SRK 18 Ylvs 1
SRK 18 Ylvs 1
'16•SRK-T-192
RESIDENTIAL AIR-CONDITIONING
TECHNICAL MANUAL & PARTS LIST
'16 • SRK-T-192
CONTENTS
1. SPECIFICATIONS ........................................................................................ 3
2. EXTERIOR DIMENSIONS ............................................................................ 4
(1) Indoor unit ............................................................................................ 4
(2) Outdoor unit ......................................................................................... 5
(3) Wireless remote control ........................................................................ 6
3. ELECTRICAL WIRING ................................................................................... 7
(1) Indoor unit .............................................................................................. 7
(2) Outdoor unit ........................................................................................... 8
4. PIPING SYSTEM ........................................................................................... 9
5. RANGE OF USAGE & LIMITATIONS .......................................................... 10
6. APPLICATION DATA .................................................................................. 12
7. OUTLINE OF OPERATION CONTROL BY MICROCOMPUTER ............... 21
(1) Operation control function by remote control ....................................... 21
(2) Unit ON/OFF button ........................................................................... 22
(3) Auto restart function ......................................................................... 22
(4) Custom cord switching procedure ....................................................... 22
(5) Flap and louver control ...................................................................... 23
(6) 3D auto operation .............................................................................. 24
5JNFSPQFSBUJPO .................................................................................. 25
(8) Installation location setting .................................................................. 25
0VUMJOFPGDPPMJOHPQFSBUJPO ............................................................... 26
0VUMJOFPGEFIVNJEJGZJOH %3: PQFSBUJPO ........................................... 26
(11) Outline of automatic operation ........................................................... 27
(12) Protective control function ................................................................... 28
8. MAINTENANCE DATA .................................................................................. 30
(1) Cautions ............................................................................................. 30
(2) Items to check before troubleshooting ................................................. 30
5SPVCMFTIPPUJOHQSPDFEVSF *GUIFBJSDPOEJUJPOFSEPFTOPUSVOBUBMM ........ 30
5SPVCMFTIPPUJOHQSPDFEVSF *GUIFBJSDPOEJUJPOFSSVOT ..................... 31
4FMGEJBHOPTJTUBCMF ............................................................................. 32
4FSWJDFNPEF 5SPVCMFNPEFBDDFTTGVODUJPO ................................... 33
(7) Inspection procedures corresponding to detail of trouble .................... 41
- 1-
- -
'16 • SRK-T-192
Series code
Inverter type
Product capacity
Model name SRK : Wall mounted type
SRC : Outdoor unit
- 2-
- -
Model SRK18YLV-S1
Item Indoor unit SRK18YLV-S1 Outdoor unit SRC18YLV-S1
Cooling capacity (1) W 5000 (1600 (Min.)~5500 (Max.))
Power source 1 Phase, 220-240V, 50Hz
Power
Cooling kW 1.56 (0.40~2.20)
consumption
Running
Cooling 7.5
Operation current A
data Inrush current 7.5
COP Cooling 3.21
Noise Sound level dB(A) Hi : 49 Me : 37 Lo : 28 55
Cooling
level Power level dB 63 67
Exterior dimensions (Height x Width x Depth) mm 268 x 790 x 213 595 x 780 (+62) x 290
Exterior appearance Fine snow Stucco white
(Munsell color) (8.0Y 9.3/0.1) near equivalent (4.2Y 7.5/1.1) near equivalent
Net weight kg 9.5 35
Compressor type & Q'ty — 5RS132XAB21 (Rotary type) x 1
Motor (Starting method) kW — 1.50 (Line starting)
Refrigerant oil 0.37 (FV50S)
Refrigerant
Refrigerant (4) kg R410A 1.30 (Pre-charged up to the piping length of 15m)
equipment
Heat exchanger Slit fins & inner grooved tubing M fins & inner grooved tubing
Refrigerant control Capillary tubes + Electronic expansion valve
Deice control Microcomputer control
Fan type & Q'ty Tangential fan x 1 Propeller fan x 1
Motor W 38 24
Air handling
Air flow Cooling m3 / min Hi : 12.0 Me : 7.6 Lo : 4.7 38
equipment
Fresh air intake Not possible —
Air filter, Quality / Quantity Polypropylene net (washable) x 2 —
Shock & vibration absorber — Cushion rubber (for compressor)
Operation switch Wireless remote control —
Operation Room temperature control Microcomputer thermostat —
control RUN : Green, TIMER : Yellow, HI POWER : Green,
Operation Display
3D AUTO : Green
Compressor overheat protection, Overcurrent protection,
Safety devices Frost protection, Serial signal error protection, Fan motor error protection,
Cooling overload protection, Lock rotor protection
Refrigerant piping size (O.D) mm Liquid line :φ6.35 (1/4") Gas line :φ12.7 (1/2")
Connecting method Flare connecting
Liquid line : 0.4
Attached length of piping m —
Installation Gas line : 0.33
data Insulation for piping Necessary (Both sides), independent
Refrigerant line (one way) length Max. 25
Vertical height difference between m Max. 15 (Outdoor unit is higher)
outdoor unit and indoor unit Max. 15 (Outdoor unit is lower)
Drain hose Connectable (VP 16) —
Recommended breaker size A 16
Size x Core number 1.5mm2 x 4 cores (Including earth cable)
Connection wiring
Connecting method Terminal block (Screw fixing type)
Accessories (included) Mounting kit
Option parts —
Note (1) The data are measured at the following conditions. The pipe length is 7.5m.
- -
45
45
C Hole on wall for right rear piping 㸦ȭ65㸧
D Hole on wall for left rear piping 㸦ȭ65㸧
(1) Indoor unit
268
60
2. EXTERIOR DIMENSIONS
9
Outlet for down piping Terminal block 45
㸦Refer to the above view㸧
F
-
Installation plate
-
㸦Service space㸧 50 138 450 202 100 㸦Service space㸧
206.5 450 133.5
102.5 585 102.5 Wireless remote control
Unit
150
39.3
43.2
7.5
65 㸦Service space㸧
60 17.3
200
252.2 Note㸦1㸧The model name label is attached
44.5
ࠉࠉࠉon the underside of the panel.
15㸦Service space㸧
44.5
8.3
Space for installation and service when viewing from the front
'16 • SRK-T-192
Notes
(1)It must not be surrounded by walls on the four sides.
390.6 50.6 (2)The unit must be fixed with anchor bolts. An anchor bolt must not
protrude more than 15mm.
E 12
(3)Where the unit is subject to strong winds, lay it in such
a direction that the blower outlet faces perpendicularly
(2) Outdoor unit
24.3
D to the dominant wind direction.
63.4
(4)Leave 1m or more space above the unit.
(5)A wall in front of the blower outlet must not exceed the units height.
(6)The model name label is attached on the lower right corner of the front panel.
Model SRC18YLV-S1
69.4
(Service
space )
14.8
Intake
390.6
111.6 510 158.4 17.9 Outlet L1
780 61.9
-
-
Minimum installation space
Terminal block Examples of
installation
Dimensions
L1 Open 280 280 180
L2 100 75 Open Open
L3 100 80 80 80
138.4 33.5
L4 250 Open 250 Open
C
595
B Symbol Content
40°
42.5
40°
97.7
A
E Anchor bolt hole M10×4places
15.8
Unit:mm
'16 • SRK-T-192
'16 • SRK-T-192
Unit: mm
150
60 17.3
- -
3. ELECTRICAL WIRING
(1) Indoor unit
Model SRK18YLV-S1
LOUVER LOUVER
MOTOR MOTOR FLAP FAN
(R) (L) MOTOR MOTOR
HEAT
M M M M EXCHANGER
5 5 5 CONTROL
BOX
YELLOW
BLACK
WHITE
BLUE
RED
CNY CNX CNM 1 3 4 5 6
CNU
N WHITE
VARISTOR
U
L BLACK
FUSE
250V 3.15A
RED
J
PRINTED CIRCUIT
BOARD YELLOW/GREEN
G
YELLOW/GREEN
WHITE
BLACK
1 2/N 3
8 2 2 2
TERMINAL
BLOCK
t゜
t゜
DISPLAY
HUMIDITY
ROOM TEMP.
HEAT EXCH.
WIRELESS
SENSOR
TO OUTDOOR UNIT
R-AMP
SENSOR
SENSOR
BACK UP SW
- -
(YE)
(OR)
TERMINAL
(2) Outdoor unit
T1
T2
TB POWER TRANSISTOR
FUSE R IN F8
(BK) (BK) F2
L 1 RO P U (RD)
250V 20A (BK) R U
250V 20A
Model SRC18YLV-S1
F3 250V 1A
F1
M
250V 2A
-
CNTH CNEEV
-
2 2 2
t゜ t゜ t゜
M
LEGEND Color
CM COMPRESSOR MOTOR BK BLACK
EEV ELECTRIC EXPANSION VALVE(COIL) RD RED
FMo FAN MOTOR WH WHITE
R REACTOR OR ORANGE
TH1 HEAT EXCHANGER SENSOR BR BROWN
(OUTDOOR UNIT) YE YELLOW
TH2 OUTDOOR AIR TEMP. SENSOR Y/G YELLOW/GREEN
TH3 DISCHARGE PIPE TEMP. SENSOR
'16 • SRK-T-192
'16 • SRK-T-192
4. PIPING SYSTEM
Model SRK18YLV-S1
Cooling cycle
Humidity
sensor
Heat
(HD) exchanger
Heat
exchanger
Compressor
Heat
exchanger
sensor
(TH1)
Capillary tube
Electronic
expansion valve
Liquid Service valve
pipe (EEV)
(Liquid)
(φ6.35) Capillary tube
Flare connection
- -
1.3
1.3
1.2
relation to temperature
1.2
Cooling
relation to temperature
Coefficient of cooling
Coefficient of cooling
Cooling
1.1
1.1
1.0
1.0
capacity in
capacity in
0.9
0.9
0.8
0.8
0.7
0.7
0.6
46 Applicable range
°Ctemperature
(°C D. B.)
40
Cooling operation
air D.B.
35
temperature
43
30
Cooling
40
D.B.
25 26
35
Outdoor
20 24
30
25
0
21
-5 Depends on installed situation
-10 16 18 20 22 24
-15 Indoor air W.B. temperature °C W.B. ISO-T1 Standard Condition
14 16 18 20 22
Indoor air W.B. temperature °C W.B. ISO-T1 Standard Condition
- 10 -
(2) Correction of cooling capacity in relation to one way length of refrigerant piping
5000 = 4875
SRK18YLV-S1
- 11 -
6. APPLICATION DATA
Safety precautions
• When install the unit, be sure to check whether the selection of installation place, power source specifications, usage limitation (piping
length, height differences between indoor and outdoor units, power source voltage and etc.) and installation spaces.
• We recommend you to read this “SAFETY PRECAUTIONS” carefully before the installation work in order to gain full advantage of the functions
of the unit and to avoid malfunction due to mishandling.
• The precautions described below are divided into WARNING and CAUTION . The matters with possibilities leading to serious conse-
quences such as death or serious personal injury due to erroneous handling are listed in the WARNING and the matters with possibilities
leading to personal injury or damage of the unit due to erroneous handling including probability leading to serious consequences in some cases are
listed in CAUTION . These are very important precautions for safety. Be sure to observe all of them without fail.
• Be sure to confirm no anomaly on the equipment by commissioning after completed installation and explain the operating methods as well as the
maintenance methods of this equipment to the user according to the owner’s manual.
• Keep the installation manual together with owner’s manual at a place where any user can read at any time. Moreover if necessary, ask to hand them
to a new user.
• For installing qualified personnel, take precautions in respect to themselves by using suitable protective clothing, groves, etc., and then perform the
installation works.
• Please pay attention not to fall down the tools, etc. when installing the unit at the high position.
• If unusual noise can be heard during operation, consult the dealer.
• Symbols which appear frequently in the text have the following meaning:
Observe instructions
Strictly prohibited Provide proper earthing
with great care
WARNING
• Installation must be carried out by the qualified installer. • The electrical installation must be carried out by the qualified electrician
If you install the system by yourself, it may cause serious trouble such as in accordance with “the norm for electrical work” and “national wiring
water leaks, electric shocks, fire and personal injury, as a result of a system regulation”, and the system must be connected to the dedicated circuit.
malfunction. Power source with insufficient capacity and incorrect function done by im-
• Install the system in full accordance with the instruction manual. proper work can cause electric shocks and fire.
Incorrect installation may cause bursts, personal injury, water leaks, electric • Be sure to shut off the power before starting electrical work.
shocks and fire. Failure to shut off the power can cause electric shocks, unit failure or incorrect
• Be sure to use only for household and residence. function of equipment.
If this appliance is installed in inferior environment such as machine shop and • Be sure to use the cables conformed to safety standard and cable ampac-
etc., it can cause malfunction. ity for power distribution work.
• Use the original accessories and the specified components for installation. Unconformable cables can cause electric leak, anomalous heat production or
If parts other than those prescribed by us are used, It may cause water leaks, fire.
electric shocks, fire and personal injury. • This appliance must be connected to main power source by means of a
circuit breaker or switch (fuse:16A) with a contact separation of at least
• Install the unit in a location with good support. 3mm.
Unsuitable installation locations can cause the unit to fall and cause material
damage and personal injury. • When plugging this appliance, a plug conforming to the norm IEC60884-
1 must be used.
• Ensure the unit is stable when installed, so that it can withstand earth-
quakes and strong winds. • Use the prescribed cables for electrical connection, tighten the cables
securely in terminal block and relieve the cables correctly to prevent
Unsuitable installation locations can cause the unit to fall and cause material overloading the terminal blocks.
damage and personal injury.
Loose connections or cable mountings can cause anomalous heat production
• Ventilate the working area well in the event of refrigerant leakage during or fire.
installation.
• Arrange the wiring in the control box so that it cannot be pushed up fur-
If the refrigerant comes into contact with naked flames, poisonous gas is pro- ther into the box. Install the service panel correctly.
duced.
Incorrect installation may result in overheating and fire.
• When installing in small rooms, take prevention measures not to exceed
the density limit of refrigerant in the event of leakage. • Be sure to fix up the service panels.
Consult the expert about prevention measures. If the density of refrigerant Incorrect fixing can cause electric shocks or fire due to intrusion of dust or
exceeds the limit in the event of leakage, lack of oxygen can occur, which can water.
cause serious accidents. • Be sure to switch off the power source in the event of installation, inspec-
tion or servicing.
• After completed installation, check that no refrigerant leaks from the system.
If refrigerant leaks into the room and comes into contact with an oven or other If the power source is not shut off, there is a risk of electric shocks, unit fail-
hot surface, poisonous gas is produced. ure or personal injury due to the unexpected start of fan.
• Use the prescribed pipes, flare nuts and tools for R410A. • Stop the compressor before disconnecting refrigerant pipes in case of
pump down operation.
Using existing parts (for R22 or R407C) can cause the unit failure and serious
accidents due to burst of the refrigerant circuit. If disconnecting refrigerant pipes in state of opening service valves before
compressor stopping, air can be sucked, which can cause burst or personal
• Tighten the flare nut by torque wrench with specified method. injury due to anomalously high pressure in the refrigerant circuit
If the flare nut were tightened with excess torque, this may cause burst and • Only use prescribed option parts. The installation must be carried out by
refrigerant leakage after a long period. the qualified installer.
• Do not open the service valves for liquid line and gas line until completed If you install the system by yourself, it can cause serious trouble such as water
refrigerant piping work, air tightness test and evacuation. leaks, electric shocks, fire.
If the compressor is operated in state of opening service valves before com-
pleted connection of refrigerant piping work, air can be sucked into refrigerant
circuit, which can cause bust or personal injury due to anomalously high pres-
sure in the refrigerant.
• Do not put the drainage pipe directly into drainage channels where poi- • Do not bundling, winding or processing for the power cable. Or, do not
sonous gases such as sulphide gas can occur. deforming the power plug due to tread it.
Poisonous gases will flow into the room through drainage pipe and seriously This may cause fire or heating.
affect the user’s health and safety. • Do not vent R410A into the atmosphere : R410A is a fluorinated green-
• Ensure that no air enters in the refrigerant circuit when the unit is in- house gas, covered by the Kyoto Protocol with Global Warming Potential
stalled and removed. (GWP)=1975.
If air enters in the refrigerant circuit, the pressure in the refrigerant circuit • Do not run the unit with removed panels or protections.
becomes too high, which can cause burst and personal injury. Touching rotating equipments, hot surfaces or high voltage parts can cause
• Do not processing, splice the power cable, or share a socket with other personal injury due to entrapment, burn or electric shocks.
power plugs. • Do not perform any change of protective device itself or its setup condition.
This may cause fire or electric shock due to defecting contact, defecting insu- The forced operation by short-circuiting protective device of pressure switch
lation and over-current etc. and temperature controller or the use of non specified component can cause
fire or burst.
• Carry out the electrical work for ground lead with care.
Do not connect the ground lead to the gas line, water line, lightning conductor or telephone line’s ground lead. Incorrect grounding can cause unit faults such as
electric shocks due to short-circuiting.
- 12 -
CAUTION
• Use the circuit breaker with sufficient breaking capacity. • Take care when carrying the unit by hand.
If the breaker does not have sufficient breaking capacity, it can cause the unit If the unit weights more than 20kg, it must be carried by two or more persons.
malfunction and fire. Do not carry by the plastic straps, always use the carry handle when carrying
• Earth leakage breaker must be installed. the unit by hand. Use gloves to minimize the risk of cuts by the aluminum
If the earth leakage breaker is not installed, it can cause electric shocks. fins.
• Install isolator or disconnect switch on the power source wiring in ac- • Dispose of any packing materials correctly.
cordance with the local codes and regulations. Any remaining packing materials can cause personal injury as it contains
nails and wood. And to avoid danger of suffocation, be sure to keep the plastic
• Be sure to install indoor unit properly according to the instruction manu- wrapper away from children and to dispose after tear it up.
al in order to run off the drainage smoothly.
Improper installation of indoor unit can cause dropping water into the room • For installation work, be careful not to get injured with the heat
and damaging personal property. exchanger, piping flare portion or screws etc.
• Install the drainage pipe to run off drainage securely according to the • Be sure to insulate the refrigerant pipes so as not to condense the ambient
installation manual. air moisture on them.
Incorrect installation of the drainage pipe can cause dropping water into the Insufficient insulation can cause condensation, which can lead to moisture
room and damaging personal property. damage on the ceiling, floor, furniture and any other valuables.
• Be sure to install the drainage pipe with descending slope of 1/100 or • When perform the air-conditioner operation (cooling or dehumidifying
more, and not to make traps and air-bleedings. operation) in which ventilator is installed in the room. In this case, using
the air-conditioner in parallel with the ventilator, there is the possibility
Check if the drainage runs off securely during commissioning and ensure the that drain water may backflow in accordance with the room lapse into
space for inspection and maintenance. the negative pressure status. Therefore, set up the opening port such as
• After maintenance, all wiring, wiring ties and the like, should be returned incorporate the air into the room that may appropriate to ventilation (For
to their original state and wiring route, and the necessary clearance from example; Open the door a little). In addition, just as above, so set up the
all metal parts should be secured. opening port if the room lapse into negative pressure status due to regis-
• Secure a space for installation, inspection and maintenance specified in ter of the wind for the high rise apartment etc.
the manual.
Insufficient space can result in accident such as personal injury due to falling
from the installation place.
• Do not install the unit in the locations listed below. • Do not install the unit near the location where leakage of combustible
• Locations where carbon fiber, metal powder or any powder is floating. gases can occur.
• Locations where any substances that can affect the unit such as sulphide If leaked gases accumulate around the unit, it can cause fire.
gas, chloride gas, acid and alkaline can occur. • Do not install the unit where corrosive gas (such as sulfurous acid gas etc.)
• Vehicles and ships. or combustible gas (such as thinner and petroleum gases) can accumulate
or collect, or where volatile combustible substances are handled.
• Locations where cosmetic or special sprays are often used.
Corrosive gas can cause corrosion of heat exchanger, breakage of plastic parts
• Locations with direct exposure of oil mist and steam such as kitchen and and etc. And combustible gas can cause fire.
machine plant.
• Locations where any machines which generate high frequency harmonics • Do not use the indoor unit at the place where water splashes may occur
are used. such as in laundries.
Since the indoor unit is not waterproof, it can cause electric shocks and fire.
• Locations with salty atmospheres such as coastlines.
• Locations with heavy snow (If installed, be sure to provide base flame and • Do not install nor use the system close to the equipment that generates
snow hood mentioned in the manual). electromagnetic fields or high frequency harmonics.
Equipment such as inverters, standby generators, medical high frequency
• Locations where the unit is exposed to chimney smoke. equipments and telecommunication equipments can affect the system, and
• Locations at high altitude (more than 1000m high). cause malfunctions and breakdowns. The system can also affect medical
• Locations with ammonic atmospheres. equipment and telecommunication equipment, and obstruct its function or
• Locations where heat radiation from other heat source can affect the unit. cause jamming.
• Locations without good air circulation. • Do not place any variables which will be damaged by getting wet under
• Locations with any obstacles which can prevent inlet and outlet air of the the indoor unit.
unit. When the relative humidity is higher than 80% or drainage pipe is clogged,
• Locations where short circuit of air can occur (in case of multiple units condensation or drainage water can drop and it can cause the damage of valu-
installation). ables.
• Locations where strong air blows against the air outlet of outdoor unit. • Do not install the remote control at the direct sunlight.
It can cause remarkable decrease in performance, corrosion and damage of It can cause malfunction or deformation of the remote control.
components, malfunction and fire. • Do not use the unit for special purposes such as storing foods, cooling pre-
• Do not install the indoor unit in the locations listed below (Be sure to cision instruments and preservation of animals, plants or art.
install the indoor unit according to the installation manual for each model It can cause the damage of the items.
because each indoor unit has each limitation). • Do not install the outdoor unit in a location where insects and small ani-
• Locations with any obstacles which can prevent inlet and outlet air of the mals can inhabit.
unit. Insects and small animals can enter the electric parts and cause damage or fire.
• Locations where vibration can be amplified due to insufficient strength of Instruct the user to keep the surroundings clean.
structure. • Do not use the base flame for outdoor unit which is corroded or damaged
• Locations where the infrared receiver is exposed to the direct sunlight or the due to long periods of operation.
strong light beam (in case of the infrared specification unit). Using an old and damage base flame can cause the unit falling down and cause
• Locations where an equipment affected by high harmonics is placed (TV set personal injury.
or radio receiver is placed within 1m). • Do not use any materials other than a fuse with the correct rating in the
• Locations where drainage cannot run off safely. location where fuses are to be used.
It can affect performance or function and etc. Connecting the circuit with copper wire or other metal thread can cause unit
• Do not install the outdoor unit in the locations listed below. failure and fire.
• Locations where discharged hot air or operating sound of the outdoor unit • Do not touch any buttons with wet hands.
can bother neighborhood. It can cause electric shocks.
• Locations where outlet air of the outdoor unit blows directly to plants. • Do not touch any refrigerant pipes with your hands when the system is in
• Locations where vibration can be amplified and transmitted due to operation.
insufficient strength of structure. During operation the refrigerant pipes become extremely hot or extremely
• Locations where vibration and operation sound generated by the outdoor cold depending the operating condition, and it can cause burn injury or frost
unit can affect seriously (on the wall or at the place near bed room). injury.
• Locations where an equipment affected by high harmonics is placed (TV set • Do not touch the suction or aluminum fin on the outdoor unit.
or radio receiver is placed within 1m). This may cause injury.
• Locations where drainage cannot run off safely. • Do not put anything on the outdoor unit and operating unit.
It can affect surrounding environment and cause a claim. This may cause damage the objects or injury due to falling to the object.
- 13 -
⑤
Wood screw
2
7 Torque wrench ( )
14.0 ~ 62.0N · m
(1.4 ~ 6.2kgf · m)
(for remote contorol switch holder 3.5dia. by 16mm)
8 Hole core drill (65mm in diameter)
⑥ Baterry [R03 (AAA, Micro) 1.5V] 2
9 Wrench key (Hexagon) [4m/m]
⑦ Air-cleaning filters 2
10 Vacuum pump
Filter holders
⑧ 2
(Attached to the front panel of the indoor unit) 11
Vacuum pump adapter
(Anti-reverse flow type) ( )
Designed specifically
for R410A
ⓒ
ⓓ
Inclination plate
Putty
1
1
14 Flaring tool set ( )
Designed specifically
for R410A
OUTDOOR UNIT
Air intake
① A place where good air circulation can be obtained and where rain, 10 cm
MIN
10 cm MIN
- 14 -
Limitations for one way piping length and vertical height difference
Model
SRK18YLV-S1
Item
Total one way
Max. 25 m
piping length ( )
h
Vertical height
Max. 15 m
difference (h) r
Look for the inside wall structures (Intersediate support or INSTALLATION SPACE (INDOOR UNIT) (FRONT VIEW)
pillar and firaly install the unit after level surface has been
Unit : mm
checked.)
450
Space for Space for
service Indoor unit service
0 Installation board 00
0 0
Space
0. 0.
.
.
.
Mating mark for level surface
00
.
• Adjustment of the installation board in the horizontal
direction is to be conducted with five screws in a
.
. .
Space *
.
for service
Piping for Liquid .
Drain hose 0( )
Standard hole
Piping hole( ) Piping hole( )
*Leave extra space on the right side to enable removal of the lid screw.
• Adjust so that board will be level by turning the
board with the standard hole as the center.
Inclined
Turn to flange
tighten Sleeve
Sealing
Paste plate
- 15 -
Terminal block
Preparation of indoor unit
① Mounting of connecting wires Screw*
•
Connect the connection wire securely to the terminal block.
If the wire is not affixed completely, contact will be poor,
and it is dangerous as the terminal block may heat up and
Drain hose
catch fire.
• Take care not to confuse the terminal numbers for indoor • Hold the bottom of the pipe and change its direction before
and outdoor connections. stretching it and shaping it.
• Earth lead wire shall be longer than the other lead wires for
the electrical safety in case of the slipping out of the cord ③ Taping of the exterior
from the anchorage.
• The earth line of power cable must be properly earthed.
• Affix the connection wire using the wiring clamp.
ⓓ Fix the connecting wire by wiring clamp.
ⓔ Attach the lid.
ⓕ Close the air inlet panel.
• Tape only the portion that runs through the wall.
• Always tape the crossover wires with the pipe.
Rear
Downward Left rear Left
Left side piping Right side piping
Left downward
• Remove the screw and • Remove it with hand • Insert the drain cap which was • Insert the drain hose securely,
drain hose, making it or pliers. removed at procedure “2” securely making rotate. And install the
rotate. using a hexagonal wrench etc. screw.
Note: Be careful that If it is not Note: Be careful that if it is
Inserted securely, water leakage may not inserted securely, water
occur. leakage may occur.
• Do not place the power cable above the gutter, because • Do not make traps in the drain hose line.
the air-conditioner is structured in a way where condensa-
tion on the back side is collected in to the drain pan before
drainage.
Gutter
Wall
- 16 -
Installation
board
Wall 2.The unit can be installed
simply by gently push-
ing in the lower part.
Indoor unit
base lower latch
① Removing
• Remove the 2 set screws.
• Move the lower part of the panel forward and push upwards to
remove. (Remove the 3 latches in the upper section.)
② Fitting
• Do remove the air filter.
• Cover the body with the front panel. Set screws
• Tighten the 2 set screws.
• Fit the air filter. Carry out in the above order.
① To open, pull the panel at both ends of lower part and release
latches, then pull up the panel until you feel resistance. (The
air inlet panel stops at approx. 60˚ open position.)
② To close, hold the panel at both ends of lower part to lower
downward and push it slightly until the latch works, then
push the center portion slightly.
③ To remove, pull up the panel to the position shown in right
illustration and pull it toward you.
④ To install, insert the air inlet panel arm into the slot on the
front panel from the position shown in right illustration,
hold the panel at both ends of lower part, lower it downward
slowly, then push it slightly until the latch works and further
push the center portion slightly.
- 17 -
• Remove the flared nuts. • Remove the flared nuts. • Install the removed flared nuts to the pipes to
(on both liquid and gas sides) (on both liquid and gas be connected, then flare the pipes.
sides)
• Flaring work
Measurement B
Flaring block
Copper pipe
Measurement B (mm) Use a flare tool designed for R410A or a conventional flare tool.
Copper pipe diameter Clutch type flare tool for Conventional (R22) flare tool Please note that measurement B (protrusion from the flaring
R410A Clutch type Wing nut type block) will vary depending on the type of a flare tool in use.
If a conventional flare tool is used, please use a copper pipe
ø6.35 0.0 ~ 0.5 1.0 ~ 1.5 1.5 ~ 2.0
gauge or a similar instrument to check protrusion so that you can
ø12.7 0.0 ~ 0.5 1.0 ~ 1.5 2.0 ~ 2.5 keep measurement B to a correct value.
Spanner
for fixing
the piping)
Torque
wrench
• Always use a Torque wrench and back up spanner to tighten the flare nut.
- 18 -
Air purge
① Tighten all flare nuts in the pipings both Service valve Compound pressure gauge
cap Pressure gauge
indoor and outside so as not to cause
leak. Service valve Gauge manifold
(two-way valve) -0.1MPa (Designed specifically for R410A)
② Connect service valve, charge hose, (-76cmHg)
manifold valve and vacuum pump as is Handle Lo Handle Hi
illustrated right. Service valve Charge hose
③ Open manifold valve handle Lo to its (three-way valve) (Designed specifically for R410A)
full width, and perform vacuum or evac- Service valve
Vacuum pump adapter
(Anti-reverse flow type)
uation. cap (Designed specifically for R410A)
Continue the vacuum or evacuation Vacuum pump
operation for 15 minutes or more and Check joint Charge hose (Designed specifically for R410A)
check to see that the vacuum gauge Securely tighten the service valve cap and the check joint blind nut after adjustment.
reads – 0.1 MPa (– 76 cmHg).
Service valve size Service valve cap Check joint blind nut
④ After completing vacuum operation, ful- (mm) tightening torque (N•m) tightening torque (N•m)
ly open service valve (Both gas and liq- ø6.35 (1/4") 20~30
uid sides) with hexagon headed wrench. 10~12
ø12.7 (1/2") 25~35
⑤ Detach the charge hoses.
⑥ Check for possible leakage of gas in the
connection parts of both indoor and out-
door.
● Since the system uses check joints differing in diameter from those found on the conventional models, a charge hose (for R22) presently in use is not
applicable.
Please use one designed specifically for R410A.
● Please use an anti-reverse flow type vacuum pump adapter so as to prevent vacuum pump oil from running back into the system.
Oil running back into an air-conditioning system may cause the refrigerant cycle to break down.
① Cover the connection portion of the refrigerant piping with the To cover the connecting portion with insula-
pipe cover and seal them. tion materials, cut upper portion and then seal
Vinyl tape it with insulation materials.
If neglecting to do so, moisture occurs on the piping and water
will drip out.
Tapping screw
- 19 -
Battery
-
CAUTION
+ + Do not use new and
- old batteries together.
Cover Screws
Earthing work
• Earth work shall be carried out without fail in order to prevent electric shock and noise generation.
• The connection of the earth cable to the following substances causes dangerous failures, therefore it shall never be done.
City water pipe, Town gas pipe, TV antenna, lightning conductor, telephone line, etc.
- 20 -
SRK10YJV-S
SRK13YJV-S
Remote control
Operation section
S Operation section
Indication
Unit section
display section
Unit indication section
SRK10YJV-S
CLEAN indicator RUN
ON/OFF lightindicator
TIMER (green)
SRK13YJV-S Illuminates during operation
Indicates during CLEAN operation. Indicates during
and CLEAN ON/OFF TIMER operation.
operation.
TEMPERATURE indicator
HI POWER
Indicates light (green)
set temperature.
TIME indicator
(Does
Illuminates not indicate
during temperature
HIGH POWER when operation
operation. Indicates present time or timer setting time.
mode is on AUTO)
3D AUTO light (green)
FAN SPEED indicator AIR FLOW indicator
Illuminates during 3D AUTO operation.
Indicates set air flow rate with lamp. Shows selected flap and louver mode.
Transmission procedure
When each button on the remote control is pressed with the remote control pointing towards the air-conditioner unit a signal is transmitted.
When the air-conditioner receives the signal correctly, it will beep.
–7–
RMA012A032_En.p65
How to close the air inlet panel
7
- 21 - 04/05/2010, 17:26
Push both sides evenly and press further lightly at the center.
Notes (1) Auto restart function is set at on when the air-conditioner is shipped from the factory. Con-
sult with your dealer if this function needs to be switched off.
(2) When power failure ocurrs, the timer setting is cancelled. Once power is resumed, reset the
timer.
(3) If the jumper wire (J12) “AUTO RESTART” is cut, auto restart is disabled. (See the diagram at
right)
- 22 -
(a) Flap
(b) Louver
(Louver stopped)
(c) Swing
(i) (ii)
Approx.
10°
Approx. 60°
- 23 -
(a)
(i)
(ii)
1)
Cooling
Flap Up/down Swing
Louver Wide (Fixed)
2)
3
Cooling
Flap Horizontal blowing (Fixed)
Louver Left/right Swing
3) 4
Cooling
Flap Up/down Swing
Louver Center (Fixed)
4)
Cooling
Flap Horizontal blowing (Fixed)
Louver Wide (Fixed)
5)
- 24 -
(7)ࠉTimer operation
(a) Setting
Installation location setting
Take the air conditioning unit’s location into account and adjust the left/right airflow rang
(i) If the air-conditioning unit is running, press the ON/OFF button to stop.
(ii) Press the AIR-FLOW (UP/DOWN) button and the 1 If the air condi
button to stop.
The installation l
AIR FLOW (LEFT/RIGHT) button together for 5 seconds
2
or more. Press the AIR
AIRFLOW
or more.
(iii) Setting the air-conditioning installation location. The installation l
L , LY
LL 3 Setting the air-
Press the AIR FL
desired location.
Each time the AI
LLL indicator is switc
(Center Installa
The air-condition
Press within 60 s
installation locati
General Information
• mark will be displayed on the display panel while the air conditioner is in operatio
• When installation location of the air conditioner had been set once, installation locatio
unplugging the power cord. Please set it with a remote control again in case of changi
• The installation location setting can not be performed while the unit is in operation.
- 25 -
Model
SRK18YLV-S1
Fan speed
Auto 23~96rps
HI 23~96rps
MED 23~62rps
LO 23~38rps
(10)
(14)Outline of of
Outline dehumidifying (DRY) operation
dry (dehumidifying) operation
(a) Purpose of DRY mode
The purpose is "Dehumidification", and not to control the humidity to the target condition.
Indoor/outdoor unit control the operation condition to reduce the humidity, and also prevent over cooling.
(b) Outline of control
(i) Indoor unit fan speed and compressor are controlled by the area which is selected by the temperature difference.
Indoor unit fan speed
Area
D C B A
Me speed
Indoor unit
fan speed Lo speed
STOP
Compressor Limited
speed Minimum Lower than the speed in”Area A”
STOP
Set temperature
Difference between set temperature and return temperature
(ii) The indoor unit check the current area by every 5 minutes, and operate by the next checking.
(c) Other
When the outside temperature and room temperature is low for cooling operation, indoor unit can not operate in cooling, and
dehumidifying.
- 26 -
25.5
18 30
Outdoor air temperature (˚C)
(b) The unit checks the temperature every hour after the start of operation and, if the result of check is not same as the previous op-
eration mode, changes the operation mode.
(c) When the unit is started again within one hour after the stop of automatic operation or when the automatic operation is selected
during cooling or dehumidifying operation, the unit is operated in the previous operation mode.
(d) Setting temperature can be adjusted within the following range. There is the relationship as shown below between the signals of
the wireless remote control and the setting temperature.
- 27 -
(a) Frost prevention for indoor heat exchanger (During cooling or dehumidifying)
(i) Operating conditions Compressor
1) Indoor heat exchanger temperature (Th2) is lower than 5ºC. command
speed
2) 8 minutes after reaching the compressor command speed except 0 rps.
Upper
(ii) Detail of anti-frost operation limit
speed
Indoor heat exchanger
temperature 5°C or lower 2.5°C or lower
Item 0 rps
Upper limit speed 68 rps 0rps
2.5 5 8
Protects the fan tap just before
Indoor fan Depends on operation mode
frost prevention control Indoor heat exchanger
Outdoor fan Depends on operation mode Depends on stop mode temperature (ºC)
(iii) Reset conditions: The indoor heat exchanger temperature (Th2) is 8ºC or higher after 5 minutes of operation following
control of the compressor command speed upper is 0 rps.
0 rps
90 100 110
Discharge pipe temperature (˚C)
Notes (1) When the discharge pipe temperature is in the range of 100 to 110ºC, the speed is reduced by 4 rps.
(2) When the discharge pipe temperature is raised and continues operation for 20 seconds without changing, then the speed is reduced again by 4 rps.
(3) If the discharge pipe temperature is still 90ºC or greater but less than 100ºC even when the compressor command speed is maintained for 3 minutes
when the temperature is 90ºC or greater but less than 100ºC, the speed is raised by 2 rps and kept at that speed for 3 minutes. This process is
repeated until the compressor command speed is reached.
(4) Lower limit speed
Cooling
Model 18 24 rps
2) If the temperature of 110ºC is detected by the sensor on the discharge pipe, then the compressor will stop immediately.
When the discharge pipe temperature drops and the time delay of 3 minutes is over, the unit starts again within 1 hour
but there is no start at the third time.
- 28 -
(f)
Outdoor unit failure
This is a function for determining when there is trouble with the outdoor unit during air-conditioning.
The compressor is stopped if any one of the following in item (i), (ii) is satisfied. Once the unit is stopped by this function, it is not
restarted.
(i) When the input current is measured at 1 A or less for 3 continuous minutes or more.
(ii) If the compressor command sends a 0 rps signal to the indoor unit 3 times or more within 20 minutes of the power being
turned on.
- 29 -
'16 • SRK-T-192
Reference
8. MAINTENANCE DATAPROCEDURES FOR ELECTRICAL EQUIPMENT
2 TROUBLESHOOTING
(1) Cautions
-
-
source
(3) Troubleshooting procedure (If the air-conditioner does not run at all)
- -
Important satisfied -
AC -
NO
source
YES
NO YES
NO
YES
NO
wireless
YES
proced-
- 30 -
NO YES
32
NO
33 - 36.
YES
YES
NO
33 - 36.
YES
NO
- 31 -
• Broken room temperature When a room temperature sensor wire disconnection is detected while operation
2-time Room sensor wire, poor connector is stopped. (If a temperature of –20ºC or lower is detected for 15 seconds, it is
ON temperature connection judged that the wire is disconnected.)
flash
sensor error • Indoor PCB is faulty (Not displayed during operation.)
5-time Active filter When the wrong voltage connected for the power source.
ON voltage error • Defective active filter When the outdoor PCB is faulty.
flash
When conditions for turning the indoor unit’s fan motor on exist during air-
6-time Indoor fan • Defective fan motor, poor
ON conditioner operation, an indoor unit fan motor speed of 300 min-1 or lower is
flash motor error connector connection
measured for 30 seconds or longer. (The air-conditioner stops.)
• Broken outdoor air temperature When an outdoor temperature sensor wire disconnection is detected while
Keeps 1-time Outdoor air sensor wire, poor connector operation is stopped. (If a temperature of –40ºC or lower is detected for 15
temperature connection
flashing flash seconds, it is judged that the wire is disconnected.)
sensor error • Outdoor PCB is faulty (The compressor is stopped.)
• Broken heat exchanger sensor When a sensor wire disconnection is detected while operation is stopped.
Keeps 2-time Outdoor heat wire, poor connector (If a temperature of –50ºC or lower is detected for 15 seconds, it is judged that
exchanger connection the wire is disconnected.)
flashing flash
sensor error • Outdoor PCB is faulty (The compressor is stopped.)
• Broken discharge pipe sensor When a compressor discharge pipe sensor wire disconnection is detected for
Keeps 4-time Discharge pipe wire, poor connector 15 seconds or longer (less than 7ºC) after the compressor command speed has
flashing flash sensor error connection continued at 0 rps or higher for 9 minutes.
• Outdoor PCB is faulty (The compressor is stopped.)
• Compressor locking, open The inverter output current (compressor motor current) exceeds the set value
1-time phase on compressor output, during compressor start.
ON Current Cut shortcircuit on power
flash (The air-conditioner stops.)
transistor, closed service valve
When there is an emergency stop caused by trouble in the outdoor unit, or the
2-time Trouble of • Broken compressor wire
ON outdoor unit • Compressor blockage input current value is found to be lower than the set value.
flash (The air-conditioner stops.)
• Overload operation
3-time Current safe When the compressor command speed is lower than the set value and the current
ON • Overcharge
flash stop safe has operated. (The compressor is stopped.)
• Compressor locking
When there is an emergency stop caused by trouble in the outdoor unit, or the
4-time Power transistor input current value is found to be lower than the set value continuously for 3
ON • Broken power transistor
flash error minutes or longer.
(The compressor is stopped.)
• Defective power source, When there is no signal between the indoor PCB and outdoor PCB for 10
6-time Error of signal seconds or longer (when the power is turned on), or when there is no signal for
ON Broken signal wire, defective
flash transmission indoor/outdoor PCB 1 minute 55 seconds or longer (during operation)(the compressor is stopped).
7-time Outdoor fan • Defective fan motor, poor When the outdoor unit’s fan motor sped continues for 30 seconds or longer at
ON motor error connector connection 75 min-1 or lower. (3 times) (The air-conditioner stops.)
flash
• Defective compressor If the compressor motor’s magnetic pole positions cannot be correctly detected
2-time 2-time when the compressor starts.
Rotor lock • Open phase on compressor
flash flash • Defective outdoor PCB (The air-conditioner stops.)
Notes (1) The air-conditioner cannot be restarted using the remote control for 3 minutes after operation stops.
- 32 -
Term Explanation
The service mode is the mode where service data are displayed by flashing of the display lights
Service mode
when the operations in item (b) below are performed with the indoor controller.
These are the contents of error displays and protective stops which occurred in the past in the air-
conditioner system. Error display contents and protective stop data from past anomalous
Service data operations of the air-conditioner system are saved in the indoor unit control’s non-volatile
memory (memory which is not erased when the power goes off). There are two types of data,
self-diagnosis data and stop data, described below.
These are the data which display the reason why a stop occurred when an error display(self-
diagnosis display) occurred in an indoor unit. Data are recorded for up to 5 previous occurrences.
Data which are older than the 5th previous occurrence are erased.
Self-diagnosis data In addition, data on the temperature of each sensor (room temperature, indoor heat exchanger,
outdoor heat exchanger, outdoor air temperature, discharge pipe), remote control information
(operation switching, fan speed switching) are recorded when trouble occurs, so more detailed
information can be checked.
These are the data which display the reason by a stop occurred when the air-conditioning system
performed protective stops, etc. in the past. Even if stop data alone are generated, the system
restarts automatically. (After executing the stop mode while the display is normal, the system
restarts automatically.) Data for up to 10 previous occasions are stored. Data older than the 10th
Stop data
previous occasion are erased.
( Important) In cases where transient stop data only are generated, the air-conditioner system
may still be normal. However, if the same protective stop occurs frequently (3 or
more times), it could lead to customer complaints.
wireless
35.)
34.)
- 33 -
safe 43
4-time flash 3-time flash.
3 43 43 safe
wireless
mode mode
wireless
Fan
Wireless remoteremote
Wireless control setting Indicates the number of
control setting
occasions previous to the present
Temperature
Operation setting
Fan the error display data are from.
speed Temperature Displayed data
mode 26ºC mode 1 time previous (previous time)
setting
27ºC 2 times
21ºCprevious
Displays the reason for the stop (error code) the previous time an error was displayed.
28ºC 3 times
22ºCprevious
Displays the reason for the stop (error code) 2 times previous when an error was displayed.
Cooling 29ºC MED 4 times
23ºCprevious
Displays the reason for the stop (error code) 3 times previous when an error was displayed.
30ºC 5 times
24ºCprevious
Displays the reason for the stop (error code) 4 times previous when an error was displayed.
25ºC Displays the reason for the stop (error code) 5 times previous when an error was displayed.
(c) Error code, stop code table (Assignment of error codes and stop codes is done in common for all models.)
Number of flashes
when in service mode Stop code Error content Error Auto
RUN TIMER or Cause Occurrence conditions display recovery
light light Error code
(10’s digit) (1’s digit) Major category Minor category
OFF OFF 0 Normal - - - - -
Compressor lock
1-time Compressor wiring short circuit Compressor start fails 42 times in succession and the
11 Compressor software start
flash Compressor output is open phase reason for the final failure is current cut. (2 times)
Outdoor PCB is faulty
Service valve closed
2-time After the compressor starts, it stops due to current cut at
flash
12 Lower than 20 rps Compressor output is open phase.
less than 20 rps. -
Electronic expansion valve is faulty.
Service valve is closed.
3-time Compressor output is open phase. When operation is stopped by current cut at 20 rps or
13 20 rps or higher
Compressor is faulty. higher.
-
flash
1-time Current Electronic expansion valve is faulty.
flash Cut
4-time Outdoor PCB is defective.
14 Excessive voltage When the DC voltage exceeds 390V. -
flash Power source is abnormal.
5-time Short circuit in the power Outdoor PCB is faulty.
. When it is judged that the power transistor was damaged
15 -
flash transistor (high side) Power transistor is damaged. at the time the compressor started.
6-time Current cut circuit Outdoor PCB is faulty. When it is judged that the power transistor was damaged
16
breakdown Power transistor is damaged. at the time the compressor started.
-
flash
Service valve is closed.
7-time Compressor output is open phase. When the compressor has stopped with the current cut
17 Software current cut Compressor is faulty.
flash after starting it
Electronic expansion valve is faulty.
2-time Compressor wiring is Compressor wiring is disconnected. When the curent is 1A or less the time the compressor
22
unconnection voltage drop Outdoor PCB is faulty. started.
-
flash
Outdoor
unit Service valve is closed.
When an abnormal stop occurs 3 times with automatic
3-time error Abnormal stop 3 times in Compressor output is open phase.
flash
23
20 minutes. Electronic expansion valve is faulty.
recovery within 20 minutes after the outdoor unit’s power -
source was turned on.
Refrigerant is insufficient.
2-time
flash Outdoor fan motor is faulty.
7-time Outdoor unit’s fan motor When a fan speed of 75 min-1 or lower continues for 30
27 Connector connections are poor.
flash is abnormal seconds or longer. (3 times)
Outdoor PCB is faulty.
Outdoor
8-time fan motor Power source construction
28 error Input of abnormal voltage is faulty. When an error voltage of 150 V or less is input
flash
9-time Power source construction is defective.
29 Voltage drop Outdoor PCB is faulty. When the power source voltage drops during operation. -
flash
1-time Overcharge When there is a current safe stop in current safe I mode
flash
31 Cooling current safe I
Compressor lock during cooling operation.
-
3-time 3-time Current Overcharge When there is a current safe stop in current safe II mode
flash
33
safe
Cooling current safe II
Compressor lock during cooling operation.
-
flash
5-time Overcharge When there is a current safe stop in current safe III mode
35 Cooling current safe III Compressor lock during cooling operation.
-
flash
- 35 -
Number of flashes
when in service mode Stop code Error content Error Auto
RUN TIMER or Cause Occurrence conditions
display recovery
light light Error code
(10’s digit) (1’s digit) Major category Minor category
Can’t receive signals for 1 Power source is faulty. When 1 minute 55 seconds passes without
OFF 60 minute 55 seconds (if Power source cables and signal lines are improperly wired. communications signals from either the outdoor unit or -
communications have recovered) Indoor or outdoor PCB is faulty. the indoor unit being detected correctly.
6-time Serial signal
1-time transmission Connection lines between the Connection lines between the indoor and When 10 seconds passes after the power is turned on without communications
flash
flash
61 error outdoor units are faulty.
signals from the indoor or outdoor unit being detected correctly.
-
indoor and outdoor units are faulty. Indoor or outdoor PCB are faulty.
2-time Indoor or outdoor PCB are faulty. When 1 minute 55 seconds passes without communications signals
62 Serial transmission error.
flash Noise is causing faulty operation. from either the outdoor unit or the indoor unit being detected correctly. (3 times)
Compressor is faulty.
Compressor output is open phase.
After the compressor starts, when the compressor stops
OFF 70 Rotor lock Rotor lock Electronic expansion valve is faulty.
due to rotor lock. (2 times)
Overload operation.
7-time Outdoor PCB is faulty
flash
Compressor is faulty
Compressor software start
6-time Compressor wiring is disconnected. When compressor start fails 42 times in succession and
76 (within 4 seconds after
flash Compressor wiring is short circuited. the reason for the final failure is rotor lock. (2 times)
phase switching)
Outdoor PCB is faulty.
Fan motor is faulty. When the indoor unit’s fan motor is detected to be
Indoor unit fan motor is
OFF 80 Connector connections are poor. running at 300 min-1 or lower speed with the fan motor in -
abnormal.
Indoor PCB is faulty. the ON condition while the air-conditioner is running.
Discharge pipe sensor wire is When a disconnection signal is sent for 15 seconds or longer as the
1-time Discharge pipe sensor is
81 discharge pipe sensor data after the outdoor unit’s speed is 0 rps or
flash abnormal (anomalous stop). disconnected. (4 times)
Connector connections are poor. higher continuously for 9 minutes.
2-time Indoor heat exchanger sensor Indoor heat exchanger sensor wire is When a temperature of -20ºC or lower is sensed continuously
flash
82 disconnected. -
is abnormal (anomalous stop). Connector connections are poor. for 40 minutes during heating operation (the compressor stops).
3-time Protective Outdoor heat exchanger sensor is Outdoor heat exchanger sensor wire
8-time 83 is disconnected. When a temperature of -55ºC or lower is sensed continuously -
flash control abnormal (anomalous stop). Connector connections are poor. for 40 minutes during heating operation (the compressor stops).
flash
operation
4-time High humidity condition. -
84 Anti-condensation control Anti-condensation prevention control is operating.
flash Humidity sensor is faulty.
5-time Indoor unit fan speed drops. When the anti-frost control operates and the compressor -
85 Anti-frost control
flash Indoor heat exchanger sensor short circuit stops during cooling operation.
Refrigerant is insufficient. When compressor overheating protective control operates
7-time Compressor overheating Discharge pipe sensor is faulty. and the compressor stops. -
87
flash protection control Service valve is closed.
8-time Refrigeration cycle system Service valve is closed. When refrigeration cycle system protective control
88 protective control
-
flash Refrigerant is insufficient. operates.
- 36 -
safe 3
4-time flash 3-time flash.
3 3 3 safe
Mode
Operation mode AUTO
Fan speed mode AUTO
1.5 sec.
ON
RUN light
(10’s digit)
OFF
0.5 sec. 0.5 sec.
ON
TIMER light
(1’s digit)
OFF
11-second interval
- 37 -
temperature information
Sensor name Sensor value displayed when the error code is normal
Room temperature sensor -64ºC
Indoor heat exchanger sensor -64ºC
Outdoor air temperature sensor -64ºC
Outdoor heat exchanger sensor -64ºC
O temperature data
0.1 sec.
ON If the temperature is < 0, the buzzer sounds.
Buzzer sound If the temperature is 0, the buzzer does not sound.
OFF
1.5 sec.
ON
RUN light
(10’s digit)
OFF
0.5 sec. 0.5 sec.
ON
TIMER light
(1’s digit)
OFF
11-second interval
- 38 -
Buzzer sound
temperature information
data
0.1 sec.
ON If the temperature is < 0, the buzzer sounds.
Buzzer sound If the temperature is 0, the buzzer does not sound.
OFF
1.5 sec.
ON
RUN light
(10’s digit)
OFF
0.5 sec. 0.5 sec.
ON
TIMER light
(1’s digit)
OFF
11-second interval
- 39 -
Wireless r
Operation mode Fan speed mode
Wireless r
Wireless r
Wireless r
Wireless r
Wireless r
- 40 -
180 30
160
25
140
Resistance (k )
Resistance (k )
120 20
100
15
80
60 10
40
5
20
0 -10 0 10 20 30 40 50 60 70
0 20 40 60 80 100 120 135
Temperature (˚C) Temperature (˚C)
- 41 -
Current cut Compressor lock, Compressor wiring short circuit, Compressor output is open phase,
Outdoor PCB is faulty, Service valve is closed, EEV is faulty, Compressor faulty.
49
- 42 -
41)
Error of signal transmission Wiring error including power cable, defective indoor/
outdoor PCB
source
-
-
-
-
- 43 -
Trouble of outdoor unit Insufficient refregerant amount, Faulty power transistor, Broken compressor wire
Service valve close, Defective EEV, Defective outdoor PCB
source source
AC AC -
AC AC -
AC AC -
(1)
(2)
(3)
Notes (1) 49
wire
ourdoor PCB
See pages 49 for the fan motor and outdoor PCB check pro-
outdoor
After making sure the fan motor and outdoor PCB are nor-
- 44 -
'09•SRK-DB-087D
Failure mode Control input circuit resding Air conditioning system operation '09•SRK-DB-087D
YES
'16 • SRK-T-192
Indoor electrical components
are normal.
DC several V (–)
(4-6 V) GND DC 308-336V
Measuring Voltage range when
DC15V point normal
White
Black
Blue
Red
FMI
- 46 -
'16 • SRK-T-192
wireless wireless
wireless
wireless
wireless
wireless
(11) Inspection procedure for blown fuse on the indoor and outdoor PCB
Is the fuse blown on the indoor and NO Go to the inspection procedure for electric
outdoor PCB? equipment of indoor and outdoor units
(See pages 45 to 49.)
( )
Faulty part, other than YES
fan motor YES Is there any faulty part (fan motor, etc)? NO
Replace the fuse, and check the operation.
(See pages 45 to 49.)
Replace the faulty part and the YES (Fan motor is faulty.)
fuse. Test-run then the unit for Is there any damage on the internal circuit
checking. of fan motor?
Check the resistance value to judge.
(See pages 46 to 49.)
YES
Replace the indoor and outdoor PCB and the fan motor. Check then the operation.
- 47 -
Color symbol
Mark Color
Model SRK18YLV-S1
RD Red
YE Yellow TERMINAL
PWB ASSY(SUB) PWB ASSY(MAIN)
BLOCK
T1
T2
Y/G Yellow/Green
TB POWER TRANSISTOR
FUSE R IN F8
(BK) (BK) F2
L 1 RO P U (RD)
250V 20A (BK) R U
250V 20A 250V 20A
Power source (WH) S IN ACTIVE
N 2 FILTER
+++ NU V (WH) M
SO V
1 Phase (WH) S UNIT
NV W (BK)
3~
220V 50Hz 3 NW W
S-1 CM
(WH) S-2
(YG)
-
G1
(YG)
48 -
F3 250V 1A
F1
M
250V 2A
CNTH CNEEV
2 2 2
t゜ t゜ t゜
M ◆Inspection of outdoor fan motor
◆Power source and serial signal inspection See page 49.
1 to 2 : AC 220V EEV
TH1 TH2 TH3
2 to 3 : Normal if the voltage oscillates between DC 0 and approx. 20V
(i)
(ii)
6 5 4 3 2 1
DC
White
Yellow
Orange
Blue
Red
(iii)
(iv)
(i)
1)
2)
3) source
FM0
Brown
White
Blue
DC several (4-7V)
DC280-373V GND
DC15V
- 49 -
- 50 -
PARTS LIST
INDOOR UNIT
SRK18YLV-S1
OUTDOOR UNIT
SRC18YLV-S1
- 51 -
31 30
34
35 29
4 32
5 27 26
7
35 12
3
4 6 12
10
10
21
18 23
22 16 13
25 20
14 11
21 19
14 15
22
9 17
3 14 22
24
8
2
CRAE0229
- 52 -
SRK18YLV-S1 CRAE0229
- 53 -
17
18 3
1 20
25 2
21 13
16 15
24
9
12
11
19
22
23 10 14
CRAE0254
- 54 -
SRK18YLV-S1 CRAE0254
14 SSA561B702B BLOCK,TERMINAL 1 1 1 2 2T
15 RKX011G603A LABEL,WIRING 1
16 SSA551B017 SENSOR(HUMIDITY) 1 1 1 2 4
17 RKX503A301 DISPLAY ASSY 1 1 1 2 3
18 RKX505A007 PWB ASSY(DISPLAY) 1 2 2 4 8
19 RKJ941F001A SPRING,LEAF 1
20 RKX502A001 CONTROL ASSY,REMOTE 1 2 3 5 10
21 RMA008A011D PARTS,STANDARD 1
22 RMA012A032B MANUAL,INSTRUCTION 1
23 RKT437A011 FILTER,CLEAN 1 2 2 4 8
24 RKT437A005 FILTER,LIGHT CLEAN 1 2 2 4 8
25 RKN032A002C HOLDER(REMO-CON) 1 1 1 1 2
(26) RMA011F013V LABEL,MODEL NAME 1
- 55 -
18 11
13
12 8
15
6
14
10
16 17
8
7
4
2
1 9
5
8
CRBE0294
- 56 -
SRC18YLV-S1 CRBE0294
- 57 -
8
7
2
3 4
16
15
25
14 5
(LIQ.)
17 19 6
11 (GAS)
28 23 10
12
13
18 21 22
24
23・26
23・27 20
CONTROL ASSY CRBE0342
- 58 -
SRC18YLV-S1 CRBE0342
28 RCV129A001A HOLDER,SENSOR 1
(29) RMC011F016Y LABEL,MODEL NAME 1
- 59 -
Because of our policy of continuous improvement, we reserve the right to make changes in all specifications without notice.
C Copyright MITSUBISHI HEAVY INDUSTRIES, LTD.