Australian Standard: Maintenance of Electrical Switchgear
Australian Standard: Maintenance of Electrical Switchgear
AS 2467—2008
Australian Standard®
Standards Australia wishes to acknowledge the participation of the expert individuals that
contributed to the development of this Standard through their representation on the
Accessed by BHP Billiton - HVEC on 21 Sep 2015 (Document currency not guaranteed when printed)
Committee.
Standards may also be withdrawn. It is important that readers assure themselves they are
using a current Standard, which should include any amendments that may have been
published since the Standard was published.
Detailed information about Australian Standards, drafts, amendments and new projects can
be found by visiting www.standards.org.au
Australian Standard®
Originated as AS CC9—1965.
Revised and redesignated as AS 2467—1981.
Second edition 2008.
COPYRIGHT
© Standards Australia
All rights are reserved. No part of this work may be reproduced or copied in any form or by
any means, electronic or mechanical, including photocopying, without the written
permission of the publisher.
Published by Standards Australia GPO Box 476, Sydney, NSW 2001, Australia
ISBN 0 7337 8527 1
AS 2467—2008 2
PREFACE
This Standard was reviewed by the Standards Australia Committee EL-007, Power
Switchgear, to supersede AS 2467—1981.
This Standard is republished from AS 2467—1981, without technical alterations.
Referenced Standards have been updated.
The objective of this Standard is to provide basic recommendations for the safety of
personnel in proximity to or engaged in maintenance of electrical switchgear and includes
detailed recommendations for particular types of switchgear.
This Standard sets out a standard of good practice and generally takes the form of
recommendations. Compliance with it does not confer immunity from relevant statutory and
legal requirements (see Clause 1.3).
The terms ‘normative’ and ‘informative’ are used to define the application of the Appendix
to which they apply. A normative Appendix is an integral part of a standard, whereas an
informative Appendix is only for information and guidance.
Accessed by BHP Billiton - HVEC on 21 Sep 2015 (Document currency not guaranteed when printed)
3 AS 2467—2008
CONTENTS
Page
Page
Page
APPENDICES
A EXAMPLE OF ELECTRICAL SAFETY RULES..................................................... 69
B MAINTENANCE RECORD FORMS ....................................................................... 80
C FIRE PROTECTION EQUIPMENT.......................................................................... 84
D GRAPHICAL ILLUSTRATION OF SOME OF THE TERMS AND DEFINITIONS
GIVEN IN CLAUSE 1.4 ........................................................................................... 85
E APPROPRIATE ACTS AND REGULATIONS ........................................................ 86
F REFERENCED DOCUMENTS ................................................................................ 89
AS 2467—2008 6
STANDARDS AUSTRALIA
Australian Standard
Maintenance of electrical switchgear
1.1 SCOPE
This Standard sets out procedures and recommendations for the maintenance of electrical
switchgear. It is applicable to electrical switchgear having rated voltages not greater than
145 kV. At voltages above this level the design of equipment, system operations and
consequently maintenance requirements and practices may differ significantly from those at
voltages up to this level. However, the principles formulated in this Standard as good
practice, especially those regarding the safety of personnel, are for the most part applicable
at the higher voltages.
The Standard does not apply to the maintenance of electrical switchgear—
(a) of sealed construction intended only to be returned to the manufacturer for adjustment
and repair; or
(b) used in explosive atmospheres and in coal mines. Reference should be made to
appropriate Standards for the maintenance of electrical equipment used in explosive
atmospheres and in coal mines.
Accessed by BHP Billiton - HVEC on 21 Sep 2015 (Document currency not guaranteed when printed)
1.2 RATIONALE
Electrical switchgear, by the nature of the service it renders, does not automatically call for
the maintenance attendance which is necessary to ensure its effective functioning at all
times. Its normally quiescent state does not generally draw attention to incipient faults or
deterioration or to the danger resulting from neglect.
It follows therefore that only an organized system of routine maintenance planned to
include all necessary details can ensure continued safe and satisfactory operation of an
electrical system with a minimum risk of breakdown and the consequent interruption of
supply.
NOTE: In this Standard, the words ‘examination’ and ‘inspection’ have a meaning strictly as
defined in Clauses 1.6.4 and 1.6.6 respectively.
1.3 OBJECT
The object of this Standard is to provide in a convenient form a record of those matters
which technical knowledge and experience have shown to be important in keeping electrical
switchgear, both indoor and outdoor, and its associated apparatus in an acceptable
condition. It also draws attention to the precautions which should be observed in order to
secure the safety of personnel while maintenance is in progress, and in this respect the
following matters are covered:
(a) Safety rules.
(b) Safety features of equipment.
(c) Measures to minimize hazards to plant and to ensure continuity of service.
(d) The use of electrical testing to detect insulation weakness or the deteriorating
condition of insulation.
1.4 APPLICATION
The application of Sections 2 to 14 is as follows:
(a) Section 2 sets out general provisions and rules for the safety of personnel engaged in
the maintenance of switchgear, first aid and the responsibility of authorized persons.
(b) Section 3 sets out general design considerations for a switchgear installation, safe
practices for the use of equipment emergency exits, instruction and warning notices
and provision of facilities to minimize the risk of injury, damage to equipment and
fire.
(c) Section 4 deals with the determination of the frequency of maintenance operations for
items of switchgear, components and materials in relation to service duty and
conditions of use.
(d) Section 5 applies to the maintenance of switchgear, intended to be serviced, for
voltages up to 1000 V a.c. and 1200 V d.c.
(e) Section 6 applies to the maintenance of air-break switchgear for voltages above
1000 V a.c. and 1200 V d.c. A number of the recommendations in this Section are
applicable to other types of high-voltage switchgear and reference is made in
subsequent Sections to appropriate clauses of Section 6.
(f) Section 7 applies to the maintenance of oil switchgear.
(g) Section 8 applies to the maintenance of air-blast circuit-breaker switchgear and
compressed air handling equipment in installations of such switchgear.
(h) Section 9 applies to the maintenance of vacuum circuit-breaker switchgear.
(i) Section 10 applies to the maintenance of sulphur hexafluoride (SF 6) switchgear and
special safety measures necessary due to the properties of this gas.
Accessed by BHP Billiton - HVEC on 21 Sep 2015 (Document currency not guaranteed when printed)
(j) Section 11 sets out diagnostic testing methods and procedures which are
recommended to prolong the intervals between dismantling of equipment for routine
maintenance.
(k) Section 12 applies to the maintenance of auxiliary equipment items such as batteries,
compressed air plant, transformers, earthing connections and oil handling plant.
(l) Section 13 applies to the maintenance of protective apparatus, fuses and relays.
(m) Section 14 deals with the testing and maintenance of electrical insulation.
1.6 DEFINITIONS
For the purpose of this Standard, the following definitions apply. Those marked with an
asterisk (*) are illustrated graphically in Appendix D.
1.6.1 Acceptable conditions*
The condition in which an item is able to perform its required function and/or meet the
relevant specification.
1.6.8 Maintenance
A combination of any actions carried out to retain an item in, or restore it to, an acceptable
condition.
1.6.8.1 Non-routine maintenance
Unplanned maintenance which is not the result of a breakdown.
1.6.8.2 Preventive maintenance*
Maintenance carried out with the objective of preventing breakdown and which may include
routine or non-routine maintenance. (See also Appendix B.)
1.6.8.3 Post-fault maintenance
Maintenance necessary on switchgear after a specified number of fault clearance operations.
1.6.8.4 Repair or corrective maintenance*
Maintenance necessary to restore to an acceptable condition an item which has ceased to
meet an acceptable condition.
1.6.8.5 Routine maintenance
Maintenance organized and carried out in accordance with a predetermined policy or plan to
prevent breakdown or reduce the likelihood of an item failing to meet an acceptable
condition.
1.6.9 Operational check
An action carried out to determine whether an item functions correctly.
1.6.10 Test
A measurement carried out to determine the condition of an item.
SE C T I ON 2 S A FE T Y O F PE RSO N N E L
2.1 GENERAL
In view of the potential dangers associated with electrical equipment, appropriate measures
shall be taken to safeguard personnel.
NOTE: Attention is drawn to the statutory requirements applicable to persons engaged in the
maintenance of electrical switchgear and associated equipment.
2.2 RESPONSIBILITY
2.2.1 Statutory requirements
It is the responsibility of engineers and other supervisory personnel engaged in electrical
work or operations to become acquainted with the statutory requirements applicable to their
industry.
2.2.2 Authorized person
Any person to whom responsibility for electrical safety is delegated should be designated as
an authorized person.
2.4 ACCESS
Access to electrical stations should be restricted and, where necessary, suitable barriers
should be installed to prevent access to enclosures, chambers, cubicles or cells containing
exposed live conductors.
SEC T I ON 3 S A FE T Y P RO V IS I O N S FO R
MA I N T E N A N CE O PE RA T I O N S
3.1 GENERAL
The performance and safe operation of electrical equipment is dependent on the initial
design of the electrical station and the layout, installation and environment of the
equipment. It is therefore important that these aspects be considered at the design and
installation stages.
Clauses 3.2 to 3.16 list the operation and maintenance procedures which should be carried
out to maintain the safety provisions.
should include inspection of any seals provided on cable access points and any other
provision made to prevent the passage of flame, smoke, gas or liquid or of any fire-resisting
barriers.
Where steps have been taken in an electrical station to prevent the spreading of an oil
spillage, such as the provision of dwarf walls, raised door thresholds or catchment areas,
these should be inspected to see that they are effective, and that any gravel or pebble bed
used is in a porous condition.
3.6 LIGHTING
Adequate lighting, either fixed or portable or a combination of both, shall be provided to
ensure safe access and working conditions for all personnel in electrical stations.
3.7 ACCESS
Electrical stations should be designed to prevent access and interference by unauthorized
persons. Inspections should be made to see that this security is maintained. Doors and other
means of entry should be kept secure by locking or other suitable methods.
To avoid danger, working space and access ways provided to apparatus and equipment
Accessed by BHP Billiton - HVEC on 21 Sep 2015 (Document currency not guaranteed when printed)
which is to be worked upon or operated should be properly maintained and kept free of
obstructions. (See AS 2067 for information on safety clearances.).
Provisions for access to allow work on equipment should be as recommended by the
manufacturer. Work platforms should not be erected around the equipment until after the
equipment has been isolated, earthed and made inoperative. The leaning of ladders against
porcelain insulation is not generally recommended.
Notices and labels required by statutory regulations shall be displayed together with any
other notices or labels necessary for identification of equipment and its function.
3.16.2 Removal and replacement of identification labels
Where more than one unit of switchgear is out of service in the one switchroom, particular
care should be taken to avoid inadvertent removal, replacement or exchange of labels which
have previously been attached to the switchgear units removed from service.
3.16.3 Caution and danger plates
Adequate quantities of caution and danger plates should be kept in the electrical station for
immediate use with the number of safety locks (see Appendix A, rule 7) required for the
operation of the equipment. (See also AS 1319.).
3.16.4 Emergency exits
Emergency exits should be clearly labelled as such inside and outside. The labels should be
clearly visible even under adverse conditions.
Accessed by BHP Billiton - HVEC on 21 Sep 2015 (Document currency not guaranteed when printed)
SE C T I ON 4 F R E Q U E N CY O F M A I N T E N A N CE
OPERAT I ONS
4.1 GENERAL
Because of the widely varying conditions of operation of individual switchgear
installations, it is not always possible to lay down a general recommendation for the
intervals between maintenance operations. These intervals may vary greatly depending
upon the design of the switchgear, the duty that it is called on to perform, and the
environment in which it is situated.
insulation, recommended clearance, and setting and efficacy of the close/open operations as
a whole.
These inspections or examinations can give guidance on the intervals that might be allowed
to elapse between future inspections, examination and overhaul operations with reference to
particular service conditions. When estimating these intervals it would be necessary to
consider the condition of the equipment at the time of the examination with regard to the
following:
(a) Contamination of external insulation.
(b) Condition of internal insulation including oil where appropriate.
(c) Condition of contacts, interrupting devices and connections.
(d) Condition of operating mechanisms and their lubrication.
(e) Condition of weather seals and gaskets.
(f) Condition of protective finishes and signs of corrosion.
4.2.2.2 Contacts, arc-control devices and internal insulation
The condition of contacts and arc-control devices will normally depend on the number of
operations performed by a circuit-breaker and whether such operations are load or fault-
current breaking. It will assist if a log of switching operations is kept.
Similar considerations may apply to the condition of the internal insulation, but in this case
the influence of moisture ingress may be relevant, this factor being generally affected by
the length of time in service.
4.2.2.3 Mechanisms
The condition of mechanisms is affected by the number of operations, the environmental
surroundings, and the period of service.
4.2.2.4 Basis for the determination of intervals between maintenance operations
The intervals between maintenance operations may be based on the number of operations
performed or on fixed time intervals, the preferred basis being determined by the electrical,
mechanical and environmental duties imposed on the switchgear. In practice a combination
of these criteria may be used in the light of service experience with individual installations.
NOTE: An example of a typical fault openings form is given in Appendix B.
4.2.3 Records
It is important to keep records of the maintenance carried out. In this connection a record of
the ‘as found’ condition of the equipment can give an effective indication of the
maintenance required and a means of assessing any necessary change in frequency. A
review of these records may highlight design or application defects.
It should be noted that whilst excessive operations may dictate more frequent maintenance
the converse cannot normally be held to be true.
NOTE: Examples of typical maintenance record forms are given in Appendix B.
4.2.4 Routine maintenance
4.2.4.1 Basis for organization
It is preferable that routine maintenance be organized on the basis of regular inspections
supplemented at more extended intervals with operational checks and examination with
some dismantling as required. The inspections should ensure that no damage or distress has
been sustained in the course of operations whereas the examination enables the
Accessed by BHP Billiton - HVEC on 21 Sep 2015 (Document currency not guaranteed when printed)
Based on operating experience and on test evidence, the user, preferably after reference to
the manufacturer for information, may decide on a permitted operating sequence which may
in certain circumstances, e.g. vacuum circuit-breakers, be well in excess of the rated
operating sequence. It is necessary, however, to ensure that the permitted operating
sequence for particular circuit-breakers is not exceeded without post-fault maintenance
being carried out.
1 The presence of carbon particles alone in oil does not necessarily indicate that the oil is in an
unacceptable condition.
2 Where insulating oil is used for insulation purposes only, special testing techniques such as
dissolved gas analysis may be necessary to detect deterioration of the oil or associated
insulation.
4.3.4 Normal maintenance tests
Electrical strength tests, and where ingress of moisture is likely, water content tests in
accordance with AS 1883 are recommended as the normal maintenance tests. There is
normally no necessity to test for acidity or flashpoint in switchgear insulating oil.
4.3.5 Auto-reclosing duty
Where switchgear is employed for auto-reclosing duty, the user may decide upon the
acceptable number of operations before oil is tested, by reference to operating experience,
test experience and/or consultation with the switchgear manufacturer.
the intervals between maintenance operations will be less than those stated in Clause 4.4.3.
In the case of circuit-breakers operated frequently to control, e.g. an electric arc furnace or
similar equipment, the intervals between maintenance operations could be measured in
weeks.
In such cases it may be preferable to relate the intervals to the number of switching
operations rather than time.
NOTE: See Clause 5.7 for a summary of recommended maintenance operations.
S E C T I ON 5 M A I N T E N A N CE O F
SWI T C H GE A R I N T E N D E D T O O PE RA T E A T
VO L TAGES UP TO 1000 V a.c. AN D
1 20 0 V d . c.
5.4.2.2 Cleaning
All loose external dirt should first be removed. In the cleaning of switchgear it is most
important not to use what is generally known as cotton waste. Material used for this
purpose should be clean and free from loose fibres, metallic threads and similar particles.
Brushes and blower nozzles should contain no metallic material.
Care should be taken to prevent loose parts, tools metal filings or dirt falling into the
apparatus.
Cleaning fluids should be very carefully selected to ensure compatibility with organic
insulation plastics, valve gear and bearings, rubber and synthetic ‘O’ rings, and other
materials used in the construction of the equipment. They should also be safe for use by
personnel.
5.4.2.3 Insulation
Insulation should be inspected, cleaned and renewed where necessary. Porcelain and
moulded insulation should be inspected for cracks or other defects. Bonded and laminated
fibrous and other organic insulation should be inspected for signs of tracking, treeing,
blistering, delamination or mechanical damage. On this type of equipment, which often
cannot be isolated, insulation resistance tests are only necessary where the insulating
material is suspect or when the connected circuits are to be tested.
For further information on the maintenance and testing of insulation see Section 14.
5.4.2.4 Equipment enclosures
Operation of any heaters should be verified, and any anti-condensation finishes inspected
for signs of deterioration.
5.4.2.5 Contacts
The following recommendations apply to contacts:
(a) Contacts should be examined for burning, overheating, misalignment or other damage
and reconditioned or renewed as required. It should be verified, by means of special
tools if provided, that bolted or wedge type contacts are correctly tightened.
Overheating may be caused by overloading, loose connections, insufficient contact
force, ineffective fuse-link contact or lack of alignment of switch contacts, and
sometimes may be detected only with the equipment on load.
(b) Slight discoloration or burning of bare copper or copper alloy contacts is not
necessarily harmful but may be removed by suitable abrasive cloth or a fine file. The
amount of material removed from contacts should be kept to a minimum and the
manufacturer’s recommended profile should be maintained. It is important that the
spring force between the contact surfaces should not be significantly reduced.
Modern high-pressure point or line contacts will normally carry their rated current
satisfactorily even if there is some pitting of the surface. Large beads or ridges on the
contacting members that would seriously impede closing or opening should be
removed.
(c) It is usually undesirable to attempt to clean or dress tipped or plated contacts and the
manufacturer’s recommendations should be followed. Silver or silver-plated contacts
seldom require cleaning despite a black appearance. If it is required to clean them,
silver polish may be used.
(d) When contacts are refitted, renewed or refurbished, the contact force, alignment and
wipe should be verified.
Accessed by BHP Billiton - HVEC on 21 Sep 2015 (Document currency not guaranteed when printed)
(e) Any flexible braids should be inspected, especially for fraying at the terminations,
and renewed if necessary. Where exposed to the atmosphere, the braids may be
treated with a suitable protective compound which will not impair their flexibility.
(f) Any recommendations of the manufacturer for treatment of the contacts should be
followed. Caution should be taken with the use of lubricants in dusty situations.
5.4.2.6 Arc-control devices and interpole barriers in the vicinity of the arc
Arc-control devices and interpole barriers in the vicinity of the arc should be examined and
cleaned or, if badly burned, renewed.
Where the surface finish of an arc-control device is critical to its performance, the device
should not be abraided during cleaning, but renewed.
Any air-puffer device should be checked for correct operation.
As far as is reasonably practicable, arc-control devices should be examined to ensure that
they are securely fastened, correctly adjusted and electrically connected. All adjustments
should be carried out in accordance with the manufacturer’s instruction.
5.4.2.7 Mechanisms
Mechanisms should be cleaned and examined and any worn parts renewed. It should be
verified that circlips are correctly seated and that split pins are opened.
5.4.2.8 Indicating devices and interlocks
The following recommendations apply to indicating devices and interlocks:
(a) Indicating devices such as mechanical ‘ON’ and ‘OFF’ indicators, semaphores, etc.
should be inspected to ensure that they are in good order and operating correctly.
(b) Correct operation of any interlocks and padlocking devices should be verified and any
adjustments required should be made.
Provided the necessary precautions have been taken, it should also be verified that
interlocks inhibit the incorrect actions.
5.4.2.9 Connections
It should be verified that all joints are sound and that good contact is maintained on current-
carrying, main earth and secondary earth connections.
NOTE: Care should be exercised when re-making aluminium connections (see AS 62271.301).
5.4.2.10 Fuses
It should be verified that fuse connections are tight and that the rating of fuses is correct.
Fuse-links should be inspected for signs of deterioration.
The fusible elements of semi-enclosed fuses should be renewed where deterioration is
suspected.
5.4.2.11 Cable terminations
Any compound-filled cable termination associated with the switchgear should be inspected
for compound leakage or distortion and any defect corrected. Cable tails and risers should
be inspected for overheating of connections or distortion.
5.4.2.12 Contactors
In addition to any relevant previous operations, the following should be carried out:
(a) Remove loose particles and dust from arc chutes and replace the arc chutes where
necessary. Inspect contacts and springs. Contacts should normally be allowed to bed
in until erosion necessitates replacement.
(b) Pivots should be lightly lubricated if required (refer to manufacturer’s instructions)
Accessed by BHP Billiton - HVEC on 21 Sep 2015 (Document currency not guaranteed when printed)
and armature pole faces cleaned. It should be verified that any shading rings are in
position.
(c) Contacts should be free to operate and should not foul the arc chutes.
(d) The alignment and security of the tube and flexible connections of mercury tube
contacts should be verified.
5.4.2.13 Busbars and busbar chambers
Any barriers and supports should be examined as is reasonably practicable, and in
accordance with the following:
(a) Air insulated equipment For air insulated equipment the examination should include
any dismantling required to enable connections to be inspected and any chambers to
be cleaned.
(b) Compound filled equipment For compound filled equipment, the examination should
be limited to the verification of the filling level and an inspection for signs of leakage
of the compound, moisture ingress and irregularities on the surface of the compound.
5.4.2.14 Final verification
Before the equipment is returned to service, the following should be done:
(a) Verification of tightness of circuit and earth connections.
(b) Verification of insulation resistance of circuit including auxiliary wiring.
(c) An operational check.
TABLE 5.1
MAINTENANCE OPERATIONS FOR SWITCHGEAR INTENDED FOR
OPERATION AT VOLTAGES UP TO 1000 V a.c. AND 1200 V d.c.*
1 2 3 4 5
Routine maintenance
Maintenance operation Pre-maintenance Inspection Examination Post-fault
requirements and overhaul maintenance
Safety of personnel 5.1.1
Equipment to be replaced inoperative 5.1.2
General inspection 5.4.1.1 5.4.1.1
Diagnostic testing 5.3 and
Section 11
Cleaning 5.4.2.2 5.5
Insulation 5.4.2.3 5.4.2.3
Enclosures 5.4.2.4
Contacts 5.4.2.5 5.4.2.5 5.5
Arc control devices 5.4.2.6 5.4.2.6 5.5
Mechanisms 5.4.2.7 5.4.2.7 5.5
Indicating devices and interlocks 5.4.2.8 5.4.2.8
Connection 5.4.2.9
Fuses 5.4.2.10 5.4.2.10
Cable terminations 5.4.2.11 5.4.2.11
Accessed by BHP Billiton - HVEC on 21 Sep 2015 (Document currency not guaranteed when printed)
Contactors 5.4.2.12
Busbars and busbar chambers 5.4.2.13
Final verification 5.4.2.14 5.4.2.14
Auxiliary equipment Section 12 Section 12 5.5
* The number quoted in the columns refers to the appropriate clause number.
SECT I O N 6 MA I N T E N A N CE O F A I R- B RE A K
SWITC H G E A R I N T E N D E D FO R O PE RA T I O N A T
VO L TAGES ABOVE 10 00 V a.c. AN D
1 2 0 0 V d . c.
For switchgear of the fully pressurized type, the switchgear should be in the
manufacturer’s recommended position, open or closed, for the draining of gas from
the receiver. If necessary the manufacturer’s instructions should be consulted.
NOTE: It is important to note that freezing of the drain valve can occur during draining so
that although air has ceased to pass through it, the pressure in the receiver may still be above
atmospheric pressure. To ensure that the air pressure has been completely released, the
pressure gauge should be checked to ensure that it is reading zero, i.e. atmospheric pressure.
(d) Stored energy devices—should be discharged.
(e) Tripping devices—should be tripped.
(f) Fuses or links—should be removed.
(g) Removable or withdrawable switchgear—before any work is carried out on the fixed
isolating contacts, the contacts should be isolated and earthed.
(h) Shutters—any shutters or other devices preventing access to isolating contacts which
may be live, should be locked closed.
6.1.3 Manufacturer’s operation and maintenance instructions
The equipment manufacturer’s operation and maintenance instructions should be read in
conjunction with this Standard.
6.1.4 Replacement parts
The suitability and interchangeability of replacement parts should be verified.
A general inspection of the substation or switchroom should be made, attention being given
to general cleanliness, heating, ventilation and other relevant requirements detailed in
Section 3. During this inspection, the condition of weather seals, signs of corrosion, leakage
of oil or compound, any unusual smell which may indicate overheating, and any noise
which may indicate electrical discharge or looseness of components should be investigated.
Also, as far as is reasonably practicable, any external insulation, trip mechanism, shutter
mechanism, gas vents, earth connection and other visible parts should be inspected for any
signs of abnormality.
Inspections should be made to ensure that any ancillary equipment, spare fuses, special
tools or other equipment required for the operation of the switchgear are available and in
good order.
6.5.1.2 Inspection of specific items of equipment
Attention should be given to the items where a clause number is shown in column 3 of
Table 6.1 (see Clause 6.9).
6.5.2 Examination and overhaul
6.5.2.1 General
Overhauls should only be carried out on such items as an inspection, examination or
manufacturer’s recommendation indicates to be necessary.
Clauses 6.5.2.2 to 6.5.2.21 give operations which may be required to be carried out during
maintenance.
6.5.2.2 Cleaning
All loose external dirt should first be removed. To avoid ingress of dirt into any internal
portion of the circuit-breaker, any joint or gasket should be cleaned prior to commencing
any dismantling. This is particularly important in the case of pneumatic valve gear, as
relatively small particles of dirt can cause damage, leakage or malfunctions.
In the cleaning of switchgear it is most important not to use what is generally known as
cotton waste. Materials used for this purpose should be clean and free from loose fibres,
metallic threads and similar particles. Brushes and blower nozzles should contain no
metallic material.
Care should be taken to prevent loose parts, tools, metal filings or dirt falling into the
apparatus.
Cleaning fluids and lubricants applied after cleaning should be very carefully selected to
ensure compatibility with organic insulation, plastics, valve gear and bearings, rubber and
synthetic ‘O’ rings, and other materials used in the construction of the equipment. They
should also be safe for use by personnel.
6.5.2.3 Insulation
Insulation should be inspected, cleaned and renewed where necessary. Porcelain and
moulded insulation should be inspected for cracks or other defects. Bonded and laminated
fibrous and other organic insulation should be inspected for signs of tracking, treeing,
blistering, delamination or mechanical damage. Insulation resistance tests are strongly
recommended as these give an indication of the condition of the insulation.
For further information on the maintenance and testing of insulation see Section 14.
6.5.2.4 Equipment enclosures
Accessed by BHP Billiton - HVEC on 21 Sep 2015 (Document currency not guaranteed when printed)
Operation of any heaters should be verified and any anti-condensation finishes inspected for
signs of deterioration.
6.5.2.5 Contacts
The following recommendations apply to contacts:
(a) Contacts should be examined for burning or other damage and reconditioned or
renewed as required. It should be verified that any backing springs are exerting the
correct force and that the contacts are in correct alignment.
It will be expected that the arcing contacts will show signs of burning and erosion,
but this will not be harmful provided that it is not excessive and provided that the
correct lead between the arcing and main contacts can be obtained. The security of
any arc-resisting tips should be checked. It should be remembered that the normal
duty of arcing tips is to carry the arc root but if excessive burning and/or erosion is
present the tips should be renewed.
(b) Hinge contacts should be examined for any signs of overheating, burning, welding or
other damage, and be reconditioned, adjusted or replaced as necessary. If such
damage is found, the cause should be investigated. Contacts should be inspected for
signs of arcing in other than normal places.
(c) Slight discoloration or burning of bare copper or copper-alloy contacts is not
necessarily harmful but may be removed by suitable abrasive cloth or a fine file. The
amount of material removed from contacts should be kept to a minimum and the
manufacturer’s recommended profile should be maintained. If necessary, the contacts
should be renewed. It is important that the spring force between the contact surfaces
not be significantly reduced.
Modern high-pressure point or line contacts will normally carry their rated current
satisfactorily even if there is some pitting of the surface. Large beads or ridges on the
contacting members that would seriously impede closing or opening should be
removed.
(d) For circuit-breakers using high-pressure contacts, e.g. high-speed circuit-breaker, or
special ‘tipped’ contacts, it is usually undesirable to attempt to clean or to dress the
contacts, and the manufacturer’s recommendations should be followed. Silver or
silver-plated contacts seldom require cleaning despite a black appearance. If it is
required to clean them, silver polish may be used.
(e) For laminated wiping contacts, the manufacturer’s recommendations should be
followed.
(f) When contacts are refitted, renewed or refurbished, contact force, alignment and wipe
should be verified.
(g) Any flexible braids should be inspected especially for fraying at the terminations, and
renewed if necessary. Where exposed to the atmosphere, the braids may be treated
with a suitable protective compound which will not impair their flexibility.
(h) The manufacturer’s recommendations should be followed concerning lubrication of
contacts pivots and hinge pins.
6.5.2.6 Arc-control devices and interpole barriers in the vicinity of the arc
Arc-control devices and interpole barriers in the vicinity of the arc should be examined and
cleaned or, if badly burned, renewed.
Where the surface finish of an arc-control device is critical to its performance, the device
should not be abraided during cleaning, but renewed.
Accessed by BHP Billiton - HVEC on 21 Sep 2015 (Document currency not guaranteed when printed)
(d) Closing mechanism The closing mechanism should be cleaned and examined and
any worn parts renewed. It should be lubricated as necessary, and all surplus oil and
grease removed.
The mechanical details of the closing mechanism should be examined and the correct
operation of any damping devices verified. For spring closing gear, special attention
should be paid to ratchet wheels and pawls, which should be examined for broken or
chipped teeth.
Where motor-wound springs are employed, the motor and its connections should be
examined and the reduction gear treated with the recommended lubricant.
Inspect line valves and joints of air-closing mechanisms. Recording of mechanism
settings may indicate the progression of wear or relaxation.
NOTE: There are statutory obligations to inspect air receivers (pressure vessels) periodically,
at which time safety and reducing valves, if fitted, should also be inspected.
(e) Interpole linkages Interpole linkages usually have carefully fitted linkage pins, and
minimum backlash mechanisms. It is important that these features be examined and
adjusted as required.
6.5.2.8 Auxiliary switches, indicating devices and interlocks
The following recommendations apply:
(a) Auxiliary switches Auxiliary switches should be kept in clean and sound condition
because upon them depends the correct functioning of other items of equipment,
including protective gear.
The contacts should be inspected and cleaned, and renewed if necessary. Where
possible, correct contact force, freedom of operating links and correct timing of
Accessed by BHP Billiton - HVEC on 21 Sep 2015 (Document currency not guaranteed when printed)
(d) Contacts Main and auxiliary contacts should be inspected, cleaned or renewed and
lubricated sparingly, if required, with the recommended lubricant. It should be
verified that contact backing or garter springs exert correct force and that contacts are
in correct alignment.
NOTE: Infrared detection techniques may be of assistance in the assessment of contact
condition (see Clause 11.3.2).
(e) Hinged contact springs The force of hinged contact springs should be verified and
lubricant should be applied to the hinges. Flexible connections should be inspected
for fraying, especially at the terminations, and for deterioration of any protective
oversheaths. Protective compound may be applied to protect bare copper flexibles in
outdoor conditions. The security of linkages should be verified and a lubricant should
be applied to the pivots of any supporting pantograph.
(f) Arc horns Arc horns should be inspected for damage and security of fixings should
be verified. It should also be verified that the horn wipes lightly through the opening
stroke and does not foul the closing stroke.
(g) Insulation Insulation should be carefully cleaned and inspected for cracks or other
damage and any defective components renewed.
(h) Operating rod insulators Operating rod insulators such as wood laminates should be
examined for both mechanical and electrical condition and should be refurbished or
changed as necessary.
(i) Joints and connections It should be verified that all joints and connections,
including earth connections are sound.
NOTES:
1 Care should be exercised when re-making aluminium connections (see AS 62271.301).
Accessed by BHP Billiton - HVEC on 21 Sep 2015 (Document currency not guaranteed when printed)
To check for possible deterioration of the compound, the insulation resistance should
be recorded at regular intervals, as a guide say every 10 years. Any significant change
in values may require a thorough investigation of the condition of the compound.
6.5.2.20 Weather shields
It should be verified that any weather shield fitted to the equipment is securely fixed and
that it is in a serviceable condition before the equipment is re-energized.
6.5.2.21 Final verification
Before the equipment and auxiliary apparatus are returned to service, an insulation
resistance test should be carried out (see Section 12), followed by an operational check.
TABLE 6.1
MAINTENANCE OPERATIONS FOR AIR-BREAK SWITCHGEAR INTENDED
FOR OPERATION ABOVE 1000 V a.c. AND 1200 V d.c.*
1 2 3 4 5
Routine maintenance
Pre-maintenance Post-fault
Maintenance operation Examination
requirements Inspection maintenance
and overhaul
Safety of personnel 6.1.1
Equipment to be rendered inoperative 6.1.2
Diagnostic testing 6.3 6.3
Operational check 6.4 6.4 6.4
General inspection 6.5.1.1 6.5.1.1
Cleaning 6.5.2.2 6.6
Insulation 6.5.2.3 6.5.2.3 6.6
Enclosures 6.5.2.4 6.5.2.4
Contacts 6.5.2.5 6.6
Arc-control devices and interpole barriers 6.5.2.6 6.6
Mechanisms 6.5.2.7 6.6
Auxiliary switches 6.5.2.8
Indicating devices and interlocks 6.5.2.8
Isolating contacts 6.5.2.9
Accessed by BHP Billiton - HVEC on 21 Sep 2015 (Document currency not guaranteed when printed)
SE C T I ON 7 M A I N T E N A N CE O F O I L
S W I T CH G E A R
7.3.1.1 Cleaning
For the cleaning of oil compartments it is good practice to use only chamois leather or
plastics sponges.
7.3.1.2 Insulation
Oil-filled bushings should be inspected for leaks and the oil level should be checked and
corrected if necessary.
Any water sumps of oil barrier bushings should be drained.
NOTE: As conducting films can occur on the bushings of outdoor switchgear special cleaning
liquids may be recommended by the manufacturer.
7.3.1.3 Arc-control devices
The following recommendations apply to arc-control devices:
(a) These should be inspected or examined and cleaned and, if there is a change in
volume or orifice size, or if they are badly burned, they should be renewed. Care
should be taken that vent holes and contact orifices are cleaned and the devices
should be flushed out with clean oil before being refitted. Retightening of any
assembly bolts may be necessary.
(b) Arc-control devices made from compressed fibrous materials which cannot be cleaned
without abrasion should be renewed. Other materials should be treated in accordance
with the manufacturer’s instructions.
Assemblies which have been removed should be immersed in clean oil during work
delays to prevent entry of moisture.
(c) Any resistors and connections should be checked for continuity or resistance value.
(d) As far as is reasonably practicable arcing tips and arc-control devices should be
inspected to ensure that they are securely fastened, correctly adjusted and electrically
connected.
(e) Vent holes and contact orifices shall be in their correct positions relative to the
contact system when arc control devices are being refitted.
(f) All adjustments should be carried out in accordance with the manufacturer’s
instruction.
7.3.1.4 Venting, gas seals and breathers
The venting system should be checked to ensure that a free passage for oil and gases exists.
Where there is a joint between fixed and movable portions of the gear ensure that it is in
sound condition. In no circumstances should the vents be made larger than the design
allows.
The condition of dehydrating agents if incorporated in breathers should be checked.
7.3.1.5 Mechanisms
Clause 6.5.2.7 applies with the following additional item relating to uncontrolled openings:
uncontrolled closing or opening operations with the tank removed or empty of oil are
undesirable unless the manufacturer’s instructions specifically indicate otherwise.
7.3.1.6 Interpole linkages
The following recommendations apply to interpole linkages:
(a) Interpole linkages usually have carefully fitted linkage pins, and minimum backlash
mechanisms. It is important that these features be examined and adjusted as required,
to ensure minimum spread of timing between poles. Any deterioration in this respect
will usually be indicated in the timing test.
Accessed by BHP Billiton - HVEC on 21 Sep 2015 (Document currency not guaranteed when printed)
(b) The manufacturer’s instructions for the setting dimensions of the interpole linkages
should be verified, and all nuts and bolts should be tight and all pivot pins secure.
(c) It should be verified that all fixings are tight and all pivot pins are secure.
(d) On circuit-breakers fitted with mechanical or pneumatic intertripping between poles,
the correct function should be verified by initiating operations (close and open) of
each pole in turn and ensuring that in each case the remaining two poles follow suit.
NOTE: Interpole linkages should not be altered unless essential adjustments are required.
7.3.1.7 Dashpots associated with interpole linkages
The following recommendations apply:
(a) Malfunction of dashpots associated with interpole linkages is usually only shown up
by an appropriate travel record during the timing test and unless such a record is
available and indicates satisfactory operation, the dashpots should be carefully
inspected.
(b) For oil type dashpots, it should be verified that the oil level is correct.
(c) For air type dashpots, it should be verified that bleed holes are not blocked and that
clearances are satisfactory.
7.3.1.8 Insulating oil (See also Clause 4.3)
The following recommendations apply:
(a) Testing and sampling A representative sample of oil should be taken and tested in
accordance with AS 1883, with suitable variation for high viscosity oil. Oil which
does not comply with the prescribed tests should be replaced with oil meeting the
required standard. The oil level should be maintained to the prescribed level.
TABLE 7.1
MAINTENANCE OPERATIONS FOR OIL SWITCHGEAR*
1 2 3 4 5
Routine maintenance
Pre-maintenance Post-fault
Maintenance operation Examination
requirements Inspection maintenance
and overhaul
Safety of personnel 6.1.1
Equipment to be rendered inoperative 6.1.2
Precautions for oil switchgear 7.2
Diagnostic testing 6.3 6.3
Operational check 6.4 6.4 6.4
General inspection 6.5.1.1 6.5.1.1
Cleaning 7.3.1.1 6.6
Insulation 7.3.1.2 7.3.1.2
Enclosures 6.5.2.4 6.5.2.4
Contacts 6.5.2.5 6.6
Arc-control devices 7.3.1.3 6.6
Isolating contacts 6.5.2.9
Venting and gas seals 7.3.1.4 7.3.1.4 7.4
Mechanisms 7.3.1.5 7.4.4
Auxiliary switches 6.5.2.8
Accessed by BHP Billiton - HVEC on 21 Sep 2015 (Document currency not guaranteed when printed)
SE C T I ON 8 MA I N T E N A N CE O F A I R- B L A ST
C I R C U I T - B R E A K E R SW I T CH G E A R
8.3.1.4 Insulation
Internal insulation of air-blast circuit-breakers rarely becomes contaminated but at overhaul
the opportunity may be taken to clean and examine it for any defects.
8.3.1.5 Local control kiosks
Operation of any heaters should be verified and any anticondensation finishes inspected for
signs of deterioration.
It should be verified that any emergency opening release fitted in or on a local control kiosk
correctly trips the circuit-breaker.
8.3.1.6 Pressure gauges
The correct operation of pressure gauges should be verified.
The accuracy of pressure gauges should be verified.
8.3.1.7 Pressure switches, including contact gauges
Pressure switches, including contact gauges should be inspected as follows:
(a) Correct operation and sequence of operations should be verified (if appropriate).
(b) Operation at correct pressure should be verified.
8.3.1.8 Interpole linkages
The following recommendations apply:
(a) Interpole linkages usually have carefully fitted linkage pins, and minimum backlash
mechanisms. It is important that these features be examined and adjusted as required,
to ensure minimum spread of timing between poles. Any deterioration in this respect
will usually be indicated in the timing test.
Accessed by BHP Billiton - HVEC on 21 Sep 2015 (Document currency not guaranteed when printed)
(b) The manufacturer’s instructions for the setting dimensions of the interpole linkages
should be verified, and all nuts and bolts should be tight and all pivot pins secure.
(c) It should be verified that all fixings are tight and all pivot pins are secure.
On circuit-breakers fitted with mechanical or pneumatic intertripping between poles,
the correct function should be verified by initiating operations (close and open) of
each pole in turn and ensuring that in each case the remaining two poles follow suit.
NOTE: Interpole linkages should not be altered unless essential adjustments are required.
8.3.1.9 Dashpots associated with interpole linkages
The following recommendations apply:
(a) Malfunction of dashpots associated with interpole linkages is usually only shown up
by an appropriate travel record during the timing test and unless such a record is
available and indicates satisfactory operation, the dashpots should be carefully
inspected.
(b) For oil type dashpots, it should be verified that the oil level is correct.
(c) For air type dashpots, it should be verified that bleed holes are not blocked and that
clearances are satisfactory.
8.3.1.10 Mechanisms
Clause 6.5.2.7 applies with the following additions:
(a) Main mechanism The main mechanism should be examined and the setting
dimensions verified. Malfunction will usually be revealed by diagnostic tests and
discrepancies in the setting dimensions.
Linkages should be inspected for free movement and attention should be given to any
signs of catching on ‘passing’ links.
(b) Valve gear Valve gear should be examined for leakage, and correct operation should
be verified.
NOTE: As diagnostic testing will not always show up faults or potential faults on valve gear,
it is recommended that a sample of valves on a rotation basis be inspected, cleaned and
relubricated. Hard, insufficient or too much lubricant can affect the operation of valves and
lubricant cannot be expected to remain effective over long periods. Seals will deteriorate over
a long period of time, especially if exposed to the atmosphere and consideration should be
given to replacement of seals on a regular basis.
To facilitate the overhaul of valve gear, consideration should be given to replacing
components and overhauling the units in a workshop under controlled conditions.
(c) Dashpots Oil type dashpots should be inspected for the correct level and operation,
and, where fitted, air type dashpots should be inspected for correct operation.
(d) Maintenance operating device Where a maintenance operating device is fitted to a
circuit-breaker, the manufacturer’s instructions with respect to tripping and closing
should be closely followed.
8.3.1.11 Sequence isolator
The fixed and moving contacts of the sequence isolator should be examined for signs of
overheating or burning, and where necessary cleaned, refurbished or replaced. The contacts,
contact springs and connecting braids should be inspected for freedom of movement within
their housings.
Circuit-breakers mounted out of doors should be inspected for signs of corrosion or
contamination.
Accessed by BHP Billiton - HVEC on 21 Sep 2015 (Document currency not guaranteed when printed)
Fixed and moving contacts should be lubricated sparingly, if required, with the
recommended lubricant. Caution should be taken with the use of lubricants in dusty
situations.
8.3.1.12 Pressure vessels, air receivers and pipe work
The internal and external surfaces of local air receivers, pressure vessels and pipe work
should be kept clean and any damage to or deterioration of the paint surface should be made
good to prevent corrosion taking place.
NOTE: Statutory authorities require air receivers, pressure vessels to be inspected, tested and
certified periodically. This should be programmed to coincide with routine overhauls.
Moisture should be bled from air pressure vessels and pipe work at regular intervals.
Under no circumstances should moisture be present in the local air receiver of an air blast
circuit-breaker.
Fusible plugs should be inspected and replaced, if appropriate.
Safety valves should be inspected for freedom of operation and particularly for correct re-
seating after operation.
8.3.1.13 Interrupters
The following recommendations apply:
(a) Interrupter components Interrupters usually comprise the fixed and moving main
contacts, the nozzle and the associated valve gear. In some cases, particularly with
fully pressurized types of circuit-breaker, the interrupter also houses the resistor.
(b) Fixed and moving main contacts At a suitable interval and on a rotation basis one
interrupter per pole should be examined to establish the rate of burning and erosion of
the contacts and the general condition in order to assess the necessity for further
maintenance, etc., of the other interrupters. This work shall be carried out under
reasonably dry weather conditions and precautions taken to avoid the ingress of any
moisture or dirt into the compartment.
Any burning away from the arcing area should be noted and investigated as this will
indicate that the arc is not positioning correctly.
The recommendations given in Clause 6.5.2.5 for the routine maintenance of contacts
should be followed, as appropriate.
(c) Nozzle The nozzle should be examined for excessive wear or cracking of the
material and any signs of non-centralization of the arc. This can best be done by
comparison with a new nozzle and measurement. The profile as well as the size of the
nozzle is important and if the size of profile or clearance to the contacts appears to be
changed considerably, the manufacturer’s recommendations should be followed.
In general nozzles will not need changing unless an increase in diameter of 5% or
more has taken place. Minor irregularities in the nozzle surface may be removed with
a fine file.
(d) Insulation The insulation adjacent to the arcing area should be examined for any
signs of contamination and if necessary cleaned. Burning of this insulation will
indicate a misplaced arc and if burning is found it should be investigated.
(e) Oil-filled grading capacitors, resistors and bushings Any oil-filled grading
capacitors, resistors or bushings should be examined for signs of leakage and
remedial action taken as necessary. Resistance measurements of resistors should be
Accessed by BHP Billiton - HVEC on 21 Sep 2015 (Document currency not guaranteed when printed)
taken and, where practicable, an oil sample taken for test. Consideration should be
given to testing of capacitors for dielectric dissipation factor.
(f) Air-insulated capacitors and resistors and foil type capacitors Air-insulated
capacitors and resistors and foil type capacitors incorporated within the pressure
containing tube rarely give trouble and provided that an inspection does not indicate
malfunction, no action is necessary. Resistors should be inspected for moisture and
resistance measurements taken.
(g) Valve gear and linkages Valve gear and linkages should be inspected for correct
operation, setting dimensions should be verified and a leakage test carried out.
NOTE: Valve gear and linkages should not be disturbed unless an inspection for leakage and
correct operation or diagnostic tests show this to be necessary. If it is necessary, the work
should be done in clean surroundings and the manufacturer’s instructions closely followed.
(h) Exhaust outlets and silencers Exhaust outlets and any silencers should be examined
for blockages by birds’ nests and similar and cleaned as necessary.
(i) Seals Particular attention should be paid to the inspection of seals and consideration
given to replacement on a regular basis.
8.3.1.14 Equipment enclosures
Where circuit-breakers are mounted in enclosures, the enclosures should be inspected for
any signs of damage from the effects of air blast, ingress of water, etc.
The correct operation of pressure-relief vents and any heaters should be verified and any
anti-condensation finishes inspected for signs of deterioration.
Recommendations for insulation are given in Clause 8.3.2.4, for sequence isolators in
Clause 8.3.2.11 and for interlocks in Clause 6.5.2.8.
TABLE 8.1
MAINTENANCE OPERATIONS FOR AIR BLAST CIRCUIT-BREAKER
SWITCHGEAR*
1 2 3 4 5
Routine maintenance
Pre-maintenance Post-fault
Maintenance operation Examination
requirements Inspection maintenance
and overhaul
Safety of personnel 6.1.1
Equipment to be rendered inoperative 6.1.2
Reduction in air pressure 8.2.1
Adjacent unsilenced circuit-breakers 8.2.2
Avoidance of hydraulic tests on air receivers 8.2.3
Diagnostic testing 6.3 6.3
Operation check 6.4 6.4 6.4
General inspection 6.5.1.1 6.5.1.1
Cleaning 8.3.1.1 8.4
Lubrication 8.3.1.2
Air conditioning 8.3.1.3 8.3.1.3
Insulation 8.3.1.4 8.3.1.4 8.4
Local control kiosk 8.3.1.5 8.3.1.5 8.4
Pressure gauges 8.3.1.6
Pressure switches 8.3.1.7
Accessed by BHP Billiton - HVEC on 21 Sep 2015 (Document currency not guaranteed when printed)
Connections 6.5.2.13
Secondary wiring and fuses 6.5.2.14
Interpole linkages 8.3.1.8
Dashpots associated with interpole linkages 8.3.1.9
Mechanism 8.3.1.10
Auxiliary switches 6.5.2.8
Indicating devices and interlocks 6.5.2.8
Sequence isolator 8.3.1.11 8.4
Pressure vessels, air receivers and pipe work 8.3.1.12
Interrupters 8.3.1.13 8.4
Isolators and earthing switches 6.5.2.16
Enclosures 8.3.1.14 8.3.1.14 8.3.1.14
Overload devices and protective relays Section 13 Section 13
Instruments and protective transformers Sections 12
and 13
Control relays or contactors 8.3.1.15 6.5.2.12
Final verification Section 12 8.3.1.15 8.3.1.15
Auxiliary equipment Section 12
* The numbers quoted in the columns refer to the appropriate clause number herein.
SECT I O N 9 MA I N T E N A N CE O F V A CU U M
C I R C U I T - B R E A K E R SW I T CH G E A R
9.2 GENERAL
Because of the sealed nature of the vacuum interrupter itself, it is not possible to carry out
any preventive or corrective maintenance on it. Certain tests can however be carried out to
obtain information on the condition of the interrupter, and correct maintenance of the
associated mechanism and components will ensure that the life of the interrupter is not
unduly affected by external factors.
service history.
NOTE: Vacuum interrupters can perform many operations before renewal becomes necessary.
The interval which can be allowed between consecutive overhauls of vacuum circuit-breaker
switchgear will depend upon the operating conditions of the circuits controlled and the history
and performance of individual designs of equipment.
9.4.1.3 Mechanisms
Clause 6.5.2.7 applies with the following additions:
(a) Examination and testing The main mechanism should be examined and the setting
dimensions verified. Malfunction will usually be revealed by diagnostic tests and
discrepancies in the setting dimensions.
Linkages should be inspected for free movement and attention should be given to any
signs of catching on ‘passing’ links.
(b) Correct damping The correct damping of vacuum circuit-breakers should be verified
to eliminate bounce on closing and to ensure that bounce on opening is not excessive.
9.4.1.4 Vacuum interrupter (see Clause 9.2).
Contact erosion should be measured and the contact force verified. The contact force is
affected by the degree of vacuum in the interrupter and any drastic change in force will
suggest a complete loss of vacuum.
NOTE: To check contact force, extensive dismantling may be necessary. The manufacturer’s
recommendation should be noted.
The integrity of the vacuum can be verified by a high-voltage breakdown test. However, the
manufacturer should be consulted for suitable test voltage levels as precautions may be
necessary to ensure that the levels of possible emitted X-radiation during these tests are
within safe limits.
Where there is more than one interrupter per pole, the inter-interrupter operating
mechanism should be inspected for synchronized operation. This mechanism should not be
slack or allow bounce of the contacts on opening.
Accessed by BHP Billiton - HVEC on 21 Sep 2015 (Document currency not guaranteed when printed)
TABLE 9.1
MAINTENANCE OPERATIONS FOR VACUUM CIRCUIT-BREAKER
SWITCHGEAR*
1 2 3 4 5
Routine maintenance
Pre-maintenance Post-fault
Maintenance operation Examination
requirements Inspection maintenance
and overhaul
Safety of personnel 6.1.1
Equipment to be rendered inoperative 6.1.2
Diagnostic testing 6.3 6.3
Operational check 6.4 6.4 6.4
General inspection 6.5.1.1 6.5.1.1
Cleaning 6.5.2.2 6.5.2.2
Opening device (trip) 9.4.1.1 9.4.1.1 9.4.1.1
Insulation 6.5.2.3 6.5.2.3 9.5
Enclosures 9.4.1.2
Connections 6.5.2.13
Secondary wiring and fuses 6.5.2.14
Mechanisms 9.4.1.3
Auxiliary switches 6.5.2.8
Indicating devices and interlocks 6.5.2.8
Accessed by BHP Billiton - HVEC on 21 Sep 2015 (Document currency not guaranteed when printed)
SE C T I O N 1 0 MA I N T E N A N CE O F SU L PH U R
H E X A F L U OR I D E C IRCU I T - B RE A K E R
S W I T CH G E A R
It should be verified that the gas system is operating at the required pressure and, on dual
pressure equipment, that the relationship between high pressure and low pressure is correct.
The pressure/temperature conditions should be recorded at regular intervals and checked
against the constant density characteristics.
The oil level in the compressor should be verified, if applicable, as should the pumping
time to raise pressure by a given amount. This latter information should be recorded.
Filters or desiccants should be replaced at periodic intervals and always after the gas system
has been opened to atmosphere. Under no circumstances should untreated filter or desiccant
material removed from the circuit-breaker after service be heated.
10.5.1.3 SF 6 gas
The SF 6 gas should be sampled and tested in accordance with the requirements of
IEC 60480.
Particular attention should be paid to the following:
(a) Condensation temperature The condensation temperature should be checked at
regular intervals. The required condensation temperature will depend on the location
of the circuit-breaker and the prevailing environmental conditions, and will usually be
specified by the manufacturer. However, in general it should not be above the
minimum expected ambient temperature.
In dual-pressure circuit-breakers this condensation temperature refers only to the low
pressure gas, provided that the high pressure gas is not used for insulation purposes.
Usually the high pressure gas is heated and the condensation temperature of the gas at
this pressure should be above the minimum operating temperature. When referred to
atmospheric pressure the condensation temperature of the high pressure gas shall be
equal to or lower than that of the low pressure gas.
It is expected that the only condensable material of any significance will be water but
the tests recommended will reveal the presence of significant amounts of other
condensable materials.
If the condensation temperature of the gas is found to be above an acceptable level,
the gas shall be dried or replaced with dry gas. The cause of the defect should be
investigated and it may be necessary to dry out the circuit-breaker before introducing
fresh gas.
After the circuit-breaker is refilled, the condensation temperature shall be checked at
a more regular intervals until an acceptable and stable level is reached.
(b) Oxygen content The oxygen content should normally be kept below 1% by volume,
but the circuit-breaker manufacturer will give recommended figures for particular
types of circuit-breaker. The oxygen content should only need to be checked
immediately after filling a circuit-breaker to ensure that no air has been left inside.
Previously used gas should be tested before the circuit-breaker is filled.
If the oxygen level is too high, the excess oxygen shall be removed. If the gas is in, or
can be put into, a storage tank at a pressure at which liquefaction has taken place,
excess oxygen can usually be removed by ‘dumping’ some of the gas above the liquid
rapidly to atmosphere for a few seconds. The ‘dumping’ process can be repeated a
number of times until the desired oxygen level is achieved.
(c) Acidity and hydrolysable fluoride content of gas The acidity and hydrolysable
fluoride content of the gas should be tested at suitable intervals to ensure that the
manufacturer’s maximum recommended level for the impurities has not been
exceeded. Previously used gas should be tested before the circuit-breaker is filled.
10.5.1.4 Insulation
Accessed by BHP Billiton - HVEC on 21 Sep 2015 (Document currency not guaranteed when printed)
It should be verified that the thermostats controlling the heaters operate within the required
limits.
10.5.1.9 Interpole linkages
The following recommendations apply:
(a) Interpole linkages usually have carefully fitted linkage pins, and minimum backlash
mechanisms. It is important that these features be examined and adjusted as required,
to ensure minimum spread of timing between poles. Any deterioration in this respect
will usually be indicated in the timing test.
(b) The manufacturer’s instructions for the setting dimensions of the interpole linkages
should be verified, and all nuts and bolts should be tight and all pivot pins secure.
(c) It should be verified that all fixings are tight and all pivot pins are secure.
NOTE: Interpole linkages should not be altered unless essential adjustments are required.
10.5.1.10 Dashpots associated with interpole linkages
The following recommendations apply to dashpots associated with interpole linkages:
(a) Malfunction of dashpots associated with interpole linkages is usually only shown up
by an appropriate travel record during the timing test and unless such a record is
available and indicates satisfactory operation, the dashpots should be carefully
inspected.
(b) For oil type dashpots, it should be verified that the oil level is correct.
(c) For air type dashpots, it should be verified that bleed holes are not blocked and that
clearances are satisfactory.
(d) On circuit-breakers fitted with mechanical or pneumatic intertripping between poles,
Accessed by BHP Billiton - HVEC on 21 Sep 2015 (Document currency not guaranteed when printed)
the correct function should be verified by initiating operations (close and open) of
each pole in turn and ensuring that in each case the remaining two poles follow suit.
10.5.1.11 Mechanisms
Clause 6.5.2.7 applies with the following additions:
(a) Main mechanism The main mechanism should be examined and the setting
dimensions verified. Malfunction will usually be revealed by diagnostic tests and
discrepancies in the setting dimensions.
Linkages should be inspected for free movement and attention should be given to any
signs of catching on ‘passing’ links.
(b) Valve gear Valve gear should be examined for leakage and correct operation should
be verified.
NOTE: Valve gear in general should not be disturbed unless an examination for leakage and
correct operation or diagnostic tests show this to be necessary. If it is necessary, the work
should be done in clean surroundings and the manufacturer’s instructions closely followed.
(c) Dashpots Oil type dashpots should be inspected for the correct level and operation,
and, where fitted, air type dashpots should be inspected for correct operation.
(d) Maintenance operating device Where a maintenance operating device is fitted to a
circuit-breaker, the manufacturer’s instructions with respect to tripping and closing
should be closely followed.
10.5.1.12 Interrupters
The following recommendations apply:
(a) Interrupter components Interrupters usually comprise the fixed and moving main
contacts, the nozzle and the associated valve gear. In some cases, particularly with
fully pressurized types of circuit-breaker, the interrupter also houses the resistor.
The nozzle is usually made from PTFE.
(b) Fixed and moving main contacts At a suitable interval, one interrupter per pole
should be examined to establish the rate of burning and erosion of the contacts and
the general condition in order to assess the necessity for further maintenance, etc., of
the other interrupters. This work should be carried out under reasonably dry weather
conditions and precautions taken to avoid the ingress of any moisture or dirt into the
compartment.
Any burning away from the arcing area should be noted and investigated as this will
indicate that the arc is not positioned correctly.
The recommendations given in Clause 6.5.2.5 for the routine maintenance of contacts
should be followed, as appropriate.
(c) Nozzle The nozzle should be examined for excessive burning or erosion and this can
be done by comparison with a new nozzle. In general the dimensions and profile of
the nozzle are not as critical as on an air-blast circuit-breaker (see Clause 8.3.2.13(c))
and therefore a greater amount of erosion can be tolerated before replacement
becomes necessary. However, the manufacturer’s recommendations in this respect
should be carefully followed.
(d) Insulation The insulation adjacent to the arcing area should be examined for any
Accessed by BHP Billiton - HVEC on 21 Sep 2015 (Document currency not guaranteed when printed)
TABLE 10.1
MAINTENANCE OPERATIONS FOR SULPHUR HEXAFLUORIDE CIRCUIT-
BREAKER SWITCHGEAR*
1 2 3 4 5
Routine maintenance
Pre-maintenance Post-fault
Maintenance operation Examination
requirements Inspection maintenance
and overhaul
Safety of personnel 10.2 and 10.3
Equipment to be rendered inoperative 6.1.2 and 10.5.1.1
Diagnostic testing 6.3 6.3
Operational check 6.4 6.4
General inspection 6.5.1.1 6.5.1.1
Cleaning 6.5.2.2 6.6
Opening device (trip) 10.5.1.1 10.5.1.1
Enclosures 6.5.2.4
Gas system 10.5.1.2 10.5.1.2
SF 6 gas 10.5.1.3 10.5.1.3
Insulation 10.5.1.4 10.5.1.4 10.6
Local control kiosks 10.5.1.5 10.5.1.5
Pressure gauges 10.5.1.6
Pressure switches 10.5.1.7
Accessed by BHP Billiton - HVEC on 21 Sep 2015 (Document currency not guaranteed when printed)
Connections 6.5.2.13
Secondary wiring and fuses 6.5.2.14
SF 6 gas heaters 10.5.1.8 10.5.1.8
Interpole linkages 10.5.1.9
Dashpots associated with interpole linkages 10.5.1.10
Mechanisms 10.5.1.11
Auxiliary switches 6.5.2.8
Indicating devices and interlocks 6.5.2.8
Interrupters 10.5.1.12 10.6
Isolators and earthing switches 6.5.2.16 6.5.2.16
Local air receivers and pressure vessels 10.5.1.13
Filters and desiccants 10.5.1.14
Overload devices and protective relays Section 13 Section 13
Instrument and protective transformers Sections 12
and 13
Control relays or contactors 6.5.2.12
Busbar and busbar chambers 6.5.2.19
Final verification 10.5.1.15 10.5.1.15 10.5.1.15
Auxiliary equipment Section 12 Section 12 10.5.1.15
* The numbers quoted in the columns refer to the appropriate clause number herein.
11.1 GENERAL
Where practicable, the maximum use should be made of diagnostic testing techniques to
indicate the condition of the equipment and to prolong the intervals between dismantling
and, for sulphur hexafluoride circuit-breaker switchgear, the opening of the interior of gas
compartments to atmosphere.
It is important to keep records of all diagnostic tests so that comparisons can be made and
trends estimated; but lists alone, which indicate only that measurements have been taken,
are not sufficient.
By comparison with previous similar tests, diagnostic tests will provide guidance to
possible deterioration and may indicate a need to vary maintenance intervals under
particular service conditions.
Clauses 11.2 to 11.4 briefly describe commonly used diagnostic tests and Table 11.2
indicates the applicability of the tests to the various types of switchgear.
By suitable calculations, the speed of the moving contact, and opening and closing times
can be obtained. The performance of other components, such as contact buffers can be
assessed.
11.2.2 Timing test
Timing tests are generally carried out using multi-channel apparatus. Sequence tests, e.g.
close, open and close/open operations, should be carried out and the time from initiation,
i.e. energization of coils, to the operation of the contact(s) recorded.
Timing of auxiliary switches and resistor switch contacts, where fitted, should also be
considered.
The timing tests should be arranged so that the number of operations given to the circuit-
breaker is kept to a minimum, consistent with the number of timing channels available and
the information required from a particular test. Comparisons between poles and for multi-
head circuit-breakers between individual breaks on the one pole are important. Tolerances,
where specified by the manufacturer, should be strictly adhered to.
Sequence timing tests should be carried out at 100% of the rated voltage of operating coils
and at 100% of the maximum operating pressure in air/gas operated circuit-breakers or at
the specified minimum operating voltage and/or lockout pressures.
11.2.3 Operating voltages
The measurement of minimum operating voltages of both closing and tripping functions or
operations at specified percentages of normal operating voltages, as given in the relevant
equipment standard, is recommended. Sluggish operation at reduced voltage may give an
early indication of mechanism deterioration.
These tests should be carried out in conjunction with time-travel or timing tests.
Where these tests are carried out it is particularly important to keep records so that changes
and trends can be established.
Reference should also be made to Section 14.
11.4.2 Insulation resistance test
11.4.2.1 Determination
The quality of the insulation can be determined by measuring the resistance between
current-carrying parts and earth by use of suitable test equipment.
11.4.2.2 Applied voltages for insulation resistance tests
The voltage which should be applied to primary insulation when making resistance tests
varies according to the voltage rating of the switchgear. Table 11.1 gives a guide to test
voltages.
The insulation resistance of small wiring and ancillary components should be tested at a
voltage not exceeding 500 V d.c.
NOTE: Certain types of equipment, e.g. equipment incorporating semiconductors, may not be
suitable for this test and should therefore be isolated.
11.4.3 Measurement of dielectric dissipation factor
The regular measurement of the dielectric dissipation factor (tangent delta) and capacitance
of electrostatically graded (condensor) bushings is recommended. The measurements should
be carried out in accordance with AS 1265.
TABLE 11.1
APPLIED VOLTAGES FOR INSULATION RESISTANCE TEST
Accessed by BHP Billiton - HVEC on 21 Sep 2015 (Document currency not guaranteed when printed)
TABLE 11.2
APPLICABILITY OF DIAGNOSTIC TESTS*
1 2 3 4 5 6 7
Air circuit-
Sulphur
Switchgear up breakers intended Air-blast Vacuum
Oil hexafluoride
to for operation at circuit- circuit-
Test switch- circuit-
1000 V a.c.and voltage above breaker breaker
gear breaker
1200 V d.c. 1000 V a.c. and switchgear switchgear
switchgear
1200 V d.c.
Operation
Time-travel test 11.2.1 11.2.1 11.2.1
Timing test 11.2.2 11.2.2 11.2.2
Operating voltages 11.2.3 11.2.3 11.2.3 11.2.3 11.2.3
Operating (11.2.4—as applicable)
pressures
Compressors/syste (11.2.5—as applicable)
m performance
Hydraulic system (11.2.6—as applicable)
performance
Contacts and
connections
Resistance tests 11.3.1 11.3.1 11.3.1 11.3.1 11.3.1 11.3.1
Infrared detection (11.3.2—as applicable)
Insulation
Accessed by BHP Billiton - HVEC on 21 Sep 2015 (Document currency not guaranteed when printed)
Separate battery utensils should be kept for lead-acid type or alkaline type batteries since
any mixture with or contamination by an incorrect electrolyte may damage a battery.
inspected to ensure that they are free from dirt and water and should be carefully flushed
with clean oil before use.
S E C T I O N 1 3 M A I N T E N A N CE O F
PROTECT IVE APPARATUS
13.1 GENERAL
When commissioning tests on protective apparatus are being carried out, detailed records of
the results should be made to provide a reference for comparison with future routine or
post-fault tests. Up-to-date records of fuse-link ratings and the correct settings of all
protective relays should also be maintained and care should be taken to restore the settings
to their correct value if they are altered during tests. In addition to these records it is
sometimes helpful to have the settings recorded in or on the relay case.
13.3 CONNECTIONS
If it is necessary to disturb any connections or make temporary connections for test
purposes, it is essential to ensure that these connections are correctly restored before the
circuit-breaker is returned to service.
NOTE: Attention is drawn to the dangerous voltages which may result if the secondary circuit of
a current transformer is opened with the primary circuit energized.
To avoid damage to the relay mechanism and contacts, the greatest care should be taken
when carrying out routine tripping tests on circuit-breakers by manipulation of the relay.
13.7 RELAYS
Tests should be made on protective relays to verify the operating and re-setting times or
pick-up and drop-out values as applicable.
Special test techniques may be required for static relays, and the manufacturer’s
instructions should be consulted.
www.standards.org.au © Standards Australia
AS 2467—2008 66
14.1 GENERAL
The insulation of electrical switchgear should be tested and the results recorded before the
equipment is commissioned. During the life of electrical equipment, insulation resistance
testing will give a good indication of the condition of the equipment and if these tests are
recorded can help in deciding maintenance requirements for the whole equipment.
Although there may be special dispensation in statutory requirements to cater for testing,
adequate precautions must be taken and it is recommended that the access permit procedure
detailed in Appendix A, rules 25 and 26, be used.
on the basis of experience, by comparison with earlier results. For this reason the test
equipment and method used should be the same on each occasion.
Test values obtained should be logged on a standard form designed for the purpose,
together with the humidity and temperature at the time of the test, and in general a steady
fall of resistance over a period of time is a more reliable indication of deterioration than is a
relatively low value which remains reasonably constant.
14.2.3 Measurement of the dielectric dissipation factor tan δ
The measurement of the dielectric dissipation factor tan δ is a preferred method of verifying
the quality of insulation when suitable test equipment is available and applicable.
14.2.4 Lift rods
On lift rods on some circuit-breakers, or on other long pieces of insulation, deterioration
may not occur uniformly and resistance measurements taken over the entire length may not
reveal localized deterioration.
Particular attention should be paid to the lift rods of circuit-breakers where these are made
of hickory or other natural wood. These should be inspected for indications of the wood
opening along the grain and where riveting is employed, for the wood pulling out of the
riveted end.
14.2.5 Ambient temperature
Where practicable, the insulation to be tested should be allowed to reach ambient
temperature before resistance tests are made.
APPENDIX A
EXAMPLE OF ELECTRICAL SAFETY RULES
(Informative)
The electrical safety rules given in this Appendix are reproduced from a publication by the
Energy Authority of N.S.W which has been abolished.
They are included herein as an example of electrical safety rules for good practice.
CONTENTS
Rule
PART II—GENERAL
All Mains and Apparatus shall be Regarded as Alive until Proved Dead....................................... 1
Danger of Contact with or Close Approach to Exposed Live Mains and Apparatus ....................... 2
Danger of Materials and Apparel which can conduct................................................................... 3
Entering Areas Containing Exposed Live Mains and Apparatus................................................... 4
Operating Circuit Opening and Closing Devices ......................................................................... 5
Accessed by BHP Billiton - HVEC on 21 Sep 2015 (Document currency not guaranteed when printed)
PART IV—HIGH-VOLTAGE
All High-voltage Mains and Apparatus shall be Regarded as Alive Until Proved Dead ................ 18
Minimum Safe Working Distances ........................................................................................... 19
Working on High-voltage Mains and Apparatus ........................................................................ 20
Isolation of High-voltage Mains and Apparatus......................................................................... 21
Proving Dead High-voltage Mains and Apparatus ..................................................................... 22
Earthing and Short-Circuiting High-voltage Mains and Apparatus .............................................. 23
White Tape Barriers................................................................................................................ 24
Access Permit for Working on High-voltage Mains and Apparatus ............................................. 25
Preparation, Issue and Cancellation of Access Permits ............................................................ 26
Commissioning of New High-voltage Mains and Apparatus ....................................................... 27
High-voltage Cables ............................................................................................................... 28
Identification of High-voltage Cables Before Working on Them ................................................. 29
Working on Voltage Transformers ........................................................................................... 30
Accessed by BHP Billiton - HVEC on 21 Sep 2015 (Document currency not guaranteed when printed)
INTRODUCTION
These Rules are expressed in mandatory terms as they set forth only minimum requirements for the
safeguarding of persons exposed to electrical hazards in electrical stations. Nevertheless, they are
framed in such a manner that they could be adopted by supply authorities as working procedures.
Any supply authority is at liberty to frame safety rules to meet its own requirements but care should
be exercised to guard against any conflict with these Rules.
Every employer shall ensure that all employees engaged on work in electrical stations—
(i) receive a copy of these Safety Rules or the employer’s own safety rules or receive appropriate
instruction relating thereto;
(ii) are instructed in emergency first-aid procedure and by a practical demonstration, indicate their
ability to apply such emergency first-aid procedure: Provided that instruction in emergency
first-aid procedure need not be given to persons employed in electrical stations in which staff
trained in first-aid are employed.
For the purpose of these Rules, emergency first-aid procedure means the procedure for
releasing a person from live conductors and applying resuscitation as approved by the
Authority for purposes of the Overhead Line (Workers) Regulations, 1964. A copy of the
approved procedure published by the Authority, shall be issued to each such employee.
Where practicable there shall be displayed in all electrical stations, detailed instructions in the
release of a person from live conductors and the treatment of persons who have received injury from
electric shock.
SCOPE
Accessed by BHP Billiton - HVEC on 21 Sep 2015 (Document currency not guaranteed when printed)
The Rules are intended for the guidance of electricity supply authorities and their employees who are
engaged on work on mains and apparatus in electrical stations. However, the Rules are also
intended to apply to any other employee or person, including visitors, workmen, etc., who may enter
an electrical station.
The requirements of the Overhead Line (Workers ) Regulations 1964, shall be observed by all
employees who carry out work on overhead lines in electrical stations. A copy of the Regulations
shall be issued to all such employees as the Regulations and these Rules are to be taken as
complementary.
These Safety Rules do not cover persons or work associated with—
(i) direct current traction systems, including associated direct current converting equipment in
electrical stations and all connections and plant up to and including the secondary side of the
power transformers feeding the converters or rectifiers;
(ii) extra low voltage installations;
(iii) equipment in the course of construction in a locality where there is no possibility of its making
contact with live conductors;
(iv) equipment which has been removed from its normal operating location to undergo repair or
overhaul.
DEFINITIONS
Throughout the Rules, terms printed in italic type shall have the defined meaning given. Where terms
are not printed in italic type they shall be interpreted as the context or subject matter indicates or
requires
Alive or Live is the term applied to a conductor or circuit when a potential difference exists between it
and earth.
Authorised employee means a person appointed or selected by an employer to carry out specific
duties associated with the generation or distribution of electricity, such person being competent for
the purposes of the rule in which the term is used.
Dead means not alive.
Earthed means electrically connected to the general mass of earth.
Electrical station means generating station, substation or switching station, whether of the
indoor, outdoor, underground or pole-mounted type.
Employer means an electricity supply authority.
Exposed means bare or not effectively insulated or not effectively guarded by either a fixed
barrier or an earthed metal shield.
Isolated means disconnected from all possible sources of supply.
Mains and Apparatus means that part of a conductor, cable, machine, transformer, switch or other
equipment which is normally subject to an electric charge.
Switching station means any premises or structure containing or carrying switchgear, but does not
include any structure carrying only one switch and/or fuse unit.
Voltage means potential differences between conductors of the following values:—
Extra Low—Normally not exceeding 32 volts alternating current or 115 volts direct
current.
Low—Normally exceeding 32 volts alternating current or 115 volts direct current, but
not exceeding 250 volts in either case.
Medium—Normally exceeding 250 volts, but not exceeding 650 volts.
High—Normally exceeding 650 volts.
PART II
GENERAL
When working on exposed live low or medium voltage mains and apparatus adequate precautions
shall be taken otherwise injury or death may result.
Contact with exposed live high-voltage mains and apparatus is almost certain to cause severe injury
or death. Therefore, except as set out in Rule 20, employees shall not—
(a) bring any portion of their bodies within the minimum safe working distance (See Rule 19) of
any exposed live high-voltage mains and apparatus;
(b) bring any material (other than equipment issued for testing, operating or working on live high-
voltage mains and apparatus) which is being carried or is otherwise in contact with their
bodies within the minimum safe working distance of exposed live high-voltage mains and
apparatus.
If any employee is in doubt as to the safe performance of any work assigned to him on or near
exposed live mains or apparatus he shall request further instructions from his supervisor.
rope, shall always be readily available for use where an employee is working on or above live
overhead conductors and when not in use, shall be kept in the box provided.
Life-lines shall be used only for rescue work and shall be inspected at least every three
months.
(d) Insulating Screens are portable barriers made of wood or other insulating materials and are
used as a protection against accidental contact with exposed live mains and apparatus when it
is necessary for an employee to work in close proximity to such live mains and apparatus.
When in use screens shall be securely fixed or supported and shall not be used resting in
contact with live high-voltage mains and apparatus.
When, during erection, use or removal, it is possible for a screen to accidentally come in
contact with live high-voltage mains and apparatus, only screens specially provided for the
purpose shall be used. These screens shall be tested at least every three months.
(e) Operating Rods, Live Line Working Sticks and Live Line Indicating Devices.†
(i) All the operating rods used for opening and closing, disconnecting switches or for other
purposes involving contact with live conductors and all live line indicating devices must,
when not in use, be kept in a dry clean place and on the supports where such are
provided. Care must be taken in the handling of the rods so as not to damage the
surface. Before use, the rods must be examined and, when necessary, wiped
thoroughly with a clean, dry cloth. Should an operating rod be cracked or the surface be
damaged or should other defects be apparent; the rod must not be used and shall be
withdrawn from service and arrangements made for its replacement.
(ii) All rods and live line indicating devices shall be marked with the voltage for which they
are suitable and shall not be used for higher voltages.
(iii) An employer shall cause all rods and sticks to be examined at least every twelve
months.
* Gloves can be air tested simply by rolling the glove from the cuff to force air into the fingers
† The term ‘live line indicating devices’ includes voltage test sticks, line testers and like equipment used for
proving dead mains and apparatus.
(f) Low and medium voltage portable electrical equipment. An employer shall cause all low
and medium voltage portable electrical equipment to be regularly examined and maintained to
ensure that the equipment and leads are in good order.
Insulation resistance tests and earth lead continuity tests shall be carried out on all low and
medium voltage portable electric hand tools and extension leads at least every six months.
(g) Safety Belts. When an employee is working in an elevated position, and not on a proper
scaffold or railed platform, he shall use where practicable, the safety belt and strap or rope
issued. Before trusting his weight to the belt, an employee shall ensure that the fastenings are
properly engaged and that he is secure in his belt.
When climbing or changing his position whilst wearing a safety belt, an employee shall secure
the free ends of the pole strap or rope to his body in such a manner as to ensure that they do
not hinder his safe movement.
An employer shall cause safety belts to be tested at least every three months.
(h) Use and Examination of Safety Equipment and Insulated and other Tools. Employees
working on or near live mains and apparatus shall use in a proper manner the safety
equipment and insulated tools provided. Before use, such equipment and tools shall be
examined and not used unless they are in good condition.
Employees shall immediately report all defects they observe in safety equipment.
In wet weather and damp places the insulation of safety equipment and insulated tools may be
less effective and greater care should be taken.
7. DANGER TABLETS
Danger tablets are boards, plates or tags on which the word ‘Danger’ is boldly marked and are a
warning against inadvertent and unauthorised operation of circuit opening and closing and other
controlling devices.
They shall be attached to the controls of such devices for this purpose or if this is impracticable they
shall be attached in such a position as to arrest the attention of any person about to operate the
circuit opening and closing device, or other controlling device. Danger tablets shall not be interfered
with and may be removed only by authorised employees.
Accessed by BHP Billiton - HVEC on 21 Sep 2015 (Document currency not guaranteed when printed)
PART III
LOW AND MEDIUM VOLTAGE
12. ALL LOW AND MEDIUM VOLTAGE MAINS AND APPARATUS SHALL BE
REGARDED AS ALIVE UNTIL PROVED DEAD
13. PROVING DEAD LOW AND MEDIUM VOLTAGE MAINS AND APPARATUS
Low and medium voltage mains and apparatus shall be proved dead by means of approved test
lamps, suitable indicating device or voltmeter. Where practicable this test equipment shall be proved
to be in good working order immediately before and after use.
14. WORK ON DEAD LOW AND MEDIUM VOLTAGE MAINS AND APPARATUS
When work is to be carried out on dead low and medium voltage mains or apparatus such mains and
apparatus shall be—
(i) isolated from all possible sources of supply; and
(ii) proved dead; and
(iii) clearly labelled at points of isolation from supply to warn persons against the operation of the
isolating devices; and
(iv) where directed, short-circuited and earthed.
15. WORK ON LIVE LOW AND MEDIUM VOLTAGE MAINS AND APPARATUS
Work on live low or medium voltage mains and apparatus shall be carried out only by persons trained
in the safe performance of such work.
apparatus, unless he has had three years training in electrical work and has reached the age of 18
years or such work is carried out under the direct supervision of an adult person trained in the safe
performance of that work (see Rule 15).
PART IV
HIGH-VOLTAGE
When it is likely that an employee’s body or any object which he might be carrying would come within
the distances specified above, insulating screens must be erected (see Rule 6(d)) or the exposed live
high-voltage mains and apparatus must be made dead and isolated and earthed in accordance with
Rule 20.
(b) after the mains and apparatus have been isolated, and immediately before the work is
commenced, the conductors are momentarily connected to earth.
(2) Overhead High-voltage Lines
The Overhead Line (Workers) Regulations, 1964, provide for the earthing and short-circuiting of
overhead high-voltage lines as follows—
(a) Earthing and short-circuiting of a high-voltage overhead line shall be effected at a place which,
where practicable, is visible from the site where work is to be carried out on such line.
(b) Such earthing and short-circuiting shall be carried out on both sides of the working site where
practicable.
(c) Where no known permanent earthing facilities are available, earth connection shall be made
by means of a metal rod not less than half inch diameter or a metal stake of equivalent cross
sectional area driven vertically into the ground to a depth not less than two feet.
(d) Except in a case of emergency involving danger to human life, a person shall not earth or
short-circuit a high-voltage overhead line otherwise than with equipment provided by his
employer for the purpose.
Note: This rule shall not preclude an authorised officer, having an appropriate reason for doing so, from
temporarily moving tape for the purpose of making an examination or for the purpose of gaining access to an
area in circumstances where such access cannot otherwise be obtained.
* Chief Electrical Engineer includes Chief Engineers, Electrical Engineers in charge and persons for the time
being acting in those positions.
The issuing officer shall enter the details of the mains and apparatus which may be worked on and
shall certify that the following requirements have been carried out:
(a) Switching operations to isolate the mains and apparatus.
(b) The earthing of the mains and apparatus.
(c) Warnings (if any) of nearby live mains and apparatus.
(d) Temporary screens (if any) erected.
(e) White tape barriers erected.
He shall then sign the Permit and enter the time and date of issue.
Note: If the space provided for the entry of any of the above items is not used, it shall be ruled out leaving no
blank spaces on the Permit.
The person in charge of the work shall sign the Permit as the recipient and shall enter the time and
date of receipt. He shall then ensure that all persons who are to work on the mains and apparatus
covered by the Permit, sign on and enter the time and date before they commence work.
When the work has been completed or is stopped the person in charge shall ensure that all persons
who worked on the job sign off and enter the time and date to indicate that they are aware that the
safe working period has terminated. He shall then sign the Permit, enter the time and date and return
the Permit to the issuing officer or to the authorised relieving officer.
The issuing officer or the authorised relieving officer shall then cancel the Permit and enter the time
and date.
Before making the mains and apparatus alive, the person responsible shall ensure that all relevant
access permits have been cancelled.
Immediately the Access Permit has been cancelled, all danger tablets and white tape barriers
erected for the work associated with the particular Permit shall be removed.
If during the course of the work the conditions governing the issue of the Permit are to be changed,
the Access Permit shall be cancelled. A new Access Permit shall then be issued if the work is
required to proceed.
Accessed by BHP Billiton - HVEC on 21 Sep 2015 (Document currency not guaranteed when printed)
have no difficulty in keeping clear of live mains and apparatus in the course of work.
Signed ................................................ Time .................. Date ....................................
5. Statement by persons under the control of and authorised by the recipient of this Permit to
work on the mains and apparatus referred to in this Permit:
Issue Cancellation
I/We the undersigned hereby acknowledge I/we the undersigned hereby acknowledge
having received instruction to carry out having received instruction to discontinue
work on the mains and apparatus referred work on the mains and apparatus referred to
to in this Permit and am/are satisfied that in this Permit and I/we will henceforth regard
I/we should have no difficulty in keeping the mains and apparatus as being alive.
clear of live mains and apparatus in the
course of my/our work.
(1) Sgd .......... Time ...... Date ......... Sgd .................. Time .......... Date .........
(2) ‘ ............... ‘............. ‘ ............... ‘ .................. ‘................. ‘ ...............
(3) ‘ ............... ‘............. ‘ ............... ‘ .................. ‘................. ‘ ...............
(4) ‘ ............... ‘............. ‘ ............... ‘ .................. ‘................. ‘ ...............
(5) ‘ ............... ‘............. ‘ ............... ‘ .................. ‘................. ‘ ...............
(6) ‘ ............... ‘............. ‘ ............... ‘ .................. ‘................. ‘ ...............
(7) ‘ ............... ‘............. ‘ ............... ‘ .................. ‘................. ‘ ...............
(8) ‘ ............... ‘............. ‘ ............... ‘ .................. ‘................. ‘ ...............
6. Cancellation of Permit for work:
I hereby state that the work on the mains and apparatus allocated to me under this Permit is
now completed/stopped, and that all persons authorised by me to work are now clear of the
mains and apparatus referred to. I hereby relinquish the Permit and state that I henceforth
regard the mains and apparatus as alive.
Signed ................................................ Time .................. Date ....................................
(Recipient of Permit)
APPENDIX B
MAINTENANCE RECORD FORMS
(Informative)
This Appendix gives examples of typical maintenance record forms (Figures B1 to B4).
Figure B1, Fault Openings Form, is a form used to list the operations of individual items of
equipment.
Figure B2, Equipment Maintenance Required Form, is a form used to request maintenance
on a specific item of equipment.
Figure B3, Record of Circuit-breaker Maintenance Form, is a form used by maintenance
staff to record work which has been carried out.
Figure B4, Circuit-breaker History Form, is compiled from information reported on
Figure B3. This form is used to record the complete history of maintenance carried out on
the circuit-breaker.
81
© Standards Australia
AS 2467—2008
SIGNED .....................................................................
AS 2467—2008
RECORD OF CIRCUIT-BREAKER MAINTENANCE
DATE: / / STATION: ..................................................................................................... PLANT No: .................................................
MAKE:......................................... TYPE ............................... SERIAL No ............................... PART No ....................................................
TYPES OF MAINTENANCE*: Inspection □: Oil Change □: Routine □: After fault □: Emergency □: Other ...............................................
(*Tick one or more as necessary)
REPORT: Tick (√) items completed, cross (X) items not done, and/or write in readings observed:
AS FOUND ACTION ON COMPLETION
COMPONENT REMARKS
R Y B YES NO R Y B
Operation counter reading
Insulation resistance (Megger volts . . . . )
Contact resistance (Ducter)
Pollution on bushings
Oil—Visual (colour, carbon, clarity, etc.)
Breakdown voltage (kV)
Moisture (crackle test)
Acidity
Contact assembly
Ace-control devices
82
Insulation
Inspection of operating mechanism
Clean, oil and adjust operating mechanism
Auxiliary switches
Control switches—Local and remote
Control cables and connections
Lights and heaters
Main connections and busbars
Earthing and bonding
Other
Reasons for non-completion or items marked X:__________________________________________________________________________________________________________
________________________________________________________________________________________________________________________________________________
Spares used (quote catalogue number were possible) _____________________________________________________________________________________________________
www.standards.org.au
REMARKS (Unrepaired defects, further attention required, follow-up inspection required, etc.):
________________________________________________________________________________________________________________________________________________
________________________________________________________________________________________________________________________________________________
__________________________________________________________________________________________________________ ..........................................................
Party Leader
Current: .............. A. Rupturing Cap: .............................. MV.A No of CT: ......................... Ratio: ............. (through type
(wound type
REMARKS: ............................................................................................................................................................................
.............................................................................................................................................................................................
APPENDIX C
FIRE PROTECTION EQUIPMENT
(Informative)
C1 AUTOMATIC CONTROL
The following procedures shall be carried out before work or inspections are undertaken in
any enclosure protected by automatic fire extinguishing equipment:
(a) The automatic control shall be rendered inoperative and the equipment left on hand
control. A Caution Notice shall be attached.
(b) Suitable breathing apparatus shall first be checked for correct operation and placed
ready at the work site.
(c) Precautions taken to render the automatic control inoperative shall be noted on any
Permit-to-Work or written instruction issued for work in the protected enclosure.
(d) The automatic control shall be restored after the persons engaged on the work or
inspections have withdrawn from the protected enclosure.
C2 PORTABLE EXTINGUISHERS
Before any work proceeds a check shall be made to ensure that portable extinguishers are in
the vicinity of the work site. Only approved portable extinguishers shall be used in the
vicinity of live electrical apparatus provided that in the handling of extinguishers safety
clearances are maintained. After the discharge of portable extinguishers in an enclosed
Accessed by BHP Billiton - HVEC on 21 Sep 2015 (Document currency not guaranteed when printed)
space, personnel shall leave the space until the precautions set out in Paragraph C3 have
been taken.
APPENDIX D
GRAPHICAL ILLUSTRATION OF SOME OF THE TERMS AND DEFINITIONS
GIVEN IN CLAUSE 1.4
(Informative)
N ew
M a n u fac tu re r’s
s t a n d a rd R e s to r ati o n s t a n d a rd
CONDITION
M i n i m u m ac c e pta b l e c o n d i ti o n
U n ac c e pt a b l e G rad u a l Sudden
Fa i l u re c o n d i ti o n f a i l u re f a i l u re
TIME
APPENDIX E
APPROPRIATE ACTS AND REGULATIONS
(Informative)
E1 GENERAL
Individual States in Australia have gazetted specific Acts and Regulations which cover all
or some of the matters listed in Paragraph E2 and which may be of concern to persons
involved with maintenance of electrical switchgear.
furnishing thereof.
29 Employees’ safety representatives.
APPENDIX F
REFERENCED DOCUMENTS
(informative)
REFERENCED STANDARDS
AS
1265 Bushings for alternating voltages above 1000 V
1319 Safety signs for the occupational environment
1883 Guide to maintenance and supervision of insulating oils in service
2067 Switchgear assemblies and ancillary equipment for alternating voltages above
1 kV
2184 Low voltage switchgear and controlgear—Moulded-case circuit-breakers for
rated voltages up to and including 600 V a.c. and 250 V d.c.
2225 Insulating gloves for electrical purposes
60947 Low-voltage switchgear and controlgear
60947.2 Part 2: Circuit-breakers
62271 High-voltage switchgear and controlgear
62271.100 Part 100: High-voltage alternating-current circuit-breakers
62271.301 Part 301: Dimensional standardization of terminals
AS/NZS
Accessed by BHP Billiton - HVEC on 21 Sep 2015 (Document currency not guaranteed when printed)
AS 2467—2008
90
NOTES
Accessed by BHP Billiton - HVEC on 21 Sep 2015 (Document currency not guaranteed when printed)
91
NOTES
AS 2467—2008
Accessed by BHP Billiton - HVEC on 21 Sep 2015 (Document currency not guaranteed when printed)
AS 2467—2008
92
NOTES
Standards Australia
Standards Australia develops Australian Standards® and other documents of public benefit and national interest.
These Standards are developed through an open process of consultation and consensus, in which all interested
parties are invited to participate. Through a Memorandum of Understanding with the Commonwealth Government,
Standards Australia is recognized as Australia’s peak non-government national standards body. Standards Australia
also supports excellence in design and innovation through the Australian Design Awards.
Australian Standards®
Committees of experts from industry, governments, consumers and other relevant sectors prepare Australian
Standards. The requirements or recommendations contained in published Standards are a consensus of the views
of representative interests and also take account of comments received from other sources. They reflect the latest
scientific and industry experience. Australian Standards are kept under continuous review after publication and are
updated regularly to take account of changing technology.
Accessed by BHP Billiton - HVEC on 21 Sep 2015 (Document currency not guaranteed when printed)
International Involvement
Standards Australia is responsible for ensuring the Australian viewpoint is considered in the formulation of
International Standards and that the latest international experience is incorporated in national Standards. This role is
vital in assisting local industry to compete in international markets. Standards Australia represents Australia at both
the International Organization for Standardization (ISO) and the International Electrotechnical Commission (IEC).