Srk25zsp W
Srk25zsp W
'20・SRK-T-320
TECHNICAL MANUAL
SRK25ZSP-W
SRK35ZSP-W
SRK45ZSP-W
SRK50ZSP-W
'20 • SRK-T-320
CONTENTS
1. SPECIFICATIONS .............................................................................................. 3
2. EXTERIOR DIMENSIONS ................................................................................. 8
(1) Indoor units ................................................................................................. 8
(2) Outdoor units .............................................................................................. 9
(3) Wireless remote control ............................................................................ 11
3. ELECTRICAL WIRING .................................................................................... 12
(1) Indoor units ............................................................................................... 12
(2) Outdoor units ............................................................................................ 13
4. NOISE LEVEL .................................................................................................. 15
5. PIPING SYSTEM ............................................................................................. 26
6. RANGE OF USAGE & LIMITATIONS .............................................................. 27
7. CAPACITY TABLES ......................................................................................... 29
8. APPLICATION DATA ....................................................................................... 31
9. OUTLINE OF OPERATION CONTROL BY MICROCOMPUTER .................... 39
(1) Operation control function by wireless remote control ............................... 39
(2) Unit ON/OFF button ................................................................................... 40
(3) Auto restart function .................................................................................. 40
(4) Installing two air-conditioners in the same room ....................................... 40
(5) High power operation ................................................................................ 41
(6) Economy operation .................................................................................... 41
(7) Air flow direction adjustment ..................................................................... 41
(8) Timer operation .......................................................................................... 42
(9) Outline of heating operation ...................................................................... 42
(10) Outline of cooling operation ...................................................................... 44
(11) Outline of automatic operation .................................................................. 44
(12) Protection control function ........................................................................ 45
10. MAINTENANCE DATA ................................................................................... 53
(1) Cautions ..................................................................................................... 53
(2) Items to check before troubleshooting ...................................................... 53
(3) Troubleshooting procedure (If the air-conditioner does not run at all) ........ 53
(4) Troubleshooting procedure (If the air-conditioner runs) .............................. 54
(5) Self-diagnosis table ................................................................................... 55
(6) Service mode (Trouble mode access function) .......................................... 56
(7) Inspection procedures corresponding to detail of trouble ......................... 64
- 1-
'20 • SRK-T-320
Series code
Inverter type
Product capacity (Cooling capacity)
25 : 2.5kW
35 : 3.2kW
45 : 4.5kW
50 : 5.0kW
- 2-
'20 • SRK-T-320
1. SPECIFICATIONS
Model SRK25ZSP-W
Model SRK25ZSP-W
Item Indoor unit SRK25ZSP-W Outdoor unit SRC25ZSP-W
Power source 1 Phase, 220 - 240V, 50Hz
Nominal cooling capacity (range) kW 2.5 ( 0.9 (Min.) - 3.1 (Max.))
Nominal heating capacity (range) kW 2.8 ( 1.0 (Min.) - 4.1 (Max.))
Heating capacity (H2) kW -
Cooling 0.710 ( 0.20 - 1.01 )
Power consumption Heating 0.690 ( 0.20 - 1.43 )
kW
Heating (H2) -
Max power consumption 1.65
Cooling 3.6 / 3.4 / 3.3 (220/ 230/ 240 V)
Running current
Heating A 3.5 / 3.4 / 3.2 (220/ 230/ 240 V)
Operation Inrush current, max current 3.6 / 3.4 / 3.3 (220/ 230/ 240 V) Max. 9
data Cooling 90
Power factor %
Heating 89
EER Cooling 3.52
Heating 4.05
COP
Heating (H2) -
Cooling 57 57
Sound power level
Heating 57 56
Cooling dB(A) Hi: 45 Me: 34 Lo: 23 47
Sound pressure level
Heating Hi: 43 Me: 34 Lo: 26 45
Silent mode sound pressure level - -
Exterior dimensions (Height x Width x Depth) mm 267 × 783 × 210 540 × 645(+57) × 275
Exterior appearance Fine snow Stucco white
(Equivalent color) Munsell : ( 8.0Y 9.3/0.1 ), RAL : 9003 Munsell : ( 4.2Y 7.5/1.1 ), RAL : 7044
Net weight kg 7.0 26.5
Compressor type & Quantity - RM-C5077SBE7( Rotary type ) x 1
Compressor motor (Starting method) kW - 0.75 ( Inverter driven )
Refrigerant oil (Amount, type) ℓ - 0.3 ( DIAMOND FREEZE MB75 )
Refrigerant (Type, amount, pre-charge length) kg R32 0.550 in outdoor unit (Incl. the amount for the piping of 10m )
Heat exchanger Louver fins & inner grooved tubing M fins & inner grooved tubing
Refrigerant control Capillary tubes + Electronic expansion valve
Fan type & Quantity Tangential fan × 1 Propeller fan × 1
Fan motor (Starting method) W 30 × 1 (Direct drive) 24 × 1 (Direct drive)
Cooling 3 Hi: 10.0 Me: 7.3 Lo: 4.2 23.7
Air flow m /min
Heating Hi: 9.5 Me: 7.3 Lo: 5.2 19.7
Available external static pressure Pa 0 0
Outside air intake Not possible -
Air filter, Quality / Quantity Polypropylene net ( Washable ) -
Shock & vibration absorber Rubber sleeve (for fan motor) Rubber sleeve (for fan motor & compressor)
Electric heater - -
Remote control Wireless remote control
Operation
Room temperature control Microcomputer thermostat
control
Operation display RUN: Green , TIMER: Yellow
Compressor overheat protection, Overcurrent protection,
Safety equipments Frost protection, Serial signal error protection, Indoor fan motor error protection,
Heating overload protection( High pressure control ), Cooling overload protection
Refrigerant piping size ( O.D ) mm Liquid line: φ 6.35 ( 1/4" ) Gas line: φ 9.52 ( 3/8" )
Connecting method Flare connection Flare connection
Attached length of piping m Liquid line : 0.46 / Gas line : 0.39 -
Installation
Insulation for piping Necessary ( Both sides ), independent
data
Refrigerant line (one way) length m Max.15
Vertical height diff. between O.U. and I.U. m Max.10 ( Outdoor unit is higher ) / Max.10 ( Outdoor unit is lower )
Drain hose Hose connectable ( VP16 ) Hole φ 20 x 2 pcs.
Drain pump, max lift height mm - -
Recommended breaker size A 16
L.R.A. (Locked rotor ampere) A 3.6 / 3.4 / 3.3 (220/ 230/ 240 V)
Interconnecting wires Size x Core number 1.5mm2 × 4 cores ( Including earth cable ) / Terminal block ( Screw fixing type )
IP number IPX0 IPX4
Standard accessories Mounting kit
Option parts -
Notes ( 1) The data are measured at the following conditions. The pipe length is 5m.
Item Indoor air temperature Outdoor air temperature
Standards
Operation DB WB DB WB
Cooling 27℃ 19℃ 35℃ 24℃ ISO5151-T1
Heating 20℃ - 7℃ 6℃ ISO5151-H1
Heating (H2) 20℃ - 2℃ 1℃ ISO5151-H2
(2) This air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient
conditions.
(4) Select the breaker size according to the own national standard.
RWA000Z275 B
- 3-
'20 • SRK-T-320
Model SRK35ZSP-W
Model SRK35ZSP-W
Item Indoor unit SRK35ZSP-W Outdoor unit SRC35ZSP-W
Power source 1 Phase, 220 - 240V, 50Hz
Nominal cooling capacity (range) kW 3.2 ( 0.9 (Min.) - 3.7 (Max.))
Nominal heating capacity (range) kW 3.6 ( 1.0 (Min.) - 4.6 (Max.))
Heating capacity (H2) kW -
Cooling 0.910 ( 0.20 - 1.32 )
Power consumption Heating 0.930 ( 0.20 - 1.43 )
kW
Heating (H2) -
Max power consumption 1.65
Cooling 4.4 / 4.3 / 4.1 (220/ 230/ 240 V)
Running current
Heating A 4.5 / 4.3 / 4.2 (220/ 230/ 240 V)
Operation Inrush current, max current 4.5 / 4.3 / 4.2 (220/ 230/ 240 V) Max. 9
data Cooling 93
Power factor %
Heating 93
EER Cooling 3.52
Heating 3.87
COP
Heating (H2) -
Cooling 58 59
Sound power level
Heating 58 60
Cooling dB(A) Hi: 45 Me: 36 Lo: 23 48
Sound pressure level
Heating Hi: 44 Me: 36 Lo: 28 48
Silent mode sound pressure level - -
Exterior dimensions (Height x Width x Depth) mm 267 x 783 x 210 540 x 645(+57) x 275
Exterior appearance Fine snow Stucco white
(Equivalent color) Munsell : ( 8.0Y 9.3/0.1 ), RAL : 9003 Munsell : ( 4.2Y 7.5/1.1 ), RAL : 7044
Net weight kg 7.0 28.5
Compressor type & Quantity - RM-C5077SBE7( Rotary type ) x 1
Compressor motor (Starting method) kW - 0.75 ( Inverter driven )
Refrigerant oil (Amount, type) ℓ - 0.3 ( DIAMOND FREEZE MB75 )
Refrigerant (Type, amount, pre-charge length) kg R32 0.68 in outdoor unit (Incl. the amount for the piping of 15m )
Heat exchanger Louver fins & inner grooved tubing M fins & inner grooved tubing
Refrigerant control Capillary tubes + Electronic expansion valve
Fan type & Quantity Tangential fan x 1 Propeller fan x 1
Fan motor (Starting method) W 30 x1 (Direct drive) 24 x1 (Direct drive)
Cooling Hi: 9.5 Me: 6.8 Lo: 4.2 22.8
Air flow m3/min
Heating Hi: 9.6 Me: 7.4 Lo: 5.5 22.0
Available external static pressure Pa 0 0
Outside air intake Not possible -
Air filter, Quality / Quantity Polypropylene net ( Washable ) -
Shock & vibration absorber Rubber sleeve (for fan motor) Rubber sleeve (for fan motor & compressor)
Electric heater - -
Remote control Wireless remote control
Operation
Room temperature control Microcomputer thermostat
control
Operation display RUN: Green , TIMER: Yellow
Compressor overheat protection, Overcurrent protection,
Safety equipments Frost protection, Serial signal error protection, Indoor fan motor error protection,
Heating overload protection( High pressure control ), Cooling overload protection
Refrigerant piping size ( O.D ) mm Liquid line: φ 6.35 ( 1/4" ) Gas line: φ 9.52 ( 3/8" )
Connecting method Flare connection Flare connection
Attached length of piping m Liquid line : 0.46 / Gas line : 0.39 -
Installation
Insulation for piping Necessary ( Both sides ), independent
data
Refrigerant line (one way) length m Max.15
Vertical height diff. between O.U. and I.U. m Max.10 ( Outdoor unit is higher ) / Max.10 ( Outdoor unit is lower )
Drain hose Hose connectable ( VP16 ) Hole φ 20 x 2 pcs.
Drain pump, max lift height mm - -
Recommended breaker size A 16
L.R.A. (Locked rotor ampere) A 4.5 / 4.3 / 4.2 (220/ 230/ 240 V)
Interconnecting wires Size x Core number 1.5mm2 × 4 cores ( Including earth cable ) / Terminal block ( Screw fixing type )
IP number IPX0 IPX4
Standard accessories Mounting kit
Option parts -
Notes ( 1) The data are measured at the following conditions. The pipe length is 5m.
Item Indoor air temperature Outdoor air temperature
Standards
Operation DB WB DB WB
Cooling 27℃ 19℃ 35℃ 24℃ ISO5151-T1
Heating 20℃ - 7℃ 6℃ ISO5151-H1
Heating (H2) 20℃ - 2℃ 1℃ ISO5151-H2
(2) This air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient
conditions.
(4) Select the breaker size according to the own national standard.
RWA000Z275 B
- 4-
'20 • SRK-T-320
Model SRK45ZSP-W
Model SRK45ZSP-W
Item Indoor unit SRK45ZSP-W Outdoor unit SRC45ZSP-W
Power source 1 Phase, 220 - 240V, 50Hz
Nominal cooling capacity (range) kW 4.5 ( 1.3 (Min.) - 4.8 (Max.))
Nominal heating capacity (range) kW 5.0 ( 1.2 (Min.) - 5.8 (Max.))
Heating capacity (H2) kW -
Cooling 1.350 ( 0.29 - 1.71 )
Power consumption Heating 1.360 ( 0.27 - 1.84 )
kW
Heating (H2) -
Max power consumption 2.68
Cooling 6.3 / 6.1 / 5.8 (220/ 230/ 240 V)
Running current
Heating A 6.4 / 6.1 / 5.8 (220/ 230/ 240 V)
Operation Inrush current, max current 6.4 / 6.1 / 5.8 (220/ 230/ 240 V) Max. 14.5
data Cooling 97
Power factor %
Heating 97
EER Cooling 3.33
Heating 3.68
COP
Heating (H2) -
Cooling 56 63
Sound power level
Heating 62 64
Cooling dB(A) Hi: 44 Me: 39 Lo: 24 51
Sound pressure level
Heating Hi: 48 Me: 41 Lo: 30 51
Silent mode sound pressure level - -
Exterior dimensions (Height x Width x Depth) mm 267 x 783 x 210 595 x 780(+62) x 290
Exterior appearance Fine snow Stucco white
(Equivalent color) Munsell : ( 8.0Y 9.3/0.1 ), RAL : 9003 Munsell : ( 4.2Y 7.5/1.1 ), RAL : 7044
Net weight kg 7.5 36.0
Compressor type & Quantity - 9RS102XDA21( Rotary type ) x 1
Compressor motor (Starting method) kW - 1.50 ( Inverter driven )
Refrigerant oil (Amount, type) ℓ - 0.32 ( FW50S )
Refrigerant (Type, amount, pre-charge length) kg R32 1.10 in outdoor unit (Incl. the amount for the piping of 15m )
Heat exchanger Louver fins & inner grooved tubing M fins & inner grooved tubing
Refrigerant control Capillary tubes + Electronic expansion valve
Fan type & Quantity Tangential fan x 1 Propeller fan x 1
Fan motor (Starting method) W 30 × 1 (Direct drive) 24 × 1 (Direct drive)
Cooling Hi: 9.0 Me: 7.2 Lo: 3.8 35.6
Air flow m3/min
Heating Hi: 12.0 Me: 9.2 Lo: 6.2 33.4
Available external static pressure Pa 0 0
Outside air intake Not possible -
Air filter, Quality / Quantity Polypropylene net ( Washable ) -
Shock & vibration absorber Rubber sleeve (for fan motor) Rubber sleeve (for fan motor & compressor)
Electric heater - -
Remote control Wireless remote control
Operation
Room temperature control Microcomputer thermostat
control
Operation display RUN: Green , TIMER: Yellow
Compressor overheat protection, Overcurrent protection,
Safety equipments Frost protection, Serial signal error protection, Indoor fan motor error protection,
Heating overload protection( High pressure control ), Cooling overload protection
Refrigerant piping size ( O.D ) mm Liquid line: φ 6.35 ( 1/4" ) Gas line: φ 12.7 ( 1/2” )
Connecting method Flare connection Flare connection
Attached length of piping m Liquid line : 0.46 / Gas line : 0.39 -
Installation
Insulation for piping Necessary ( Both sides ), independent
data
Refrigerant line (one way) length m Max.25
Vertical height diff. between O.U. and I.U. m Max.15 ( Outdoor unit is higher ) / Max.15 ( Outdoor unit is lower )
Drain hose Hose connectable ( VP16 ) Hole φ 20 x 2 pcs.
Drain pump, max lift height mm - -
Recommended breaker size A 20
L.R.A. (Locked rotor ampere) A 6.4 / 6.1 / 5.8 (220/ 230/ 240 V)
Interconnecting wires Size x Core number 1.5mm2 × 4 cores ( Including earth cable ) / Terminal block ( Screw fixing type )
IP number IPX0 IPX4
Standard accessories Mounting kit
Option parts -
Notes ( 1) The data are measured at the following conditions. The pipe length is 5m.
Item Indoor air temperature Outdoor air temperature
Standards
Operation DB WB DB WB
Cooling 27℃ 19℃ 35℃ 24℃ ISO5151-T1
Heating 20℃ - 7℃ 6℃ ISO5151-H1
Heating (H2) 20℃ - 2℃ 1℃ ISO5151-H2
(2) This air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient
conditions.
(4) Select the breaker size according to the own national standard.
RWA000Z275 B
- 5-
'20 • SRK-T-320
Model SRK50ZSP-W
Model SRK50ZSP-W
Item Indoor unit SRK50ZSP-W Outdoor unit SRC50ZSP-W
Power source 1 Phase, 220 - 240V, 50Hz
Nominal cooling capacity (range) kW 5.0 ( 1.3 (Min.) - 5.2 (Max.))
Nominal heating capacity (range) kW 5.6 ( 1.2 (Min.) - 5.8 (Max.))
Heating capacity (H2) kW -
Cooling 1.740 ( 0.29 - 1.86 )
Power consumption Heating 1.660 ( 0.27 - 1.84 )
kW
Heating (H2) -
Max power consumption 2.68
Cooling 7.9 / 7.6 / 7.3 (220/ 230/ 240 V)
Running current
Heating A 7.6 / 7.3 / 7.0 (220/ 230/ 240 V)
Operation Inrush current, max current 7.9 / 7.6 / 7.3 (220/ 230/ 240 V) Max. 14.5
data Cooling 99
Power factor %
Heating 99
EER Cooling 2.87
Heating 3.37
COP
Heating (H2) -
Cooling 59 65
Sound power level
Heating 63 66
Cooling dB(A) Hi: 46 Me: 39 Lo: 24 52
Sound pressure level
Heating Hi: 48 Me: 41 Lo: 30 52
Silent mode sound pressure level - -
Exterior dimensions (Height x Width x Depth) mm 267 x 783 x 210 595 x 780(+62) x 290
Exterior appearance Fine snow Stucco white
(Equivalent color) Munsell : ( 8.0Y 9.3/0.1 ), RAL : 9003 Munsell : ( 4.2Y 7.5/1.1 ), RAL : 7044
Net weight kg 7.5 36.0
Compressor type & Quantity - 9RS102XDA21( Rotary type ) x 1
Compressor motor (Starting method) kW - 1.50 ( Inverter driven )
Refrigerant oil (Amount, type) ℓ - 0.32 ( FW50S )
Refrigerant (Type, amount, pre-charge length) kg R32 1.10 in outdoor unit (Incl. the amount for the piping of 15m )
Heat exchanger Louver fins & inner grooved tubing M fins & inner grooved tubing
Refrigerant control Capillary tubes + Electronic expansion valve
Fan type & Quantity Tangential fan x 1 Propeller fan x 1
Fan motor (Starting method) W 30 × 1 (Direct drive) 24 × 1 (Direct drive)
Cooling Hi: 9.9 Me: 7.2 Lo: 3.8 37.7
Air flow m3/min
Heating Hi: 12.0 Me: 9.2 Lo: 6.2 35.6
Available external static pressure Pa 0 0
Outside air intake Not possible -
Air filter, Quality / Quantity Polypropylene net ( Washable ) -
Shock & vibration absorber Rubber sleeve (for fan motor) Rubber sleeve (for fan motor & compressor)
Electric heater - -
Remote control Wireless remote control
Operation
Room temperature control Microcomputer thermostat
control
Operation display RUN: Green , TIMER: Yellow
Compressor overheat protection, Overcurrent protection,
Safety equipments Frost protection, Serial signal error protection, Indoor fan motor error protection,
Heating overload protection( High pressure control ), Cooling overload protection
Refrigerant piping size ( O.D ) mm Liquid line: φ 6.35 ( 1/4" ) Gas line: φ 12.7 ( 1/2” )
Connecting method Flare connection Flare connection
Attached length of piping m Liquid line : 0.46 / Gas line : 0.39 -
Installation
Insulation for piping Necessary ( Both sides ), independent
data
Refrigerant line (one way) length m Max.25
Vertical height diff. between O.U. and I.U. m Max.15 ( Outdoor unit is higher ) / Max.15 ( Outdoor unit is lower )
Drain hose Hose connectable ( VP16 ) Hole φ 20 x 2 pcs.
Drain pump, max lift height mm - -
Recommended breaker size A 20
L.R.A. (Locked rotor ampere) A 7.9 / 7.6 / 7.3 (220/ 230/ 240 V)
Interconnecting wires Size x Core number 1.5mm2 × 4 cores ( Including earth cable ) / Terminal block ( Screw fixing type )
IP number IPX0 IPX4
Standard accessories Mounting kit
Option parts -
Notes ( 1) The data are measured at the following conditions. The pipe length is 5m.
Item Indoor air temperature Outdoor air temperature
Standards
Operation DB WB DB WB
Cooling 27℃ 19℃ 35℃ 24℃ ISO5151-T1
Heating 20℃ - 7℃ 6℃ ISO5151-H1
Heating (H2) 20℃ - 2℃ 1℃ ISO5151-H2
(2) This air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient
conditions.
(4) Select the breaker size according to the own national standard.
RWA000Z275 C
- 6-
'20 • SRK-T-320
Material
Packing Foam
Gross Alumi-
parts Paper poly- Plastic Steel Wood Glass Others
weight nium
weight styrene
Model
SRK25ZSP-W 9.0 0.94 0.64 0.24 0.06 0.00 0.00 0.00 0.00 0.00
SRK35ZSP-W 9.0 0.94 0.64 0.24 0.06 0.00 0.00 0.00 0.00 0.00
Indoor
SRK45ZSP-W 9.5 0.94 0.64 0.24 0.06 0.00 0.00 0.00 0.00 0.00
SRK50ZSP-W 9.5 0.94 0.64 0.24 0.06 0.00 0.00 0.00 0.00 0.00
SRC25ZSP-W 28.0 1.64 1.36 0.24 0.04 0.00 0.00 0.00 0.00 0.00
SRC35ZSP-W 30.0 1.64 1.36 0.24 0.04 0.00 0.00 0.00 0.00 0.00
Outdoor
SRC45ZSP-W 38.0 2.13 1.78 0.27 0.08 0.00 0.00 0.00 0.00 0.00
SRC50ZSP-W 38.0 2.13 1.78 0.27 0.08 0.00 0.00 0.00 0.00 0.00
- 7-
25 60 60 39
Symbol Content
G G SRK25,35 φ9.52(3/8")
(Flare)
A Gas piping
SRK45,50 φ12.7(1/2")
(Flare)
B Liquid piping φ6.35(1/4")
(Flare)
(1) Indoor units
45
45
C Hole on wall for right rear piping (φ65)
D Hole on wall for left rear piping (φ65)
E Drain hose VP16
F Outlet for wiring
783 210 3 G Outlet for piping(on both side)
267
G
2. EXTERIOR DIMENSIONS
55
-
16
Outlet for downward piping Terminal block 45
F
8-
(Refer to the top view)
Installation board Wireless remote control
Models SRK25ZSP-W, 35ZSP-W, 45ZSP-W, 50ZSP-W
12.3
60 17
44.6
Note(1)The model name label is attached
on the underside of the indoor unit.
190
247.3
47
47
Unit:mm
6.9
D 55 E B A 69 C
443.5
511.5
15(Service space)
546
Space for installation and service when viewing from the front
RLC000Z106
'20 • SRK-T-320
Notes
Symbol Content (1)The unit must not be surrounded by walls on the four sides.
A Service valve connection(gas side) φ9.52(3/8")
(Flare) (2)The unit must be fixed with anchor bolts.
B Service valve connection(liquid side) φ6.35(1/4")
(Flare) An anchor bolt must not protrude more than 15mm.
(3)If the unit is installed in the location where there is a possibility of strong winds,
C Pipe/cable draw-out hole
place the unit such that the direction of air from the outlet gets perpendicular to
D Drain discharge hole φ20 × 2 places
the wind direction.
E Anchor bolt hole M10-12 × 4 places (4)Leave 200mm or more space above the unit.
(5)The wall height on the outlet side should be 1200mm or less.
(2) Outdoor units
(6)The model name label is attached on the lower right corner of the front panel.
※1
Center of gravity
40
14.6 322 12
E D E
16.8
2-R
50
Inlet L3
Models SRC25ZSP-W, 35ZSP-W
L2 L4
275
336
( Service
space )
304.4
Inlet
※3
135
(※5)
Dimensions
※1 ※2 ※3 ※4 ※5 Outlet L1
Model
12
-
15.7
2-12X16
14.8
120.5 Slot hole (※4) SRC25ZSP-W 200 240 115 109.5 130.7
9-
74.5 480 90.5 20.2
645 57.2 SRC35ZSP-W 215 240 140 124.5 155.7
Installation space(mm)
L1 280 or more
L2 100 or more
L3 80 or more
L4 250 or more
Terminal block
540
Unit:mm
B
20°
43.2
20°
※2
16.5
86.3
A
RCW000Z007
'20 • SRK-T-320
Notes
Symbol Content (1)The unit must not be surrounded by walls on the four sides.
A Service valve connection(gas side) φ12.7(1/2")
(Flare) (2)The unit must be fixed with anchor bolts.
B Service valve connection(liquid side) φ6.35(1/4")
(Flare) An anchor bolt must not protrude more than 15mm.
(3)If the unit is installed in the location where there is a possibility of strong winds,
C Pipe/cable draw-out hole
place the unit such that the direction of air from the outlet gets perpendicular to
D Drain discharge hole φ20 × 2 places
the wind direction.
E Anchor bolt hole M10-12 × 4 places (4)Leave 200mm or more space above the unit.
(5)The wall height on the outlet side should be 1200mm or less.
Center of gravity
(6)The model name label is attached on the right side of the unit.
270
50.6
14.6 390.6 12
E D E
24.3
2-R
63.4
L3
Models SRC45ZSP-W, 50ZSP-W
Inlet
L2 L4
290
( Service
space )
312.5
351.6
Inlet
145
(161.4)
Outlet L1
-
20
69.4
390.6
14.8
16.4
2-12X16
10 -
Slot hole (111.6)
111.6 510 158.4 17.9
780 61.9 Installation space(mm)
L1 280 or more
L2 100 or more
L3 80 or more
Terminal block L4 250 or more
595
B Unit:mm
40°
42.5
40°
275
15.8
97.7
A
RCV000Z038
'20 • SRK-T-320
'20 • SRK-T-320
Unit: mm
150
60 17
- 11 -
FLAP INDOOR
MOTOR FAN MOTOR Meaning of marks
M M Item Description
CNE Connector
BOX, CNF
5
CONTROL CNG
CNM
(1) Indoor units
CNU
RED
BLACK
WHITE
YELLOW
BLUE
CNM 1 3 4 5 6
CNU G YELLOW/GREEN
DIODE
STACK
S/N WHITE
VARISTOR
U
3. ELECTRICAL WIRING
FUSE L BLACK
250V 3.15A
TO HEAT EXCHANGER
-
PCB ASSY
J RED
12 -
Models SRK25ZSP-W, 35ZSP-W, 45ZSP-W, 50ZSP-W
BLACK
WHITE
RED
YELLOW/GREEN
1 2/N 3
6
2
2
2
TERMINAL
BLOCK
DISPLAY
t°
WIRELESS
R-AMP
BACK UP SW
ROOM TEMPERATURE.
SENSOR
HEAT EXCHANGER
TEMPERATURE SENSOR t°
HUMIDITY
SENSOR
TO OUTDOOR UNIT
RLC000Z107
'20 • SRK-T-320
Power source
1 Phase
220-240V 50Hz (YELLOW)
(ORANGE) REACTOR
3 PCB ASSY
(2) Outdoor units
T1 T2 POWER
F7 t° TRANSISTOR
TERMINAL F2 U (RED)
T 250V E 15A (BLACK) R.IN U
BLOCK P
TB1 NOISE + + 250V 20A NU V V (WHITE) M
L 1 (WHITE) S.IN FILTER NV 3~
NW W W (BLACK) COMPRESSOR
N 2 MOTOR
(RED) C-2 F3 T 1A L 250V
3 (YELLOW/ PAM
F1
Models SRC25ZSP-W, 35ZSP-W
250V 2A
(YELLOW/ (YELLOW/
GREEN) 250V 10A FAN MOTOR
GREEN) G2 SWITCHING POWER
4 CIRCUIT
CN20S CNTH CNEEV
TO INDOOR UNIT 2 2 2 2
-
2
POWER CABLE 1 N
SIGNAL WIRE 3 M
13 -
[ EARTH WIRE ] Meaning of marks
Item Description
CN20S Connector
CNEEV
CNFAN
CNTH
RWC000Z324
'20 • SRK-T-320
Power source
1 Phase
220-240V 50Hz
220V 60Hz
PCB ASSY PCB1
3
DIODE POWER
STACK1 T1 (YE) (YE) T2
F4 L1 TRANSISTOR
(BK) R.IN ~ +
250V 20A NOISE T11 (BL) (BL) T12 U (RD)
FILTER L2 P U
(WH) S.IN
+ + + V (WH) MS
~ - V
(RD) C-2 3~
F8 W (BK)
W
N
250V 20A CM
(BK)
L 1 (YG) G2
~ - CNFAN M
(WH)
N 2
FMo
3
(YG) (RD)
CN20S CNTH(BK) CNEEV(WH)
-
4
14 -
TO INDOOR UNIT 2 2 2 2
2
POWER CABLE 1 N M
t゜
t゜
t゜
SIGNAL WIRE 3 20S Meaning of marks
TH1 TH2 TH3 EEV
[ EARTH WIRE ] Item Description
20S 4-way valve(coil)
CN20S Connector
CNEEV
CNFAN
Power cable, indoor-outdoor connecting wires Color marks CNTH
MAX running current Power cable Power cable length Connecting cable Mark Color CM Compressor motor
Model name
(A) wire size x number* (m) wire size x number* BK Black EEV Electric expansion valve(coil)
BL Blue FMo Fan motor
SRC45, 50ZSP-W 14.5 2.5mm 2x 3 17 1.5mm 2x 4
RD Red L1,2 Reactor
WH White TH1 Heat exchanger temperature sensor
* The wire numbers include Earth wire(Yellow/Green). YE Yellow TH2 Outdoor air temperature sensor
Switchgear or circuit breaker capacity should be chosen according to national or regional electricity
regulations. YG Yellow/Green TH3 Discharge pipe temperature sensor
The power cable specifications are based on the assumption that a metal or plastic conduit is used
with no more than three cables contained in a conduit and a voltage drop is 2%. For an installation
falling outside of these conditions, please follow the national or regional electricity regulations.
RWC000Z325
A
'20 • SRK-T-320
'20 • SRK-T-320
4. NOISE LEVEL
(1) Sound power level
Model SRK25ZSP-W
(Indoor unit)
Model SRK25ZSP-W Condition ISO5151 T1/H1
Noise Cooling 57 dB(A) MODE Rated capacity value (Hi)
level Heating 57 dB(A)
60.0
Sound power level (dB)
50.0
40.0
30.0
20.0
10.0
63 125 250 500 1000 2000 4000 8000
Mid octave band frequency (Hz)
(Outdoor unit)
Model SRC25ZSP-W
Noise Cooling 57 dB(A)
level Heating 56 dB(A)
× ...... Cooling Heating
70.0
60.0
Sound power level (dB)
50.0
40.0
30.0
20.0
10.0
63 125 250 500 1000 2000 4000 8000
Mid octave band frequency (Hz)
- 15 -
'20 • SRK-T-320
Model SRK35ZSP-W
(Indoor unit)
Model SRK35ZSP-W Condition ISO5151 T1/H1
Noise Cooling 58 dB(A) MODE Rated capacity value (Hi)
level Heating 58 dB(A)
60.0
Sound power level (dB)
50.0
40.0
30.0
20.0
10.0
63 125 250 500 1000 2000 4000 8000
Mid octave band frequency (Hz)
(Outdoor unit)
Model SRC35ZSP-W
Noise Cooling 59 dB(A)
level Heating 60 dB(A)
× ...... Cooling Heating
70.0
60.0
Sound power level (dB)
50.0
40.0
30.0
20.0
10.0
63 125 250 500 1000 2000 4000 8000
Mid octave band frequency (Hz)
- 16 -
'20 • SRK-T-320
Model SRK45ZSP-W
(Indoor unit)
Model SRK45ZSP-W Condition ISO5151 T1/H1
Noise Cooling 56 dB(A) MODE Rated capacity value (Hi)
level Heating 62 dB(A)
60.0
Sound power level (dB)
50.0
40.0
30.0
20.0
10.0
63 125 250 500 1000 2000 4000 8000
Mid octave band frequency (Hz)
(Outdoor unit)
Model SRC45ZSP-W
Noise Cooling 63 dB(A)
level Heating 64 dB(A)
× ...... Cooling Heating
80.0
70.0
Sound power level (dB)
60.0
50.0
40.0
30.0
20.0
63 125 250 500 1000 2000 4000 8000
Mid octave band frequency (Hz)
- 17 -
'20 • SRK-T-320
Model SRK50ZSP-W
(Indoor unit)
Model SRK50ZSP-W Condition ISO5151 T1/H1
Noise Cooling 59 dB(A) MODE Rated capacity value (Hi)
level Heating 63 dB(A)
60.0
Sound power level (dB)
50.0
40.0
30.0
20.0
10.0
63 125 250 500 1000 2000 4000 8000
Mid octave band frequency (Hz)
(Outdoor unit)
Model SRC50ZSP-W
Noise Cooling 65 dB(A)
level Heating 66 dB(A)
× ...... Cooling Heating
80.0
70.0
Sound power level (dB)
60.0
50.0
40.0
30.0
20.0
63 125 250 500 1000 2000 4000 8000
Mid octave band frequency (Hz)
- 18 -
'20 • SRK-T-320
60 60
Mike position: at highest
N60 noise level in position as mentioned below
Sound pressure level (dB)
N50
40 40
N40
30 30
N30
20 20
N20
10 10
63 125 250 500 1000 2000 4000 8000
Mid octave band frequency (Hz)
(Outdoor unit)
Model SRC25ZSP-W ◦ Mike position: at highest noise level in position as
mentioned below
Noise Cooling 47 dB(A)
Distance from front side 1m
level Heating 45 dB(A)
× ...... Cooling Heating
70 70
N70
60 60
N60
Sound pressure level (dB)
50 50
(Standard 2×10-5Pa)
N50
40 40
N40
30 30
N30
20 20
N20
10 10
63 125 250 500 1000 2000 4000 8000
Mid octave band frequency (Hz)
- 19 -
'20 • SRK-T-320
60 60
Mike position: at highest
N60 noise level in position as mentioned below
Distance from front side 1m
Sound pressure level (dB)
50 50
(Standard 2×10-5Pa)
N50
40 40
N40
30 30
N30
20 20
N20
10 10
63 125 250 500 1000 2000 4000 8000
Mid octave band frequency (Hz)
(Outdoor unit)
Model SRC35ZSP-W ◦ Mike position: at highest noise level in position as
mentioned below
Noise Cooling 48 dB(A)
Distance from front side 1m
level Heating 48 dB(A)
× ...... Cooling Heating
70 70
N70
60 60
N60
Sound pressure level (dB)
50 50
(Standard 2×10-5Pa)
N50
40 40
N40
30 30
N30
20 20
N20
10 10
63 125 250 500 1000 2000 4000 8000
Mid octave band frequency (Hz)
- 20 -
'20 • SRK-T-320
60 60
Mike position: at highest
N60 noise level in position as mentioned below
Distance from front side 1m
Sound pressure level (dB)
50 50
(Standard 2×10-5Pa)
N50
40 40
N40
30 30
N30
20 20
N20
10 10
63 125 250 500 1000 2000 4000 8000
Mid octave band frequency (Hz)
(Outdoor unit)
Model SRC45ZSP-W ◦ Mike position: at highest noise level in position as
mentioned below
Noise Cooling 51 dB(A)
Distance from front side 1m
level Heating 51 dB(A)
× ...... Cooling Heating
70 70
N70
60 60
N60
Sound pressure level (dB)
50 50
(Standard 2×10-5Pa)
N50
40 40
N40
30 30
N30
20 20
N20
10 10
63 125 250 500 1000 2000 4000 8000
Mid octave band frequency (Hz)
- 21 -
'20 • SRK-T-320
60 60
Mike position: at highest
N60 noise level in position as mentioned below
Distance from front side 1m
Sound pressure level (dB)
50 50
(Standard 2×10-5Pa)
N50
40 40
N40
30 30
N30
20 20
N20
10 10
63 125 250 500 1000 2000 4000 8000
Mid octave band frequency (Hz)
(Outdoor unit)
Model SRC50ZSP-W ◦ Mike position: at highest noise level in position as
mentioned below
Noise Cooling 52 dB(A)
Distance from front side 1m
level Heating 52 dB(A)
× ...... Cooling Heating
70 70
N70
60 60
N60
Sound pressure level (dB)
50 50
(Standard 2×10-5Pa)
N50
40 40
N40
30 30
N30
20 20
N20
10 10
63 125 250 500 1000 2000 4000 8000
Mid octave band frequency (Hz)
- 22 -
'20 • SRK-T-320
MODE Me
(Indoor unit) Mike position
Model SRK25ZSP-W 1m
Noise Cooling 34 dB(A) 0.8m
Unit
level Heating 34 dB(A) Mike position
(Center & low points)
60 60
N60
Mike position: at highest noise level in position as mentioned below
50 50
Distance from front side 1m
Sound pressure level (dB)
N50
(Standard 2×10-5Pa)
40 40
N40
30 30
N30
20 20
N20
10 10
0 0
63 125 250 500 1000 2000 4000 8000
Mid octave band frequency (Hz)
(Indoor unit) MODE Lo
Model SRK25ZSP-W Mike position
Noise Cooling 23 dB(A) 1m
level Heating 26 dB(A) 0.8m
Unit
Mike position
(Center & low points)
60 60
N60
40 40
N40
30 30
N30
20 20
N20
10 10
0 0
63 125 250 500 1000 2000 4000 8000
Mid octave band frequency (Hz)
- 23 -
'20 • SRK-T-320
60 60
N60
Mike position: at highest noise level in position as mentioned below
50 50
Distance from front side 1m
Sound pressure level (dB)
N50
(Standard 2×10-5Pa)
40 40
N40
30 30
N30
20 20
N20
10 10
0 0
63 125 250 500 1000 2000 4000 8000
Mid octave band frequency (Hz)
(Indoor unit) MODE Lo
Model SRK35ZSP-W Mike position
Noise Cooling 23 dB(A) 1m
level Heating 28 dB(A) 0.8m
Unit
Mike position
(Center & low points)
× ...... Cooling Heating
70 70
N70
60 60
N60
40 40
N40
30 30
N30
20 20
N20
10 10
0 0
63 125 250 500 1000 2000 4000 8000
Mid octave band frequency (Hz)
- 24 -
'20 • SRK-T-320
60 60
N60
Mike position: at highest noise level in position as mentioned below
50 50
Distance from front side 1m
Sound pressure level (dB)
N50
(Standard 2×10-5Pa)
40 40
N40
30 30
N30
20 20
N20
10 10
0 0
63 125 250 500 1000 2000 4000 8000
Mid octave band frequency (Hz)
(Indoor unit) MODE Lo
Model SRK45ZSP-W, 50ZSP-W Mike position
Noise Cooling 24 dB(A) 1m
level Heating 30 dB(A) 0.8m
Unit
Mike position
(Center & low points)
60 60
N60
40 40
N40
30 30
N30
20 20
N20
10 10
0 0
63 125 250 500 1000 2000 4000 8000
Mid octave band frequency (Hz)
- 25 -
'20 • SRK-T-320
5. PIPING SYSTEM
Models SRK25ZSP-W, 35ZSP-W
Outdoor air
temperature
sensor
Discharge pipe
Heat temperature sensor
Room exchanger
temperature temperature
sensor sensor
Heat
exchanger
Heat
exchanger
temperature
sensor
Strainer
Capillary tube SRK35ZSP-W
only
Outdoor air
temperature
sensor
Discharge pipe
Heat temperature sensor
Room exchanger
temperature temperature
sensor sensor
4-way valve
Heat
exchanger
temperature
sensor
- 26 -
'18'20 • SRK-T-320
• LMK-DB-257
1.3
1.2
Coefficient of cooling &
relation to temperature
Cooling
heating capacity in
1.1
1.0
Heating
0.9
0.8
0.7
0.6
Applicable range
Cooling operation
46
Outdoor air DB
temperature
40
°C DB
35
30
25 26
20 24
0
-5 Depends on installed situation
-10
-15
14 16 18 20 22
Heating operation
30
25
20
15
-10 -5 0 5 10 15
ISO-H1 Standard Condition
Outdoor air WB temperature °C WB
- 27
23 -
'18'20
• LMK-DB-257
• SRK-T-320
(2) Correction of cooling and heating capacity in relation to one way length of refrigerant piping
Adjustment coefficient 0.95 0.95 0.94 0.93 0.91 0.88 0.86 0.87 0.92 1.00
3.2 ≒ 3.1kW
SRK35ZSP-W
- 24 -
28
'20 • SRK-T-320
7. CAPACITY TABLES
Model SRK25ZSP-W Cooling Mode (kW) Heating Mode (HC) (kW)
Indoor air temperature Outdoor
Outdoor air Indoor air temperature
air 21 ℃DB 23 ℃DB 26 ℃DB 27 ℃DB 28 ℃DB 31 ℃DB 33 ℃DB Air flow temperature
Air flow temperature
14 ℃WB 16 ℃WB 18 ℃WB 19 ℃WB 20 ℃WB 22 ℃WB 24 ℃WB ℃WB 16℃ DB 18℃ DB 20℃ DB 22℃ DB 24℃ DB
℃DB
TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC -15 1.72 1.69 1.65 1.61 1.58
10 2.82 2.47 2.95 2.43 3.06 2.56 3.11 2.53 3.16 2.50 3.26 2.61 3.34 2.54 -10 1.95 1.91 1.89 1.84 1.80
12 2.77 2.45 2.90 2.41 3.01 2.54 3.07 2.52 3.12 2.48 3.22 2.60 3.31 2.53 -5 2.11 2.08 2.04 2.02 1.98
14 2.71 2.43 2.85 2.39 2.97 2.52 3.03 2.50 3.08 2.47 3.18 2.59 3.28 2.52 Hi 0 2.21 2.18 2.14 2.12 2.09
16 2.66 2.40 2.80 2.37 2.92 2.50 2.98 2.48 3.04 2.45 3.15 2.57 3.24 2.51 10.0 5 2.82 2.79 2.77 2.72 2.68
18 2.60 2.38 2.74 2.34 2.88 2.49 2.94 2.46 2.99 2.44 3.11 2.56 3.20 2.50 (m3/min) 6 2.87 2.83 2.80 2.76 2.73
20 2.55 2.35 2.68 2.32 2.83 2.47 2.89 2.45 2.95 2.42 3.07 2.54 3.17 2.49 10 3.04 3.02 3.00 2.96 2.93
Hi 22 2.49 2.32 2.63 2.30 2.78 2.44 2.84 2.43 2.90 2.40 3.02 2.53 3.13 2.48 15 3.31 3.28 3.26 3.23 3.20
10.1 24 2.43 2.29 2.57 2.27 2.72 2.42 2.80 2.41 2.85 2.39 2.98 2.52 3.08 2.46 20 3.56 3.53 3.52 3.48 3.45
3
(m /min) 26 2.37 2.25 2.51 2.24 2.67 2.40 2.74 2.39 2.80 2.37 2.93 2.50 3.04 2.45
28 2.31 2.19 2.44 2.22 2.61 2.38 2.69 2.37 2.75 2.35 2.89 2.48 3.00 2.44
30 2.24 2.13 2.38 2.19 2.56 2.36 2.64 2.35 2.70 2.33 2.84 2.47 2.95 2.40
32 2.18 2.07 2.31 2.16 2.50 2.34 2.58 2.33 2.64 2.31 2.79 2.45 2.90 2.39
34 2.11 2.00 2.25 2.13 2.44 2.31 2.53 2.31 2.59 2.29 2.74 2.42 2.85 2.38
35 2.08 1.97 2.21 2.10 2.41 2.29 2.50 2.30 2.56 2.28 2.71 2.41 2.83 2.37
36 2.04 1.94 2.18 2.07 2.38 2.26 2.47 2.29 2.53 2.27 2.69 2.40 2.80 2.36
38 1.97 1.87 2.11 2.00 2.32 2.20 2.41 2.26 2.47 2.24 2.63 2.39 2.75 2.35
40 1.90 1.81 2.03 1.93 2.25 2.14 2.35 2.23 2.41 2.22 2.58 2.37 2.70 2.33
43 1.79 1.70 1.92 1.83 2.15 2.04 2.26 2.15 2.32 2.19 2.49 2.34 2.61 2.31
46 1.68 1.59 1.81 1.72 2.05 1.95 2.16 2.05 2.22 2.11 2.40 2.28 2.53 2.28
- 29 -
'20 • SRK-T-320
- 30 -
RLC012A105A
SELECTING OF INSTA
After getting customer’s approval, select in
Model DXK09, 12, 15, 18Z6-W / SRK25, 35, 45, 50ZSP-W / LMK09, 12, 15Z6-W
INSTALLATION MANUAL R32 REFRIGERANT USED 1. Indoor unit
• Where there is no obstruction to the air
distributed.
SAFETY PRECAUTIONS • A solid place where the unit or the wall w
• A place where there will be enough spac
• Before installation, read the “SAFETY PRECAUTIONS” carefully and strictly follow it during the installa- • Be sure to conrm no operation problem on the equipment after completing the installation. If unusual can be secured.)
tion work in order to protect yourself. noise can be heard during the test run, consult the dealer. • Where it is easy to conduct wiring and pi
• The precautionary items mentioned below are distinguished into two levels, WARNING and CAUTION . • Be sure to explain the operating methods as well as the maintenance methods of this equipment to the
• A place where unit is not directly expose
WARNING Indicates a potentially hazardous situation which, if not avoided, can result in serious con- user according to the user’s manual. • A place where it can be easily drained.
sequences such as death or severe injury. • Be sure to keep the installation manual together with user’s manual at a place where it is easily accessi-
• A place separated at least 1 m away fro
CAUTION Indicates a potentially hazardous situation which, if not avoided, can result in personal in- ble to the user any time. Moreover, ask the user to hand the manuals to a new user, whenever required.
jury or property damage. images and sounds.)
Both mention the important items to protect your health and safety. Therefore, strictly follow them by any means. • A place where this unit is not affected by
• Avoid installing this unit in place where t
• A place where there is no electric equip
WARNING • Install the indoor unit on the wall where t
180 cm.
• Be sure to use only for residential purpose. • Make sure that no air enters the refrigerant circuit Circuit breaker should be able to disconnect all poles under over
If this unit is installed in inferior environment such as machine when the unit is installed and removed. current. Absence of appropriate breakers can cause electric
8. APPLICATION DATA
2. Remote control
shop, vehicle (like ship), warehouse, etc., it can malfunction. If air enters the refrigerant circuit, the pressure in the refrigerant shock, personal injury or property damage. • A place where the air-conditioner can rec
• Installation must be carried out by the qualified circuit will become too high, which can cause burst and personal • Be sure to switch off the power source in the • A place where it is not affected by the TV
installer completely in accordance with the instal- injury. event of installation, maintenance or service. • Do not place where it is exposed to direc
lation manual. • Be sure to use the prescribed pipes, are nuts and If the power source is not switched off, there is a risk of electric
Installation by non qualified person or incorrect installation can tools for R32. shock, unit failure or personal injury. 3. Outdoor unit
Select the suitable installation location wh
cause serious troubles such as water leak, electric shock, re and Using existing parts (for R22 or R407C) can cause refrigerant cir- • Be sure to tighten the cables securely in terminal
• Unit will be stable, horizontal and free of
personal injury. cuit burst resulting in unit failure and personal injury. block and relieve the cables properly to prevent • There is no obstacle which can prevent
-
• Be sure to wear protective goggles and gloves • Be sure to connect both liquid and gas connecting overloading the terminal blocks. • There is enough space for service and
while performing installation work. pipes properly before operating the compressor. Loose connections or cable mountings can cause anomalous heat • Neighbours are not bothered by noise o
Models SRK25ZSP-W, 35ZSP-W, 45ZSP-W, 50ZSP-W
Improper safety measures can result in personal injury. Do not open the liquid and gas operation valves production or re. • Outlet air of the unit does not blow direc
31 -
• Use the original accessories and the specified before completing piping work, and evacuation. • Do not process, splice or modify the power cable, • Drain water can be discharged properly.
components for the installation. If the compressor is operated when connecting pipes are not or share the socket with other power plugs. • There is no risk of ammable gas leaka
Using parts other than those prescribed may cause water leak, connected and operation valves are open, air can be sucked into Improper power cable or power plug can cause re or electric shock • There are no other heat sources nearby.
electric shock, re and personal injury. the refrigerant circuit which can cause anomalous high pressure due to poor connection, insufcient insulation or over-current. • Unit is not directly exposed to rain or su
• Do not install the unit near the location where resulting in burst or personal injury. • Do not perform any change in protective device or • Unit is not directly exposed to oil mist an
• Chemical substances like ammonia (or
leakage of ammable gases can occur. • Be sure to tighten the flare nuts to specified its setup condition yourself.
acid (sulfurous acid etc.), which can har
If leaked gases accumulate around the unit, it can cause fire torque using the torque wrench. Changing protective device specifications can cause electric • Unit is not directly exposed to corrosive
resulting in property damage and personal injury. Tightening are nuts with excess torque can cause burst and re- shock, re or burst. atmosphere.
• When installing the unit in small rooms, make frigerant leakage after a long period. • Be sure to clamp the cables properly so that they • No TV set or radio receiver is placed wit
sure that refrigerant density does not exceed the • During pump down work, be sure to stop the com- do not touch any internal component of the unit. • Unit is not affected by electromagnetic
limit (Reference: ISO5149) in the event of leakage. pressor before closing operation valves and re- If cables touch any internal component, it can cause overheating and re. ments.
If refrigerant density exceeds the limit, consult the dealer and in- moving connecting pipes. • Be sure to install service cover properly. • Strong wind does not blow against the u
stall the ventilation system. If the connecting pipes are removed when the compressor is in Improper installation can cause electric shock or re due to intru- • Heavy snowfalls do not occur (If installe
Otherwise lack of oxygen can occur resulting in serious accident. operation and operation valves are open, air can be sucked into sion of dust or water. • There must be 1 meter or larger spac
• Install the unit in a location where unit will remain the refrigerant circuit which can cause anomalous high pressure • Be sure to use the prescribed power and connect- Walls surrounding the unit from 4 sides i
1200 mm or less. Refer to the following
stable, horizontal and free of any vibration trans- resulting in burst or personal injury. ing cables for electrical work.
mission. • In the event of refrigerant leakage during instal- Using improper cables can cause electric leak or re.
Unsuitable installation location can cause the unit to fall resulting lation, be sure to ventilate the working area prop- • This appliance must be connected to main power Inlet L3
in material damage and personal injury. erly. source by means of a circuit breaker or switch L2 (Service
space )
• Do not run the unit with removed panels or protections. If the refrigerant comes into contact with naked ames, poisonous with a contact separation of at least 3 mm. L4
Inlet
Touching rotating equipments, hot surfaces or high voltage parts gases will be produced. Improper electrical work can cause unit failure or personal injury.
can cause personal injury due to entrapment, burn or electric shock. • Electrical work must be carried out by the quali- • Be sure to connect the power source cable with Outlet
L1
• This unit is designed specically for R32. ed electrician, strictly in accordance with nation- power source properly.
Using any other refrigerant can cause unit failure and personal al or regional electricity regulations. Improper connection can cause intrusion of dust or water resulting
injury. Incorrect installation can cause electric shock, fire or personal in electric shock or re.
• Do not vent R32 into atmosphere. injury. NOTE
R32 is a fluorinated greenhouse gas with a Global Warming • Make sure that earth leakage breaker and circuit
Potential (GWP) = 675. breaker of appropriate capacities are installed. When more than one unit are installed sid
'20 • SRK-T-320
as a service space.
CAUTION CAUTION
• Take care when carrying the unit by hand. It can cause corrosion of heat exchanger and damage to plastic It can cause performance degradation, corrosion and damage of When more than one unit are installed in
If the unit weight is more than 20 kg, it must be carried by two or parts. components, unit malfunction and re. circuiting may not occur.
more persons. • Do not install the unit close to the equipments • Dispose of all packing materials properly.
Do not carry the unit by the plastic straps. Always use the carry that generate electromagnetic waves and/or high- Packing materials contain nails and wood which can cause per-
handle. harmonic waves. sonal injury.
• Do not install the outdoor unit in a location where Equipment such as inverters, standby generators, medical high Keep the polybag away from children to avoid the risk of suffoca- DRAIN PIPING WORK (
insects and small animals can inhabit. frequency equipments and telecommunication equipments can af- tion. Carry out drain piping work by using a drai
Insects and small animals can enter the electrical parts and cause fect the system, and cause malfunctions and breakdowns. • Do not put anything on the outdoor unit. accessories if condensed water needs to
damage resulting in fire or personal injury. Instruct the user to The system can also affect medical equipment and telecommuni- Object may fall causing property damage or personal injury. (1) Install drain elbow and drain grommet.
mission. • In the event of refrigerant leakage during instal- Using improper cables can cause electric leak or re.
Unsuitable installation location can cause the unit to fall resulting lation, be sure to ventilate the working area prop- • This appliance must be connected to main power Inlet L3
in material damage and personal injury. erly. source by means of a circuit breaker or switch L2 (Service
space )
• Do not run the unit with removed panels or protections. If the refrigerant comes into contact with naked ames, poisonous with a contact separation of at least 3 mm. L4
Inlet
Touching rotating equipments, hot surfaces or high voltage parts gases will be produced. Improper electrical work can cause unit failure or personal injury.
can cause personal injury due to entrapment, burn or electric shock. • Electrical work must be carried out by the quali- • Be sure to connect the power source cable with Outlet
L1
• This unit is designed specically for R32. ed electrician, strictly in accordance with nation- power source properly.
Using any other refrigerant can cause unit failure and personal al or regional electricity regulations. Improper connection can cause intrusion of dust or water resulting
injury. Incorrect installation can cause electric shock, fire or personal in electric shock or re.
• Do not vent R32 into atmosphere. injury. NOTE
R32 is a fluorinated greenhouse gas with a Global Warming • Make sure that earth leakage breaker and circuit
Potential (GWP) = 675. breaker of appropriate capacities are installed. When more than one unit are installed sid
as a service space.
CAUTION CAUTION
• Take care when carrying the unit by hand. It can cause corrosion of heat exchanger and damage to plastic It can cause performance degradation, corrosion and damage of When more than one unit are installed in
If the unit weight is more than 20 kg, it must be carried by two or parts. components, unit malfunction and re. circuiting may not occur.
more persons. • Do not install the unit close to the equipments • Dispose of all packing materials properly.
Do not carry the unit by the plastic straps. Always use the carry that generate electromagnetic waves and/or high- Packing materials contain nails and wood which can cause per-
handle. harmonic waves. sonal injury.
• Do not install the outdoor unit in a location where Equipment such as inverters, standby generators, medical high Keep the polybag away from children to avoid the risk of suffoca- DRAIN PIPING WORK (
insects and small animals can inhabit. frequency equipments and telecommunication equipments can af- tion. Carry out drain piping work by using a drai
Insects and small animals can enter the electrical parts and cause fect the system, and cause malfunctions and breakdowns. • Do not put anything on the outdoor unit. accessories if condensed water needs to
damage resulting in fire or personal injury. Instruct the user to The system can also affect medical equipment and telecommuni- Object may fall causing property damage or personal injury. (1) Install drain elbow and drain grommet.
keep the surroundings clean. cation equipment, and obstruct its function or cause jamming. • Do not touch the aluminum n of the outdoor unit. (2) Seal around the drain elbow and drain
• If the outdoor unit is installed at height, make sure • Do not install the unit in the locations where: Aluminium fin temperature is high during heating operation.
that there is enough space for installation, mainte- • There are heat sources nearby. Touching n can cause burn. Do not put a grom
This is a supplem
nance and service. • Unit is directly exposed to rain or sunlight. • Do not touch any refrigerant pipe with your hands
when a large amo
Insufcient space can result in personal injury due to falling from • There is any obstacle which can prevent smooth air circulation when the system is in operation.
the height. from inlet and outlet side of the unit. During operation the refrigerant pipes become extremely hot or <DXK09/12, SRK25/35, LMK09/1
• Do not install the unit near the location where • Unit is directly exposed to oil mist and steam such as kitchen. extremely cold depending on the operating condition. Touching
neighbours are bothered by noise or air generat- • Chemical substances like ammonia (organic fertilizer), calcium pipes can cause personal injury like burn (hot/cold).
ing from the unit. chloride (snow melting agent) and acid (sulfurous acid etc.), • Install isolator or disconnect switch on the power
It can affect surrounding environment and cause a claim. which can harm the unit, will generate or accumulate. source wiring in accordance with the local codes
• Do not install in the locations where unit is direct- • Drain water can not be discharged properly. and regulations.
ly exposed to corrosive gases (like sulphide gas, • TV set or radio receiver is placed within 1 m. The isolator should be locked in OFF state in accordance with
chloride gas), sea breeze or salty atmosphere. • Height above sea level is more than 1000 m. EN60204-1.
-
Standard accessories (supplied with indoor unit) Locally procured parts Tools for installation work
(a) Sleeve (1 pc.) Plus headed driver Hole core drill (65 mm in diameter) Drain grommet
(1) Installation board 1 pc. (6) Batteries [R03 (AAA, Micro) 1.5 V] 2 pcs. (b) Sealing plate (1 pc.) Knife Wrench key (Hexagon) [4 mm] Drain elbow
32 -
(c) Inclination plate (1 pc.) Saw Flaring tool set*
lters
(2) Remote control 1 pc. (7) Air-cleaning 2 pcs. (d) Putty Tape measure Gas leak detector*
(LMK model only)
(e) Connecting cable Torque wrench
holders Pipe bender
(3) Remote control holder 1 pc. (8) Filter 2 pcs. (f) Drain hose (extension hose) (14.0-62.0 N·m (1.4-6.2 kgf·m))
(LMK model only)
Piping cover Plier
(g) Gauge for projection adjustment
Tapping screws (for insulation of connection piping) Pipe cutter (Used when are is made by using
(4) (for installation board ø4 X 25 mm) 5 pcs. (9) Insulation (#486 50 X 100 t3) 1 pc.
(h) Clamp and screw (for nishing work) conventional are tool) CAUTION
Spanner wrench
(i) Anchor bolt (M10-M12) × 4 pcs. Do not use drain elbow and drain gromm
(5) Wood screws 2 pcs. Flare adjustment gauge Charge hose *
(for remote control holder ø3.5 X 16 mm) (j) Electrical tape days of sub zero temperature. (There is a
Vacuum pump* Vacuum pump adapter* drain.)
(k) Connecting pipe (Anti-reverse ow type)
Standard accessories (supplied with outdoor unit) Gauge manifold *
(l) Power cable
* Designed specically for R32 or R410A
(1) Drain grommet 1 pc. (2) Drain elbow 1 pc.
RLC012A105A_EN.indd 1
'20 • SRK-T-320
MITSUBISHI HEAVY INDUSTRIES THERMAL SYSTEMS, LTD.
RLC012A105A
SELECTING OF INSTALLATION LOCATION
After getting customer’s approval, select installation location according to following guidelines.
RK25, 35, 45, 50ZSP-W / LMK09, 12, 15Z6-W 5 cm
1. Indoor unit m 6.5 cm minimum from the ceiling
from inimum (Recommendation 8.0 cm)
the w
• Where there is no obstruction to the airow and where the cooled and heated air can be evenly all
distributed. Installation board
• A solid place where the unit or the wall will not vibrate. 10 cm
• A place where there will be enough space for servicing. (Where space mentioned on the right side m
from inimum
quipment after completing the installation. If unusual can be secured.)
the w
all
dealer. • Where it is easy to conduct wiring and piping work.
s the maintenance methods of this equipment to the • A place where unit is not directly exposed to sunlight or street light.
• A place where it can be easily drained.
th user’s manual at a place where it is easily accessi-
• A place separated at least 1 m away from the television or the radio. (To prevent interference to
hand the manuals to a new user, whenever required.
images and sounds.)
• A place where this unit is not affected by the high frequency equipment or electric equipment.
• Avoid installing this unit in place where there is much oil mist.
Sleeve
• A place where there is no electric equipment or household.
(sold separately)
• Install the indoor unit on the wall where the height from the oor to the bottom of the unit is more than
180 cm.
r should be able to disconnect all poles under over
nce of appropriate breakers can cause electric 2. Remote control
al injury or property damage. • A place where the air-conditioner can receive the signal surely during operating the remote control.
switch off the power source in the • A place where it is not affected by the TV, radio etc. Remote control
stallation, maintenance or service. • Do not place where it is exposed to direct sunlight or near heat devices such as a stove.
ource is not switched off, there is a risk of electric Remote control holder
lure or personal injury. 3. Outdoor unit
Select the suitable installation location where: Wood screws
tighten the cables securely in terminal
• Unit will be stable, horizontal and free of any vibration transmission.
relieve the cables properly to prevent • There is no obstacle which can prevent smooth air circulation from inlet and outlet side of the unit.
g the terminal blocks. • There is enough space for service and maintenance of unit.
180 cm minimum from the oor
tions or cable mountings can cause anomalous heat • Neighbours are not bothered by noise or air generating from the unit.
re.
-
• Outlet air of the unit does not blow directly to animals or plants.
cess, splice or modify the power cable, • Drain water can be discharged properly.
e socket with other power plugs. • There is no risk of ammable gas leakage.
r cable or power plug can cause re or electric shock • There are no other heat sources nearby.
33 -
• Unit is not directly exposed to rain or sunlight. The screw of the
nnection, insufcient insulation or over-current. service panel is
form any change in protective device or • Unit is not directly exposed to oil mist and steam.
tightened securely.
• Chemical substances like ammonia (organic fertilizer), calcium chloride (snow melting agent) and
ondition yourself. Service panel for
acid (sulfurous acid etc.), which can harm the unit, will not generate or accumulate.
tective device specifications can cause electric electrical parts
• Unit is not directly exposed to corrosive gases (like sulphide gas, chloride gas), sea breeze or salty
urst. atmosphere. Note as a unit designed for R32
clamp the cables properly so that they • No TV set or radio receiver is placed within 1 m. • Do not use any refrigerant other than R32. R32 will rise to pressure about 1.6 times higher than that of
h any internal component of the unit. • Unit is not affected by electromagnetic waves and/or high-harmonic waves generated by other equip- a conventional refrigerant. A cylinder containing R32 has a light blue indication mark on the top.
any internal component, it can cause overheating and re. ments. • Do not use a charge cylinder. The use of a charge cylinder will cause the refrigerant composition to
change, which results in performance degradation.
install service cover properly. • Strong wind does not blow against the unit outlet.
• In charging refrigerant, always take it out from a cylinder in the liquid phase.
llation can cause electric shock or re due to intru- • Heavy snowfalls do not occur (If installed, provide proper protection to avoid snow accumulation). • All indoor units must be models designed exclusively for R32. Check connectable indoor unit models in
water. • There must be 1 meter or larger space between the unit and the wall in at least 1 of the 4 sides. a catalog, etc. (A wrong indoor unit, if connected into the system, will impair proper system operation)
use the prescribed power and connect- Walls surrounding the unit from 4 sides is not acceptable. The wall height on the outlet side should be
Limitation of the piping length
1200 mm or less. Refer to the following gure and table for details.
for electrical work.
Model DXK09, SRK25, LMK09 DXK12, SRK35, LMK12 DXK15/18, SRK45/50, LMK15
r cables can cause electric leak or re.
nce must be connected to main power Installation space (mm) Total one way length MAX. 15 m MAX. 15 m MAX. 25 m
Inlet L3
means of a circuit breaker or switch L2 (Service L1 280 or more Vertical height difference MAX. 10 m MAX. 10 m MAX. 15 m
space )
act separation of at least 3 mm. L4 L2 100 or more
Inlet Less than 10 m : Not required Less than 15 m : Not required
trical work can cause unit failure or personal injury. L3 80 or more Additional refrigerant Not required
More than 10 m : 20 g/m More than 15 m : 20 g/m
connect the power source cable with Outlet L4 250 or more
L1
rce properly. Charging refrigerant
ection can cause intrusion of dust or water resulting (1) Charge the R32 refrigerant in liquid phase from service port with both liquid and gas operation valves
shut. Since R32 refrigerant must be charged in the liquid phase, make sure that refrigerant is dis-
ck or re. charged from the cylinder in the liquid phase all the time.
NOTE (2) When it is difcult to charge a required refrigerant amount, fully open both liquid and gas operation
valves and charge refrigerant, while running the unit in the cooling mode. When refrigerant is charged
When more than one unit are installed side by side, provide a 250 mm or wider interval between them with the unit being run, complete the charge operation within 30 minutes.
as a service space. (3) Write the additional refrigerant charge calculated from the connecting pipe length on the label attached
on the service cover.
CAUTION CAUTION
erformance degradation, corrosion and damage of When more than one unit are installed in parallel directions, provide sufcient inlet space so that short-
• Running the unit with an insufcient quantity of refrigerant for a long time can cause unit malfunction.
nit malfunction and re. circuiting may not occur.
• Do not charge more than the maximum refrigerant amount. It can cause unit malfunction.
'20 • SRK-T-320
bag away from children to avoid the risk of suffoca- DRAIN PIPING WORK (if necessary) INSTALLING REMOTE CONTROL
Carry out drain piping work by using a drain elbow and a drain grommet supplied separately as Mount the batteries
anything on the outdoor unit. accessories if condensed water needs to be drained out. (1) Slide and take out the cover of backside.
ll causing property damage or personal injury. (1) Install drain elbow and drain grommet. (2) Mount the batteries [R03 (AAA, Micro), × 2 pieces]
ch the aluminum n of the outdoor unit. (2) Seal around the drain elbow and drain grommet with putty or adequate caulking material. in the body properly.
(Fit he poles with the indication marks + & −)
n temperature is high during heating operation. (3) Set the cover again.
an cause burn. Do not put a grommet on this hole. Remote control
This is a supplementary drain hole to discharge drain water,
ch any refrigerant pipe with your hands Installing remote control holder
when a large amount of it is gathered. Wood screws
ystem is in operation. (1) Select the place where the unit can receive signals.
(2) Fix the holder to pillar or wall with wood screws. ø3.5 X 16
ion the refrigerant pipes become extremely hot or <DXK09/12, SRK25/35, LMK09/12> <DXK15/18, SRK45/50, LMK15>
e intrusion of dust or water resulting (1) Charge the R32 refrigerant in liquid phase from service port with both liquid and gas operation valves
shut. Since R32 refrigerant must be charged in the liquid phase, make sure that refrigerant is dis-
charged from the cylinder in the liquid phase all the time.
NOTE (2) When it is difcult to charge a required refrigerant amount, fully open both liquid and gas operation
valves and charge refrigerant, while running the unit in the cooling mode. When refrigerant is charged
When more than one unit are installed side by side, provide a 250 mm or wider interval between them with the unit being run, complete the charge operation within 30 minutes.
as a service space. (3) Write the additional refrigerant charge calculated from the connecting pipe length on the label attached
on the service cover.
CAUTION CAUTION
radation, corrosion and damage of When more than one unit are installed in parallel directions, provide sufcient inlet space so that short-
• Running the unit with an insufcient quantity of refrigerant for a long time can cause unit malfunction.
and re. circuiting may not occur.
• Do not charge more than the maximum refrigerant amount. It can cause unit malfunction.
materials properly.
ils and wood which can cause per-
children to avoid the risk of suffoca- DRAIN PIPING WORK (if necessary) INSTALLING REMOTE CONTROL
Carry out drain piping work by using a drain elbow and a drain grommet supplied separately as Mount the batteries
the outdoor unit. accessories if condensed water needs to be drained out. (1) Slide and take out the cover of backside.
rty damage or personal injury. (1) Install drain elbow and drain grommet. (2) Mount the batteries [R03 (AAA, Micro), × 2 pieces]
num n of the outdoor unit. (2) Seal around the drain elbow and drain grommet with putty or adequate caulking material. in the body properly.
(Fit he poles with the indication marks + & −)
is high during heating operation. (3) Set the cover again.
Do not put a grommet on this hole. Remote control
This is a supplementary drain hole to discharge drain water,
erant pipe with your hands Installing remote control holder
when a large amount of it is gathered. Wood screws
peration. (1) Select the place where the unit can receive signals.
(2) Fix the holder to pillar or wall with wood screws. ø3.5 X 16
nt pipes become extremely hot or <DXK09/12, SRK25/35, LMK09/12> <DXK15/18, SRK45/50, LMK15>
the operating condition. Touching
ry like burn (hot/cold).
nnect switch on the power HOW TO REMOVE AND INSTALL FRONT PANEL
dance with the local codes
1. Removing
(1) Remove the air inlet panel and the air lters. Latch
d in OFF state in accordance with (2) Remove the 2 screws.
(3) Remove the 3 upper latches and then front panel
can be removed.
2. Installing
(1) Cover the unit with the front panel and x 3
upper latches.
nstallation work (2) Secure the front panel with the 2 screws.
Hole core drill (65 mm in diameter) Drain grommet (3) Install the air inlet panel and the air lters.
Wrench key (Hexagon) [4 mm] Drain elbow
Flaring tool set* Drain grommet
Gas leak detector*
Drain elbow PUMP DOWN WORK
Pipe bender Drain hose For the environmental protection, be sure to pump down when relocating or disposing of the unit. Pump
(To be procured on
-
down is the method of recovering refrigerant from the indoor unit to the outdoor unit before the connecting
the installer’s part) pipes are removed from the unit. When pump down is carried out, forced cooling operation is needed.
Gauge for projection adjustment
(Used when are is made by using
conventional are tool) CAUTION Forced cooling operation
(1) Turn off the power source and turn it on again
34 -
Charge hose * Do not use drain elbow and drain grommet if there is a possibility to have several consecutive after 1 minute.
days of sub zero temperature. (There is a risk of drain water freezing inside and blocking the (2) Press the ON/OFF button continuously for at
Vacuum pump adapter* drain.) least 5 seconds. Then operation will start.
(Anti-reverse ow type)
ed specically for R32 or R410A For the detail of pump down, refer to the
installation manual of outdoor unit.
Unit ON/OFF button
Standard hole
394
44.6
6. INSTALLING INDOO
47
47
55 69
443.5 (Gas pipe)
511.5 (Liquid pipe)
546 (Drain hose) atio
Mating mark for level surface Latch (2 loc
Unit: mm
15 (Service Space)
CAUTION
Improper adjustment of the installation board can cause water leakage.
'20 • SRK-T-320
Installation board
Wall
47
47
In case of fixing the unit on Indoor unit
concrete wall, use nut anchor.
6.9
55 69
443.5 (Gas pipe)
511.5 (Liquid pipe)
546 (Drain hose) atio
Mating mark for level surface Latch (2 loc
Unit: mm
15 (Service Space)
CAUTION
Improper adjustment of the installation board can cause water leakage.
Installation board
Wall
-
Main fuse specication Copper pipe
(3) Attach round crimp-type terminal to each wire as shown in the below. A
Model Specication Parts No. Code on LABEL,WIRING outer diameter
Select the size of round crimp-type terminal after considering the specications of terminal block and wire diameter.
<Connecting cable (4 wires)> DXK09/12, SRK25/35, LMK09/12 250V 15A SSA564A136 F7 ø6.35 9.1
<Wire end> DXK15/18, SRK45/50, LMK15 250V 20A SSA564A136A F4
35 -
<Power source cable (3 wires)>
ø9.52 13.2
30 mm or more Round crimp- 3. Connecting cable (Outdoor)
type terminal (1) Remove the service cover. ø12.7 16.6
10 mm (2) Connect the cables according to the instructions and gures given below.
(a) Connect the earth wire of power source cable. 2.2 Connecting pipes
An earth wire must be connected before connecting the other wires of power source cable. (1) Connect pipes on both liquid and gas si
40 mm or more Sleeve Keep the earth wire longer than the remaining two wires of power source cable. (2) Tighten nuts to specied torque shown i
Earth wire
(b) Connect the remaining two wires (N and L) of power source cable.
(c) Connect the wires of connecting cable. Make sure that for each wire, outdoor and indoor side Operation valve size (mm) Tightening
2. Connecting cable (Indoor) terminal numbers match.
The screw of the lid (3) Fasten the cables properly with cable clamps so that no external force may work on terminal connections. ø6.35 (1/4") 1
(1) Remove the lid. is tightened securely. Moreover, make sure that cables do not touch the piping, etc. When cables are connected, make
Terminal block
(2) Remove the terminal cover. sure that all electrical components within the electrical component box are free of loose connector ø9.52 (3/8") 3
(3) Remove the cable clamp. Terminal cover coupling or terminal connection.
(4) Connect the connecting wire to ø12.7 (1/2") 4
the terminal block. <Circuit diagram>
Lid
(5) Fix the connecting cable by
cable clamp. Outdoor unit CAUTION
(6) Fix the terminal cover. N L 1 2/N 3 • Do not apply refrigerating machine oil to t
(7) Fix the lid. • Do not apply excess torque to the ared
Power
leakage.
Screw
source
Cable clamp cable 3. Heating and condensation pr
Connecting cable
Earth wire shall be Yellow/Green (Y/G) in color (1) Dress the connecting pipes (both liquid
Circuit
and longer than other wires for safety reason. breaker and dew condensation.
Use the heat insulating material which
NOTE that insulation is wrapped tightly aroun
Earth Earth (2) Wrap the refrigerant pipings of indoor u
Take care not to confuse the terminal numbers for indoor and outdoor connections. leakage
breaker 1 2/N 3 (3) Cover the are-connected joints (indo
WARNING Indoor unit Connecting cable Power source with an insulation pad (standard access
Power
source cable (4) Wrap the connecting pipes, connecting
Incorrect wiring connection can cause malfunction or re.
(2) (3)
Tape
Right
8. INSTALLATION CHE
Drain hose
2. Drain change procedures After nishing the installation work, check t
(1) Remove the screw and drain hose. before turning on the power. Conduct a tes
unit operates properly.
Rear (2) Remove the drain cap by hand or pliers. At the same time, explain to the customer
(7) Fix the lid. • Do not apply excess torque to the ared
Power
leakage.
Screw
source
Cable clamp cable 3. Heating and condensation pr
Connecting cable
Earth wire shall be Yellow/Green (Y/G) in color (1) Dress the connecting pipes (both liquid
Circuit
and longer than other wires for safety reason. breaker and dew condensation.
Use the heat insulating material which
NOTE that insulation is wrapped tightly aroun
Earth Earth (2) Wrap the refrigerant pipings of indoor u
Take care not to confuse the terminal numbers for indoor and outdoor connections. leakage
breaker 1 2/N 3 (3) Cover the are-connected joints (indo
WARNING Indoor unit Connecting cable Power source with an insulation pad (standard access
Power
source cable (4) Wrap the connecting pipes, connecting
Incorrect wiring connection can cause malfunction or re.
(2) (3)
Tape
Right
8. INSTALLATION CHE
Drain hose
2. Drain change procedures After nishing the installation work, check t
(1) Remove the screw and drain hose. before turning on the power. Conduct a tes
unit operates properly.
Rear (2) Remove the drain cap by hand or pliers. At the same time, explain to the customer
Left (3) Insert the drain cap which was removed at procedure (2) securely using a hexagonal wrench etc. how to take care of the unit following the u
Downward rear Left (4) Install the drain hose and screw securely.
Left downward (1) (2) (3) (4)
Screw NOTE
Left hand side piping Right hand side piping During restart or change in operation mode
operating for approximately 3 minutes. Thi
Piping in the left rear direction Piping in the right rear direction Drain cap
and it is not malfunction.
5. DRAINAGE WORK
RLC012A105A_EN.indd 2
-
nit • Arrange the drain hose in a downward angle. • Pour water to the drain pan located under the heat exchanger, and ensure that the water is discharged outdoor.
100
144.5 (Service space) • Avoid the following drain piping. • When extended drain hose is present inside the room, insulate it securely with heat insulator available in the market.
57 Gutter
171 Since this air-conditioner is designed to collect dew drops on the rear surface to the
254
36 -
drain pan, do not install the connecting wire above the gutter.
65 (Service Space)
Odor from
the gutter Wall
12.3
CAUTION
Higher than The drain hose Wavy The gap to the ground The drain hose tip
specified tip is in water. is 5 cm or less. is in the gutter. Incorrect drainage work can cause water leakage.
Pipe space
247.3
6. INSTALLING INDOOR UNIT
47
Indoor unit
Installation steps ● How to remove the indoor unit from the installation board
6.9
69 (1) Pass the pipe through the hole
443.5 (Gas pipe) (1) Push up at the marked portion of
Installation in the wall, and hook the upper
511.5 (Liquid pipe) the indoor unit base lower latch,
board
ain hose) ations) part of the indoor unit to the
Latch (2 loc and slightly pull it toward you.
Unit: mm installation board.
15 (Service Space)
(both right and left hand sides)
(The indoor unit base lower
latch can be removed from the
cause water leakage. (2) Gently push the lower part to installation board.)
Installation board secure the unit. (2) Push up the indoor unit upward
Wall The marked portion of the indoor
so that it can be removed from
the installation board. unit base lower latch
15 (Service S
(both right and left hand sides)
(The indoor unit base lower
latch can be removed from the
cause water leakage. (2) Gently push the lower part to installation board.)
Installation board secure the unit. (2) Push up the indoor unit upward
Wall The marked portion of the indoor
so that it can be removed from
the installation board. unit base lower latch
B
Copper pipe Copper pipe B [ Rigid (clutch) type ]
A for indoor unit
outer diameter outer diameter Wall
Code on LABEL,WIRING R32 Conventional
F7 ø6.35 9.1 ø6.35
A F4
CAUTION
ø9.52 13.2 ø9.52 0-0.5 1.0-1.5 Make sure that the connecting pipes do not touch the components within the unit. If pipes touch the
-
internal components, it may generate abnormal sounds and/or vibrations.
ø12.7 16.6 ø12.7
n below. 5. Evacuation
2.2 Connecting pipes (1) Connect vacuum pump to gauge manifold. Connect charge hose of gauge manifold to service port of outdoor unit.
r wires of power source cable. (1) Connect pipes on both liquid and gas sides.
37 -
(2) Run the vacuum pump for at least one hour after the vacuum gauge shows -0.1 MPa (–76 cm Hg).
ower source cable. (2) Tighten nuts to specied torque shown in the table below. Liquid side (3) Conrm that the vacuum gauge indicator does not rise even if the system is left for 15 minutes or more.
cable. Gas side Vacuum gauge indicator will rise if the system has moisture left inside or has a leakage point.
each wire, outdoor and indoor side Operation valve size (mm) Tightening torque (N·m) Check the system for the leakage point. If leakage point is found, repair it and return to (1) again.
(4) Close the Handle Lo and stop the vacuum pump.
ce may work on terminal connections. ø6.35 (1/4") 14-18
When cables are connected, make (Do not turn) Keep this state for a few minutes to make sure that the compound pressure gauge pointer does not swing back.
ent box are free of loose connector ø9.52 (3/8") 34-42 (5) Remove valve caps from liquid operation valve and gas operation valve.
(6) Turn the liquid operation valve’s rod 90 degree counterclockwise with a hexagonal wrench key to open valve.
ø12.7 (1/2") 49-61 Close it after 5 seconds, and check for gas leakage.
Using soapy water, check for gas leakage from indoor unit’s are and outdoor unit’s are and valve rods.
Wipe off all the water after completing the check.
CAUTION (7) Disconnect charging hose from gas operation valve’s service port and fully open liquid and gas
• Do not apply refrigerating machine oil to the ared surface. It can cause refrigerant leakage. operation valves. (Do not attempt to turn valve rod beyond its stop.)
• Do not apply excess torque to the ared nuts. The ared nuts may crack resulting in refrigerant (8) Tighten operation valve caps and service port cap to the specied torque shown in the table below.
leakage. Operation valve cap tightening Service port cap tightening
Operation valve size (mm)
3. Heating and condensation prevention torque (N·m) torque (N·m)
ø6.35 (1/4")
(1) Dress the connecting pipes (both liquid and gas pipes) with insulation to prevent it from heating 20-30
and dew condensation. ø9.52 (3/8") 10-12
Use the heat insulating material which can withstand 120 °C or higher temperature. Make sure ø12.7 (1/2") 25-35
that insulation is wrapped tightly around the pipes and no gap is left between them. Compound pressure gauge
(2) Wrap the refrigerant pipings of indoor unit with indoor unit heat insulation using tape. Pressure gauge
(3) Cover the are-connected joints (indoor side) with the indoor unit heat insulation and wrap it Handle Lo Gauge manifold
g cable Power source with an insulation pad (standard accessory provided with indoor unit).
cable (4) Wrap the connecting pipes, connecting cable and drain hose with the tape. Liquid operation valve Handle Hi
(2) (3) (4) Valve cap
Insulation pad Connecting cable
Tape Gas operation valve
Gas pipe Vacuum pump
Liquid pipe Service port
Tape
Charge hose
terior
rtion that goes through the wall. CAUTION
wiring with the piping.
Position it so that the slit area faces Insulation To prevent vacuum pump oil from entering into the refrigerant system, use a counterow prevention
upward. Drain hose adapter.
'20 • SRK-T-320
8/18/2020 9:49:39 AM
-
38 -
'20 • SRK-T-320
'20 • SRK-T-320
Remote control
◆ Operation section
Accessories
- 39 -
Filter holder × 2
Remote control Remote control Wood screw × 2 Photocatalytic washable
holder (for remote control holder mounting) deodorizing filter (Orange)
NOTE
Notes (1) A
uto restart function is set at on when the air-conditioner is shipped from the factory.
Consult with your dealer if this function needs to be switched off.
(2) W hen power failure ocurrs, the timer setting is cancelled. Once power is resumed, reset the timer.
(3) If the jumper wire (J1) “AUTO RESTART” is cut, auto restart is disabled. (See the diagram at right.)
(i) Take out the printed circuit board from the control box.
(ii) Disconnect jumper wire (J2) with wire cutters.
(iii) Install a printed circuit board.
(b) Setting a wireless remote control
(i) P
ull out the cover and take out batteries.
(ii) Disconnect the switching line next to the battery with wire cutters.
(iii) Insert batteries. Close the cover.
Cut
- 40 -
'20 • SRK-T-320
Mode
Cooling Heating ① at the start of operation.
Item
①+0.5 ①-1.0 ② one hour after the start of operation.
Temperature ③ two hours after the start of operation.
adjustment ②+1.0 ②-2.0
③+1.5 ③-2.5
- 41 -
'20 • SRK-T-320
(b) Swing
Flap moves in upward and downward directions continuously.
◆ In HEAT operation ◆ In COOL, DRY, FAN operation
Approx.
20°
Approx. 35°
Approx. 59°
Approx. 65°
When the defrost operation, protection device, etc. is actuated, operation is performed in the corresponding mode.
- 42 -
(16)ࠉOutline of heating operation
(9)ࠉOutline of heating operation
(a) Operation of major functional components in heating mode
(a) Operation of major functional components in heating mode
Heating
Thermostat ON Heating
Thermostat OFF Failure
Thermostat ON Thermostat OFF Failure
'20 • SRK-T-320
Compressor ON OFF OFF
Compressor
Indoor fan motor ON
ON ON(HOT OFF
KEEP)* OFF
OFF
Indoor fan motor ON ON(HOT
OFF KEEP) OFF
Outdoor fan motor ON OFF
(ii) Outdoor
Hot keep (few minutes
OFF ON)
fan operation
motor ON OFF
During the heating operation, ON
4-way valve the indoor
fan speed(few
canminutes ON)
be controlled
of the indoor heat ex-
ON based on OFF
the temperature
(3 minutes
OFFON)
4-way valve ON ON
changer (Th2) to prevent blowing of cold air.
*It can be set the indoor fan motor off or the heating thermostat OFF with connecting a wired remote control.
(3 minutes ON)
(c)InDefrost
the case, operation
indoor air temperature is detected by sensor on the wired remote control.
(b) Details of control at each operation mode (pattern)
(i) Fuzzy operation
1) satisfied.
(b) Details of control at each operation mode (pattern)
1)
(i) Fuzzy operation
35 (model SRK35 : 45) Total
2) Model
SRK20ZJ-S SRK25ZJ-S SRK35ZJ-S SRK50ZJ-S
Fan speed Model
35 (model SRK35 : 45)
SRK20ZS-S Total
SRK25ZS-S SRK35ZS-S SRK50ZS-S
Fan speed Auto 30~115rps 30~115rps 30~115rps 23~106rps
3)
HI
Auto 30~115rps
20~115rps 30~115rps
20~115rps 30~115rps
20~115rps 23~106rps
23~106rps
MED
HI -
30~66rps
20~115rps or less 30~72rps
20~115rps 30~76rps
20~115rps 23~78rps
23~106rps
4) The difference
MEDLO between the20~86rps
outdoor
30~40rps air temperature sensor temperature
30~42rps
20~104rps and the outdoor23~82rps
30~46rps
20~108rps heat exchanger temperature
23~50rps
sensor temperature
LO 20~70rps
is as follows. 20~84rps 20~96rps 23~70rps
ULO 20~44rps 20~54rps 20~60rps 23~37rps
2) Hot•0℃≦ keepTH2: TH2-TH1≧7℃, TH1≦TH2-7℃
operation
•-15℃≦TH2<0℃: TH2-TH1≧2/15×TH2+7℃, TH1≦13/15×TH2-7℃
(ii) Hot•TH2keep<-15operation
℃: TH2-TH1≧-5℃, TH1≦TH2+5℃
During the heating operation, the indoor fan speed can be controlled based on the temperature of the indoor heat
exchanger
(c) Defrosting (Th2) to prevent
operation blowing out of cold air.
5) Models LMK09, 12, 45,
SRK25, 35, 15Z6-W 50ZSP-W Model DXK15Z6-S
(i)
(c) Defrost operation 0 0
met.
(i) 1) are satisfied.)
1) 2) 3) 5) Outdoor heat exchanger temperature (℃)
Outdoor heat exchanger temperature (℃)
TH1
t a
1) ra
ti (LMK15 p : 10 )
pe tem
3) -15
s to
-15
sta
rt
ro
2) 4) De
f Defrost operation
start 16 minutes and 50 seconds ati
o (model LMK15
n 17 minutes
Defrost :operation
C or less for 3 minutes continuously. op
er start
and 30 seconds).
-20 (model DXK15 : 2-20
ࠉ) (model
fr o st
DXK15 : 10 ࠉ)
4) De
Heating operation
Max. 16 minutes and 50 seconds 2-7 minutes ͤ
- 43 -
'20 • SRK-T-320
Cooling
Thermostat ON Thermostat OFF Failure
Compressor ON OFF OFF
Indoor fan motor ON ON ON
Outdoor fan motor ON OFF OFF
(few minutes ON) (few minutes ON)
4-way valve OFF OFF OFF
25.5
Heating
18 30
Outdoor air temperature (˚C)
(b) The unit checks the temperature every hour after the start of operation and, if the result of check is not same as the pre-
vious operation mode, changes the operation mode.
(i) If the setting temperature is changed with the remote control, the operation mode is judged immediately.
(ii) When both the indoor and the outdoor air temperatures are in the range “A”, cooling or heating is switched depending
on the difference between the setting temperature and the indoor air temperature.
(iii) When the operation mode has been judged following the change of setting temperature with the remote control, the hour-
ly judgment of operation mode is cancelled.
(c) When the unit is started again within one hour after the stop of automatic operation or when the automatic operation is
selected during heating, cooling or dehumidifying operation, the unit is operated in the previous operation mode.
(d) Setting temperature can be adjusted within the following range. There is the relationship as shown below between the
signals of the wireless remote control and the setting temperature.
Signals of wireless remote control (Display)
–6 –5 –4 –3 –2 –1 ±0 +1 +2 +3 +4 +5 +6
Cooling 18 19 20 21 22 23 24 25 26 27 28 29 30
Setting
Dehumidifying 19 20 21 22 23 24 25 26 27 28 29 30 31
temperature
Heating 20 21 22 23 24 25 26 27 28 29 30 31 32
(e) When the unit is operated automatically with the wired remote control connected, the cooling operation is controlled ac-
cording to the display temperatures while the setting temperature is compensated by + 1˚C during dehumidifying or by
+ 2˚C during heating.
- 44 -
'20 • SRK-T-320
Upper limit of compressor speed RangeA: 41rps, RangeB: 41rps RangeA: 57rps, RangeB: 39rps
AUTO,HI,MED
Adaptable to compressor
Indoor fan speed (Lower limit 4th speed)
Note (1) Ranges A and B are as shown below.
Range B
Range A
68 73
Humidity(%)
2) When this control has continued for more than 30 minutes continuously,the following wind direction control is per-
formed.
a) When the vertical wind direction is set at other than the vertical swing,the flaps change to the horizontal position.
b) When the horizontal wind direction is set at other than the horizontal swing,the louver changes to the vertical po-
sition.
(iii) Reset condition
When any of followings is satisfied
Humidity is less than 63%. (SRK45, 50 : 55%)
- 45 -
'09•SRK-DB-087D
'20 • SRK-T-320
1)
2)
(d)
(c) Cooling
Coolingoverload
overloadprotective
protectivecontrol
control
(i) (i)
Operating conditions
Operating conditions:
When the outdoor air temperature (TH2)
more, has become
or 47ºC or morecontinuously
(model SRK50for: 41ºC
30 seconds at 41ºC
or more) or more,
with the or 47ºC
compressor or morethe lower
running,
with the compressor running, the lower limit speed of compressor is brought up.
limit
Model
Model SRK25, 35ZSP-W SRK45, 50ZSP-W
Item SRK20~35ZJ-S SRK50ZJ-S
Item
Outdoor air temperature 41°C or more 47°C or more 41°C or more 47°C or more
Outdoor air temperature 41°C or more
Lower limit speed 30 rps 45 rps 27 rps 35 rps
Lower limit speed 29 rps
(ii) (ii)
Detail of operation
Detail of operation
1) The1)outdoor fan is stepped up by 3 speed step. (Upper limit; 8th speed.)
2) The2)lower
Thelimit
loweroflimit
compressor speed iscommand
of compressor set to 30 or 45(models
speed is set toSRK45,50 : 27 or SRK50
30 or 40 (model 35 rps).:However, when
29) rps and eventheif thermo
the calculated
OFF, the speed is reduced to 0 rps.
result becomes lower than that after fuzzy calculation, the speed is kept to 30 or 40 (model SRK50 : 29) rps. Howev-
(iii) Reset conditions
er, when the thermo OFF, the speed is reduced to 0 rps.
When either of the following condition is satisfied
(iii) Reset conditions:
1) The outdoor air temperature is lower than 40ºC.
1)
2) The compressor speed is 0 rps.
2)
( e) Cooling high pressure control
(d) Cooling high pressure control
(i) Purpose
(i) Purpose:
Prevents anomalous high pressure operation during cooling.
(ii) Detector:
(ii) Detector
(iii) Detail of operation:
Outdoor heat exchanger temperature sensor (TH1)
(Example) Fuzzy
(iii) Detail of operation After lapse of 30 sec. or over
(3)
6rps
(1)
6rps
(1)
After lapse of 30 sec. or over
(3)
(Example) Fuzzy
After lapse lower limit 8rps(1)
After of 20 sec.
of 30orsec.
overor over(3)
(3)
lapse speed 30 (model SRK50 : 29) rps
After lapse of 20 sec. or over(3) 0rps 8rps(1)
0rps
53 58 63
Outdoor heat exchanger temperature (°C)
A B C
Outdoor heat exchanger temperature(°C)
- 46 -
'20 • SRK-T-320
Notes (1) When the outdoor heat exchanger temperature is in the range of B-C ºC, the speed is reduced by 8 rps at each 20 seconds.
(2) When the temperature is C ºC or higher, the compressor is stopped.
(3) When the outdoor heat exchanger temperature is in the range of A-B ºC, if the compressor speed is been maintained and the operation has
continued for more than 20 seconds at the same speed, it returns to the normal cooling operation.
● Temperature list
SRK25, 35 SRK45, 50
A B C A B C
Outdoor air temperature > 53 58 63 48 53
'09•SRK-DB-087D
55
= 32 ºC
Outdoor air temperature < 32 ºC 40 43 46 53 58 63
0rps
A B C D
Indoor heat exchanger temperature(°C)
A B B-C C D
Indoor heat exchanger Ctemperature(°C)
-D
10
-
When the indoor heat exchanger temperature is in the range of A-B °C, if the compressor
- speed is been maintained and the operation has continued for more
Temperature list
than 20 seconds at the same speed, it returns to the normal heating operation.
fan speed - fan
Models DXK09.12
Temperature list fan
10
A
-
B
47 - C D
speed fan
Models
RPSmin SRK20,
< 50
Temperature 25, 35
list 52 54 55
50 <
= RPSmin < 91 A 54.5
B C D
Models DXK09.12
91 <
= RPSmin
RPSmin < 50< 97 48 54.5 5351.5 55 58
A B C D
50<
97 =<
=RPSmin
RPSmin<<100
91 48.5 51.5 5650 58 61
RPSmin < 50 52 54 55
100 <<
= RPSmin<<97
91 = RPSmin 115 48.5 50 - 52.5
56 58 61
50 <= RPSmin < 91 54.5
97 <<
115 RPSmin< 100
=RPSmin 48.5 52.5 - 50.8 58 - 56.2 61
(iii) Detail of operation
(Example) Fuzzy
After lapse of 10 sec. or over(3) 4rps(1) 8rps(2)
After lapse of 10 sec. or over (3)
4rps (1)
8rps(2)
lower limit
After lapse of 10 sec. or over (3)
speed 30(35) rps
0rps
'20 • SRK-T-320
A B C D
Indoor heat exchanger temperature(°C)
-
-
-
10
fan speed fan
Temperature list
● Temperature list
Models DXK09.12
Models SRK25, 35 Unit : ºC
A B C D
A B C D
RPSminRPSmin
< 50 < 50 47 52 52 54 54 55 55
50 < 50 <
= RPSmin < 91 < 92
= RPSmin 47.5 54.5 55 57 61
91 < 92 <
RPSmin
= < 97 <
RPSmin = 115 47.5-39.0 54.5-51.555.0-40.0 57.0-42.0 61
=
97 <
= RPSmin < 100 51.5-50 -
100 < Models SRK45, 50 - 50- - Unit : ºC Unit : ºC
'09•SRK-DB-087D
= RPSmin < 115
<
115 = RPSmin A B C D
RPSmin < 30 45 49 50 RPSmin < 35 55.5
30 <
= RPSmin < 40 45-49 49-55 50-57 35 <
= RPSmin < 40 55.5-62
40 <
= RPSmin < 80 49 55 57 40 <
= RPSmin < 80 62
80 <
= RPSmin < 90 49-48 55-53 57-55 80 <
= RPSmin < 95 62-56
90 <
= RPSmin < 100 48-37 53-42 55-44 95 <
= RPSmin < 100 56-50.5
2) Detail of operation
3) Reset conditions
2) Detail of operation
b) Detail
Upper of operation
and lower limits of compressor speed and the outdoor unit fan speed are restricted.
i) Taking the upper limit of compressor command speed range at 60 rps, if the output speed obtained with the fuzzy
Models SRK25, 35
calculation
Compressor exceeds
command speedthe upper limit, the upper limit value is maintained.
(rps)
Thelimit
ii)Lower lower limitUpper
of compressor
limit command
Outdoor speed is set to 40 rps and even if the calculated result becomes lower than
fan speed
Range A Range B
that after fuzzy calculation, the speed is kept to 40 rps. However, when thethermo becomes OFF, the speed is
ON1 - - - -
ON2 40 reduced to 0 prs. 60
Release 2nd speed
iii) 50
Models SRK45,
rps.
Compressor command speed (rps)
Lower limit Outdoor fan speed
iv) Upper limit
Range A Range B
ON1 35 Release 85 It depends on compressor speed
Protective
ON2 35 35 55 2nd speed control
Protective Normal
ON2operation
control
Range A
ON1
Normal
operation Range B
OFF 21 22
10 11 21 (19) 22 (20) Outdoor air temperature(°C)
21 23
Outdoor air temperature(°C) Indoor air temperature ( Υ)
c) Reset conditions: .
3) Reset
• Model 50 conditions
When the outdoor air temperature drops below 19 (13)ºC.
a) Operating conditions : When the outdoor air temperature (TH2) is 11ºC or higher continues for 30 seconds while
Note (1) Values in ( ) are for the model SRK45, 50.
the compressor command speed other than 0 rps.
b) Detail of operation
- 48 -
i) Taking the upper limit of compressor command speed range at 78 rps, if the output speed obtained with the fuzzy
calculation exceeds the upper limit, the upper limit value is maintained.
ii) The lower limit of compressor command speed is set to 30 rps and even if the calculated result becomes lower than
that after fuzzy calculation, the speed is kept to 30 rps. However, when thethermo becomes OFF, the speed is
reduced to 0 prs.
iii)
Protective control ON1
Normal operation
10 11 19 20 '20 • SRK-T-320
Outdoor air temperature(°C)
c) Reset conditions: 10 .
( i ) Heating low outdoor temperature protective control
(i) Protective control I
1) Operating conditions
2 (-8) lower
2) Detail of operation
changed as shown in the figure below.
Models SRK25, 35 Models SRK45, 50
Lower limit 45(55) rps
Lower limit 27 rps
Lower limit 40 rps
Lower limit 38(40) rps Normal operation
Normal operation
-10 -8 0 2 4 -8 -6
Outdoor air temperature(°C ) Outdoor air temperature(°C )
3) Reset conditions
a) 4 (-6)
b)
• Model 50 Note (1) Values in ( ) are for the model SRK35.
1)ࠉOperating conditions: When the outdoor air temperature (TH2) is lower than 4ºC or higher continues for 30 seconds
( j ) Compressor overheat protection
while the compressor command speed is other than 0 rps.
(i) 2)ࠉDetail
Purpose of operation: The lower limit compressor command speed is change as shown in the figure belo.
It is designedLower
to prevent deterioration
limit 29 rps of oil, burnout of motor coil and other trouble resulting from the compressor over-
heat.
(ii) Detail of operation Normal operation
1) Speeds are controlled with temperature detected by the sensor mounted on the discharge pipe.
4 6
(Example) Fuzzy
Outdoor air of
After lapse temperature(°C)
60 seconds. or over (3) 4 rps (1)
(3)
After lapse of 60 seconds. or over 4 rps
0 rps
90 100 110
Discharge pipe temperature (˚C)
Notes (1) When the discharge pipe temperature is in the range of 100 to 110 ºC, the speed is reduced by 4 rps.
(2) When the discharge pipe temperature is raised and continues operation for 20 seconds without changing, then the speed is reduced again by 4
rps.
(3) If the discharge pipe temperature is in the range of 90-100ºC even when the compressor speed is maintained for 60 second when the tempera-
ture is in the range of 90-100ºC, the speed is raised by 1 rps and kept at that speed for 60 second. This process is repeated until the compres-
sor speed is reached.
(4) Lower limit speed
Cooling Heating
Models SRK25, 35 15 rps 20 rps
Models SRK45, 50 20 rps 30rps
- 49 -
'20 • SRK-T-320
2) If the temperature of 110ºC is detected by the sensor on the discharge pipe, then the compressor will stop immediately.
When the discharge pipe temperature drops and 3 minutes has elapsed, the unit starts again within 1 hour but there
is no start at the third time.
( l ) Current cut
(i) Purpose
Inverter is protected from overcurrent.
(ii) Detail of operation
Output current from the inverter is monitored with a shunt resistor and, if the current exceeds the setting value, the
compressor is stopped immediately. Operation starts again after 3 minutes.
2) Detail of operation
2) Detail of operation
- 50 -
Outdoor fan
Outdoor fan
Outdoor temperature > 10˚C
Outdoor temperature > 10˚C
Outdoor temperature <
= 10˚C
Outdoor temperature <
= 10˚C
a)
(p ) Rotor lock
2) Detail of operation
N
Outdoor fan
a)
-
b)
-
c)
3) Reset conditions
a) 24
b)
(ii) Heating
1) Operating conditions
(models SRK45, 50:0 )
2) Detail of operation
; models SRK25, 35 : refer to belows,
models SRK45, 50 : 8th speed)
ON2
SRK25, 35 Th1<21℃ = 21℃
Th1 >
ON1 8th speed 8th speed ON1
ON2 9th(8th) speed 8th speed
OFF
-1 1 4 6
Outdoor air temperature(°C )
Values in ( ) are for the model SRK35.
3) Reset conditions
3) Reset conditions
'20 • SRK-T-320
a) (models SRK45, 50:2 )
b)
- 52 -
'20 • SRK-T-320
Troubleshooting procedure (If the air-conditioner does not run at all) * If the voltage is correct, it will be
within the following voltage range.
AC 198-264 V
Is the correct voltage Make sure the correct volt-
connected for the power NO
age is connected, then per-
source? form an operation check.
YES
- 53 -
'20 • SRK-T-320
Check the self-diagnosis display. Eliminate the cause of the trouble and perform an
operation check.
See page 55.
Is an error code displayed by NO Using the service mode, access the self-diagnosis
the self-diagnosis function? displays generated in the past.
Replace the faulty component, then perform an The air-conditioning system is operating normally.
operation check.
Note (1) Even in cases where only intermittent stop data are generated, the air-conditioning system is normal. However, if the same protective operation
recurs repeatedly (3 or more times), it will lead to customer complaints. Judge the conditions in comparison with the contents of the complaints.
- 54 -
'20 • SRK-T-320
• Broken room temperature When a room temperature sensor wire disconnection is detected while operation
2‐time Room sensor wire, poor connector is stopped. (If a temperature of –45ºC or lower is detected for 15 seconds, it is
ON temperature connection judged that the wire is disconnected.)
flash sensor error • Indoor unit PCB is faulty (Not displayed during operation.)
5‐time Active filter When the wrong voltage connected for the power source.
ON voltage error • Defective active filter When the outdoor unit PCB is faulty.
flash
When conditions for turning the indoor unit’s fan motor on exist during air-
6‐time Indoor fan • Defective fan motor, poor
ON conditioner operation, an indoor unit fan motor speed of 300 min-1 or lower is
flash motor error connector connection
measured for 30 seconds or longer. (The air-conditioner stops.)
Refrigeration
7‐time cycle system • Service valve is closed.
ON When refrigeration cycle system protective control operates.
flash protective • Refrigerant is insufficient
control
• Broken outdoor air temperature -55℃ or lower is detected for 5 seconds continuously 3 times within 40 minutes
Outdoor air sensor wire, poor connector
Keeps 1‐time temperature
after initial detection of this anomalous temperature.
flashing flash connection Or -55℃ or higher is detected for within 20 seconds after power ON.
sensor error • Outdoor unit PCB is faulty (The compressor is stopped.)
Outdoor heat • Broken heat exchanger temperature -55℃ or lower is detected for 5 seconds continuously 3 times within 40 minutes
Keeps 2‐time exchanger sensor wire, poor connector after initial detection of this anomalous temperature.
flashing flash temperature connection Or -55℃ or higher is detected for within 20 seconds after power ON.
sensor error • Outdoor unit PCB is faulty (The compressor is stopped.)
• Compressor locking, open The compressor output current (compressor motor current) exceeds the set value
1‐time phase on compressor output, during compressor start.
ON Current cut short-circuit on power
flash (The air-conditioner stops.)
transistor, closed service valve
When there is an emergency stop caused by trouble in the outdoor unit, or the
2‐time Trouble of • Broken compressor wire
ON outdoor unit • Compressor blockage input current value is found to be lower than the set value.
flash (The air-conditioner stops.)
• Overload operation
3‐time Current safe When the compressor speed is lower than the set value and the current safe has
ON • Overcharge
flash stop operated. (The compressor is stopped.)
• Compressor locking
When there is an emergency stop caused by trouble in the outdoor unit, or the
4‐time Power transistor input current value is found to be lower than the set value continuously for 3
ON • Broken power transistor
flash error minutes or longer.
(The compressor is stopped.)
7‐time Outdoor fan • Defective fan motor, poor When the outdoor unit’s fan motor sped continues for 30 seconds or longer at
ON motor error connector connection 75 min-1 or lower. (3 times) (The air-conditioner stops.)
flash
• Defective compressor If the compressor motor’s magnetic pole positions cannot be correctly detected
2‐time 2‐time when the compressor starts.
Rotor lock • Open phase on compressor
flash flash • Defective outdoor unit PCB (The air-conditioner stops.)
Note (1) The air-conditioner cannot be restarted using the wireless remote control for 3 minutes after operation stops.
- 55 -
'20 • SRK-T-320
Start
- 56 -
'20 • SRK-T-320
*3: To count the number of flashes in the service mode, count the number of flashes after the light lights up for 1.5 second
initially (start signal). (The time that the light lights up for 1.5 second (start signal) is not counted in the number of
flashes.)
• In the case of current cut (example: stop code “42”)
The RUN light (10’s digit) flashes 4 times and the TIMER light (1’s digit) flashes 2 times.
4 × 10 + 2 × 1 = 42 → From the table, read the instructions for error code 42, “current cut”.
1.5 sec.
ON
RUN light
(10’s digit)
OFF
0.5 sec. 0.5 sec.
ON
TIMER light
(1’s digit)
OFF
11-second interval
*4: When in the service mode, when the remote control settings (operation switching, fan speed switching, temperature
setting) are set as shown in the following table and sent to the air-conditioner unit, the unit switches to display of service data.
① Self-diagnosis data
What are Self-diagnosis data?
These are control data (reasons for stops, temperature at each sensor, wireless remote control information) from the time when
there were error displays (abnormal stops) in the indoor unit in the past. Data from up to 5 previous occasions are stored in
memory. Data older than the 5th previous occasion are erased. The temperature setting indicates how many occasions previous
to the present setting the error display data are and the operation switching and fan speed switching data show the type of data.
(Example)
- 57 -
'20 • SRK-T-320
② Stop data
Remote control setting
Operation Fan speed Temperature Displayed data
switching switching setting
21ºC Displays the reason for the stop (stop code) the previous time when the air-conditioner was stopped by protective stop control.
22ºC Displays the reason for the stop (stop code) 2 times previous when the air-conditioner was stopped by protective stop control.
23ºC Displays the reason for the stop (stop code) 3 times previous when the air-conditioner was stopped by protective stop control.
24ºC Displays the reason for the stop (stop code) 4 times previous when the air-conditioner was stopped by protective stop control.
25ºC Displays the reason for the stop (stop code) 5 times previous when the air-conditioner was stopped by protective stop control.
Cooling LO
26ºC Displays the reason for the stop (stop code) 6 times previous when the air-conditioner was stopped by protective stop control.
27ºC Displays the reason for the stop (stop code) 7 times previous when the air-conditioner was stopped by protective stop control.
28ºC Displays the reason for the stop (stop code) 8 times previous when the air-conditioner was stopped by protective stop control.
29ºC Displays the reason for the stop (stop code) 9 times previous when the air-conditioner was stopped by protective stop control.
30ºC Displays the reason for the stop (stop code) 10 times previous when the air-conditioner was stopped by protective stop control.
- 58 -
'09•SRK-DB-087D
'20 • SRK-T-320
OFF Can not receive signals for 35 Power source is faulty. When 35 seconds passes without
5̺time Power source cables and signal lines
05 seconds communications signals from either the outdoor unit or
flash are improperly wired.
(if communications have recovered) the indoor unit being detected correctly.
Indoor or outdoor unit PCB are faulty.
6̺time Refrigerant is insufficient. When the discharge pipe temperature sensor's value
36 Compressor overheat 110°C Discharge pipe temperature sensor. is faulty. exceeds the set value.
flash (2 times)
Service valve is closed.
8̺time Outdoor unit's fan motor is Outdoor fan motor is faulty. When a fan speed of 75 min-1 or lower continues for 30
48 Connector connections are poor.
flash abnormal seconds or longer. (3 times)
Outdoor unit PCB is faulty.
Short-circuit in the power
1̺time Outdoor unit PCB is faulty. When it is judged that the power transistor was
51 transistor (high side)
flash Power transistor is damaged. damaged at the time the compressor started.
Current cut circuit breakdown
7̺time Refrigeration cycle system Service valve is closed. When refrigeration cycle system protective control
57
flash protective control Refrigerant is insufficient. operates. (3 times)
Compressor wiring is disconnected. When the current is 1A or less at the time the
Compressor wiring is unconnection Power transistor is damaged. compressor started.
9̺time
59 Voltage drop Power source construction is defective. When the power source voltage drops during operation.
flash
Low speed protective control Outdoor unit PCB is faulty. When the compressor command speed is lower than 32
Compressor is faulty. rps for 60 minutes.
Compressor is faulty.
Compressor output is open phase. After the compressor starts, when the compressor stops
OFF 60 Rotor lock Electronic expansion valve is faulty. due to rotor lock. (2 times)
Overload operation.
Outdoor unit PCB is faulty.
6̺time
Connection lines between the When 10 seconds passes after the power is turned on
flash 1̺time Connection lines are faulty.
61 indoor and outdoor units are without communications signals from the indoor or
flash Indoor or outdoor unit PCB are faulty.
faulty outdoor unit being detected correctly.
Indoor or outdoor unit PCB are faulty. When 7 minutes 35 seconds passes without
2̺time
62 Serial transmission error communications signals from either the outdoor unit or
flash Noise is causing faulty operation.
the indoor unit being detected correctly.
Indoor unit's fan motor is Indoor fan motor is faulty. When the indoor unit's fan motor is detected to be running
OFF 80 Connector connections are poor. at 300 min-1 or lower speed with the fan motor in the ON
abnormal
Indoor unit PCB is faulty. condition while the air-conditioner is running.
Indoor heat exchanger Indoor heat exchanger temperature When a temperature of –28°C or lower is sensed
2̺time
82 temperature sensor sensor wire is disconnected. continuously for 40 minutes during heating operation.
flash
is abnormal (anomalous stop) Connector connections are poor. (The compressor stops.)
8̺time
4̺time High humidity condition.
flash 84 Anti-condensation control Anti-condensation prevention control is operating.
flash Humidity sensor is faulty.
5̺time Indoor unit fan speed drops. When the anti-frost control operates and the compressor
85 Anti-frost control Indoor heat exchanger temperature
flash stops during cooling operation.
sensor is broken wire.
Heating overload operation.
6̺time Indoor unit fan speed drops. When high pressure control operates during heating
86 Heating high pressure control
flash Indoor heat exchanger temperature operation and the compressor stops.
sensor is short-circuit.
- 59 -
'20 • SRK-T-320
Notes (1) The number of flashes when in the service mode do not include the 1.5 second period when the lights light up at first (start signal). (See the ex-
ample shown below.)
1.5 sec.
ON
RUN light
(10’s digit)
OFF
0.5 sec. 0.5 sec.
ON
TIMER light
(1’s digit)
OFF
11-second interval
* If no data are recorded (error code is normal), the information display in the wireless remote control becomes as follows.
1.5 sec.
ON
RUN light
(10’s digit)
OFF
0.5 sec. 0.5 sec.
ON
TIMER light
(1’s digit)
OFF
11-second interval
- 60 -
'20 • SRK-T-320
(e) Room temperature sensor, indoor heat exchanger temperature sensor, outdoor air temperature sen-
sor, outdoor heat exchanger temperature sensor table
Unit: ºC
TIMER light
(1’s digit)
RUN light
(10’s digit) 0 1 2 3 4 5 6 7 8 9
Buzzer sound
6 -60 -61 -62 -63 -64
5 -50 -51 -52 -53 -54 -55 -56 -57 -58 -59
4 -40 -41 -42 -43 -44 -45 -46 -47 -48 -49
Yes
(sounds for 0.1 second) 3 -30 -31 -32 -33 -34 -35 -36 -37 -38 -39
2 -20 -21 -22 -23 -24 -25 -26 -27 -28 -29
1 -10 -11 -12 -13 -14 -15 -16 -17 -18 -19
0 -1 -2 -3 -4 -5 -6 -7 -8 -9
0 0 1 2 3 4 5 6 7 8 9
1 10 11 12 13 14 15 16 17 18 19
2 20 21 22 23 24 25 26 27 28 29
3 30 31 32 33 34 35 36 37 38 39
No 4 40 41 42 43 44 45 46 47 48 49
(does not sound) 5 50 51 52 53 54 55 56 57 58 59
6 60 61 62 63 64 65 66 67 68 69
7 70 71 72 73 74 75 76 77 78 79
8 80 81 82 83 84 85 86 87 88 89
9 90 91 92 93 94 95 96 97 98 99
* If no data are recorded (error code is normal), the display for each sensor becomes as shown below.
Sensor name Sensor value displayed when the error code is normal
Room temperature sensor -19ºC
Indoor heat exchanger temperature sensor -64ºC
Outdoor air temperature sensor -64ºC
Outdoor heat exchanger temperature sensor -64ºC
(Example) Room temperature, indoor heat exchanger temperature, outdoor air temperature, outdoor heat exchanger tem-
perature: “-9ºC”
0.1 sec.
ON If the temperature is < 0, the buzzer sounds.
Buzzer sound If the temperature is >
= 0, the buzzer does not sound.
OFF
1.5 sec.
ON
RUN light
(10’s digit)
OFF
0.5 sec. 0.5 sec.
ON
TIMER light
(1’s digit)
OFF
11-second interval
- 61 -
'20 • SRK-T-320
Buzzer sound
3 -60 -62 -64
Yes 2 -40 -42 -44 -46 -48 -50 -52 -54 -56 -58
(sounds for 0.1 second) 1 -20 -22 -24 -26 -28 -30 -32 -34 -36 -38
0 -2 -4 -6 -8 -10 -12 -14 -16 -18
0 0 2 4 6 8 10 12 14 16 18
1 20 22 24 26 28 30 32 34 36 38
2 40 42 44 46 48 50 52 54 56 58
No 3 60 62 64 66 68 70 72 74 76 78
(does not sound)
4 80 82 84 86 88 90 92 94 96 98
5 100 102 104 106 108 110 112 114 116 118
6 120 122 124 126 128 130 132 134 136 138
7 140 142 144 146 148 150
* If no data are recorded (error code is normal), the display for sensor becomes as shown below.
Sensor name Sensor value displayed when the error code is normal
Discharge pipe temperature sensor -64ºC
0.1 sec.
ON If the temperature is < 0, the buzzer sounds.
Buzzer sound If the temperature is >
= 0, the buzzer does not sound.
OFF
1.5 sec.
ON
RUN light
(10’s digit)
OFF
0.5 sec. 0.5 sec.
ON
TIMER light
(1’s digit)
OFF
11-second interval
- 62 -
'20 • SRK-T-320
Customer Model
Date of investigation
Machine name
Content of complaint
Judgment
Remarks
- 63 -
'20 • SRK-T-320
180 30
160
25
140
Resistance (k )
Resistance (k )
120 20
100
15
80
60 10
40
5
20
- 0 -
-10 0 10 20 30 40 50 60 70
0 20 40 60 80 100 120 135
Temperature (˚C) Temperature (˚C)
unit
unit
- 64 -
'09•SRK-DB-087D
'20 • SRK-T-320
Current cut Compressor lock, Compressor wiring short-circuit, Compressor output is open phase,
Outdoor unit PCB is faulty, Service valve is closed, EEV is faulty, Compressor faulty.
73.
unit
unit
unit
70.
unit
- 65 -
'09•SRK-DB-087D
'20 • SRK-T-320
unit
Error of signal transmission Wiring error including power cable, defective indoor/
outdoor unit PCB
-
- unit
-
-
unit
-
unit
- 66 -
'09•SRK-DB-087D
'20 • SRK-T-320
Trouble of outdoor unit Insufficient refregerant amount, Faulty power transistor, Broken compressor wire
Service valve close, Defective EEV, Defective outdoor unit PCB
(1)
unit
(2)
unit
operation
(3)
Notes (1) 73.
See page 71-73 for the fan motor and outdoor unit PCB
outdoor unit check pro
After making sure the fan motor and outdoor unit PCB are
nor
- 67 -
'20 • SRK-T-320
unit
short-
-
.
.
NO
Is the fuse burnt out? (3.15 A) Replace fuse.
YES
YES
NO
Is the fuse burnt out? (3.15 A) Replace fuse.
YES
YES
unit
unit
DC several V (–)
(4-6 V) GND DC 308-336V
Measuring Voltage range when
DC15V point normal
-
CNU Indoor unit PCB
-
Yellow
White
Black
Blue
Red
FMi
- 69 -
'20 • SRK-T-320
(Example)
RUN light : ON
TIMER light: 2 time flash
Output voltage
(ACV)
0
8-10 sec. 1 sec. 3 min. 1 sec. 3 min. 1 sec.
(10)(10)
How to make
How sure
to make of wireless
sure remote
of wireless control
remote controller
(1)
Is wireless NO Wireless remote
remote control control defects
normal?
Again pushing
operating switch
Is the unit
YES
operable with Normal
wireless remote
YES Abnormality is not control?
Operating the unit?
found. NO
Defective wireless
NO remote control
YES
Operating the unit.
NO
Control problem on
main unit
- 70 -
◆ Check point of outdoor unit
3 PCB ASSY
T1 T2 POWER
F7 t° TRANSISTOR
TERMINAL F2 U (RED)
T 250V E 15A (BLACK) R.IN U
BLOCK P
(11) Outdoor unit inspection points
NOISE NU V V (WHITE) M
L 1 (WHITE) S.IN FILTER NV 3~
NW W W (BLACK) COMPRESSOR
N 2 MOTOR
(RED) C-2 F3 T 1A L 250V
3 (YELLOW/ PAM
F1
GREEN) G1 F4 CIRCUIT CNFAN M
(YELLOW/ 250V 2A
-
(YELLOW/ 250V 10A FAN MOTOR
GREEN) GREEN) G2 SWITCHING POWER
4 CIRCUIT
CN20S CNTH CNEEV
71 -
2 2 2 2
2 to 3 : Normal if the voltage oscillates between DC 0 and approx. 20V ◆Inspection of electronic expansion valve
(OUTDOOR UNIT ) t°
Power source
1 Phase
220-240V 50Hz
220V 60Hz
PCB ASSY PCB1
3
DIODE POWER
STACK1 T1 (YE) (YE) T2
F4 L1 TRANSISTOR
(BK) R.IN ~ +
250V 20A NOISE T11 (BL) (BL) T12 U (RD)
FILTER L2 P U
(WH) S.IN
+ + + V (WH) MS
~ - V
Models SRC45ZSP-W, 50ZSP-W
(RD) C-2 3~
F8 W (BK)
W
N
250V 20A CM
-
~ - CNFAN M
(WH)
N 2
FMo
3
72 -
(YG) (RD)
CN20S CNTH(BK) CNEEV(WH)
4
2 2 2 2
t゜
t゜
t゜
20S
TH1 TH2 TH3 EEV
1 -3
6 5 4 3 2 1
Expansion valve connector 1 -4
(6P, black)
Approx. DC5 V is detected for 10 seconds after the power on.
White
Yellow
Orange
Blue
Red
1 -5
1 -6
FM0
Measuring Voltage range when
point normal
⑥-④ DC 308-336V
③-④ DC 15V
White
Yellow
Blue
Red
Black
DC several (4-7V)
DC308-336V GND
DC15V
- 73 -
'20 • SRK-T-320
Declared capacity for cooling, at indoor temperature 27(19)℃ and Declared energy efficiency ratio, at indoor temperature 27(19)℃ and
outdoor temperature Tj outdoor temperature Tj
Tj=35℃ Pdc 2.50 kW Tj=35℃ EERd 3.52 -
Tj=30℃ Pdc 1.85 kW Tj=30℃ EERd 5.70 -
Tj=25℃ Pdc 1.25 kW Tj=25℃ EERd 9.36 -
Tj=20℃ Pdc 1.10 kW Tj=20℃ EERd 12.90 -
Declared capacity for heating / Average season, at indoor Declared coefficient of performance / Average season, at indoor
temperature 20℃ and outdoor temperature Tj temperature 20℃ and outdoor temperature Tj
Tj=-7℃ Pdh 2.50 kW Tj=-7℃ COPd 2.44 -
Tj=2℃ Pdh 1.44 kW Tj=2℃ COPd 3.98 -
Tj=7℃ Pdh 1.00 kW Tj=7℃ COPd 5.74 -
Tj=12℃ Pdh 1.10 kW Tj=12℃ COPd 7.30 -
Tj=bivalent temperature Pdh 2.50 kW Tj=bivalent temperature COPd 2.44 -
Tj=operating limit Pdh 2.40 kW Tj=operating limit COPd 2.06 -
Declared capacity for heating / Warmer season, at indoor Declared coefficient of performance / Warmer season, at indoor
temperature 20℃ and outdoor temperature Tj temperature 20℃ and outdoor temperature Tj
Tj=2℃ Pdh 3.30 kW Tj=2℃ COPd 2.34 -
Tj=7℃ Pdh 2.10 kW Tj=7℃ COPd 4.80 -
Tj=12℃ Pdh 1.10 kW Tj=12℃ COPd 7.30 -
Tj=bivalent temperature Pdh 3.30 kW Tj=bivalent temperature COPd 2.34 -
Tj=operating limit Pdh 2.40 kW Tj=operating limit COPd 2.06 -
Declared capacity for heating / Colder season, at indoor Declared coefficient of performance / Colder season, at indoor
temperature 20℃ and outdoor temperature Tj temperature 20℃ and outdoor temperature Tj
Tj=-7℃ Pdh - kW Tj=-7℃ COPd - -
Tj=2℃ Pdh - kW Tj=2℃ COPd - -
Tj=7℃ Pdh - kW Tj=7℃ COPd - -
Tj=12℃ Pdh - kW Tj=12℃ COPd - -
Tj=bivalent temperature Pdh - kW Tj=bivalent temperature COPd - -
Tj=operating limit Pdh - kW Tj=operating limit COPd - -
Tj=-15℃ Pdh - kW Tj=-15℃ COPd - -
Electric power input in power modes other than 'active mode' Annual electricity consumption
off mode Poff 6 W cooling Qce 129 kWh/a
standby mode Psb 6 W heating / Average Qhe 957 kWh/a
thermostat-off mode Pto(cooling) 11 W heating / Warmer Qhe 855 kWh/a
Pto(heating) 15 W heating / colder Qhe - kWh/a
crankcase heater mode Pck 0 W
Contact details for obtaining Name and address of the manufacturer or of its authorised representative.
more information MHIAE SERVICES B.V.
Herikerbergweg 238, Luna ArenA, 1101 CM Amsterdam, Netherlands
C RWA000Z275 C
- 74 -
'20 • SRK-T-320
Model SRK35ZSP-W
Information to identify the model(s) to which the information relates to: If function includes heating: Indicate the heating season the
Indoor unit model name SRK35ZSP-W information relates to. Indicated values should relate to one
Outdoor unit model name SRC35ZSP-W heating season at a time. Include at least the heating season 'Average'.
Declared capacity for cooling, at indoor temperature 27(19)℃ and Declared energy efficiency ratio, at indoor temperature 27(19)℃ and
outdoor temperature Tj outdoor temperature Tj
Tj=35℃ Pdc 3.20 kW Tj=35℃ EERd 3.52 -
Tj=30℃ Pdc 2.36 kW Tj=30℃ EERd 5.50 -
Tj=25℃ Pdc 1.52 kW Tj=25℃ EERd 9.70 -
Tj=20℃ Pdc 1.14 kW Tj=20℃ EERd 16.06 -
Declared capacity for heating / Average season, at indoor Declared coefficient of performance / Average season, at indoor
temperature 20℃ and outdoor temperature Tj temperature 20℃ and outdoor temperature Tj
Tj=-7℃ Pdh 2.66 kW Tj=-7℃ COPd 2.64 -
Tj=2℃ Pdh 1.62 kW Tj=2℃ COPd 4.36 -
Tj=7℃ Pdh 1.04 kW Tj=7℃ COPd 5.95 -
Tj=12℃ Pdh 1.19 kW Tj=12℃ COPd 7.48 -
Tj=bivalent temperature Pdh 2.66 kW Tj=bivalent temperature COPd 2.64 -
Tj=operating limit Pdh 2.57 kW Tj=operating limit COPd 2.21 -
Declared capacity for heating / Warmer season, at indoor Declared coefficient of performance / Warmer season, at indoor
temperature 20℃ and outdoor temperature Tj temperature 20℃ and outdoor temperature Tj
Tj=2℃ Pdh 3.60 kW Tj=2℃ COPd 2.55 -
Tj=7℃ Pdh 2.32 kW Tj=7℃ COPd 5.17 -
Tj=12℃ Pdh 1.19 kW Tj=12℃ COPd 7.48 -
Tj=bivalent temperature Pdh 3.60 kW Tj=bivalent temperature COPd 2.55 -
Tj=operating limit Pdh 2.57 kW Tj=operating limit COPd 2.21 -
Declared capacity for heating / Colder season, at indoor Declared coefficient of performance / Colder season, at indoor
temperature 20℃ and outdoor temperature Tj temperature 20℃ and outdoor temperature Tj
Tj=-7℃ Pdh - kW Tj=-7℃ COPd - -
Tj=2℃ Pdh - kW Tj=2℃ COPd - -
Tj=7℃ Pdh - kW Tj=7℃ COPd - -
Tj=12℃ Pdh - kW Tj=12℃ COPd - -
Tj=bivalent temperature Pdh - kW Tj=bivalent temperature COPd - -
Tj=operating limit Pdh - kW Tj=operating limit COPd - -
Tj=-15℃ Pdh - kW Tj=-15℃ COPd - -
Electric power input in power modes other than 'active mode' Annual electricity consumption
off mode Poff 6 W cooling Qce 154 kWh/a
standby mode Psb 6 W heating / Average Qhe 955 kWh/a
thermostat-off mode Pto(cooling) 11 W heating / Warmer Qhe 884 kWh/a
Pto(heating) 15 W heating / colder Qhe - kWh/a
crankcase heater mode Pck 0 W
Contact details for obtaining Name and address of the manufacturer or of its authorised representative.
more information MHIAE SERVICES B.V.
Herikerbergweg 238, Luna ArenA, 1101 CM Amsterdam, Netherlands
C RWA000Z275 C
- 75 -
'20 • SRK-T-320
Model SRK45ZSP-W
Information to identify the model(s) to which the information relates to: If function includes heating: Indicate the heating season the
Indoor unit model name SRK45ZSP-W information relates to. Indicated values should relate to one
Outdoor unit model name SRC45ZSP-W heating season at a time. Include at least the heating season 'Average'.
Declared capacity for cooling, at indoor temperature 27(19)℃ and Declared energy efficiency ratio, at indoor temperature 27(19)℃ and
outdoor temperature Tj outdoor temperature Tj
Tj=35℃ Pdc 4.50 kW Tj=35℃ EERd 3.33 -
Tj=30℃ Pdc 3.32 kW Tj=30℃ EERd 5.05 -
Tj=25℃ Pdc 2.13 kW Tj=25℃ EERd 7.75 -
Tj=20℃ Pdc 1.80 kW Tj=20℃ EERd 12.09 -
Declared capacity for heating / Average season, at indoor Declared coefficient of performance / Average season, at indoor
temperature 20℃ and outdoor temperature Tj temperature 20℃ and outdoor temperature Tj
Tj=-7℃ Pdh 3.36 kW Tj=-7℃ COPd 2.61 -
Tj=2℃ Pdh 2.05 kW Tj=2℃ COPd 4.10 -
Tj=7℃ Pdh 1.44 kW Tj=7℃ COPd 5.70 -
Tj=12℃ Pdh 1.62 kW Tj=12℃ COPd 7.10 -
Tj=bivalent temperature Pdh 3.36 kW Tj=bivalent temperature COPd 2.61 -
Tj=operating limit Pdh 3.09 kW Tj=operating limit COPd 2.34 -
Declared capacity for heating / Warmer season, at indoor Declared coefficient of performance / Warmer season, at indoor
temperature 20℃ and outdoor temperature Tj temperature 20℃ and outdoor temperature Tj
Tj=2℃ Pdh 4.30 kW Tj=2℃ COPd 2.76 -
Tj=7℃ Pdh 2.76 kW Tj=7℃ COPd 5.12 -
Tj=12℃ Pdh 1.62 kW Tj=12℃ COPd 7.10 -
Tj=bivalent temperature Pdh 4.30 kW Tj=bivalent temperature COPd 2.76 -
Tj=operating limit Pdh 3.09 kW Tj=operating limit COPd 2.34 -
Declared capacity for heating / Colder season, at indoor Declared coefficient of performance / Colder season, at indoor
temperature 20℃ and outdoor temperature Tj temperature 20℃ and outdoor temperature Tj
Tj=-7℃ Pdh - kW Tj=-7℃ COPd - -
Tj=2℃ Pdh - kW Tj=2℃ COPd - -
Tj=7℃ Pdh - kW Tj=7℃ COPd - -
Tj=12℃ Pdh - kW Tj=12℃ COPd - -
Tj=bivalent temperature Pdh - kW Tj=bivalent temperature COPd - -
Tj=operating limit Pdh - kW Tj=operating limit COPd - -
Tj=-15℃ Pdh - kW Tj=-15℃ COPd - -
Electric power input in power modes other than 'active mode' Annual electricity consumption
off mode Poff 7 W cooling Qce 251 kWh/a
standby mode Psb 7 W heating / Average Qhe 1269 kWh/a
thermostat-off mode Pto(cooling) 18 W heating / Warmer Qhe 1095 kWh/a
Pto(heating) 20 W heating / colder Qhe - kWh/a
crankcase heater mode Pck 0 W
Contact details for obtaining Name and address of the manufacturer or of its authorised representative.
more information MHIAE SERVICES B.V.
Herikerbergweg 238, Luna ArenA, 1101 CM Amsterdam, Netherlands
C RWA000Z275 C
- 76 -
'20 • SRK-T-320
Model SRK50ZSP-W
Information to identify the model(s) to which the information relates to: If function includes heating: Indicate the heating season the
Indoor unit model name SRK50ZSP-W information relates to. Indicated values should relate to one
Outdoor unit model name SRC50ZSP-W heating season at a time. Include at least the heating season 'Average'.
Declared capacity for cooling, at indoor temperature 27(19)℃ and Declared energy efficiency ratio, at indoor temperature 27(19)℃ and
outdoor temperature Tj outdoor temperature Tj
Tj=35℃ Pdc 5.00 kW Tj=35℃ EERd 2.87 -
Tj=30℃ Pdc 3.69 kW Tj=30℃ EERd 4.86 -
Tj=25℃ Pdc 2.37 kW Tj=25℃ EERd 7.65 -
Tj=20℃ Pdc 1.80 kW Tj=20℃ EERd 12.59 -
Declared capacity for heating / Average season, at indoor Declared coefficient of performance / Average season, at indoor
temperature 20℃ and outdoor temperature Tj temperature 20℃ and outdoor temperature Tj
Tj=-7℃ Pdh 3.36 kW Tj=-7℃ COPd 2.61 -
Tj=2℃ Pdh 2.05 kW Tj=2℃ COPd 4.10 -
Tj=7℃ Pdh 1.44 kW Tj=7℃ COPd 5.70 -
Tj=12℃ Pdh 1.62 kW Tj=12℃ COPd 7.10 -
Tj=bivalent temperature Pdh 3.36 kW Tj=bivalent temperature COPd 2.61 -
Tj=operating limit Pdh 3.09 kW Tj=operating limit COPd 2.34 -
Declared capacity for heating / Warmer season, at indoor Declared coefficient of performance / Warmer season, at indoor
temperature 20℃ and outdoor temperature Tj temperature 20℃ and outdoor temperature Tj
Tj=2℃ Pdh 4.30 kW Tj=2℃ COPd 2.76 -
Tj=7℃ Pdh 2.76 kW Tj=7℃ COPd 5.12 -
Tj=12℃ Pdh 1.62 kW Tj=12℃ COPd 7.10 -
Tj=bivalent temperature Pdh 4.30 kW Tj=bivalent temperature COPd 2.76 -
Tj=operating limit Pdh 3.09 kW Tj=operating limit COPd 2.34 -
Declared capacity for heating / Colder season, at indoor Declared coefficient of performance / Colder season, at indoor
temperature 20℃ and outdoor temperature Tj temperature 20℃ and outdoor temperature Tj
Tj=-7℃ Pdh - kW Tj=-7℃ COPd - -
Tj=2℃ Pdh - kW Tj=2℃ COPd - -
Tj=7℃ Pdh - kW Tj=7℃ COPd - -
Tj=12℃ Pdh - kW Tj=12℃ COPd - -
Tj=bivalent temperature Pdh - kW Tj=bivalent temperature COPd - -
Tj=operating limit Pdh - kW Tj=operating limit COPd - -
Tj=-15℃ Pdh - kW Tj=-15℃ COPd - -
Electric power input in power modes other than 'active mode' Annual electricity consumption
off mode Poff 7 W cooling Qce 283 kWh/a
standby mode Psb 7 W heating / Average Qhe 1269 kWh/a
thermostat-off mode Pto(cooling) 18 W heating / Warmer Qhe 1095 kWh/a
Pto(heating) 20 W heating / colder Qhe - kWh/a
crankcase heater mode Pck 0 W
Contact details for obtaining Name and address of the manufacturer or of its authorised representative.
more information MHIAE SERVICES B.V.
Herikerbergweg 238, Luna ArenA, 1101 CM Amsterdam, Netherlands
C RWA000Z275 C
- 77 -
INVERTER WALL MOUNTED TYPE
RESIDENTIAL AIR-CONDITIONERS
Because of our policy of continuous improvement, we reserve the right to make changes in all specifications without notice.
C Copyright
Because of our policy of continuous improvement, MITSUBISHI
we reserve the rightHEAVY
to makeINDUSTRIES
changes in allTHERMAL SYSTEMS,
specifications LTD.
without notice.
C Copyright MITSUBISHI HEAVY INDUSTRIES THERMAL SYSTEMS, LTD.