Peppers Cable Glands Limited
Stanhope Road, Camberley, Surrey, GU15 3BT United Kingdom
Telephone: +44 (0) 1276 64232
Facsimile: +44 (0) 1276 691752
Email: sales@peppers.co.uk
Cable Gland:- Type BW
BW type glands provide an integral armour clamp for armoured cable. The integral armour clamp provides an electrical
bond between the cable armour and the gland. BW type glands maintain IP30.
Design Standard BS 6121:1989
B
GLAND MARKING Example:
BS6121 Part 1 BW [size] [thread] PCGL (or
PEPPERS) A D C
INGRESS IP30
PROTECTION
MATERIALS Brass CZ121
VARIATIONS All variants of the BW type gland feature a separate armour clamping ring to allow for inspection of the clamped
armour:-
Brass (BWL)
Integral Earth version for HV applications:
Brass (BWLIE)
OPERATING
-100OC to +600OC
TEMPERATURES
options THREADS ISO Metric only
CLAMPS SWA Clamping using gland body (BW)
SWA steel wire armour - clamping ring (BWL)
SWB woven steel wire armour or STA steel tape armour - clamping ring (BXL/BZL)
plating Zinc (ZP); Nickel (NP); Tin (TP); Electroless Nickel (EN)
accessories Locknut - Brass (ACBLN); Steel (ACMLN)
Earth Tag - Brass (ACBET)
Shroud - PVC (ACSPVC)
Gland and accessory kits:
K1- includes gland, steel locknut, earthtag and PVC shroud
example part Sample: BW K1/ZP/20S/M20
number BW:
BW - Gland type, armour type (SWA) and body material (Brass)
K1 - Supplied complete with accessories (PVC Shroud)
ZP - Zinc plating
20s - Gland size with regards to cable acceptance range
M20 - Entry thread
2008 Catalogue Page 5.1.0 © Peppers Cable Glands Limited 2008
Gland Entry Entry Max Max Gland Seal Range Armour Acceptance
Size Threads Thread Across Protrusion Range Shroud
Cable Inner Cable Outer
Length Corners Length Size
Sheath [C] Sheath [D]
Metric [B] [A] Min Max Min Max
W XZ
Clamp Ring
Version Only
20s M20 10 24.2 20.0 - 11.7 - 16.0 0.90-1.25 0.15-0.35 S22
20 M20 10 29.7 20.0 - 14.0 - 21.0 0.90-1.25 0.15-0.50 S27
25 M25 10 45.1 22.0 - 20.0 - 27.4 1.25-1.60 0.15-0.50 S36
32 M32 10 50.6 25.0 - 26.3 - 34.0 1.60-2.00 0.15-0.55 S41
40 M40 15 60.5 30.0 - 32.2 - 40.6 1.60-2.00 0.20-0.60 L55
50 M50 15 71.5 32.0 - 44.1 - 53.2 2.00-2.50 0.20-0.60 L65
63 M63 15 88.0 42.0 - 56.0 - 65.8 2.50 0.30-0.80 L80
75 M75 15 99.0 50.0 - 68.0 - 78.0 2.50 0.30-1.00 L90
80 M80 20 115.2 50.0 - 72.0 - 84.0 3.15 0.45-1.00 S104
85 M85 20 115.2 50.0 - 78.0 - 90.0 3.15 0.45-1.00 S104
90 M90 20 125.7 50.0 - 84.0 - 96.0 3.15 0.45-1.00 S114
100 M100 20 125.7 50.0 - 90.0 - 102.0 -3.15 0.45-1.00 S114
All Dimensions are in Millimetres
NOTES:
● Gland Size does not necessarily equate to the entry thread size
● "W" refers to the wire diameter in a steel wire armoured cable
● Unless otherwise stated ISO Metric entry threads have a 1.5mm pitch
● Shroud sizes above are for type BW only
● Full assembly instructions are available upon request, the instructions should be read prior to installation and adhered to in full
http://www.cableglands.com
© Peppers Cable Glands Limited 2008 Page 5.1.0 2008 Catalogue