable 3 33 HT-102 End 3 N/A N/A 62.01 Noise Low Critical PD

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 11 of 173


Test Report for On Line Partial Discharge Testing at IOCL Gujarat
Refinery (WO : 26807898 Dated: 06/02/21)

33 HT-104 End 5 N/A N/A 156.9 External Noise


33 HT-102 End 2 N/A N/A 125.0
67 Cable 1 Noise Low Critical PD
33 HT-104 End 0 N/A N/A 82.52
HT-102 OG to 33kV 33 HT-102 End 3 N/A N/A 92.52
68 Distribution Switch Cable 2 Minor Corona Discharge Moderately Low Critical PD
Board 104A Y Phase 33 HT-104 End 1 N/A N/A 32.25
33 HT-102 End 4 N/A N/A 116.1 Possible Cross-talk from
69 Cable 3 Y2 Cable Moderately Low Critical PD
33 HT-104 End 2 N/A N/A 21.20
Possible Surface
33 HT-102 End 2 N/A N/A 90.00
70 Cable 1 Discharge Moderately low Critical PD
33 HT-104 End 0 N/A N/A 35.50 Noise
HT-102 OG to 33kV
Distribution Switch 33 HT-102 End 6 N/A N/A 97.44
71 Cable 2 Noise No Critical PD
Board 104A B Phase 33 HT-104 End 2 N/A N/A 25.32
33 HT-102 End 7 N/A N/A 97.44
72 Cable 3 Noise No Critical PD
33 HT-104 End 4 N/A N/A 32.02
33 SS End 9 N/A N/A 328.5 Surface Discharge
73 HT-102 SAT 3 R Phase Cable 1 Moderately Critical PD
33 TR End 8 N/A N/A 56.53 Noise
Possible Cross talk from R
33 SS End 6 N/A N/A 101.4
74 HT-102 SAT 3 Y Phase Cable 1 phase Moderately Low Critical PD
33 TR End 7 N/A N/A 35.23 Noise
33 SS End 4 N/A N/A 251.3
75 HT-102 SAT 3 B Phase Cable 1 Noise Low Critical PD
33 TR End 3 N/A N/A 45.32
33 HT-102 End 1 N/A N/A 342.0
76 Cable 1 Noise Low Critical PD
33 TR End 4 N/A N/A 120.0
33 HT-102 End 0 N/A N/A 65.91
77 Cable 2 Noise Low Critical PD
33 TR End 2 N/A N/A 32.20
HT-102 GT 5 IC R
Phase 33 HT-102 End 3 N/A N/A 111.2
78 Cable 3 Noise Low Critical PD
33 HT-101 End 3 N/A N/A 45.62
33 HT-102 End 2 N/A N/A 21.17
79 Cable 4 Noise Low Critical PD
33 HT-101 End 0 N/A N/A 15.56

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 12 of 173


Test Report for On Line Partial Discharge Testing at IOCL Gujarat
Refinery (WO : 26807898 Dated: 06/02/21)

33 HT-102 End 15 N/A N/A 667.0 External Noise


80 Cable 1 Low Critical PD
33 TR End 12 N/A N/A 85.64 External Noise
33 HT-102 End 8 N/A N/A 588.2 External Noise
81 Cable 2 Low Critical PD
HT-102 GT 5 IC Y 33 TR End 6 N/A N/A 85.35 External Noise
Phase 33 HT-102 End 7 N/A N/A 509.4 External Noise
82 Cable 3 Low Critical PD
33 HT-101 End 3 N/A N/A 64.58 External Noise
33 HT-102 End 11 N/A N/A 102.4 External Noise
83 Cable 4 Low Critical PD
33 HT-101 End 10 N/A N/A 89.56 External Noise
33 HT-102 End 15 N/A N/A 245.0 Noise
84 Cable 1 Low Critical PD
33 TR End 14 N/A N/A 102.5 Noise
33 HT-102 End 12 N/A N/A 44.91 Noise
85 Cable 2 Low Critical PD
HT-102 GT 5 IC B 33 TR End 10 N/A N/A 85.32 Noise
Phase 33 HT-102 End 11 N/A N/A 73.03 Corona Discharge
86 Cable 3 Moderately Low Critical PD
33 HT-101 End 13 N/A N/A 35.28 Corona Discharge
33 HT-102 End 12 N/A N/A 79.39 Corona Discharge
87 Cable 4 Moderately Low Critical PD
33 HT-101 End 12 N/A N/A 65.24 Corona Discharge

33 CGP-II End 2 N/A N/A 42.32 Noise


88 Cable 1 Low Critical PD
33 GRE End 2 N/A N/A 30.21 Noise
GRE Feeder-1
33 CGP-II End 0 N/A N/A 62.01 Noise
89 Cable 2 Low Critical PD
33 GRE End 1 N/A N/A 35.12 Noise
33 CGP-II End 1 N/A N/A 60.04 Noise
90 Cable 1 Low Critical PD
33 SS-37 End 1 N/A N/A 25.20 Noise
33 CGP-II End 0 N/A N/A 17.00 Noise
91 Cable 2 Low Critical PD
SS-37 BUS A 33 SS-37 End 1 N/A N/A 12.0 Noise
33 CGP-II End 2 N/A N/A 61.48 Noise
92 Cable 3 Low Critical PD
33 SS-37 End 3 N/A N/A 14.58 Noise
93 Cable 4 33 CGP-II End 0 N/A N/A 77.95 Noise Low Critical PD

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 13 of 173


Test Report for On Line Partial Discharge Testing at IOCL Gujarat
Refinery (WO : 26807898 Dated: 06/02/21)

33 SS-37 End 2 N/A N/A 32.15 Noise

33 CGP-II End 1 N/A N/A 20.03 Corona Discharge


94 Cable 5 Moderately Low Critical PD
33 SS-37 End 1 N/A N/A 18.08 Noise
33 CGP-II End 6 N/A N/A 90.00 Noise
95 Cable 1 Low Critical PD
33 SS-39 End 0 N/A N/A 10.25 Noise
SS-39 BUS A Possible Surface
33 CGP-II End 3 N/A N/A 133.7
96 Cable 2 Discharge Moderately Low Critical PD
33 SS-39 End 2 N/A N/A 58.25 Noise
33 CGP-II End 2 N/A N/A 28.61 Noise
97 Cable 1 Low Critical PD
33 GRE End 0 N/A N/A 22.32 Noise
GRE Feeder-3
33 CGP-II End 1 N/A N/A 21.37 Noise
98 Cable 2 Low Critical PD
33 GRE End 0 N/A N/A 12.45 Noise
33 SS End 4 N/A N/A 105.0 Noise
99 DTR-5 R Phase Cable 1 Low Critical PD
33 TR End 3 N/A N/A 25.32 Noise
33 SS End 2 N/A N/A 223.4 Noise
100 DTR-5 Y Phase Cable 2 Low Critical PD
33 TR End 8 N/A N/A 64.52 Noise
33 SS End 4 N/A N/A 309.7 Noise
101 DTR-5 B Phase Cable 3 Low Critical PD
33 TR End 6 N/A N/A 102.5 Noise
External Interference
33 CGP-II End 3 N/A N/A 146.6
102 Cable 1 Low Critical PD
33 SS-38 End 2 N/A N/A 97.6 Noise
33 CGP-II End 2 N/A N/A 368.1 Noise
103 Cable 2 Low Critical PD
33 SS-38 End 4 N/A N/A 278.6 Noise
SS-38 Bus A 33 CGP-II End 1 N/A N/A 82.2 Noise
104 Cable 3 Low Critical PD
33 SS-38 End 0 N/A N/A 56.4 Noise
33 CGP-II End 3 N/A N/A 51.92 Noise
105 Cable 4 Moderately Low Critical PD
33 SS-38 End 1 N/A N/A 50.90 Corona Discharge
33 CGP-II End 4 N/A N/A 58.07 Noise
106 Cable 5 Moderately Low Critical PD
33 SS-38 End 0 N/A N/A 10.57 Corona Discharge

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 14 of 173


Test Report for On Line Partial Discharge Testing at IOCL Gujarat
Refinery (WO : 26807898 Dated: 06/02/21)

33 CGP-II End 3 N/A N/A 25.7 Noise


107 Cable 1 Moderately Low Critical PD
33 SS-39 End 2 N/A N/A 30.24 Corona Discharge
SS-39 Bus B
33 CGP-II End 3 N/A N/A 20.0 Noise
108 Cable 2 Moderately Low Critical PD
33 SS-39 End 3 N/A N/A 24.00 Corona Discharge
33 CGP-II End 0 N/A N/A 65.90 Noise
109 Cable 1 Low Critical PD
33 SS-38 End 1 N/A N/A 45.89 Noise
33 CGP-II End 1 N/A N/A 46.36 Noise
110 Cable 2 Low Critical PD
33 SS-38 End 0 N/A N/A 39.87 Noise
33 CGP-II End 0 N/A N/A 34.02 Noise
111 SS-38 Bus B Cable 3 Low Critical PD
33 SS-38 End 1 N/A N/A 25.09 Noise
33 CGP-II End 1 N/A N/A 31.87 Noise
112 Cable 4 Moderately Low Critical PD
33 SS-38 End 1 N/A N/A 40.31 Corona Discharge
33 CGP-II End 0 N/A N/A 67.91 Noise
113 Cable 5 Low Critical PD
33 SS-38 End 1 N/A N/A 56.98 Noise
33 CGP-II End 1 N/A N/A 65.79 Noise
114 Cable 1 Moderately Low Critical PD
33 SS-37 End 0 N/A N/A 26.76 Corona Discharge
33 CGP-II End 1 N/A N/A 29.67 Noise
115 Cable 2 Moderately Low Critical PD
33 SS-37 End 2 N/A N/A 23.39 Corona Discharge
SS-37 BUS B
33 CGP-II End 2 N/A N/A 47.34 Noise Moderately Low Critical
116 Cable 3
33 SS-37 End 4 N/A N/A 48.38 Corona Discharge PD
33 CGP-II End 1 N/A N/A 72.98 Noise
117 Cable 4 Low Critical PD
33 SS-37 End 3 N/A N/A 67.91 Noise
33 SS End 2 N/A N/A 85.63 External Interference
118 Cable 1 Low Critical PD
33 GRE End 1 N/A N/A 47.12 External Interference
GRE Feeder-2
33 SS End 0 N/A N/A 55.43 External Interference
119 Cable 2 Low Critical PD
33 GRE End 2 N/A N/A 37.32 External Interference
33 SS End 1 N/A N/A 111.2 External Interference
120 DTR-6 R Phase Cable 1 Low Critical PD
33 TR End 0 N/A N/A 91.03 Noise
121 DTR-6 Y Phase Cable 1 33 SS End 1 N/A N/A 119.1 Noise Low Critical PD

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 15 of 173


Test Report for On Line Partial Discharge Testing at IOCL Gujarat
Refinery (WO : 26807898 Dated: 06/02/21)

33 TR End 0 N/A N/A 104.3 Noise


33 SS End 0 N/A N/A 64.00 Noise
122 DTR-6 B Phase Cable 1 Low Critical PD
33 TR End 1 N/A N/A 41.32 Noise
CGP-1
33 CGP-I End 0 N/A N/A 32.48 Noise
123 Cable 1 Low Critical PD
33 BS-VI End 1 N/A N/A 23.01 Noise
33 CGP-I End 2 N/A N/A 19.23 Noise
124 OG TO BS-VI FDR1 Cable 2 Low Critical PD
33 BS-VI End 3 N/A N/A 25.02 Noise
33 CGP-I End 4 N/A N/A 21.17 Noise
125 Cable 3 Low Critical PD
33 BS-VI End 2 N/A N/A 23.71 Noise
33 CGP-I End 0 N/A N/A 30.40 Corona Discharge
126 Cable 1 Moderately Low Critical PD
33 BS-VI End 1 N/A N/A 45.98 Noise
33 CGP-I End 0 N/A N/A 22.35 Corona Discharge
127 OG TO BS-VI FDR2 Cable 2 Moderately Low Critical PD
33 BS-VI End 1 N/A N/A 29.80 Noise
33 CGP-I End 0 N/A N/A 23.41 Noise
128 Cable 3 Low Critical PD
33 BS-VI End 1 N/A N/A 18.78 Noise
33 GIS-1 End 0 N/A N/A 30.92 Noise
129 Cable 1 Low Critical PD
33 GIS-2 End 1 N/A N/A 26.54 Noise
33 GIS-1 End 1 N/A N/A 30.92 Noise
130 Cable 2 Low Critical PD
33 GIS-2 End 0 N/A N/A 26.87 Noise
InterConnection-1 P5 & 33 GIS-1 End 3 N/A N/A 41.10 Noise
131 P16 Cable 3 Low Critical PD
33 GIS-2 End 1 N/A N/A 23.33 Noise
33 GIS-1 End 3 N/A N/A 147.4 Noise
132 Cable 4 Low Critical PD
33 GIS-2 End 2 N/A N/A 56.76 Noise
33 GIS-1 End 0 N/A N/A 42.52 Noise
133 Cable 5 Low Critical PD
33 GIS-2 End 1 N/A N/A 21.65 Noise
134 InterConnection-1 P12 & Cable 1 33 GIS-2 End 0 N/A N/A 36.85 Noise Low Critical PD

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 16 of 173


Test Report for On Line Partial Discharge Testing at IOCL Gujarat
Refinery (WO : 26807898 Dated: 06/02/21)

P20 33 GIS-1 End 1 N/A N/A 23.32 Noise


33 GIS-2 End 4 N/A N/A 37.56 Noise
135 Cable 2 Low Critical PD
33 GIS-1 End 1 N/A N/A 24.43 Noise
33 GIS-2 End 2 N/A N/A 58.07 Noise
136 Cable 3 Low Critical PD
33 GIS-1 End 0 N/A N/A 17.32 Noise
33 GIS-2 End 1 N/A N/A 67.91 Noise
137 Cable 4 Low Critical PD
33 GIS-1 End 0 N/A N/A 19.12 Noise
33 GIS-2 End 0 N/A N/A 62.01 Noise
138 Cable 5 Low Critical PD
33 GIS-1 End 1 N/A N/A 18.43 Noise
33 TR End 1 N/A N/A 28.58 Noise
139 Cable 1 Moderately Low Critical PD
33 SS End 2 N/A N/A 34.54 Corona Discharge
OG TO CGP-1 ICT-1 R-
Phase 33 TR End 1 N/A N/A 31.70 Noise
140 Cable 2 Corona Discharge Moderately Low Critical PD
33 SS End 0 N/A N/A 24.00
33 SS End 2 N/A N/A 40.31 Noise
141 Cable 1 Low Critical PD
OG TO CGP-1 ICT-1 Y- 33 TR End 1 N/A N/A 35.87 Noise
Phase 33 SS End 3 N/A N/A 29.88 Noise
142 Cable 2 Low Critical PD
33 TR End 2 N/A N/A 34.12 Noise
33 SS End 2 N/A N/A 49.89 Noise
143 Cable 1 Low Critical PD
OG TO CGP-1 ICT-1 B- 33 TR End 1 N/A N/A 27.67 Noise
Phase 33 SS End 4 N/A N/A 64.00 Noise
144 Cable 2 Low Critical PD
33 TR End 2 N/A N/A 22.56 Noise
33 SS End 2 N/A N/A 21.57 Noise
145 Cable 1 Low Critical PD
OG to CGP-1 ICT-2 R 33 TR End 1 N/A N/A 23.56 Noise
Phase 33 SS End 4 N/A N/A 24.00 Noise
146 Cable 2 Low Critical PD
33 TR End 3 N/A N/A 11.34 Noise
33 SS End 0 N/A N/A 24.00 Noise
147 Cable 1 Low Critical PD
OG to CGP-1 ICT-2 Y 33 TR End 1 N/A N/A 21.43 Noise
Phase 33 SS End 0 N/A N/A 33.00 Noise
148 Cable 2 Low Critical PD
33 TR End 0 N/A N/A 22.98 Noise

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 17 of 173


Test Report for On Line Partial Discharge Testing at IOCL Gujarat
Refinery (WO : 26807898 Dated: 06/02/21)

33 SS End 1 N/A N/A 103.3 Minor Internal Discharge


149 Cable 1 Moderately Low Critical PD
OG to CGP-1 ICT-2 B 33 TR End 0 N/A N/A 22.43 Noise
Phase 33 SS End 3 N/A N/A 28.61 Noise
150 Cable 2 Low Critical PD
33 TR End 1 N/A N/A 22.34 Noise
33 SS End 0 N/A N/A 60.24 Noise
Cable 1
33 TR End 1 N/A N/A 51.03 Noise
33 SS End 4 N/A N/A 46.06 Noise
Cable 2
33 TR End 3 N/A N/A 56.67 Noise
33 SS End 2 N/A N/A 50.31 Noise
151 I/C FROM TR-1 Cable 3 Low Critical PD
33 TR End 1 N/A N/A 29.32 Noise
33 SS End 1 N/A N/A 34.72 Noise
Cable 4
33 TR End 2 N/A N/A 21.75 Noise
33 SS End 0 N/A N/A 39.81 Noise
Cable 5
33 TR End 1 N/A N/A 32.54 Noise
SS-16A
33 SS End 10 N/A N/A 15.80 Noise
152 Cable 1 Low Critical PD
GRE OG TO 33/6.6KV 33 TR End 11 N/A N/A 25.86 Noise
TR-1 33 SS End 12 N/A N/A 35.86 Noise
153 Cable 2 Low Critical PD
33 TR End 13 N/A N/A 25.87 Noise
33 SS End 13 N/A N/A 10.98 Noise
154 Cable 1 Low Critical PD
GRE OG TO 33/6.6KV 33 TR End 10 N/A N/A 24.00 Noise
TR-2 33 SS End 12 N/A N/A 293.5 Noise
155 Cable 2 Low Critical PD
33 TR End 10 N/A N/A 21.76 Noise
33 SS End 10 N/A N/A 27.69 Noise
156 Cable 1 Low Critical PD
GRE OG TO 33/6.6KV 33 TR End 8 N/A N/A 19.54 Noise
TR-3 33 SS End 12 N/A N/A 27.86 Noise
157 Cable 2 Low Critical PD
33 TR End 17 N/A N/A 31.54 Noise
SS-37
33 SS End 2 N/A N/A 33.00 Noise
158 C37 TR-11A R Phase Cable 1 Low Critical PD
33 TR End 1 N/A N/A 26.78 Noise

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 18 of 173


Test Report for On Line Partial Discharge Testing at IOCL Gujarat
Refinery (WO : 26807898 Dated: 06/02/21)

33 SS End 1 N/A N/A 46.00 Noise


159 Cable 2 Low Critical PD
33 TR End 0 N/A N/A 41.54 Noise
33 SS End 4 N/A N/A 46.00 Noise
160 Cable 1 Low Critical PD
33 TR End 2 N/A N/A 21.87 Noise
C37 TR-11A Y Phase
33 SS End 6 N/A N/A 38.76 Noise
161 Cable 2 Low Critical PD
33 TR End 0 N/A N/A 24.00 Noise
33 SS End 0 N/A N/A 26.80 Corona Discharge
162 Cable 1 Moderately Low Critical PD
33 TR End 1 N/A N/A 21.56 Noise
C37 TR-11A B Phase
33 SS End 1 N/A N/A 26.24 Noise
163 Cable 2 Low Critical PD
33 TR End 2 N/A N/A 17.65 Noise
33 SS End 5 N/A N/A 38.89 Corona Discharge
164 Cable 1 Moderately Low Critical PD
33 TR End 5 N/A N/A 23.54 Noise
C37 TR-11C R Phase
33 SS End 0 N/A N/A 29.10 Corona Discharge
165 Cable 2 Moderately Low Critical PD
33 TR End 1 N/A N/A 17.98 Noise
33 SS End 0 N/A N/A 24.69 Corona Discharge
166 Cable 1 Moderately Low Critical PD
33 TR End 0 N/A N/A 14.76 Noise
C37 TR-11C Y Phase
33 SS End 0 N/A N/A 38.75 Noise
167 Cable 2 Low Critical PD
33 TR End 0 N/A N/A 19.89 Noise
33 SS End 0 N/A N/A 29.06 Noise
168 Cable 1 Low Critical PD
33 TR End 0 N/A N/A 18.02 Noise
C37 TR-11C B Phase
33 SS End 0 N/A N/A 32.60 Noise
169 Cable 2 Low Critical PD
33 TR End 0 N/A N/A 21.61 Noise
33 SS End 0 N/A N/A 111.6 Noise
170 Cable 1 Low Critical PD
33 TR End 0 N/A N/A 34.01 Noise
C37 TR-11D R Phase
33 SS End 1 N/A N/A 19.46 Noise
171 Cable 2 Low Critical PD
33 TR End 1 N/A N/A 29.98 Noise
33 SS End 2 N/A N/A 76.54 Noise
172 Cable 1 Low Critical PD
33 TR End 0 N/A N/A 21.65 Noise
C37 TR-11D Y Phase
33 SS End 1 N/A N/A 24.00 Noise
173 Cable 2 Low Critical PD
33 TR End 2 N/A N/A 21.98 Noise

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 19 of 173


Test Report for On Line Partial Discharge Testing at IOCL Gujarat
Refinery (WO : 26807898 Dated: 06/02/21)

Possible Corona
33 SS End 4 N/A N/A 17.15
174 Cable 1 Discharge Moderately Low Critical PD
33 TR End 0 N/A N/A 19.87 Noise
C37 TR-11D B Phase
33 SS End 0 N/A N/A 20.65 Noise
175 Cable 2 Low Critical PD
33 TR End 1 N/A N/A 22.98 Noise
33 SS End 0 N/A N/A 54.93 Corona Discharge
176 Cable 1 Moderately Low Critical PD
33 TR End 1 N/A N/A 17.01 Noise
C37 TR-11B R Phase
33 SS End 0 N/A N/A 21.17 Noise
177 Cable 2 Low Critical PD
33 TR End 0 N/A N/A 14.07 Noise
33 SS End 2 N/A N/A 20.66 Noise
178 Cable 1 Low Critical PD
33 TR End 0 N/A N/A 33.07 Noise
C37 TR-11B Y Phase
33 SS End 2 N/A N/A 21.37 Noise
179 Cable 2 Low Critical PD
33 TR End 0 N/A N/A 31.03 Noise
33 SS End 4 N/A N/A 20.66 Noise
180 Cable 1 Low Critical PD
33 TR End 1 N/A N/A 23.87 Noise
C37 TR-11B B Phase
33 SS End 1 N/A N/A 17.00 Noise
181 Cable 2 Low Critical PD
33 TR End 2 N/A N/A 24.07 Noise
SS-39
182 SS39 OG TO DUMAD-1 Cable 1 33 SS-39 End 4 N/A N/A 46.06 Noise Low Critical PD
FDR
183 Cable 2 33 SS-39 End 3 N/A N/A 50.31 Noise Low Critical PD

184 Cable 1 33 SS-39 End 0 N/A N/A 19.09 Corona Discharge Moderately Low Critical PD
SS39 to DUMAD-2 FDR
185 Cable 2 33 SS-39 End 0 N/A N/A 34.72 Noise Low Critical PD
Cable 1 33 Reactor End 17 N/A N/A 189.1 Internal Surface Discharge Moderately High PD
SS39 REACTOR-11/C
186
CABLES Cable 2 33 Reactor End 12 N/A N/A 11.38 Internal Surface Discharge Moderately Low PD
Moderately Critical PD is
Cable 1 33 Reactor End 4 N/A N/A 46.36 Internal Surface Discharge
SS39 REACTOR-1 O/G observed
187
CABLES Moderately Critical PD is
Cable 2 33 Reactor End 6 N/A N/A 48.39 Internal Surface Discharge
observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 20 of 173


Test Report for On Line Partial Discharge Testing at IOCL Gujarat
Refinery (WO : 26807898 Dated: 06/02/21)

33 SS End 2 N/A N/A 43.34 Noise Low Critical PD


188 Cable 1
33 TR End 1 N/A N/A 23.65 Noise Low Critical PD
SS39 TR-1 R Phase
33 SS End 3 N/A N/A 30.51 Noise Low Critical PD
189 Cable 2
33 TR End 1 N/A N/A 27.34 Noise Low Critical PD
33 SS End 1 N/A N/A 125.0 Noise Low Critical PD
190 Cable 1
33 TR End 0 N/A N/A 15.06 Noise Low Critical PD
SS39 TR-1 Y Phase
33 SS End 0 N/A N/A 90.00 Noise Low Critical PD
191 Cable 2
33 TR End 1 N/A N/A 25.98 Noise Low Critical PD
33 SS End 2 N/A N/A 31.50 Noise Low Critical PD
192 Cable 1
33 TR End 1 N/A N/A 33.00 Noise Low Critical PD
SS39 TR-1 B Phase
33 SS End 1 N/A N/A 20.27 Noise Low Critical PD
193 Cable 2
33 TR End 0 N/A N/A 33.02 Noise Low Critical PD
33 SS End 2 N/A N/A 17.67 Noise
194 Cable 1 Low Critical PD
33 TR End 1 N/A N/A 20.09 Noise
SS39 TR-2 R Phase
33 SS End 4 N/A N/A 29.73 Noise
195 Cable 2 Low Critical PD
33 TR End 1 N/A N/A 21.52 Noise
33 SS End 1 N/A N/A 24.00 Corona Discharge
196 Cable 1 Moderately Low Critical PD
33 TR End 0 N/A N/A 16.86 Noise
SS39 TR-2 Y Phase
33 SS End 0 N/A N/A 20.27 Noise
197 Cable 2 Low Critical PD
33 TR End 1 N/A N/A 25.04 Noise
33 SS End 2 N/A N/A 29.24 Noise
198 Cable 1 Low Critical PD
33 TR End 0 N/A N/A 24.76 Noise
SS39 TR-2 B Phase
33 SS End 2 N/A N/A 22.09 Noise
199 Cable 2 Low Critical PD
33 TR End 1 N/A N/A 23.87 Noise
SS-38
33 SS End 2 N/A N/A 63.07 Noise
200 38 TRP-01-01 Cable 1 Noise Low Critical PD
33 TR End 1 N/A N/A 34.87

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 21 of 173


Test Report for On Line Partial Discharge Testing at IOCL Gujarat
Refinery (WO : 26807898 Dated: 06/02/21)

33 SS End 4 N/A N/A 15.93 Noise


201 Cable 2 Low Critical PD
33 TR End 2 N/A N/A 31.54 Noise
33 SS End 4 N/A N/A 17.00 Corona Discharge
202 Cable 1 Moderately Low Critical PD
33 TR End 1 N/A N/A 32.67 Noise
38 TRP-01-02
33 SS End 3 N/A N/A 17.76 Noise
203 Cable 2 Low Critical PD
33 TR End 2 N/A N/A 24.56 Noise
33 SS End 4 N/A N/A 102.4 Noise
204 Cable 1 Low Critical PD
33 TR End 1 N/A N/A 54.87 Noise
38 TRP-01-03
33 SS End 3 N/A N/A 7.228 Noise
205 Cable 2 Low Critical PD
33 TR End 2 N/A N/A 19.97 Noise
33 SS End 4 N/A N/A 23.91 Noise
206 Cable 1 Low Critical PD
33 TR End 1 N/A N/A 23.02 Noise
38 TRP-01-04
33 SS End 3 N/A N/A 25.46 Corona Discharge
207 Cable 2 Moderately Low Critical PD
33 TR End 2 N/A N/A 24.51 Noise
33 SS End 8 N/A N/A 14.93 Noise
208 38 TRP-01-05 Cable 1 Low Critical PD
33 TR End 5 N/A N/A 23.31 Noise
33 SS End 0 N/A N/A 14.93 Noise
209 38 TRP-01-06 Cable 1 Low Critical PD
33 TR End 1 N/A N/A 26.08 Noise
SS-61
33 SS End 6 N/A N/A 50.37 Noise
210 Cable 1 Low Critical PD
33 TR End 2 N/A N/A 565.1 Noise
SS61 TR-61021
33 SS End 9 N/A N/A 420.7 Noise
211 Cable 2 Low Critical PD
33 TR End 4 N/A N/A 512.5 Noise
33 SS End 6 N/A N/A 675.1 Noise
212 Cable 1 Low Critical PD
33 TR End 2 N/A N/A 174.9 Noise
SS61 TR-61022
33 SS End 8 N/A N/A 704.5 Noise
213 Cable 2 Low Critical PD
33 TR End 4 N/A N/A 161.7 Noise
33 SS End 3 N/A N/A 587.1 Noise
214 SS61 TR-61023 Cable 1 Low Critical PD
33 TR End 4 N/A N/A 121.5 Noise

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 22 of 173


Test Report for On Line Partial Discharge Testing at IOCL Gujarat
Refinery (WO : 26807898 Dated: 06/02/21)

33 SS End 7 N/A N/A 102.4 Noise


215 Cable 2 Low Critical PD
33 TR End 3 N/A N/A 138.4 Noise
33 SS End 6 N/A N/A 675.1 Noise
216 Cable 1 Low Critical PD
33 TR End 4 N/A N/A 573.9 Noise
SS61 TR-61024
33 SS End 8 N/A N/A 704.5 Noise
217 Cable 2 Low Critical PD
33 TR End 2 N/A N/A 471.2 Noise

PDPattern Low Moderately Low Moderate Moderately High High


Noise/External Interference Minor Surface Surface discharge/ Minor Internal Surface Internal Discharge
Discharge/Corona Internal Surface Discharge Discharge/ Minor
Internal Discharge

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 23 of 173


at
Test Report for On Line Partial Discharge Testing at IOCL Gujarat
Refinery (WO No.- 26807898 Dated: 06/02/21)

5 Annexure-I (Detailed Analysis- Cables)

5.1 HT-101 TIE FEEDER 1A -R Phase Cables


This feeder has 4 cable runs.

TEST-1

The TeV test has been carried out for all the cables of the feeder. The result is as follows:

Cable 1 2 3 4
TeV (dBmV) 2 0 0 0

TEST-2

Test-2 has not been conducted through HFCT based device as the common earth sheaths of the
three cables were not accessible.

TEST-3

Test-3 has been conducted through EMI based device in advanced mode, of all the cables. The
results obtained are as follows:

1. Cable 1

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Possible Corona Discharge External interference


Amplitude 46.00 mV 75.12 mV
Criticality Moderately Low Low

Conclusion No PD inception is observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 24 of 173


at
Test Report for On Line Partial Discharge Testing at IOCL Gujarat
Refinery (WO No.- 26807898 Dated: 06/02/21)

2. Cable 2

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Corona Discharge External Interference


Amplitude 46.00 mV 68.03 mV
Criticality Moderately Low Low
Conclusion No PD inception is observed

3. Cable 3

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern External Interference External Interference


Amplitude 61.90 mV 61.65
Criticality Low Low
Conclusion No PD inception is observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 25 of 173


at
Test Report for On Line Partial Discharge Testing at IOCL Gujarat
Refinery (WO No.- 26807898 Dated: 06/02/21)

4. Cable 4

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern External Interference External Interference


Amplitude 75.12 mV 64.00 mV
Criticality Low Low
Conclusion No PD inception is observed

5.2 HT-101 TIE FEEDER 1A Y Phase Cables


This feeder has 4 cable runs.

TEST-1

The TeV test has been carried out for all the cables of the feeder. The result is as follows:

Cable 1 2 3 4
TeV (dBmV) 6 2 0 1

TEST-2

Test-2 has not been conducted through HFCT based device as the common earth sheath of the four
cables was not accessible.

TEST-3

Test-3 has been conducted through EMI based device in advanced mode, of all the cables. The
results are as follows:

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 26 of 173


at
Test Report for On Line Partial Discharge Testing at IOCL Gujarat
Refinery (WO No.- 26807898 Dated: 06/02/21)

1. Cable 1

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern External Interference External Interference


Amplitude 64.00 mV 36.79 mV
Criticality Low Low
Conclusion No PD inception is observed

2. Cable 2

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern External Interference External Interference


Amplitude 64.00 mV 94.49 mV
Criticality Low Low
Conclusion No PD inception is observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 27 of 173


at
Test Report for On Line Partial Discharge Testing at IOCL Gujarat
Refinery (WO No.- 26807898 Dated: 06/02/21)

3. Cable 3

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
th
6th Phase 7 Phase
PRPD Pattern

Pattern External Interference External Interference


Amplitude 64.00 mV 39.84 mV
Criticality Low Low
Conclusion No New PD inception is observed

4. Cable 4

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
th
6th Phase 7 phase
PRPD Pattern

Pattern External Noise External Noise


Amplitude 64.00 mV 74.80 mV
Criticality Low Low
Conclusion No New PD inception is observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 28 of 173


at
Test Report for On Line Partial Discharge Testing at IOCL Gujarat
Refinery (WO No.- 26807898 Dated: 06/02/21)

5.3 HT-101 TIE FEEDER 1A B Phase Cables


This feeder has 4 cable runs.

TEST-1

The TeV test has been carried out for all the cables of the feeder. The result is as follows:

Cable 1 2 3 4
TeV (dBmV) 4 5 1 0

TEST-2

Test-2 has not been conducted through HFCT based device as the common earth sheath of the four
cables was not accessible.

TEST-3

Test-3 has been conducted through EMI based device in advanced mode, of all the cables. The
results are as follows:

1. Cable 1

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th phase
PRPD Pattern

Pattern External Noise External Noise


Amplitude 53.92 mV 77.95 mV
Criticality Low Low
Conclusion No PD inception is observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 29 of 173


at
Test Report for On Line Partial Discharge Testing at IOCL Gujarat
Refinery (WO No.- 26807898 Dated: 06/02/21)

2. Cable 2

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
th
6th Phase 7 phase
PRPD Pattern

Pattern External Noise External Noise


Amplitude 44.85 mV 77.95 mV
Criticality Low Low
Conclusion No PD inception is observed

3. Cable 3

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern External Noise External Noise


Amplitude 36.79 mV 74.80 mV
Criticality Low Low
Conclusion No New PD inception is observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 30 of 173


at
Test Report for On Line Partial Discharge Testing at IOCL Gujarat
Refinery (WO No.- 26807898 Dated: 06/02/21)

4. Cable 4

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
th
6th Phase 7 Phase
PRPD Pattern

Pattern External Noise External Noise


Amplitude 53.92 mV 77.95 mV
Criticality Low Low
Conclusion No New PD inception is observed

5.4 HT-101 SAT 4 Cables


The feeder has 3 cable runs.

TEST-1

The TeV test has been carried out for all the cables of the feeder. The result is as follows:

TeV SS end

Cable R Y B
TeV (dBmV) 2 1 0

TEST-2

Test-2 has not been conducted through HFCT based device as the common earth sheath of all the
cables was not available.

TEST-3

Test-3 has been conducted through EMI based device, of all the cables. The result is as follows:

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 31 of 173


at
Test Report for On Line Partial Discharge Testing at IOCL Gujarat
Refinery (WO No.- 26807898 Dated: 06/02/21)

1. R Phase

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known

6th Phase 7th Phase


PRPD Pattern

Pattern Noise Noise


Amplitude 90.94 mV 38.30 mV
Criticality Low Low
Conclusion No PD inception is observed

2. Y Phase

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known

6th Phase 7th Phase


PRPD Pattern

Pattern Noise Noise


Amplitude 46.36 mV 35.43 mV
Criticality Low Low
Conclusion No PD inception is observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 32 of 173


at
Test Report for On Line Partial Discharge Testing at IOCL Gujarat
Refinery (WO No.- 26807898 Dated: 06/02/21)

3. B Phase

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result of SS End
6th Phase 7th Phase
PRPD Pattern

Pattern Noise Surface Discharge


Amplitude 90.94 mV 135.0 mV
Criticality Low Moderate PD
Conclusion No Critical PD is observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 33 of 173


at
Test Report for On Line Partial Discharge Testing at IOCL Gujarat
Refinery (WO No.- 26807898 Dated: 06/02/21)

5.5 HT-101 OG to 33kV Distribution Switch Board 103A


This feeder has 9 runs of cable.

TEST-1

The TeV test has been carried out for all the cables of the feeder. The result is as follows:

Cable R-1 R-2 R-3 Y-1


TeV (dBmV) 0 4 1 2

Cable Y-2 Y-3 B-1 B-2 B-3


TeV (dBmV) 1 5 3 8 2

TEST-2

Test-2 has not been conducted through HFCT based device as the common earth sheath of all the
cables was not available.

TEST-3
Test-3 has been conducted through EMI based device, of all the cables. The result is as follows:-

1. Cable R1

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Noise Noise


Amplitude 65.91 mV 77.95 mV
Criticality Low Low
Conclusion No PD inception is observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 34 of 173


at
Test Report for On Line Partial Discharge Testing at IOCL Gujarat
Refinery (WO No.- 26807898 Dated: 06/02/21)

2. Cable R2

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Noise Noise


Amplitude 46.36 mV 62.01 mV
Criticality Low Low
Conclusion No PD inception is observed

3. Cable R3

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Noise Noise


Amplitude 46.36 36.85 mV
Criticality Low Low
Conclusion No PD inception is observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 35 of 173


at
Test Report for On Line Partial Discharge Testing at IOCL Gujarat
Refinery (WO No.- 26807898 Dated: 06/02/21)

4. Cable Y1

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Noise Noise


Amplitude 88.58 mV 60.04 mV
Criticality Low Low
Conclusion No Critical PD is observed

5. Cable Y2

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Noise Noise


Amplitude 46.36 mV 77.95 mV
Criticality Low Low
Conclusion No Critical PD is observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 36 of 173


at
Test Report for On Line Partial Discharge Testing at IOCL Gujarat
Refinery (WO No.- 26807898 Dated: 06/02/21)

6. Cable Y3

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Noise Noise


Amplitude 46.36 mV 61.65 mV
Criticality Low Low
Conclusion No Critical PD is observed

7. Cable B1

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Noise Noise


Amplitude 88.58 mV 15.80 mV
Criticality Low Low
Conclusion No PD inception is observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 37 of 173


at
Test Report for On Line Partial Discharge Testing at IOCL Gujarat
Refinery (WO No.- 26807898 Dated: 06/02/21)

8. Cable B2

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Noise Noise


Amplitude 34.02 mV 21.37 mV
Criticality Low Low
Conclusion No PD inception is observed

9. Cable B3

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Noise Noise


Amplitude 35.43 mV 21.37 mV
Criticality Low Low
Conclusion No PD inception is observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 38 of 173


at
Test Report for On Line Partial Discharge Testing at IOCL Gujarat
Refinery (WO No.- 26807898 Dated: 06/02/21)

5.6 HT-101 SAT-2 Cables


The feeder has 3 cable runs.

TEST-1

The TeV test has been carried out for all the cables of the feeder. The result is as follows:

Cable R Y B
TeV (dBmV) 1 1 3

TEST-2

Test-2 has not been conducted through HFCT based device as the common earth sheath of all the
cables was not available.

TEST-3

Test-3 has been conducted through EMI based device, of all the cables. The result is as follows:

1. Cable R

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Noise Noise


Amplitude 46.87 mV 93.70 mV
Criticality Low Low
Conclusion No PD inception is observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 39 of 173


at
Test Report for On Line Partial Discharge Testing at IOCL Gujarat
Refinery (WO No.- 26807898 Dated: 06/02/21)

2. Cable Y

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Noise Noise


Amplitude 14.99 mV 54.57 mV
Criticality Low Low
Conclusion No PD inception is observed

3. Cable B

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Noise Noise


Amplitude 64.00 mV 17.39 mV
Criticality Low Low
Conclusion No PD inception is observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 40 of 173


at
Test Report for On Line Partial Discharge Testing at IOCL Gujarat
Refinery (WO No.- 26807898 Dated: 06/02/21)

5.7 HT-101 OG to 33kV Distribution Switch Board 103B


This feeder has 9 cables.

TEST-1

The TeV test has been carried out for all the cables of the feeder. The result is as follows:

Cable R1 R2 R3 Y1 Y2 Y3
TeV (dBmV) 0 1 1 4 3 7

Cable B1 B2 B3
TeV (dBmV) 3 2 5

TEST-2

Test-2 has not been conducted through HFCT based device as the common earth sheath of all the
cables was not available.

TEST-3

Test-3 has been conducted through EMI based device, of all the cables. The result is as follows:

1. Cable R1

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern External Interference External Interference


Amplitude 53.92 mV 75.12 mV
Criticality Low Low
Conclusion No PD inception is observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 41 of 173


at
Test Report for On Line Partial Discharge Testing at IOCL Gujarat
Refinery (WO No.- 26807898 Dated: 06/02/21)
2. Cable R2

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern External Interference External Interference


Amplitude 64.00 mV 68.03 mV
Criticality Low Low
Conclusion No PD inception is observed

3. Cable R3

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern External Interference External Interference


Amplitude 36.85 mV 61.98 mV
Criticality Low Low
Conclusion No PD inception is observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 42 of 173


at
Test Report for On Line Partial Discharge Testing at IOCL Gujarat
Refinery (WO No.- 26807898 Dated: 06/02/21)

4. Cable Y1

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern External Interference External Interference


Amplitude 36.79 mV 64.00 mV
Criticality Low Low
Conclusion No PD inception is observed

5. Cable Y2

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern External Interference External Interference


Amplitude 53.92 mV 36.85 mV
Criticality Low Low
Conclusion No PD inception is observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 43 of 173


at
Test Report for On Line Partial Discharge Testing at IOCL Gujarat
Refinery (WO No.- 26807898 Dated: 06/02/21)
6. Cable Y3

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 6th Phase
PRPD Pattern

Pattern External Interference External Interference


Amplitude 36.79 mV 64.00 mV
Criticality Low Low
Conclusion No PD inception is observed

7. Cable B1

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern External Interference External Interference


Amplitude 64.00 mV 53.92 mV
Criticality Low Low
Conclusion No PD inception is observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 44 of 173


at
Test Report for On Line Partial Discharge Testing at IOCL Gujarat
Refinery (WO No.- 26807898 Dated: 06/02/21)

8. Cable B2

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern External Interference External Interference


Amplitude 53.92 mV 44.85 mV
Criticality Low Low
Conclusion No PD inception is observed

9. Cable B3

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern External Interference External Interference


Amplitude 64.00 mV 36.79 mV
Criticality Low Low
Conclusion No PD inception is observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 45 of 173


at
Test Report for On Line Partial Discharge Testing at IOCL Gujarat
Refinery (WO No.- 26807898 Dated: 06/02/21)

5.8 HT-101 GT 6 I/C cables


This feeder has 12 cables.

TEST-1

The TeV test has been carried out for all the cables of the feeder. The result is as follows:

Cable R-1 R-2 R- 3 R- 4 Y-1 Y-2


TeV (dBmV) 1 5 0 2 3 1

Cable Y- 3 Y- 4 B-1 B-2 B- 3 B- 4


TeV (dBmV) 0 2 5 1 2 9

TEST-2

Test-2 has not been conducted through HFCT based device as the common earth sheath of all
the cables was not available.

TEST-3

Test-3 has been conducted through EMI based device, of all the cables. The result is as follows:

1. Cable R1

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Noise Noise


Amplitude 77.24 mV 40.35 mV
Criticality Low Low
Conclusion No PD inception is observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 46 of 173


at
Test Report for On Line Partial Discharge Testing at IOCL Gujarat
Refinery (WO No.- 26807898 Dated: 06/02/21)
2. Cable R2

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Noise Noise


Amplitude 74.80 mV 30.51 mV
Criticality Low Low
Conclusion No PD inception is observed

3. Cable R3

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Noise Noise


Amplitude 67.91 mV 36.85 mV
Criticality Low Low

Conclusion No PD inception is observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 47 of 173


at
Test Report for On Line Partial Discharge Testing at IOCL Gujarat
Refinery (WO No.- 26807898 Dated: 06/02/21)
4. Cable R4

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Noise Noise


Amplitude 65.91 mV 36.22 mV
Criticality Low Low
Conclusion No PD inception is observed

5. Cable Y1

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern External Interference Noise


Amplitude 77.95 mV 25.72 mV
Criticality Low Low
Conclusion No New PD inception is observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 48 of 173


at
Test Report for On Line Partial Discharge Testing at IOCL Gujarat
Refinery (WO No.- 26807898 Dated: 06/02/21)
6. Cable Y2

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Noise Noise


Amplitude 43.23 mV 46.36 mV
Criticality Low Low
Conclusion No PD inception is observed

7. Cable Y3

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Noise Noise


Amplitude 36.85 mV 90.94 mV
Criticality Low Low
Conclusion No PD inception is observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 49 of 173


at
Test Report for On Line Partial Discharge Testing at IOCL Gujarat
Refinery (WO No.- 26807898 Dated: 06/02/21)

8. Cable Y4

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Noise Noise


Amplitude 65.91 mV 75.79 mV
Criticality Low Low
Conclusion No PD inception is observed

9. Cable B1

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Noise Noise


Amplitude 67.91 mV 79.92 mV
Criticality Low Low
Conclusion No PD inception is observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 50 of 173


at
Test Report for On Line Partial Discharge Testing at IOCL Gujarat
Refinery (WO No.- 26807898 Dated: 06/02/21)

10. Cable B2

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Noise Noise


Amplitude 36.85 mV 73.03 mV
Criticality Low Low
Conclusion No PD inception is observed

11. Cable B3

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Noise Noise


Amplitude 55.98 mV 63.07 mV
Criticality Low Low
Conclusion No PD inception is observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 51 of 173


at
Test Report for On Line Partial Discharge Testing at IOCL Gujarat
Refinery (WO No.- 26807898 Dated: 06/02/21)
12. Cable B4

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Noise Noise


Amplitude 61.65 mV 73.70 mV
Criticality Low Low
Conclusion No PD inception is observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 52 of 173


at
Test Report for On Line Partial Discharge Testing at IOCL Gujarat
Refinery (WO No.- 26807898 Dated: 06/02/21)

5.9 HT-102 TIE FEEDER 2B


This feeder has 12 runs of cable.

TEST-1

The TeV test has been carried out for all the cables of the feeder. The result is as follows:

Cable R1 R2 R3 R4
TeV (dBmV) 1 1 1 1

Cable Y1 Y2 Y3 Y4
TeV (dBmV) 0 2 1 0

Cable B1 B2 B3 B4
TeV (dBmV) 1 1 1 0

TEST-2

Test-2 has not been conducted through HFCT based device as the common earth sheath of all the
cables was not available.

TEST-3

Test-3 has been conducted through EMI based device, of all the cables. The result is as follows:
1. Cable R1

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Corona Discharge Corona Discharge


Amplitude 52.17 mV 64.00 mV
Criticality Moderately Low Moderately Low
Conclusion Moderately Low critical PD inception is observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 53 of 173


at
Test Report for On Line Partial Discharge Testing at IOCL Gujarat
Refinery (WO No.- 26807898 Dated: 06/02/21)
2. Cable R2

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Possible Cross Talk from R3 External Noise


Amplitude 66.93 mV 175.0 mV
Criticality Moderately Low Low
Conclusion No PD inception is observed

3. Cable R3

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Minor Surface Discharge External Noise


Amplitude 100.4 mV 342.0 mV
Criticality Moderately Low Low
Conclusion No PD inception is observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 54 of 173


at
Test Report for On Line Partial Discharge Testing at IOCL Gujarat
Refinery (WO No.- 26807898 Dated: 06/02/21)

4. Cable R4

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Noise Noise


Amplitude 113.2 mV 125.0 mV
Criticality Low Low
Conclusion No PD inception is observed

5. Cable Y1

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Possible Minor Surface Discharge External Noise


Amplitude 66.14 mV 125.0 mV
Criticality Moderately Low Low
Conclusion No PD inception is observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 55 of 173


at
Test Report for On Line Partial Discharge Testing at IOCL Gujarat
Refinery (WO No.- 26807898 Dated: 06/02/21)

6. Cable Y2

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Possible Minor Surface Discharge External Noise


Amplitude 61.02 mV 245.0 mV
Criticality Moderately Low Low
Conclusion No PD inception is observed

7. Cable Y3

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Possible Minor Surface Discharge External Noise


Amplitude 49.21 mV 175.0 mV
Criticality Moderately Low Low
Conclusion No PD inception is observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 56 of 173


at
Test Report for On Line Partial Discharge Testing at IOCL Gujarat
Refinery (WO No.- 26807898 Dated: 06/02/21)

8. Cable Y4

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Possible Minor Surface Discharge Possible Minor Surface Discharge


Amplitude 98.43 mV 65.59 mV
Criticality Moderately Low Moderately Low
Conclusion Moderately Low critical PD inception is observed

5. Cable B1

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern External Noise External Noise


Amplitude 71.65 mV 64.00 mV
Criticality Low Low
Conclusion No PD inception is observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 57 of 173


at
Test Report for On Line Partial Discharge Testing at IOCL Gujarat
Refinery (WO No.- 26807898 Dated: 06/02/21)
6. Cable B2

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Possible Minor Surface Discharge External Noise


Amplitude 56.50 mV 175.0 mV
Criticality Moderately Low Low
Conclusion No PD inception is observed

7. Cable B3

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Possible Minor Surface Discharge External Noise


Amplitude 44.09 mV 175.0 mV
Criticality Moderately Low Low
Conclusion No Critical PD inception is observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 58 of 173


at
Test Report for On Line Partial Discharge Testing at IOCL Gujarat
Refinery (WO No.- 26807898 Dated: 06/02/21)

8. Cable B4

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Possible Minor Surface Discharge Minor Surface Discharge


Amplitude 55.12 mV 75.79 mV
Criticality Moderately Low Moderately Low
Conclusion Moderately Low Critical PD inception is observed

5.10 HT-102 SAT 1 Cables


The feeder has 3 cable runs.

TEST-1

The TeV test has been carried out for all the cables of the feeder. The result is as follows:

Cable R Y B
TeV (dBmV) 0 2 3

TEST-2

Test-2 has not been conducted through HFCT based device as the common earth sheath of all the
cables was not available.

TEST-3
Test-3 has been conducted through EMI based device, of all the cables. The result is as follows:-

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 59 of 173


at
Test Report for On Line Partial Discharge Testing at IOCL Gujarat
Refinery (WO No.- 26807898 Dated: 06/02/21)

1. Cable R

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Possible Surface Discharge Noise


Amplitude 139.2 mV 88.58 mV
Criticality Moderately Low Low
Conclusion No PD inception is observed

2. Cable Y

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Possible Surface Discharge Noise


Amplitude 119.9 mV 46.00 mV
Criticality Moderately Low Low
Conclusion No PD inception is observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 60 of 173


at
Test Report for On Line Partial Discharge Testing at IOCL Gujarat
Refinery (WO No.- 26807898 Dated: 06/02/21)

3. Cable B

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Possible Cross Talk Noise


Amplitude 89.57 mV 125.0 mV
Criticality Moderately Low Low
Conclusion No PD inception is observed

5.11 HT-102 OG to 33kV Distribution Switch Board 104A


This feeder has 9 cables.

TEST-1

The TeV test has been carried out for all the cables of the feeder. The result is as follows:

Cable R1 R2 R3 Y1 Y2 Y3
TeV (dBmV) 0 1 1 2 3 4

Cable B1 B2 B3
TeV (dBmV) 2 6 7

TEST-2

Test-2 has not been conducted through HFCT based device as the common earth sheath of all the
cables was not available.

TEST-3

Test-3 has been conducted through EMI based device, of all the cables. The result is as follows:

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 61 of 173


at

Test Report for On Line Partial Discharge Testing at IOCL Gujarat


Refinery (WO No.- 26807898 Dated: 06/02/21)

1. Cable R1

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Possible Surface Discharge Noise


Amplitude 202.6 mV 58.07 mV
Criticality Moderately Low Low
Conclusion No PD inception is observed

2. Cable R2

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Possible Surface Discharge Noise


Amplitude 177.5 mV 28.06 mV
Criticality Moderately Low Low
Conclusion No PD inception is observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 62 of 173


at

Test Report for On Line Partial Discharge Testing at IOCL Gujarat


Refinery (WO No.- 26807898 Dated: 06/02/21)

3. Cable R3

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern External Noise External Noise


Amplitude 173.6 mV 62.01 mV
Criticality Low Low
Conclusion No PD inception is observed

4. Cable Y1

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Possible Surface Discharge Noise


Amplitude 231.5 mV 125.0 mV
Criticality Moderately Low Low
Conclusion No PD inception is observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 63 of 173


at

Test Report for On Line Partial Discharge Testing at IOCL Gujarat


Refinery (WO No.- 26807898 Dated: 06/02/21)

5. Cable Y2

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Possible Surface Discharge Minor Corona Discharge


Amplitude 219.9 mV 92.52 mV
Criticality Moderately Low Moderately Low
Conclusion Moderately Low PD inception is observed

6. Cable Y3

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Possible Surface Discharge Possible Cross-talk from Y2 Cable


Amplitude 206.4 mV 116.1 mV
Criticality Moderately Low Moderately Low
Conclusion Moderately Low PD is observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 64 of 173


at

Test Report for On Line Partial Discharge Testing at IOCL Gujarat


Refinery (WO No.- 26807898 Dated: 06/02/21)

7. Cable B1

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Possible Surface Discharge Minor Surface Discharge


Amplitude 110.2 mV 90.00 mV
Criticality Moderate Low
Conclusion Moderately Low PD is observed

8. Cable B2

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Possible Surface Discharge Noise


Amplitude 135.0.0 mV 97.44 mV
Criticality Moderate Low
Conclusion No PD inception is observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 65 of 173


at

Test Report for On Line Partial Discharge Testing at IOCL Gujarat


Refinery (WO No.- 26807898 Dated: 06/02/21)

9. Cable B3

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Possible Surface Discharge Noise


Amplitude 198.7 mV 97.44 mV
Criticality Moderate Low
Conclusion No PD inception is observed

5.12 HT-102 SAT 3 Cables


The feeder has 3 cable runs.

TEST-1

The TeV test has been carried out for all the cables of the feeder. The result is as follows:

Cable R Y B
TeV (dBmV) 9 6 4

TEST-2

Test-2 has not been conducted through HFCT based device as the common earth sheath of all the
cables was not available.

TEST-3

Test-3 has been conducted through EMI based device, of all the cables. The result is as follows:

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 66 of 173


at

Test Report for On Line Partial Discharge Testing at IOCL Gujarat


Refinery (WO No.- 26807898 Dated: 06/02/21)

1. Cable R

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Corona Discharge Surface Discharge


Amplitude 11.24 mV 328.5 mV
Criticality Moderately Low Moderate
Conclusion Moderately Critical PD inception is observed

2. Cable Y

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Corona Discharge Possible Cross talk from R phase


Amplitude 172.3 101.4 mV
Criticality Moderately Low Moderately Low
Conclusion Moderately Low Critical PD inception is observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 67 of 173


at

Test Report for On Line Partial Discharge Testing at IOCL Gujarat


Refinery (WO No.- 26807898 Dated: 06/02/21)

3. Cable B

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Corona Discharge Noise


Amplitude 293.5 mV 251.3 mV
Criticality Moderately Low Low
Conclusion No Critical PD inception is observed

5.13 HT-102 GT 5 IC Cables


This feeder has 12 cables.

TEST-1

The TeV test has been carried out for all the cables of the feeder. The result is as follows:

Cable R1 R2 R3 R4 Y1 Y2
TeV (dBmV) 1 0 3 2 15 8

Cable Y3 Y4 B1 B2 B3 B4
TeV (dBmV) 7 11 15 12 11 12

TEST-2

Test-2 has not been conducted through HFCT based device as the common earth sheath of all the
12 cables was not available.

TEST-3

Test-3 has been conducted through EMI based device, of all the cables. The result is as follows:

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 68 of 173


at

Test Report for On Line Partial Discharge Testing at IOCL Gujarat


Refinery (WO No.- 26807898 Dated: 06/02/21)

1. Cable R1

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Corona Discharge External Noise


Amplitude 362.4 mV 342.0 mV
Criticality Moderately Low Low
Conclusion No Critical PD inception is observed

2. Cable R2

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Corona Discharge External Noise


Amplitude 399.1 mV 65.91 mV
Criticality Moderately Low Low
Conclusion No Critical PD inception is observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 69 of 173


at

Test Report for On Line Partial Discharge Testing at IOCL Gujarat


Refinery (WO No.- 26807898 Dated: 06/02/21)

3. Cable R3

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Corona Discharge External Noise


Amplitude 399.1 mV 111.2 mV
Criticality Moderately Low Low
Conclusion No Critical PD inception is observed

4. Cable R4

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Corona Discharge External Noise


Amplitude 441.2 mV 21.17 mV
Criticality Moderately Low Low
Conclusion No Critical PD inception is observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 70 of 173


at

Test Report for On Line Partial Discharge Testing at IOCL Gujarat


Refinery (WO No.- 26807898 Dated: 06/02/21)

5. Cable Y1

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern External Noise External Noise


Amplitude 245.0 mV 667.0 mV
Criticality Low Low
Conclusion No PD inception is observed

6. Cable Y2

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Noise External Noise


Amplitude 27.89 mV 588.2 mV
Criticality Low Low

Conclusion No PD inception is observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 71 of 173


at

Test Report for On Line Partial Discharge Testing at IOCL Gujarat


Refinery (WO No.- 26807898 Dated: 06/02/21)

7. Cable Y3

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern External Noise External Noise


Amplitude 90.67 mV 509.4 mV
Criticality Low Low
Conclusion No PD inception is observed

8. Cable Y4

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern External Noise Noise


Amplitude 140.8 mV 102.4 mV
Criticality Low Low
Conclusion No PD inception is observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 72 of 173


at

Test Report for On Line Partial Discharge Testing at IOCL Gujarat


Refinery (WO No.- 26807898 Dated: 06/02/21)

9. Cable B1

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern External Noise External Noise


Amplitude 175.0 mV 245.0 mV
Criticality Low Low
Conclusion No PD inception is observed

10. Cable B2

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern External Noise External Noise


Amplitude 175.0 mV 44.91 mV
Criticality Low Low
Conclusion No PD inception is observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 73 of 173


at

Test Report for On Line Partial Discharge Testing at IOCL Gujarat


Refinery (WO No.- 26807898 Dated: 06/02/21)

11. Cable B3

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Noise External Noise


Amplitude 30.92 mV 73.03 mV
Criticality Low Low
Conclusion No Critical PD inception is observed

12. Cable B4

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Corona Discharge Noise


Amplitude 67.52 mV 79.37 mV
Criticality Moderately Low Low
Conclusion No Critical PD inception is observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 74 of 173


at

Test Report for On Line Partial Discharge Testing at IOCL Gujarat


Refinery (WO No.- 26807898 Dated: 06/02/21)

5.14 GRE Feeder-1


The feeder has 2 cables.

TEST-1

The TeV test has been carried out for all the cables of the feeder. The result is as follows:

Cable Cable 1 Cable 2


TeV (dBmV) 2 0

TEST-2

Test-2 has not been conducted through HFCT based device as the common earth sheath of all the
cables was not available.

TEST-3

Test-3 has been conducted through EMI based device, of all the cables. The result is as follows:

1. Cable 1

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Noise Noise


Amplitude 41.10 mV 42.32 mV
Criticality Low Low
Conclusion No PD inception is observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 75 of 173


at

Test Report for On Line Partial Discharge Testing at IOCL Gujarat


Refinery (WO No.- 26807898 Dated: 06/02/21)

2. Cable 2

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Noise Noise


Amplitude 51.02 62.01 mV
Criticality Low Low
Conclusion No PD inception is observed

5.15 SS 37 BUS -A
The feeder has 5 cables.

TEST-1

The TeV test has been carried out for all the cables of the feeder. The result is as follows:

Cable Cable 1 Cable 2 Cable 3 Cable 4 Cable 5


TeV (dBmV) 1 0 2 0 1

TEST-2

Test-2 has not been conducted through HFCT based device as the common earth sheath of all the
cables was not available.

TEST-3

Test-3 has been conducted through EMI based device, of all the cables. The result is as follows:

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 76 of 173


at

Test Report for On Line Partial Discharge Testing at IOCL Gujarat


Refinery (WO No.- 26807898 Dated: 06/02/21)

1. Cable 1

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Noise Noise


Amplitude 42.52 60.04 mV
Criticality Low Low
Conclusion No PD inception is observed

2. Cable 2

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Noise Noise


Amplitude 51.02 17.00 mV
Criticality Low Low

Conclusion No PD inception is observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 77 of 173


at

Test Report for On Line Partial Discharge Testing at IOCL Gujarat


Refinery (WO No.- 26807898 Dated: 06/02/21)

3. Cable 3

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Noise Noise


Amplitude 7.838 61.48 mV
Criticality Low Low
Conclusion No PD inception is observed

4. Cable 4

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Noise Noise


Amplitude 34.02 mV 77.95 mV
Criticality Low Low
Conclusion No PD Inception is Observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 78 of 173


at

Test Report for On Line Partial Discharge Testing at IOCL Gujarat


Refinery (WO No.- 26807898 Dated: 06/02/21)

5. Cable 5

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result SS 37 End
6th Phase 7th Phase
PRPD Pattern

Pattern Noise Corona Discharge


Amplitude 35.43 20.03
Criticality Low Moderately Low
Conclusion Moderately Low PD Inception is Observed

5.16 SS-39 BUS A


TEST-1

The TeV test has been carried out for all the cables of the feeder. The result is as follows:

CGP-II End

Cable Cable 1 Cable 2


TeV (dBmV) 6 3

TEST-2

Test-2 has not been conducted through HFCT based device as the common earth sheath of all the
cables was not available.

TEST-3

Test-3 has been conducted through EMI based device, of all the cables. The result is as follows:

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 79 of 173


at

Test Report for On Line Partial Discharge Testing at IOCL Gujarat


Refinery (WO No.- 26807898 Dated: 06/02/21)

1. Cable 1

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result of CGP2 End
6th Phase 7th Phase
PRPD Pattern

Pattern Noise External Interference


Amplitude 35.43 90.00 mV
Criticality Low Low
Conclusion No PD Inception is Observed

2. Cable 2

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result of CGP2 End
6th Phase 7th Phase
PRPD Pattern

Pattern Noise Possible Surface Discharge


Amplitude 35.43 mV 133.7 mV
Criticality Low Moderately Low
Conclusion Moderately Low PD Inception Observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 80 of 173


at

Test Report for On Line Partial Discharge Testing at IOCL Gujarat


Refinery (WO No.- 26807898 Dated: 06/02/21)

5.17 GRE Feeder-3


TEST-1

The TeV test has been carried out for all the cables of the feeder. The result is as follows:

Cable Cable 1 Cable 2


TeV (dBmV) 2 1

TEST-2

Test-2 has not been conducted through HFCT based device as the common earth sheath of all the
cables was not available.

TEST-3

Test-3 has been conducted through EMI based device, of all the cables. The result is as follows:

1. Cable 1

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Noise Noise


Amplitude 43.23 mV 28.61 mV
Criticality Low Low
Conclusion No PD Inception is Observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 81 of 173


at

Test Report for On Line Partial Discharge Testing at IOCL Gujarat


Refinery (WO No.- 26807898 Dated: 06/02/21)

2. Cable 2

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Noise Noise


Amplitude 36.85 mV 21.37 mV
Criticality Low Low
Conclusion No PD Inception is Observed

5.18 DTR-5 Cables


The feeder has 3 cable runs.

TEST-1

The TeV test has been carried out for all the cables of the feeder. The result is as follows:-

Cable R Y B
TeV (dBmV) 4 2 4

TEST-2

Test-2 has not been conducted through HFCT based device as the common earth sheath of all the
cables was not available.

TEST-3

Test-3 has been conducted through EMI based device, of all the cables from both ends. The result is as
follows:

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 82 of 173


at

Test Report for On Line Partial Discharge Testing at IOCL Gujarat


Refinery (WO No.- 26807898 Dated: 06/02/21)

1. Cable R

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not
known
Advanced Test result
5th Phase 6th Phase
PRPD Pattern

Pattern PD activity not observed Noise


Amplitude 90.94 mV 105.0 mV
Criticality Re-test Recommended Low
Conclusion No PD inception is observed

2. Cable Y
Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not
known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Noise Noise


Amplitude 36.85 mV 233.4 mV
Criticality Low Low
Conclusion No PD inception is observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 83 of 173


at

Test Report for On Line Partial Discharge Testing at IOCL Gujarat


Refinery (WO No.- 26807898 Dated: 06/02/21)

3. Cable B

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): unknown
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Noise Noise


Amplitude 125.0 mV 309.7 mV
Criticality Low Low
Conclusion No PD inception is observed

5.19 SS-38 BUS A


The feeder has 5 cables.

TEST-1

The TeV test has been carried out for all the cables of the feeder. The result is as follows:

Cable Cable 1 Cable 2 Cable 3 Cable 4 Cable 5


TeV (dBmV) 3 2 1 3 4

TEST-2

Test-2 has not been conducted through HFCT based device as the common earth sheath of all the
cables was not available.

TEST-3

Test-3 has been conducted through EMI based device, of all the cables. The result is as follows:

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 84 of 173


at

Test Report for On Line Partial Discharge Testing at IOCL Gujarat


Refinery (WO No.- 26807898 Dated: 06/02/21)

1. Cable 1
Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 3
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern External Interference External Interference


Amplitude 53.92 mV 146.6 mV
Criticality Low Low
Conclusion No PD inception is observed

2. Cable 2

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 3
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern External Interference Noise


Amplitude 37.56 mV 368.1 mV
Criticality Low Low
Conclusion No PD inception is observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 85 of 173


at

Test Report for On Line Partial Discharge Testing at IOCL Gujarat


Refinery (WO No.- 26807898 Dated: 06/02/21)

3. Cable 3
Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 3
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern External Interference Noise


Amplitude 75.79 mV 82.20 mV
Criticality Low Low
Conclusion No PD inception is observed

4. Cable 4

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 3
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result : In S/S-38 End
6th Phase 7th Phase
PRPD Pattern

Pattern External Interference Corona Discharge


Amplitude 53.92 mV 50.90 mV
Criticality Low Moderately Low

Conclusion Moderately Low PD inception is observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 86 of 173


at

Test Report for On Line Partial Discharge Testing at IOCL Gujarat


Refinery (WO No.- 26807898 Dated: 06/02/21)

5. Cable 5

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 3
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result: SS-38 END
6th Phase 7th Phase
PRPD Pattern

Pattern Noise Corona Discharge


Amplitude 58.07 mV 10.57 mV
Criticality Low Moderately Low
Conclusion Moderately Low PD inception is observed

5.20 SS-39 Bus B


This feeder has 2 cable runs.

TEST-1

The TeV test has been carried out for all the cables of the feeder. The result is as follows:

Cable 1 2
TeV (dBmV) 2 3

TEST-2

Test-2 has not been conducted through HFCT based device as the common earth sheaths of the
three cables were not accessible.

TEST-3

Test-3 has been conducted through EMI based device in advanced mode, of all the cables. The
results obtained are as follows:

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 87 of 173


at

Test Report for On Line Partial Discharge Testing at IOCL Gujarat


Refinery (WO No.- 26807898 Dated: 06/02/21)

1. Cable 1

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 3
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result: SS-39 END
6th Phase 7th Phase
PRPD Pattern

Pattern Minor Surface Discharge Corona Discharge


Amplitude 11.65 mV 30.24 mV
Criticality Moderately Low Moderately Low
Conclusion Moderately Low Critical PD is observed

2. Cable 2
Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 3
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Minor Surface Discharge Minor Corona Discharge


Amplitude 7.094 mV 24.00 mV
Criticality Moderately Low Moderately Low
Conclusion Moderately Low Critical PD is observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 88 of 173


at

Test Report for On Line Partial Discharge Testing at IOCL Gujarat


Refinery (WO No.- 26807898 Dated: 06/02/21)

5.21 SS-38 Bus B


The feeder has 5 cables.

TEST-1

The TeV test has been carried out for all the cables of the feeder. The result is as follows:

Cable Cable 1 Cable 2 Cable 3 Cable 4 Cable 5


TeV (dBmV) 0 1 0 1 0

TEST-2

Test-2 has not been conducted through HFCT based device as the common earth sheath of all the
cables was not available.

TEST-3

Test-3 has been conducted through EMI based device, of all the cables. The result is as follows:

1. Cable 1

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 3
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Noise Noise


Amplitude 67.91 mV 65.91 mV
Criticality Low Low
Conclusion No PD inception is observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 89 of 173


at

Test Report for On Line Partial Discharge Testing at IOCL Gujarat


Refinery (WO No.- 26807898 Dated: 06/02/21)

2. Cable 2

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 3
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Noise Noise


Amplitude 62.01 mV 46.36 mV
Criticality Low Low

Conclusion No PD inception is observed

3. Cable 3

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 3
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Noise Noise


Amplitude 125.0 mV 34.02 mV
Criticality Low Low

Conclusion No PD inception is observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 90 of 173


at

Test Report for On Line Partial Discharge Testing at IOCL Gujarat


Refinery (WO No.- 26807898 Dated: 06/02/21)

4. Cable 4

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 3
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result: SS-38 End
6th Phase 7th Phase
PRPD Pattern

Pattern Noise Corona Discharge


Amplitude 67.91 mV 40.31 mV
Criticality Low Moderately Low

Conclusion Moderately Low PD inception is observed

5. Cable 5

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 3
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Noise Noise


Amplitude 34.02 mV 67.91 mV
Criticality Low Low
Conclusion No PD inception is observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 91 of 173


at

Test Report for On Line Partial Discharge Testing at IOCL Gujarat


Refinery (WO No.- 26807898 Dated: 06/02/21)

5.22 SS37 BUS B


The feeder has 4 cables.

TEST-1

The TeV test has been carried out for all the cables of the feeder. The result is as follows:

Cable Cable 1 Cable 2 Cable 3 Cable 4


TeV (dBmV) 0 2 4 3

TEST-2

Test-2 has not been conducted through HFCT based device as the common earth sheath of all the
cables was not available.

TEST-3

Test-3 has been conducted through EMI based device, of all the cables. The result is as follows:

1. Cable1

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 3
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result: SS-37 End
6th Phase 7th Phase
PRPD Pattern

Pattern External Interference Corona Discharge


Amplitude 75.79 mV 26.76 mV
Criticality Low Moderately Low

Conclusion Moderately Low PD inception is observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 92 of 173


at

Test Report for On Line Partial Discharge Testing at IOCL Gujarat


Refinery (WO No.- 26807898 Dated: 06/02/21)

2. Cable2

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 3
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result: SS-37 End
6th Phase 7th Phase
PRPD Pattern

Pattern External Interference Corona Discharge


Amplitude 37.56 mV 23.39 mV
Criticality Low Moderately Low

Conclusion Moderately Low PD inception is observed

3. Cable 3

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 3
Voltage level 33 kV
Failure History (If any): Not
known
Advanced Test result: SS-37 End
6th Phase 7th Phase
PRPD Pattern

Pattern External Interference Corona Discharge


Amplitude 60.63 mV 48.38
Criticality Low Moderately Low
Conclusion Moderately Low PD inception is observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 93 of 173


at

Test Report for On Line Partial Discharge Testing at IOCL Gujarat


Refinery (WO No.- 26807898 Dated: 06/02/21)

4. Cable 4

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 3
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result: SS-37 End
6th Phase 7th Phase
PRPD Pattern

Pattern External Interference Noise


Amplitude 74.43 mV 67.91 mV
Criticality Low Low

Conclusion No PD inception is observed

5.23 GRE Feeder-2


This feeder has 2 cable runs.

TEST-1

The TeV test has been carried out for all the cables of the feeder. The result is as follows:

Cable 1 2
TeV (dBmV) 2 0

TEST-2

Test-2 has not been conducted through HFCT based device as the common earth sheaths of the
three cables were not accessible.

TEST-3

Test-3 has been conducted through EMI based device in advanced mode, of all the cables. The
results obtained are as follows:

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 94 of 173


at

Test Report for On Line Partial Discharge Testing at IOCL Gujarat


Refinery (WO No.- 26807898 Dated: 06/02/21)

1. Cable 1

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 3
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern External Interference External Interference


Amplitude 88.58 mV 85.63 mV
Criticality Low Low
Conclusion No PD inception is observed

2. Cable 2

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 3
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern External Interference External Interference


Amplitude 65.94 mV 55.43 mV
Criticality Low Low
Conclusion No PD inception is observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 95 of 173


at

Test Report for On Line Partial Discharge Testing at IOCL Gujarat


Refinery (WO No.- 26807898 Dated: 06/02/21)

5.24 DTR-6 Cables


The feeder has 3 cable runs.

TEST-1

The TeV test has been carried out for all the cables of the feeder. The result is as follows:

Cable R Y B
TeV (dBmV) 1 1 0

TEST-2

Test-2 has not been conducted through HFCT based device as the common earth sheath of all the
cables was not available.

TEST-3

Test-3 has been conducted through EMI based device, of all the cables from both ends. The result is as
follows:

1. Cable R

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Possible Surface Discharge External Interference


Amplitude 2.163 V 111.2 mV
Criticality Moderately Low Low
Conclusion Moderately High PD is observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 96 of 173


at

Test Report for On Line Partial Discharge Testing at IOCL Gujarat


Refinery (WO No.- 26807898 Dated: 06/02/21)

2. Cable Y

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
5th Phase 6th Phase
PRPD Pattern

Pattern Possible Surface Discharge Noise


Amplitude 2.323 V 119.1 mV
Criticality Moderately Low Low
Conclusion No PD is observed

3. Cable B

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Possible Surface Discharge Noise


Amplitude 269.3 64.00 mV
Criticality Moderate Low
Conclusion Moderate PD is observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 97 of 173


at

Test Report for On Line Partial Discharge Testing at IOCL Gujarat


Refinery (WO No.- 26807898 Dated: 06/02/21)

5.25 OG TO BS-VI FDR1


The feeder has 3 cable runs.

TEST-1

The TeV test has been carried out for all the cables of the feeder. The result is as follows:

Cable 1 2 3
TeV (dBmV) 0 2 4..

TEST-2

Test-2 has not been conducted through HFCT based device as the common earth sheath of all the
cables was not available.

TEST-3

Test-3 has been conducted through EMI based device, of all the cables. The result is as follows:

1. Cable 1

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Noise Noise


Amplitude 63.07 mV 32.48 mV
Criticality Low Low
Conclusion No PD inception is observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 98 of 173


at

Test Report for On Line Partial Discharge Testing at IOCL Gujarat


Refinery (WO No.- 26807898 Dated: 06/02/21)

2. Cable 2

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Noise Noise


Amplitude 102.4 mV 19.23 mV
Criticality Low Low
Conclusion No PD inception is observed

3. Cable 3

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Noise Noise


Amplitude 75.79 mV 21.17 mV
Criticality Low Low
Conclusion No PD inception is observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 99 of 173


at

Test Report for On Line Partial Discharge Testing at IOCL Gujarat


Refinery (WO No.- 26807898 Dated: 06/02/21)

5.26 OG TO BS-VI FDR2


The feeder has 3 cable runs.

TEST-1

The TeV test has been carried out for all the cables of the feeder. The result is as follows:

Cable 1 2 3
TeV (dBmV) 0 0 0

TEST-2

Test-2 has not been conducted through HFCT based device as the common earth sheath of all the
cables was not available.

TEST-3

Test-3 has been conducted through EMI based device, of all the cables. The result is as follows:

1. Cable 1

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 3
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
th th
6 phase 7 Phase
PRPD Pattern

Pattern External Interface Corona Discharge


Amplitude 196.8 30.40 mV
Criticality Low Moderately Low
Conclusion Moderately Low PD inception is observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 100 of 173


at

Test Report for On Line Partial Discharge Testing at IOCL Gujarat


Refinery (WO No.- 26807898 Dated: 06/02/21)

2. Cable 2

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 3
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Corona Discharge Corona Discharge


Amplitude 21.57 mV 22.35 mV
Criticality Moderately Low Moderately Low
Conclusion Moderately Low Critical PD inception is observed

3. Cable 3

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 3
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Corona Discharge Noise


Amplitude 24.00 mV 23.91 mV
Criticality Moderately Low Noise
Conclusion No Critical PD inception is observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 101 of 173


at

Test Report for On Line Partial Discharge Testing at IOCL Gujarat


Refinery (WO No.- 26807898 Dated: 06/02/21)

5.27 InterConnection-1 P5 & P16


The feeder has 5 cables.

TEST-1

The TeV test has been carried out for all the cables of the feeder. The result is as follows:

Cable Cable 1 Cable 2 Cable 3 Cable 4 Cable 5


TeV (dBmV) 0 1 3 3 0

TEST-2

Test-2 has not been conducted through HFCT based device as the common earth sheath of all the
cables was not available.

TEST-3

Test-3 has been conducted through EMI based device, of all the cables. The result is as follows:

1. Cable1

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 3
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Noise Noise


Amplitude 102.4 mV 30.92 mV
Criticality Low Low
Conclusion No PD inception is observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 102 of 173


at

Test Report for On Line Partial Discharge Testing at IOCL Gujarat


Refinery (WO No.- 26807898 Dated: 06/02/21)

2. Cable 2

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 3
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Noise Noise


Amplitude 15.87 mV 30.92 mV
Criticality Low Low
Conclusion No PD inception is observed

3. Cable 3

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 3
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Noise Noise


Amplitude 79.92 mV 41.10 mV
Criticality Low Low
Conclusion No PD inception is observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 103 of 173


at

Test Report for On Line Partial Discharge Testing at IOCL Gujarat


Refinery (WO No.- 26807898 Dated: 06/02/21)

4. Cable 4

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 3
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Noise Noise


Amplitude 73.03 mV 147.4 mV
Criticality Low Low
Conclusion No PD inception is observed

5. Cable 5

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 3
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Noise Noise


Amplitude 7.228 mV 42.52 mV
Criticality Low Low
Conclusion No PD inception is observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 104 of 173


at

Test Report for On Line Partial Discharge Testing at IOCL Gujarat


Refinery (WO No.- 26807898 Dated: 06/02/21)

5.28 InterConnection-2 P12 & P20


The feeder has 5 cables.

TEST-1

The TeV test has been carried out for all the cables of the feeder. The result is as follows:

Cable Cable 1 Cable 2 Cable 3 Cable 4 Cable 5


TeV (dBmV) 0 4 2 1 0

TEST-2

Test-2 has not been conducted through HFCT based device as the common earth sheath of all the
cables was not available.

TEST-3

Test-3 has been conducted through EMI based device, of all the cables. The result is as follows:

1. Cable 1

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 3
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Noise Noise


Amplitude 79.37 mV 36.85 mV
Criticality Low Low
Conclusion No PD inception is observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 105 of 173


at

Test Report for On Line Partial Discharge Testing at IOCL Gujarat


Refinery (WO No.- 26807898 Dated: 06/02/21)

2. Cable 2

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 3
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Noise Noise


Amplitude 15.13 mV 37.56 mV
Criticality Low Low
Conclusion No PD inception is observed

3. Cable 3

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 3
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Noise Noise


Amplitude 40.39 mV 58.07 mV
Criticality Low Low
Conclusion No PD inception is observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 106 of 173


at

Test Report for On Line Partial Discharge Testing at IOCL Gujarat


Refinery (WO No.- 26807898 Dated: 06/02/21)

4. Cable 4

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 3
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Noise Noise


Amplitude 38.98 mV 67.91
Criticality Low Low
Conclusion No PD inception is observed

5. Cable 5

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 3
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Noise Noise


Amplitude 60.24 mV 62.01 mV
Criticality Low Low
Conclusion No PD inception is observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 107 of 173


at

Test Report for On Line Partial Discharge Testing at IOCL Gujarat


Refinery (WO No.- 26807898 Dated: 06/02/21)

5.29 OG to CGP-1 ICT-1 R-Phase


TEST-1

The TeV test has been carried out for all the cables of the feeder. The result is as follows:

Cable 1 2
TeV (dBmV) 2 0

TEST-2

Test-2 has not been conducted through HFCT based device as the common earth sheaths of the
cables were not accessible.

TEST-3

Test-3 has been conducted through EMI based device in advanced mode, of all the cables. The
results obtained are asfollows:

1. Cable 1

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result: SWGR END
6th Phase 7th Phase
PRPD Pattern

Pattern External Interference Corona Discharge


Amplitude 53.92 mV 28.58 mV
Criticality Low Moderately Low
Conclusion Moderately Low PD inception is observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 108 of 173


at

Test Report for On Line Partial Discharge Testing at IOCL Gujarat


Refinery (WO No.- 26807898 Dated: 06/02/21)

2. Cable 2

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result: SWGR END
6th Phase 7th Phase
PRPD Pattern

Pattern Corona Discharge Corona Discharge


Amplitude 31.70 mV 33.00 mV
Criticality Moderately Low Moderately Low
Conclusion Moderately Low PD inception is observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 109 of 173


at

Test Report for On Line Partial Discharge Testing at IOCL Gujarat


Refinery (WO No.- 26807898 Dated: 06/02/21)

5.30 OG to CGP-1 ICT-1 Y-Phase


This feeder has 2 cable runs.

TEST-1

The TeV test has been carried out for all the cables of the feeder. The result is as follows:

Cable 1 2
TeV (dBmV) 2 3

TEST-2

Test-2 has not been conducted through HFCT based device as the common earth sheaths of the
cables were not accessible.

TEST-3

Test-3 has been conducted through EMI based device in advanced mode, of all the cables. The
results obtained are asfollows:

1. Cable 1

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result:
6th Phase 7th Phase
PRPD Pattern

Pattern Noise Noise


Amplitude 46.06 mV 40.31 mV
Criticality Low Low
Conclusion No PD inception is observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 110 of 173


at

Test Report for On Line Partial Discharge Testing at IOCL Gujarat


Refinery (WO No.- 26807898 Dated: 06/02/21)

2. Cable 2

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Noise Noise


Amplitude 63.07 mV 29.88 mV
Criticality Low Low
Conclusion No Significant PD is observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 111 of 173


at

Test Report for On Line Partial Discharge Testing at IOCL Gujarat


Refinery (WO No.- 26807898 Dated: 06/02/21)

5.31 OG to CGP-1 ICT-1 B-Phase


This feeder has 2 cable runs.

TEST-1

The TeV test has been carried out for all the cables of the feeder. The result is as follows:

Cable 1 2
TeV (dBmV) 2 3

TEST-2

Test-2 has not been conducted through HFCT based device as the common earth sheaths of the
cables were not accessible.

TEST-3

Test-3 has been conducted through EMI based device in advanced mode, of all the cables. The
results obtained are as follows:

1. Cable 1

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result:
6th Phase 7th Phase
PRPD Pattern

Patten Noise Noise


Amplitude 46.06 mV 49.89 mV
Criticality Low Low
Conclusion No PD inception is observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 112 of 173


at

Test Report for On Line Partial Discharge Testing at IOCL Gujarat


Refinery (WO No.- 26807898 Dated: 06/02/21)

2. Cable 2

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Noise Noise


Amplitude 63.07 mV 64.00 mV
Criticality Low Low
Conclusion No Significant PD is observed

5.32 OG to CGP-1 ICT-2 R-Phase


This feeder has 2 cable runs.

TEST-1

The TeV test has been carried out for all the cables of the feeder. The result is as follows:

Cable 1 2
TeV (dBmV) 2 4

TEST-2

Test-2 has not been conducted through HFCT based device as the common earth sheaths of the
cables were not accessible.

TEST-3

Test-3 has been conducted through EMI based device in advanced mode, of all the cables. The
results obtained are as follows:

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 113 of 173


at

Test Report for On Line Partial Discharge Testing at IOCL Gujarat


Refinery (WO No.- 26807898 Dated: 06/02/21)

1. Cable 1

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Noise Noise


Amplitude 34.72 mV 21.57
Criticality Low Low
Conclusion No PD inception is Observed

2. Cable 2

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Noise Noise


Amplitude 46.06 mV 24.00 mV
Criticality Low Low
Conclusion No PD inception is Observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 114 of 173


at

Test Report for On Line Partial Discharge Testing at IOCL Gujarat


Refinery (WO No.- 26807898 Dated: 06/02/21)

5.33 OG to CGP-1 ICT-2 Y-Phase


This feeder has 2 cable runs.

TEST-1

The TeV test has been carried out for all the cables of the feeder. The result is as follows:

Cable 1 2
TeV (dBmV) 0 0

TEST-2

Test-2 has not been conducted through HFCT based device as the common earth sheaths of the
cables were not accessible.

TEST-3

Test-3 has been conducted through EMI based device in advanced mode, of all the cables. The
results obtained are asfollows:

1. Cable 1

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Noise Noise


Amplitude 43.34 mV 24.00 mV
Criticality Low Low
Conclusion No PD inception is Observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 115 of 173


at

Test Report for On Line Partial Discharge Testing at IOCL Gujarat


Refinery (WO No.- 26807898 Dated: 06/02/21)

2. Cable 2

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Noise Noise


Amplitude 39.01 mV 33.00 mV
Criticality Low Low
Conclusion No PD inception is Observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 116 of 173


at

Test Report for On Line Partial Discharge Testing at IOCL Gujarat


Refinery (WO No.- 26807898 Dated: 06/02/21)

5.34 OG to CGP-1 ICT-2 B Phase


This feeder has 2 cable runs.

TEST-1

The TeV test has been carried out for all the cables of the feeder. The result is as follows:

Cable 1 2
TeV (dBmV) 1 3

TEST-2

Test-2 has not been conducted through HFCT based device as the common earth sheaths of the
cables were not accessible.

TEST-3

Test-3 has been conducted through EMI based device in advanced mode, of all the cables. The
results obtained are asfollows:

1. Cable 1

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Noise Minor Internal Discharge


Amplitude 30.51 mV 103.3 mV
Criticality Low Moderately Low
Conclusion Moderately Low PD inception is Observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 117 of 173


at

Test Report for On Line Partial Discharge Testing at IOCL Gujarat


Refinery (WO No.- 26807898 Dated: 06/02/21)

2. Cable 2

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Noise Noise


Amplitude 38.39 mV 28.06 mV
Criticality Low Low
Conclusion No PD inception is Observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 118 of 173


at

Test Report for On Line Partial Discharge Testing at IOCL Gujarat


Refinery (WO No.- 26807898 Dated: 06/02/21)

5.35 I/C FROM TR-1


This feeder has 2 cable runs.

TEST-1

The TeV test has been carried out for all the cables of the feeder. The result is as follows:

Cable 1 2 3 4 5
TeV (dBmV) 0 4 2 1 0

TEST-2

Test-2 has not been conducted through HFCT based device as the common earth sheaths of the
cables were not accessible.

TEST-3

Test-3 has been conducted through EMI based device in advanced mode, of all the cables. The
results obtained are as follows:

1. Cable 1

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Noise Noise


Amplitude 15.93 mV 60.24 mV
Criticality Low Low
Conclusion No PD inception is Observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 119 of 173


at

Test Report for On Line Partial Discharge Testing at IOCL Gujarat


Refinery (WO No.- 26807898 Dated: 06/02/21)

2. Cable 2

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Noise Noise


Amplitude 17.76 mV 46.06 mV
Criticality
Conclusion No PD inception is Observed

3. Cable 3

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Noise Noise


Amplitude 15.07 mV 50.31 mv
Criticality Low Low
Conclusion No PD inception is Observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 120 of 173


at

Test Report for On Line Partial Discharge Testing at IOCL Gujarat


Refinery (WO No.- 26807898 Dated: 06/02/21)

4. Cable 4

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Noise Noise


Amplitude 14.93 mV 34.72 mV
Criticality Low Low
Conclusion No PD inception is Observed

5. Cable 5

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Noise Noise


Amplitude 14.93 mV 39.81 mV
Criticality Low Low
Conclusion No PD inception is Observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 121 of 173


at

Test Report for On Line Partial Discharge Testing at IOCL Gujarat


Refinery (WO No.- 26807898 Dated: 06/02/21)

5.36 GRE OG TO 33/6.6KV TR-1


This feeder has 2 cable runs.

TEST-1

The TeV test has been carried out for all the cables of the feeder. The result is as follows:

Cable 1 2
TeV (dBmV) 10 12

TEST-2

Test-2 has not been conducted through HFCT based device as the common earth sheaths of the
cables were not accessible.

TEST-3

Test-3 has been conducted through EMI based device in advanced mode, of all the cables. The
results obtained are as follows:

1. Cable 1

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 3
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Noise Noise


Amplitude 36.42 mV 15.80 mV
Criticality Low Low
Conclusion No PD inception is Observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 122 of 173


at

Test Report for On Line Partial Discharge Testing at IOCL Gujarat


Refinery (WO No.- 26807898 Dated: 06/02/21)

2. Cable 2

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 3
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Noise Noise


Amplitude 33.46 mV 35.86 mV
Criticality Low Low
Conclusion No PD inception is Observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 123 of 173


at

Test Report for On Line Partial Discharge Testing at IOCL Gujarat


Refinery (WO No.- 26807898 Dated: 06/02/21)

5.37 GRE OG TO 33/6.6KV TR-2


This feeder has 2 cable runs

TEST-1

The TeV test has been carried out for all the cables of the feeder. The result is as follows:

Cable 1 2
TeV (dBmV) 13 12

TEST-2

Test-2 has not been conducted through HFCT based device as the common earth sheaths of the
cables were not accessible.

TEST-3

Test-3 has been conducted through EMI based device in advanced mode, of all the cables. The
results obtained are as follows:

1. Cable 1

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 3
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Noise Noise


Amplitude 38.39 mV 10.98 mV
Criticality Low Low
Conclusion No PD inception is Observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 124 of 173


at

Test Report for On Line Partial Discharge Testing at IOCL Gujarat


Refinery (WO No.- 26807898 Dated: 06/02/21)

2. Cable 2

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 3
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Noise Noise


Amplitude 38.39 mV 293.5 mV
Criticality Low Low
Conclusion No PD inception is Observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 125 of 173


at

Test Report for On Line Partial Discharge Testing at IOCL Gujarat


Refinery (WO No.- 26807898 Dated: 06/02/21)

5.38 GRE OG TO 33/6.6KV TR-3


This feeder has 2 cable runs.

TEST-1

The TeV test has been carried out for all the cables of the feeder. The result is as follows:

Cable 1 2
TeV (dBmV) 10 12

TEST-2

Test-2 has not been conducted through HFCT based device as the common earth sheaths of the
three cables were not accessible.

TEST-3

Test-3 has been conducted through EMI based device in advanced mode, of all the cables. The
results obtained are asfollows:

1. Cable 1

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Noise Noise


Amplitude 42.26 mV 27.69 mV
Criticality Low Low
Conclusion No PD inception is Observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 126 of 173


at

Test Report for On Line Partial Discharge Testing at IOCL Gujarat


Refinery (WO No.- 26807898 Dated: 06/02/21)

2. Cable 2

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Noise Noise


Amplitude 31.50 mV 27.86 mV
Criticality Low Low
Conclusion No PD inception is Observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 127 of 173


at

Test Report for On Line Partial Discharge Testing at IOCL Gujarat


Refinery (WO No.- 26807898 Dated: 06/02/21)

5.39 SS 37 TR-11A Cables


This feeder has 6 cables

TEST-1

The TeV test has been carried out for all the cables of the feeder. The result is as follows:

Cable R1 R2 Y1 Y2 B1 B2
TeV (dBmV) 2 1 4 6 0 1

TEST-2

Test-2 has not been conducted through HFCT based device as the common earth sheath of all the
cables was not available.

TEST-3

Test-3 has been conducted through EMI based device, of all the cables. The result is as follows:

1. Cable R1

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Corona Discharge Noise


Amplitude 24.17 mV 33.00 mV
Criticality Moderately Low Low
Conclusion No Critical PD is observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 128 of 173


at

Test Report for On Line Partial Discharge Testing at IOCL Gujarat


Refinery (WO No.- 26807898 Dated: 06/02/21)

2. Cable R2

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Noise Noise


Amplitude 24.19 mV 46.00 mV
Criticality Low Low
Conclusion No Critical PD is observed

3. Cable Y1

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Possible Minor Corona Noise


Amplitude 33.00 mV 46.00 mV
Criticality Low Low
Conclusion Low PD inception is Observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 129 of 173


at

Test Report for On Line Partial Discharge Testing at IOCL Gujarat


Refinery (WO No.- 26807898 Dated: 06/02/21)

4. Cable Y2

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Possible Minor Corona Noise


Amplitude 33.00 mV 38.76
Criticality Low Noise
Conclusion No PD is Observed

5. Cable B1

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Corona Discharge Corona Discharge


Amplitude 35.78 mV 26.80 mV
Criticality Moderately Low Moderately Low
Conclusion Moderately Low Critical PD is observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 130 of 173


at

Test Report for On Line Partial Discharge Testing at IOCL Gujarat


Refinery (WO No.- 26807898 Dated: 06/02/21)

6. Cable B2

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Corona Discharge Noise


Amplitude 33.76 mV 26.24 mV
Criticality Moderately Low Low
Conclusion No Critical PD is observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 131 of 173


at

Test Report for On Line Partial Discharge Testing at IOCL Gujarat


Refinery (WO No.- 26807898 Dated: 06/02/21)

5.40 C37 TR-11C Cables


This feeder has 6 cables.

TEST-1

The TeV test has been carried out for all the cables of the feeder. The result is as follows:

Cable R1 R2 Y1 Y2 B1 B2
TeV (dBmV) 5 1 0 0 0 0

TEST-2

Test-2 has not been conducted through HFCT based device as the common earth sheath of all the
cables was not available.

TEST-3

Test-3 has been conducted through EMI based device, of all the cables. The result is as follows:

1. Cable R1

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Corona Discharge Corona Discharge


Amplitude 28.84 mV 38.89 mV
Criticality Moderately Low Moderately Low
Conclusion Moderately Low Critical PD is observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 132 of 173


at

Test Report for On Line Partial Discharge Testing at IOCL Gujarat


Refinery (WO No.- 26807898 Dated: 06/02/21)

2. Cable R2

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Corona Discharge Corona Discharge


Amplitude 25.98 mV 29.10 mV
Criticality Moderately Low Moderately Low
Conclusion Moderately Low Critical PD is observed

3. Cable Y1

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Noise Corona Discharge


Amplitude 29.73 mV 24.69
Criticality Low Moderately Low
Conclusion Moderately Low Critical PD is observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 133 of 173


at

Test Report for On Line Partial Discharge Testing at IOCL Gujarat


Refinery (WO No.- 26807898 Dated: 06/02/21)

4. Cable Y2

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Noise Noise


Amplitude 17.15 mV 38.75
Criticality Low Noise
Conclusion No PD inception is Observed

5. Cable B1

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Noise Noise


Amplitude 25.70 mV 29.06 mV
Criticality Low Low
Conclusion No PD inception is Observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 134 of 173


at

Test Report for On Line Partial Discharge Testing at IOCL Gujarat


Refinery (WO No.- 26807898 Dated: 06/02/21)

6. Cable B2

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Noise Noise


Amplitude 27.72 mV 32.60 mV
Criticality Low Low
Conclusion No PD inception is Observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 135 of 173


at

Test Report for On Line Partial Discharge Testing at IOCL Gujarat


Refinery (WO No.- 26807898 Dated: 06/02/21)

5.41 C37 TR-11D Cables


This feeder has 6 cables.

TEST-1

The TeV test has been carried out for all the cables of the feeder. The result is as follows:

Cable R1 R2 Y1 Y2 B1 B2
TeV (dBmV) 0 1 2 1 4 0

TEST-2

Test-2 has not been conducted through HFCT based device as the common earth sheath of all the
cables was not available.

TEST-3

Test-3 has been conducted through EMI based device, of all the cables. The result is as follows:

1. Cable R1

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Noise Noise


Amplitude 48.38 mV 111.6 mV
Criticality Low Low
Conclusion No PD inception is Observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 136 of 173


at

Test Report for On Line Partial Discharge Testing at IOCL Gujarat


Refinery (WO No.- 26807898 Dated: 06/02/21)

2. Cable R2

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Noise Noise


Amplitude 27.72 mV 19.46 mV
Criticality Low Low
Conclusion No PD inception is Observed

3. Cable Y1

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Noise Noise


Amplitude 27.21 mV 76.54 mV
Criticality Low Low
Conclusion No PD inception is Observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 137 of 173


at

Test Report for On Line Partial Discharge Testing at IOCL Gujarat


Refinery (WO No.- 26807898 Dated: 06/02/21)

4. Cable Y2

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Corona Discharge Noise


Amplitude 24.00 mV 24.00 mV
Criticality Moderately Low Low
Conclusion No Critical PD is observed

5. Cable B1

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Corona Discharge Possible Corona Discharge


Amplitude 24.00 mV 17.15 mV
Criticality Moderately Low Moderately Low
Conclusion Moderately Low PD inception is Observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 138 of 173


at

Test Report for On Line Partial Discharge Testing at IOCL Gujarat


Refinery (WO No.- 26807898 Dated: 06/02/21)

6. Cable B2

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Noise Noise


Amplitude 23.69 mV 20.65 mV
Criticality Low Low
Conclusion No PD inception is Observed

5.42 C37 TR-11B Cables


This feeder has 6 cables.

TEST-1

The TeV test has been carried out for all the cables of the feeder. The result is as follows:

Cable R1 R2 Y1 Y2 B1 B2
TeV (dBmV) 0 0 2 2 4 1

TEST-2

Test-2 has not been conducted through HFCT based device as the common earth sheath of all the
cables was not available.

TEST-3

Test-3 has been conducted through EMI based device, of all the cables. The result is as follows:

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 139 of 173


at

Test Report for On Line Partial Discharge Testing at IOCL Gujarat


Refinery (WO No.- 26807898 Dated: 06/02/21)

1. Cable R1

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Noise Corona Discharge


Amplitude 29.73 mV 54.93 mV
Criticality Low Moderately Low
Conclusion Moderately Low PD inception is Observed

2. CableR2

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Noise Noise


Amplitude 25.20 mV 21.17 mV
Criticality Low Low
Conclusion No PD inception is Observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 140 of 173


at

Test Report for On Line Partial Discharge Testing at IOCL Gujarat


Refinery (WO No.- 26807898 Dated: 06/02/21)

3. Cable Y1

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Noise Noise


Amplitude 26.71 mV 20.66 mV
Criticality Low Low
Conclusion No PD inception is Observed

4. Cable Y2

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Noise Noise


Amplitude 29.23 mV 21.37 mV
Criticality Low Low
Conclusion No PD inception is Observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 141 of 173


at

Test Report for On Line Partial Discharge Testing at IOCL Gujarat


Refinery (WO No.- 26807898 Dated: 06/02/21)

5. Cable B1

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Noise Noise


Amplitude 26.71 mV 20.66 mV
Criticality Low Low
Conclusion No PD inception is Observed

6. Cable B2

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Noise Noise


Amplitude 90.00 mV 17.00 mV
Criticality Low Low
Conclusion No PD inception is Observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 142 of 173


at

Test Report for On Line Partial Discharge Testing at IOCL Gujarat


Refinery (WO No.- 26807898 Dated: 06/02/21)

5.43 SS39 OG TO DUMAD-1 FDR Cables


The feeder has 2 cable runs

TEST-1

The TeV test has been carried out for all the cables of the feeder. The result is as follows:

Cable 1 2
TeV (dBmV) 4 3

TEST-2

Test-2 has not been conducted through HFCT based device as the common earth sheath of all the
cables was not available.

TEST-3

Test-3 has been conducted through EMI based device, of all the cables. The result is as follows:

1. Cable 1

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 3
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Corona Discharge Noise


Amplitude 21.92 mV 46.06
Criticality Moderately Low Low
Conclusion No PD is observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 143 of 173


at

Test Report for On Line Partial Discharge Testing at IOCL Gujarat


Refinery (WO No.- 26807898 Dated: 06/02/21)

2. Cable 2

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 3
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Noise Noise


Amplitude 14.93 mV 50.31 mV
Criticality Low Low
Conclusion No PD inception is Observed

5.44 SS39 to DUMAD-2 FDR Cables


The feeder has 2 cable runs.

TEST-1

The TeV test has been carried out for all the cables of the feeder. The result is as follows:

Cable 1 2
TeV (dBmV) 0 0

TEST-2

Test-2 has not been conducted through HFCT based device as the common earth sheath of all the
cables was not available.

TEST-3

Test-3 has been conducted through EMI based device, of all the cables. The result is as follows:

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 144 of 173


at

Test Report for On Line Partial Discharge Testing at IOCL Gujarat


Refinery (WO No.- 26807898 Dated: 06/02/21)

1. Cable 1

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 3
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result Sub Station End
6th Phase 7th Phase
PRPD Pattern

Pattern Corona Discharge Corona Discharge


Amplitude 33.00 mV 19.09
Criticality Moderately Low Moderately Low
Conclusion Moderately Low Critical PD is observed

2. Cable 2

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 3
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Noise Noise


Amplitude 90.00 mV 34.72 mV
Criticality Low Low
Conclusion No PD is observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 145 of 173


at

Test Report for On Line Partial Discharge Testing at IOCL Gujarat


Refinery (WO No.- 26807898 Dated: 06/02/21)

5.45 SS39 Reactor-1 I/C Cables


The feeder has 2 cable runs.

TEST-1

The TeV test has been carried out for all the cables of the feeder. The result is as follows:

Cable 1 2
TeV (dBmV) 17 12

TEST-2

Test-2 has not been conducted through HFCT based device as the common earth sheath of all the
cables was not available.

TEST-3

Test-3 has been conducted through EMI based device, of all the cables. The result is as follows:

1. Cable 1

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 3
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result: Reactor End
7th Phase
PRPD Pattern

Pattern Internal Surface Discharge


Amplitude 189.1 mV
Criticality Moderately high
Conclusion Moderately Critical PD is observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 146 of 173


at

Test Report for On Line Partial Discharge Testing at IOCL Gujarat


Refinery (WO No.- 26807898 Dated: 06/02/21)

2. Cable 2

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 3
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result: Reactor End
7th Phase
PRPD Pattern

Pattern Internal Surface Discharge


Amplitude 11.38 mV
Criticality Moderately Low
Conclusion Moderately Critical PD is observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 147 of 173


at

Test Report for On Line Partial Discharge Testing at IOCL Gujarat


Refinery (WO No.- 26807898 Dated: 06/02/21)

5.46 SS39 Reactor-1 0/G Cables


The feeder has 2 cable runs.

TEST-1

The TeV test has been carried out for all the cables of the feeder. The result is as follows:

Cable 1 2
TeV (dBmV) 4 6

TEST-2

Test-2 has not been conducted through HFCT based device as the common earth sheath of all the
cables was not available.

TEST-3

Test-3 has been conducted through EMI based device, of all the cables. The result is as follows:

2. Cable 1

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 3
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result: Reactor End
7th Phase
PRPD Pattern

Pattern Internal Surface Discharge


Amplitude 46.36 mV
Criticality Moderate
Conclusion Moderately Critical PD is observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 148 of 173


at

Test Report for On Line Partial Discharge Testing at IOCL Gujarat


Refinery (WO No.- 26807898 Dated: 06/02/21)

4. Cable 2

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 3
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result: Reactor End
7th Phase
PRPD Pattern

Pattern Internal Surface Discharge


Amplitude 48.39 mV
Criticality Moderate
Conclusion Moderately Critical PD is observed

5.47 SS39 TR-1 Cables


This feeder has six runs of cable.

TEST-1

The TeV test has been carried out for all the cables of the feeder. The result is as follows:

Cable R1 R2 Y1 Y2
TeV (dBmV) 2 3 1 0

Cable B1 B2
TeV (dBmV) 2 1

TEST-2

Test-2 has not been conducted through HFCT based device as the common earth sheath of all the
six cables was not available.

TEST-3
Test-3 has been conducted through EMI based device, of all the cables. The result is as follows.

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 149 of 173


at

Test Report for On Line Partial Discharge Testing at IOCL Gujarat


Refinery (WO No.- 26807898 Dated: 06/02/21)

1. Cable R1

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Noise Noise


Amplitude 76.54 mV 43.34
Criticality Low Low
Conclusion No PD inception is Observed

2. Cable R2

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Corona Discharge Noise


Amplitude 16.33 mV 30.51 mV
Criticality Moderately Low Low
Conclusion No Critical PD is observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 150 of 173


at

Test Report for On Line Partial Discharge Testing at IOCL Gujarat


Refinery (WO No.- 26807898 Dated: 06/02/21)

3. Cable Y1

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Noise Noise


Amplitude 56.69 mV 125.0 mV
Criticality Low Low
Conclusion No PD inception is Observed

4. Cable Y2

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Noise Noise


Amplitude 63.07 mV 90.00 mV
Criticality Low Low
Conclusion No PD inception is Observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 151 of 173


at

Test Report for On Line Partial Discharge Testing at IOCL Gujarat


Refinery (WO No.- 26807898 Dated: 06/02/21)

5. Cable B1

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Noise Noise


Amplitude 68.03 mV 31.50
Criticality Low low
Conclusion No PD inception is Observed

6. Cable B2

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Noise Noise


Amplitude 19.20 mV 20.27 mV
Criticality Low Low
Conclusion No PD inception is Observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 152 of 173


at

Test Report for On Line Partial Discharge Testing at IOCL Gujarat


Refinery (WO No.- 26807898 Dated: 06/02/21)

5.48 SS39 TR-2 Cables


This feeder has six runs of cable.

TEST-1

The TeV test has been carried out for all the cables of the feeder. The result is as follows:

Cable R1 R2 Y1 Y2
TeV (dBmV) 2 4 1 0

Cable B1 B2
TeV (dBmV) 1 2

TEST-2

Test-2 has not been conducted through HFCT based device as the common earth sheath of all the
six cables was not available.

TEST-3

Test-3 has been conducted through EMI based device, of all the cables. The result is as follows

1. Cable R1

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Noise Noise


Amplitude 21.37 mV 17.67 mV
Criticality Low Low
Conclusion No PD inception is Observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 153 of 173


at

Test Report for On Line Partial Discharge Testing at IOCL Gujarat


Refinery (WO No.- 26807898 Dated: 06/02/21)

2. Cable R2

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Corona Discharge Noise


Amplitude 15.93 mV 29.73 mV
Criticality Moderately Low Low
Conclusion Moderately Low PD inception is Observed

3. Cable Y1

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Corona Discharge Corona Discharge


Amplitude 15.87 mV 24.00 mV
Criticality Moderately Low Moderately Low
Conclusion Moderately Low PD inception is Observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 154 of 173


at

Test Report for On Line Partial Discharge Testing at IOCL Gujarat


Refinery (WO No.- 26807898 Dated: 06/02/21)

4. Cable Y2

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Corona Discharge Noise


Amplitude 19.84 mV 20.27
Criticality Moderately Low Low
Conclusion No PD inception is Observed

5. Cable B1

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Corona Discharge Noise


Amplitude 24.00 mV 29.24 mV
Criticality Moderately Low Low
Conclusion No Critical PD is observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 155 of 173


at

Test Report for On Line Partial Discharge Testing at IOCL Gujarat


Refinery (WO No.- 26807898 Dated: 06/02/21)

6. Cable B2

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 1
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Corona Discharge Noise


Amplitude 21.17 mV 22.09 mV
Criticality Moderately Low Low
Conclusion Moderately Low Critical PD is observed

5.49 38 TRP-01-01 Cables


TEST-1

The TeV test has been carried out for all the cables of the feeder. The result is as follows:

Cable 1 2
TeV (dBmV) 2 4

TEST-2

Test-2 has not been conducted through HFCT based device as the common earth sheaths of the two
cables were not accessible.

TEST-3

Test-3 has been conducted through EMI based device in advanced mode, of all the cables. The
results obtained are as follows:

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 156 of 173


at

Test Report for On Line Partial Discharge Testing at IOCL Gujarat


Refinery (WO No.- 26807898 Dated: 06/02/21)

1. Cable 1

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 3
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Corona Discharge Noise


Amplitude 27.54 mV 63.07 mV
Criticality Moderately Low Noise
Conclusion No PD is observed

2. Cable 2

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 3
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Noise Noise


Amplitude 19.20 mV 15.93 mV
Criticality Low Low
Conclusion No PD inception is Observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 157 of 173


at

Test Report for On Line Partial Discharge Testing at IOCL Gujarat


Refinery (WO No.- 26807898 Dated: 06/02/21)

5.50 38 TRP-01-02 Cables


TEST-1

The TeV test has been carried out for all the cables of the feeder. The result is as follows:

Cable 1 2
TeV (dBmV) 4 3

TEST-2

Test-2 has not been conducted through HFCT based device as the common earth sheaths of the two
cables were not accessible.

TEST-3

Test-3 has been conducted through EMI based device in advanced mode, of all the cables. The
results obtained are as follows:

1. Cable 1

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 3
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase
PRPD Pattern

Pattern External Noise Corona Discharge


Amplitude 86.46 mV 17.00 mV
Criticality Low Moderately Low
Conclusion Moderately Low Critical PD is observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 158 of 173


at

Test Report for On Line Partial Discharge Testing at IOCL Gujarat


Refinery (WO No.- 26807898 Dated: 06/02/21)

2. Cable 2

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 3
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern External Noise Noise


Amplitude 52.44 mV 17.76 mV
Criticality Low Low
Conclusion No PD is observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 159 of 173


at

Test Report for On Line Partial Discharge Testing at IOCL Gujarat


Refinery (WO No.- 26807898 Dated: 06/02/21)

5.51 38 TRP-01-03 Cables


TEST-1

The TeV test has been carried out for all the cables of the feeder. The result is as follows:

Cable 1 2
TeV (dBmV) 4 3

TEST-2

Test-2 has not been conducted through HFCT based device as the common earth sheaths of the
three cables were not accessible.

TEST-3

Test-3 has been conducted through EMI based device in advanced mode, of all the cables. The
results obtained are as follows:

1. Cable 1

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 3
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Corona Discharge Noise


Amplitude 33.00 mV 102.4 mV
Criticality Moderately Low Low
Conclusion No Critical PD is observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 160 of 173


at

Test Report for On Line Partial Discharge Testing at IOCL Gujarat


Refinery (WO No.- 26807898 Dated: 06/02/21)

2. Cable 2

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 3
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern External Noise External Noise


Amplitude 24.19 mV 7.228 mV
Criticality Low Low
Conclusion No PD inception is Observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 161 of 173


at

Test Report for On Line Partial Discharge Testing at IOCL Gujarat


Refinery (WO No.- 26807898 Dated: 06/02/21)

5.52 38 TRP-01-04 Cables


TEST-1

The TeV test has been carried out for all the cables of the feeder. The result is as follows:

Cable 1 2
TeV (dBmV) 4 3

TEST-2

Test-2 has not been conducted through HFCT based device as the common earth sheaths of the
cables were not accessible.

TEST-3

Test-3 has been conducted through EMI based device in advanced mode, of all the cables. The
results obtained are as follows:

1. Cable 1

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 3
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern External Interference Noise


Amplitude 866.0 mV 23.91 mV
Criticality Low Low
Conclusion No PD inception is Observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 162 of 173


at

Test Report for On Line Partial Discharge Testing at IOCL Gujarat


Refinery (WO No.- 26807898 Dated: 06/02/21)

2. Cable 2

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 3
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern External Interference Corona Discharge


Amplitude 873.3 mV 25.46 mV
Criticality Low Moderately Low
Conclusion Moderately Low PD is Observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 163 of 173


at

Test Report for On Line Partial Discharge Testing at IOCL Gujarat


Refinery (WO No.- 26807898 Dated: 06/02/21)

5.53 38 TRP-01-05 Cables


TEST-1

The TeV test has been carried out for all the cables of the feeder. The result is as follows:

Cable 1
TeV (dBmV) 8

TEST-2

Test-2 has not been conducted through HFCT based device as the common earth sheaths of the
three cables were not accessible.

TEST-3

Test-3 has been conducted through EMI based device in advanced mode, of all the cables. The
results obtained are asfollows:

1. Cable 1

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 3
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Noise Noise


Amplitude 19.65 mV 14.93 mV
Criticality Low Low
Conclusion No PD inception is Observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 164 of 173


at

Test Report for On Line Partial Discharge Testing at IOCL Gujarat


Refinery (WO No.- 26807898 Dated: 06/02/21)

5.54 38 TRP-01-06 Cable


TEST-1

The TeV test has been carried out for the cable of the feeder. The result is as follows:

Cable 1
TeV (dBmV) 0

TEST-2

Test-2 has not been conducted through HFCT based device as the common earth sheaths of the
three cables were not accessible.

TEST-3

Test-3 has been conducted through EMI based device in advanced mode, of all the cables. The
results obtained are asfollows:

1. Cable

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 3
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Noise Noise


Amplitude 17.00 mV 14.93 mV
Criticality Low Low
Conclusion No PD inception is Observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 165 of 173


at

Test Report for On Line Partial Discharge Testing at IOCL Gujarat


Refinery (WO No.- 26807898 Dated: 06/02/21)

5.55 SS61TR-61021
TEST-1

The TeV test has been carried out for the cable of the feeder. The result is as follows:

Cable 1 2
TeV (dBmV) 6 9

TEST-2

Test-2 has not been conducted through HFCT based device as the common earth sheaths of the
three cables were not accessible.

TEST-3

Test-3 has been conducted through EMI based device in advanced mode, of all the cables. The
results obtained are as follows:

1. Cable 1

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 3
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern External Interference Noise


Amplitude 19.65 mV 50.37 mV
Criticality Low Low
Conclusion No PD inception is Observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 166 of 173


at

Test Report for On Line Partial Discharge Testing at IOCL Gujarat


Refinery (WO No.- 26807898 Dated: 06/02/21)

2. Cable 2

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 3
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern External Interference Noise


Amplitude 22.82 mV 420.7 mV
Criticality Low Low
Conclusion No PD inception is Observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 167 of 173


at

Test Report for On Line Partial Discharge Testing at IOCL Gujarat


Refinery (WO No.- 26807898 Dated: 06/02/21)

5.56 SS61 TR-61022


TEST-1

The TeV test has been carried out for the cable of the feeder. The result is as follows:

Cable 1 2
TeV (dBmV) 6 8

TEST-2

Test-2 has not been conducted through HFCT based device as the common earth sheaths of the
three cables were not accessible.

TEST-3

Test-3 has been conducted through EMI based device in advanced mode, of all the cables. The
results obtained are as follows:

1. Cable 1

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 3
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern External Interference Noise


Amplitude 27.89 mV 675.1 mV
Criticality Low Low
Conclusion No PD inception is Observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 168 of 173


at

Test Report for On Line Partial Discharge Testing at IOCL Gujarat


Refinery (WO No.- 26807898 Dated: 06/02/21)

2. Cable 2

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 3
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern External Interference Noise


Amplitude 24.99 mV 704.5 mV
Criticality Low Low
Conclusion No PD inception is Observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 169 of 173


at

Test Report for On Line Partial Discharge Testing at IOCL Gujarat


Refinery (WO No.- 26807898 Dated: 06/02/21)

5.57 SS61 TR-61023


TEST-1

The TeV test has been carried out for the cable of the feeder. The result is as follows:

Cable 1 2
TeV (dBmV) 3 7

TEST-2

Test-2 has not been conducted through HFCT based device as the common earth sheaths of the
three cables were not accessible.

TEST-3

Test-3 has been conducted through EMI based device in advanced mode, of all the cables. The
results obtained are as follows:

1. Cable 1

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 3
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Noise Noise


Amplitude 39.40 mV 587.1 mV
Criticality Low Low
Conclusion No PD inception is Observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 170 of 173


at

Test Report for On Line Partial Discharge Testing at IOCL Gujarat


Refinery (WO No.- 26807898 Dated: 06/02/21)

2. Cable 2

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 3
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Noise Noise


Amplitude 39.48 mV 102.4 mV
Criticality Low Low
Conclusion No PD inception is Observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 171 of 173


at

Test Report for On Line Partial Discharge Testing at IOCL Gujarat


Refinery (WO No.- 26807898 Dated: 06/02/21)

5.58 SS61 TR-61024


TEST-1

The TeV test has been carried out for the cable of the feeder. The result is as follows:

Cable 1 2
TeV (dBmV) 6 8

TEST-2

Test-2 has not been conducted through HFCT based device as the common earth sheaths of the
three cables were not accessible.

TEST-3

Test-3 has been conducted through EMI based device in advanced mode, of all the cables. The
results obtained are asfollows:

1. Cable 1

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 3
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Noise Noise


Amplitude 24.99 mV 675.1 mV
Criticality Low Low
Conclusion No PD inception is Observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 172 of 173


at

Test Report for On Line Partial Discharge Testing at IOCL Gujarat


Refinery (WO No.- 26807898 Dated: 06/02/21)

2. Cable 2

Cable details
Type XLPE
Length Not Known
No of joints Not Known
No of cores 3
Voltage level 33 kV
Failure History (If any): Not known
Advanced Test result
6th Phase 7th Phase
PRPD Pattern

Pattern Noise Noise


Amplitude 29.34 mV 704.5 mV
Criticality Low Low
Conclusion No PD inception is Observed

RPT_IOCL_GR_CB_CM_TST_V005 NCEPL, Confidential Page 173 of 173