Im1152 10
Im1152 10
Group: ATS
Part Number: IM1152-10
Date: July 2024
©2024 Daikin Applied, Minneapolis, MN. All rights reserved throughout the world. This document contains the most current product
information as of this printing. Daikin Applied Americas Inc. has the right to change the information, design, and construction of the
product represented within the document without prior notice. For the most up-to-date product information, please go to
www.DaikinApplied.com.
™® MicroTech and Daikin Applied are trademarks or registered trademarks of Daikin Applied Americas Inc. The following are
trademarks or registered trademarks of their respective companies: BACnet from American Society of Heating, Refrigerating and
Air-Conditioning Engineers, Inc.; Echelon, LonWorks, LonMark, and LonTalk from Echelon Corporation; Modbus from Schneider
Electric; and Windows from Microsoft Corporation.
FC H C – 2 02 A
Unit Configuration
H= Horizontal Unit Size
02 = 200 CFM
03 = 300 CFM
Cabinet Type 04 = 400 CFM
C = Cabinet 06 = 600 CFM
R = Recessed 08 = 800 CFM
H = Hideaway 10 = 1000 CFM
12 = 1200 CFM
Design Series
Return Plenum
Primary Coil
(Chilled Water Cooling)
2-, 3- or 4-row
Secondary Coil
Drain Pain
(Hot Water or Steam Heating)
Galvanized or Stainless Steel
Standard or High Capacity
CAUTION
Sharp edges and coil surfaces are injury hazards. Avoid
contact with them.
CAUTION
Moving machinery and electrical power hazards may cause
severe personal injury or death. Disconnect and lock off
power before servicing equipment.
NOTICE
Installation and maintenance are to be performed only by
qualified personnel who are familiar with and in compliance
with state, local and national codes and regulations, and
experienced with this type of equipment.
7. After installation, cover the unit with the shipping carton 9. Air ducts, when used with hideaway units, should be
or other appropriate material for protection during installed in accordance with local and national codes,
finishing of the building. This is critical while spraying including National Fire Protection Association standards
fireproofing material on ceiling beams, bar joists, for the Installation of Air Conditioning and Ventilating
sandblasting, spray painting and plastering. Damage to Systems and the National Fire Protection Association
the unit due to a failure to protect it during finishing of the standards for the Installation of Air Conditioning and
building is not covered by the warranty. Ventilation Systems other than Residence Type.
8. Maximum entering water temperature is 200°F (93°C). 10. Completed installation of hideaway units without return
plenum must comply with the requirements of NFPA90B
Figure 3: Data Plate Location with regard to the use of concealed ceiling spaces as
return air plenums.
11. When a return air duct is not provided, applicable codes
may limit installation to single story buildings.
12. A one-inch duct collar is provided on units with a ducted
return and/or discharge to attach ductwork. Daikin
Applied recommends using galvanized sheet metal
ductwork. Slide the sheet metal duct over the duct collar
flange of the unit, seal the joint and fasten with sheet
metal screws.
13. Vibration isolators are generally not needed, if required
by local codes, they must be provided by the installing
contractor.
14. Valve and Piping Packages supplied with the unit
should be supported during the installation process. It is
advisable to keep the support in place after the unit has
been installed and started.
Ceiling
C
Electrical Connections
WARNING Electrical Data
A means for disconnect from electrical supply shall be The wiring diagram for the unit is attached to the exterior of the
provided according to NEC or local codes. Confirm that the blower housing. See Figure 11. Be sure the available power
power has been switched OFF before installing or servicing is the same voltage and phase as that shown on the unit data
the unit. plate. See Figure 3, for the location of the data plate. See page
44 through page 50 for typical wiring diagrams.
Installation and maintenance must be performed only by Line and low voltage wiring must be done in accordance
qualified personnel who are familiar with local codes and with local codes or the National Electrical Code, whichever is
regulations, and are experienced with this type of equipment. applicable.
Wiring connection must be completed according to the wiring
diagram on the unit. The unit must be GROUNDED. Installation Apply correct line voltage to the unit. Power wires to the unit
of all field wiring must comply with NEC and local codes. must be sized correctly. Branch circuit overcurrent protection
must be provided per local codes. See the data plate for
Line and voltage wiring must be done in accordance with local correct ratings.
codes or the National Electrical Code, whichever is applicable.
All 208-230V single-phase units are factory wired for
Apply correct line voltage to the unit. Power to the unit must be 230 V operation. For 208 V operation, the L1 wire connection
sized correctly. Branch circuit overcurrent protection must be to the unit transformer (found in the main control box) must be
provided per local codes. See the data plate for correct ratings. changed. The L1 wire must be disconnected from the 230 V
(orange) wire and connected to the 208 V (red) wire. The
Standard Electrical Connection 230 V wire must then be capped off with a wire nut or male
Field electrical power connections are made in the electrical terminal as appropriate. Please refer to the unit wiring diagram.
control box, which is mounted to the side of the chassis
opposite the primary coil piping connections. See Figure 10. An Figure 11: Location of the Wiring Diagram.
optional disconnect switch is located in this box.
Units with an electric heat option that have the same voltage
as the unit have single-point power connections and bring the
power conductors into this same connection box through one
of the knockouts. Units with electric heat that has a different
voltage should bring the electric heat into one of the knockouts
on the chase. See Figure 10.
If provided by the field, low voltage wires should be brought
into a knockout located next to the electrical control box. See
Figure 4.
Install a strain relief and pass the wires through the strain relief Operating Voltages
into the control box. Make the connections and reinstall the
control box cover. Operating voltages are as follows (+/– 10%).
• 115/60/1
Figure 10: Electrical Power Connections • 208-230/60/1
• 265-277/60/1
NOTE: Voltages listed are to show voltage range. However,
units operating with overvoltage and undervoltage for
extended periods of time will experience premature
component failure.
← Electrical Knockout
Bottom View
ECM Blower
If the unit is equipped with an ECM blower, additional steps Figure 14: Power Connector
may be required during the air balancing process. The ECM
blower is controlled by a control board. Three-speed taps are
provided with an ECM blower: high, medium and low.
Power Connector
The unit has been factory configured to produce PSC
equivalent airflow on high speed, with medium speed at 80%
and low speed at 60% of full volume. If these settings are
acceptable, then no further configuring is necessary. If different Pin Description
speeds are required select a field adjustment ECM. 1 JUMPER PIN 1 TO PIN 2 FOR
2 120 VAC LINE INPUT ONLY
Figure 12: ECM Blower 3 CHASSIS GROUND
4 AC LINE
5 AC LINE
Signal Connector
← Decorative Trim
Unit
Unit Cabinet
Initial Start-Up • *Flush should continue for at least two hours or longer
until the drain water is clean and clear.
• Shut off the circulator pump and open all drains and vents
Cleaning & Flushing the Water to completely drain down the system.
System • Short-circuited supply and return run outs should now be
connected to the unit supply and return connections. Do
CAUTION not use sealers at the swivel flare connections of hoses.
• Refill the system with clean water. Test the water using
Units must be checked for water leaks upon initial water
litmus paper for acidity, and treat as required to leave the
system startup. Water leaks may be a result of mishandling or
water slightly alkaline (pH 7.5 to 8.5).
damage during shipping. Failure by the installing contractor to
check for leaks upon start-up of the water system could result • Antifreeze may also be added at this time. Use
in property damage commercial grade antifreeze designed for HVAC systems
only. Do not use automotive grade antifreeze. Antifreeze
• Prior to first operation of any unit, clean and flush the will have an effect on the performance of the unit.
water circulating system of all construction dirt and debris. • Once the system has been filled with clean water and
• If units are equipped with water shutoff valves, either antifreeze (if used), precautions should be taken to
electric or pressure operated, connect the supply and protect the system from contamination.
return runouts together at each unit location. This will
prevent the introduction of dirt into the unit. See Figure 20.
• Fill the system at the water makeup connection with all air
Venting Hydronic Coils
vents open. After filling, close all air vents.
IMPORTANT
• Start the main circulator with the pressure reducing
valve open. It is not Daikin Applied’s policy to make recommendations
on what brand or type of water treatment is to be installed
• Check vents in sequence to bleed off any trapped air,
and used. It is the responsibility of the general contractor/
ensuring circulation through all components of the
owner to verify that the water supply to the units is free from
system.
contaminates, corrosive agents, chemicals and/or minerals.
• While circulating water, check for any leaks in the unit The general contractor/owner should contact a local water
and surrounding piping and repair as necessary. treatment company regarding water quality issues and
• Drains at the lowest point(s) in the system should be treatment. A fouled water system will lead to premature
opened for initial flush and blow-down, making sure city component failure.
water fill valves are set to make up water at the same rate.
• Check the pressure gauge at pump suction and manually Hydronic coils require a vent, either manual or automatic, to
adjust the makeup to hold the same positive steady release air from the unit. Primary coils on all ThinLine fan coils
pressure both before and after opening the drain valves. come standard with a coil air vent. It is located on the piping
side of the unit, above the coil connections.
Figure 20: Connections for flushing system piping Secondary coils on ThinLine units are not equipped with an
air vent, but one is included on all factory-supplied valve and
piping packages. It is located on the pipe closest to the outlet
Return Runout coil connection. See Figure 20.
Perform the following steps to vent both primary and secondary
Supply Runout coils after installing the unit:
• Pressurize the building piping system with water and vent
any trapped air at system vents.
• For units with manual air vents, back the set screw out to
Mains expel air from the unit and then re-tighten the set screw.
• Automatic air vents should require no adjustment for
the coil to vent. However, if the coil does not vent
Flexible Hose immediately, unscrew the outer portion of the fitting to
expel air from the port. If debris has become trapped in
the vent, completely remove the outer portion of the fitting
and clean.
Ductwork Connections
□ Install ductwork, fittings and grilles, as required
□ Flexible duct connections at unit
□ Proper supply and return grille type and size
□ Control outside air for freeze protection
□ Insulate all ductwork, as required
Maintenance Figure 21: Filter Removal for Units with Bottom Returns
General Maintenance
Normal maintenance on all units is generally limited to filter
changes and cleaning the condensate drain pans. Units are
provided with permanently lubricated motors and require no
oiling.
Record performance measurements of volts, amps, and
water temperature differences (both heating and cooling). A
comparison of logged data with start-up and other annual data
is useful as an indicator of general equipment condition.
Filter Changes Figure 22: Filter Removal for Units with Rear Returns
3. Firmly grasp the fan deck and lift upward and off the unit.
See Figure 28.
4. Disconnect the fan motor wiring harness by removing the
plug where it attaches to the connector on the side of the
chassis. See Figure 28.
5. To reinstall, follow these steps in reverse order.
NOTE: Push the tabs inward on the sides of the plug to free it
from the connector base.
Monthly Intervals
• Inspect and clean the condensate drain pan to help avoid
clogging of drainage by dirt, dust, etc. Inspect drainage Replacement Parts
piping for proper condensate flow.
Factory replacement parts should be used wherever possible
• Check and clean the coil. Clean the coil with a low to maintain the unit’s performance, service life, operating
pressure water jet or low pressure air. characteristics and testing agency listings. Replacement
• Clean and tighten all the wiring connections. parts may be purchased through a local Daikin Applied sales
representative.
Figure 26: Fan Housing
Contact your local Daikin Applied sales representative or
Daikin Applied Parts before attempting any unit modifications.
Any modifications not authorized by Daikin Applied could void
all factory warranties and result in personal injury and/or unit
damage.
When ordering replacement parts the following information
must be supplied to ensure proper item identification:
1. Unit model number
2. Unit serial number
3. Unit orientation, hand connection (right or left hand when
facing into the airstream)
4. Complete part description including any numbers
See replacement parts list for descriptions and part numbers.
Contact Daikin Applied for authorization of any returned parts,
such as defective parts covered under warranty.
MT155 Thermostat
For more details refer to Addendum IM 1014 — MT155 on TA155: A HEAT-OFF-COOL system switch manually selects
page 57. The MT155 series thermostat provides ON- heating or cooling mode (Addendum IM 1089 — MT155 A/B
OFF control for low-voltage or line-voltage valves and fan on page 61). In the HEAT position, only the heat output
motors. This thermostat is designed as a remote-mount with cycles with demand. In the COOL position, only the cool output
connection to the LV interface board mounted on the fan coil cycles with demand. In the OFF position, heating and cooling
unit. Options include manual or automatic changeover and outputs are off. Units with a two position system switch or
three-speed fan control for continuous or cycling fan operation. without a system switch must use a load transfer switch when
both heating and cooling outputs are used. This prevents
Figure 31: MT155 Thermostats control failure and equipment damage caused by direct cycling
between loads.
TB155: An ON-OFF system switch enables auto-changeover
of heating and cooling modes (Addendum IM 1089 — MT155
A/B on page 61). In the ON position the thermostat activates
heating or cooling outputs dependant upon the relationship
between set point and ambient temperature. Heat on to cool
on dead band is 4°F. In the OFF position, heating and cooling
outputs are OFF. Units without a system switch cycle between
heating and cooling with a 4°F dead band.
FAN: Some units have a switch for manual selection of fan
speed. On these units fan operation is either internally wired for
fan continuous operation or is dependant upon connection to
the fan supply input . When internally wired for fan continuous
operation, the fan will be OFF when the system switch is OFF.
Two standard control options are available: When dependant upon external connections the fan may not
• Continuous fan and ON-OFF valve cycle operation: The be OFF with the system switch in the OFF position. The fan
thermostat cycles the valves on and OFF. The fan runs supply input is switched to fan speed outputs (HI-MED-LO).
continuously at the manually selected fan speed.
• ON-OFF fan and ON-OFF valve cycle operation: The
thermostat cycles the fan from the manually selected fan
speed to OFF and it cycles the valves ON and OFF.
When the system switch is in the OFF position, the fan coil
system including the fan is shut OFF.
Digital Thermostats
Daikin Applied offers a broad Two standard control options are available:
range of remote, wall-mounted • Continuous fan and modulating (or ON-OFF) valve
digital thermostats with the operation: The fan runs continuously at the manually
capability to control ON- selected fan speed (high, medium or low). The controller
OFF, 3-wire and proportional modulates the valves or, on the MT158, dip-switches can
modulating valves and be set to cycle the valves ON and OFF.
Normally-Closed or Normally-
Open actuator valves. For • ON-OFF fan cycle operation and modulating (or ON-
more information, refer to OFF) valve operation: The controller cycles the fan from
Daikin Applied publications ED the manually selected fan speed to OFF. The controller
18513 and ED 18527. modulates the valves or, on the MT158, dip-switches can
be set to cycle the valves ON and OFF.
Sensors
Room Temperature Sensor with Setpoint MicroTech III Wall-Mounted Room
Adjustable Module and Fan Speed Temperature Sensor with Timed
Control Override
The Digitally Adjustable sensor MicroTech III Wall Mounted Room
provides the ultimate of temperature Temperature Sensors provide electronic
control and display, simple user sensing of room temperatures at wall
interface, alarm annunciation, and locations. The sensor features a thermistor
alarm reset. The easy to ready LCD (10kO), a green LED for unit status and
clearly identifies the system operating tenant override button.
mode including occupied/unoccupied
mode, fan operation and control, unit Sensor Specifications
status, timed override status, alarm • Thermistor resistance (10kΩ)
annunciation, and energy savings (Conforms to Advance Thermal
mode through a series of recognizable Products curve 2)
icons. Tactile response buttons initiate
adjustments for temperature set • Ambient Temperature Limits:
points, system mode, fan mode, occupancy, tenant override — Shipping and Storage: 40°F to 160°F (–40°C to 71°C)
and fault reset functions. The large numeric LCD will display — Operating: 40°F to 140°F (4°C to 60°C)
space temperature (°F or °C) with the corresponding setpoint • Locations: NEMA Type 1, Indoor only
conditions. This sensor is designed for use with BACnet or
• Connections: Color Coded Leads
LonWorks applications. However, it can also be installed as a
standalone sensor using factory default set points. Wiring
For detailed installation instructions and modes of operation 3-lead NEC Class II low voltage wiring.
see Addendum IM 1171 — Digitally Adjustable Display Sensor
on page 92. NOTE:
1. Do not install the wire cables in the same conduit with
power wiring.
2. Never apply external voltage of any type to any terminal
or damage will result.
3. Do not exceed ratings of the device. This is a low voltage
device:
4. Always use 22-gauge wire and never locate the room
temperature sensor more than 250′ from the unit:
Wiring must be installed in accordance with the National
Electrical Code and all local codes and ordinances, which can
require the use of plenum rated cable or conduit.
Mounting Location
Locate the sensor on a wall where exposure to unrestricted air
circulation represents the average temperature of the space. A
common mistake is to mount the sensor too close to the supply
air diffuser in a room. This causes short cycling of the air
conditioning unit and large room temperature swings.
Installation
Utility Box Mounting of Sensor 669529001
DANGER
THIS EQUIPMENT PRESENTS 1. Feed the cable from the utility box.
HAZARDS OF ELECTRICITY. 2. Strip 1/4–inch of insulation from the end of the wires.
Failure to read and follow these instructions can result in 3. Connect stripped, labeled wires to matching terminals on
property damage, severe personal injury or death. the temperature sensor base. See Figure 35.
4. Tighten screws on terminal connections. Gently tug wire
CAUTION to check for secure connections. Confirm that each wire
is connected to the proper terminal.
Be certain that exposed portions of wires do not come in
contact with each other. 5. Neatly store excess wire back inside the utility box.
6. Mount the sensor base to the utility box using two 6-32 ×
1. Turn off power at the main service panel by removing the 5/8–inch flat head sheet metal screws provided with the
fuse or switching the appropriate circuit breaker to the sensor.
OFF position. 7. Replace cover on wall temperature sensor by attaching
2. To remove the cover on sensor 669529001, loosen two the catches at the top of the cover to the top tabs on the
Allen-wrench set screws located on the underside of the sensor base. Secure the cover to the base by tightening
cover. the two Allen wrench set-screws on the bottom of the
sensor cover. Do not overtighten.
3. Place the wall sensor mounting base against the wall
where the sensor where be located. Using the base as a NOTE: Sensor 669529001 has two Allen wrench set-screws
template trace the mounting holes onto the wall. on the underside of the sensor cover to secure it in
place. Do not overtighten.
4. Drill a 3/16" hole at each mounting hole mark.
5. Insert wall anchors into mounting holes and tap in to the
wall surface.
6. Feed wires through the back of the sensor mounting
base and align sensor mounting holes with wall anchors.
7. Use supplied screws to secure sensor base to wall.
8. Connect stripped, labeled wires to matching terminals
on the temperature sensor. Refer to Figure 35 for wiring
details.
9. Tighten screws on terminal connections. Gently tug wire
to check for secure connections. Confirm that each wire
is connected to the proper terminal.
10. Seal the hole where the wire enters through the wall
behind the temperature sensor, with non-flammable
insulation or putty.
11. Replace cover on wall temperature sensor by snapping
it in place.
12. Turn on power to the system at the main service panel.
13. Test wall temperature sensor operation as described in
“Testing”.
NOTE: Mount the sensor five feet above the floor. Do
not mount the sensor on an outside wall, in direct
sunlight, behind a door, or in an area affected by a
vent or duct.
Cool Test
1. Using the building automation system (BMS), adjust
room cooling setpoint to 5 degrees below room
temperature.
2. Air conditioning should come on within five (5) minutes. Troubleshooting
Status indicator may come on.
Symptom Remedy
3. Using the BMS, adjust the set temperature 2 degrees
Check for 5 VDC at sensor, LED is
above the room temperature and the A/C should turn off. No LED illuminated dark when 5 VDC
There may be a fan delay on your system. is not present
Sensor must be located as described
Heat Test Unit turns on and off too frequently in
“ Mounting Location”.
1. Using the building automation system (BMS), adjust
room heating setpoint to 5 degrees above room
temperature.
2. Heating should come on within five (5) minutes. Status
indicator may come on.
3. Using the BMS, adjust the set temperature 2 degrees
above the room temperature and the A/C should turn off.
There may be a fan delay on your system.
The fresh air damper module with top or rear fresh air inlets
is available for concealed, recessed or exposed units. Fresh
Air Damper control can be automated or manual. Automatic
options include a 2-position control or a full economizer option
(MicroTech controller only).
Manual Damper – The manual damper is field-adjustable to
allow a zero to 25 percent fresh air position.
Auto Two-Position Damper – The auto two-position damper
is factory set at 25 percent when open. The damper can be set
in the field to allow a zero to 50 percent fresh air position.
Economizer Damper – The economizer damper is
accompanied by a factory-installed and wired modulating
actuator. The damper is factory set at 25 percent default
minimum and 100 percent maximum opening. The damper
is field adjustable using MicroTech III to allow a zero to 100
percent fresh air.
Physical Data
Unit Data
Table 1: Physical Data: Coils, Fans, Motors and Filters
Size 02 Size 03 Size 04 Size 06 Size 08 Size 10 Size 12
Primary Coil Data
Face Area, ft2 (cm2) 1.08 (1004) 1.08 (1004) 1.43(1323) 2.11(1962) 2.46(2281) 3.14(2917) 3.83(3559)
Fins/inch (cm) 12 (4.7) 12 (4.7) 12 (4.7) 12 (4.7) 12 (4.7) 12 (4.7) 12 (4.7)
Connection Size 1/2" Nominal Copper (5/8" OD)
Coil Dimensions
2-Row 17.3 × 1.7 × 9 17.3 × 1.7 × 9 22.8 × 1.7 × 9 33.8 × 1.7 × 9 39.3 × 1.7 × 9 50.2 × 1.7 × 9 61.3 × 1.7 × 9
L × D × H, in (cm) (43.9 × 4.4 × 22.9) (43.9 × 4.4 × 22.9) (57.9 × 4.4 × 22.9) (85.9 × 4.4 × 22.9) (99.8 × 4.4 × 22.9) (127.6 × 4.4 × 22.9) (155.7 × 4.4 × 22.9)
3-Row 17.3 × 2.6 × 9 17.3 × 2.6 × 9 22.8 × 2.6 × 9 33.8 × 2.6 × 9 39.3 × 2.6 × 9 50.2 × 2.6 × 9 61.3 × 2.6 × 9
L × D × H, in (cm) (43.9 × 6.6 × 22.9) (43.9 × 6.6 × 22.9) (57.9 × 6.6 × 22.9) (85.9 × 6.6 × 22.9) (99.8 × 6.6 × 22.9) (127.6 × 6.6 × 22.9) (155.7 × 6.6 × 22.9)
4-Row 17.3 × 1.7 × 9 17.3 × 3.5 × 9 22.8 × 3.5 × 9 33.8 × 3.5 × 9 39.3 × 3.5 × 9 50.2 × 3.5 × 9 61.3 × 3.5 × 9
L × D × H, in (cm) (43.9 × 8.8 × 22.9) (43.9 × 8.8 × 22.9) (57.9 × 8.8 × 22.9) (85.9 × 8.8 × 22.9) (99.8 × 8.8 × 22.9) (127.6 × 8.8 × 22.9) (155.7 × 8.8 × 22.9)
Coil Volume, Gal (Liters)
2-Row 0.19 (0.7) 0.19 (0.7) 0.24(.9) 0.32(1.2) 0.37(1.4) 0.46(1.7) 0.55(2.1)
3-Row 0.26 (1.0) 0.26 (1.0) 0.32(1.2) 0.45(1.7) 0.52(2.0) 0.64(2.4) 0.77(2.9)
4-Row 0.34 (1.3) 0.34 (1.3) 0.43(1.6 0.61(2.3) 0.70(2.6) 0.87(3.3) 1.05(4.0)
Secondary Coil Data: 1-Row Standard Capacity, Hot Water or Steam
Face Area, ft2 (cm2) 0.61(567) 0.61(567) 0.84(780.1) 1.3(1208) 1.5(1421) 1.99(1845) 2.44(2267)
Fins/inch (cm) 12 (4.7) 12 (4.7) 12 (4.7) 12 (4.7) 12 (4.7) 12 (4.7) 12 (4.7)
14.7 × .86 × 6 14.7 × .86 × 6 20.2 × .86 × 6 31.2 × .86 × 6 36.7 × .86 × 6 47.7 × .86 × 6 58.7 × .86 × 6 (149.0
L × D × H, in (cm)
(37.3 × 2.2 × 15.2) (37.3 × 2.2 × 15.2) (51.3 × 2.2 × 22.9) (79.2 × 2.2 × 22.9) (93.2 × 2.2 × 22.9) (121.1 × 2.2 × 22.9) × 2.2 × 22.9)
Coil Volume,
0.06 (0.23) 0.06 (0.23) 0.08 (0.30) 0.11 (0.42) 0.12 (0.45) 0.15 (0.57) 0.18 (0.70)
Gal (Liters)
Secondary Coil Data: 1-Row High Capacity, Hot Water or Steam
Face Area, ft2 (cm2) 0.82 (762) 0.82 (762) 1.26 (1171) 1.73 (1607) 2.04 (1895) 2.65 (2460) 3.26 (3029)
Fins/inch (cm) 12 (4.7) 12 (4.7) 12 (4.7) 12 (4.7) 12 (4.7) 12 (4.7) 12 (4.7)
14.7 × .86 × 8 14.7 × .86 × 8 20.2 × .86 × 8 31.2 × .86 × 8 36.7 × .86 × 8 47.7 × .86 × 8 58.7 × .86 × 8
L × D × H, in (cm)
(37.3 × 2.2 × 20.3) (37.3 × 2.2 × 20.3) (51.3 × 2.2 × 22.9) (79.2 × 2.2 × 22.9) (93.2 × 2.2 × 22.9) (121.1 × 2.2 × 22.9) (149.0 × 2.2 × 22.9)
Coil Volume,
0.08 (0.30) 0.08 (0.30) 0.11 (0.42) 0.14 (0.53) 0.16 (0.61) 0.20 (0.76) 0.24 (0.92)
Gal (Liters)
Fan/Motor Data
Fan Quantity 1 1 2 2 2 4 4
Motor Quantity 1 1 1 1 1 2 2
Filter Data
Throwaway (MERV 4), MERV 8*, MERV 13**, and Aluminum Washable
Quantity
1 1 1 1 1 2 2
Hideaway 9(3/8) x 19(1/4) x 1 9(3/8) x 19(1/4) x 1 9(3/8) x 24(3/4) x 1 9(3/8) x 35(3/4) x 1 9(3/8) x 41(1/4) x 1 9(3/8) x 26 x 1 9(3/8) x 31(1/2) x 1
L x D x H (in) 9(3/8) x 19(1/4) x 2 9(3/8) x 19(1/4) x 2 9(3/8) x 24(3/4) x 2 9(3/8) x 35(3/4) x 2 9(3/8) x 41(1/4) x 2 9(3/8) x 26 x 2 9(3/8) x 31(1/2) x 2
Cabinet 10(3/4) x 20(7/8) x 1 10(3/4) x 20(7/8) x 1 10(3/4) x 24(3/4) x 1 10(3/4) x 36(3/8) x 1 10(3/4) x 40(1/4) x 1 10(3/4) x 25(7/8) x 1 10(3/4) x 31(3/4) x 1
L x D x H (in) 10(3/4) x 20(7/8) x 2 10(3/4) x 20(7/8) x 2 10(3/4) x 24(3/4) x 2 10(3/4) x 36(3/8) x 2 10(3/4) x 40(1/4) x 2 10(3/4) x 25(7/8) x 2 10(3/4) x 31(3/4) x 2
*PSC requires 2" depth
**For use with ECM only
Shipping Weights
Table 2: Approximate Shipping Weights - lbs (kg)*
Unit Size
Unit Type
S02 S03 S04 S06 S08 S10 S12
FCHC/FCHR 108 (49) 110 (50) 124 (56) 139 (63) 151 (69) 184 (84) 196 (89)
FCHH 30 (14) 33 (15) 35 (16) 45 (20) 55 (25) 62 (28) 65 (30)
Note: *Approximate dry weights do not include plenums, valve packages, hot water coils, electric heaters or other options.
Unit Dimensions
Figure 38: Dimensions – Hideaway Fan Coil, Front Discharge – Free Return
Reheat coil shown
Top View
5.01
(4) Mounting
Holes Secondary Drain Pan (1)
⅜" × ⅝"
Control
Box
⅝" O.D. Coil
Connections
(Typical)
1.0 NOTES: (1) Secondary drain pan is only supplied with factory-provided
C 1.73 piping packages
(2) Same-hand connection shown, opposite-hand configuration
6.0
has secondary coil connections on the control box side
○
×
REFERENCE POINT
F
0.5 D H
1.54
0.64 2.49 1.25
4.35
3.4
B 0.68 L 15.28
1.62
REFERENCE POINT REFERENCE POINT
○
× ○
×
9.25
5.21 1.5
0.5" O.D.
A Overflow Connection
3.11
0.75" O.D.
Drain Connection
Front View Side View
Figure 39: Dimensions – Hideaway Fan Coil With Plenum, Front Discharge – Rear Return
Top View
5.01
(4) Mounting
Holes Secondary Drain Pan (1)
⅜" × ⅝"
Control
Box
⅝" O.D. Coil
Connections
(Typical)
1.0 NOTES: (1) Secondary drain pan is only supplied with factory-provided
C 1.73 piping packages
(2) For units without mixing box
6.0
(3) Same-hand connection shown, opposite-hand configuration
has secondary coil connections on the control box side
○
×
REFERENCE POINT
F
0.5 D H
1.54
0.64 2.49 1.25 21.5 (2)
4.35 20.2 (2)
5.4
B 0.68 L 17.3 (2)
1.62
REFERENCE POINT REFERENCE POINT
○
× ○
×
9.25 8.8
5.21 1.5
0.5" O.D.
A Overflow Connection
3.11
0.75" O.D.
Drain Connection
Front View Side View
Figure 40: Dimensions – Hideaway Fan Coil With Plenum, Front Discharge – Bottom Return
Top View
G
Secondary Drain Pan (1)
5.01
0.952 E 0.952
(4) Mounting
Holes
⅜" × ⅝"
Control Return Air Opening
Box
⅝" O.D. Coil
Connections
(Typical)
1.0 NOTES: (1) Secondary drain pan is only supplied with factory-provided
C 1.73 piping packages
(2) Same-hand connection shown, opposite-hand configuration
6.0
has secondary coil connections on the control box side
○
×
REFERENCE POINT
F
0.5 D H
1.54
0.64 2.49 1.25
4.35 20.2
5.4
B 0.68 L 17.3
1.62
REFERENCE POINT REFERENCE POINT
○
× ○
×
9.25
0.647
5.21
0.75" O.D.
Drain Connection 2.11 2.25
A
0.5" O.D. 7.812
Overflow Connection
Front View 3.11
1.5
Side View
Figure 41: Dimensions – Cabinet Fan Coil, Front Discharge – Rear Return
Control
Top Box
25.0
18.0
View
(4)
¾" Mounting
Holes
RefeRence Point
○
×
C.XX
2.375 D
4.5
NOTE: (1) Unit is shown with duct collar flanges for return and discharge openings
3.51
RefeRence Point
Back View 7.26
○
× 9.01
4.88
3.53
Figure 42: Dimensions – Cabinet Fan Coil, Front Discharge – Bottom Return
Control
Top Box
25.0
18.0
View
(4)
¾" Mounting
Holes
RefeRence Point
○
×
C.XX
2.375 D
4.5 NOTE: (1) Unit is shown with duct collar flange for discharge opening
15.28 F 15.28
RefeRence Point
○
×
2.23
3.98
5.48 6.48
8.91
11.75
12.00
14.0
3.51
Bottom
5.81
View
Back View 7.26
9.01
Return 8.82
(8) 2" Piping (4) 1" Electrical Power 10.09
Knockouts Knockouts
12.04
S E S 2.36 (4) 2" Drain
Knockouts
1.0
RefeRence Point
○
×
1.63
7.55
Side
View
4.88
Figure 43: Dimensions – Cabinet Fan Coil, Bottom Discharge – Rear Return
Control
Top Box
35.0
28.0
View
(4)
¾" Mounting
Holes
REFERENCE POINT
○
×
C.XX
2.375 D
4.5
3.51
5.81
15.2 9.01
REFERENCE POINT
○
×
1.65
8.82 Side
View
3.53
Figure 44: Dimensions – Cabinet Fan Coil, Bottom Discharge – Bottom Return
Return
Control
Top Box
35.0
28.0
View
(4)
¾" Mounting
Holes
REFERENCE POINT
○
×
C.XX
2.375 D
4.5
3.51
Bottom
5.81
View
15.2
Back View 7.26
9.01
S E S 2.36
Side
View
Figure 45: Dimensions – Recessed Cabinet Fan Coil with Ceiling Plate
25.0 29.5
3.0
Detail A
Floating Ceiling Panel
Detail A
Side View Plate to cabinet connection for fully recessed units
25.0 29.5
3.0
Connecting
ConnectingPipe
PipeLocations:
Locations: 2-Pipe
2-Pipe Cooling or Heating
Cooling Only, Right-hand
Deluxe Package shown
Deluxe Package shown, see schematic (page 2) for the list of components selected for this package
5.38
3.42
REFERENCE POINT
○
×
Primary
Supply
Front
View
Primary
Return
0.56‡
1.5†
7.0
20.25
B † Overflow Connection
A ‡ Drain Connection
REFERENCE POINT
○
×
4.43
Primary
End 5.5
Supply
View
10.42 11.1
10.8
Primary
Return
10.58†
Figure 54: Factory-installed Valve & Piping Packages (right-hand shown), continued
Connecting Pipe
Connecting Locations:
Pipe 4-Pipe
Locations: Cooling
4-Pipe and
Cooling & Heating, Same-side Right-hand
Heating Same-side,
Deluxe Package shown
Deluxe Package shown, see schematic (page 2) for the list of components selected for this package
10.35
7.7
5.38 Primary
3.42 Supply
REFERENCE POINT
○
× Secondary
Return
Primary
Return
Secondary
Supply
0.56‡
1.5†
7.0
Front View
† Overflow Connection
20.25 ‡ Drain Connection
B K C
A D
REFERENCE POINT REFERENCE POINT
○
× ○
×
4.4
Secondary X
Primary Return
Supply
5.5
11.1
10.42
10.8 7.9
Primary
Return
10.58†
Secondary
Supply
Primary Package
Secondary Package Secondary Coil Connection
Connections from Reference
Length from Reference Point
Point (2- & 3-row Coil)
Name Component Description
High Standard
Return Supply Preheat Reheat
Supply (A)* Return (B)* Capacity Capacity
(C) (D) (K) (K)
(X) (X)
Basic 2W 2Way control valve, shut-off valves 12.2 16.2 6.5 7.1
Basic 3W 3Way control valve, shut-off valves 12.2 17.0 9.0 7.1
Enhanced 2W 2Way control valve, shut-off valves, strainer 15.8 16.3 6.5 10.7
Enhanced 3W 3Way control valve, shut-off valves, strainer 15.8 17.0 9.0 10.7
Premium 2W, auto flow 2Way control valve, shut-off valves, auto flow-setter 12.3 15.8 6.1 7.1
Premium 2W, manual flow 2Way control valve, shut-off valves, manual flow-setter 12.3 16.6 10.6 7.1
4.53 1.03 0.8 2.8
Premium 3W, auto flow 3Way control valve, shut-off valves, auto flow-setter 12.2 14.8 5.1 7.1
Premium 3W, manual flow 3Way control valve, shut-off valves, manual flow-setter 12.2 15.6 9.6 7.1
Deluxe 2W, auto flow 2Way control valve, shut-off valves, strainer, auto flow-setter 15.8 15.8 6.1 10.7
Deluxe 2W, manual flow 2Way control valve, shut-off valves, strainer, manual flow-setter 15.8 16.6 10.6 10.7
Deluxe 3W, auto flow 3Way control valve, shut-off valves, strainer, auto flow-setter 12.2 14.8 5.1 10.7
Deluxe 3W, manual flow 3Way control valve, shut-off valves, strainer, manual flow-setter 12.2 15.6 9.6 10.7
NOTE: For 4-row Primary Coils add 1" to the dimensions A and B shown
Wiring Diagrams
Figure 55: Fan Coil Wiring Diagram – Typical Low Voltage Interface Board and PSC, Intermediate Electric Heat, F/A
Damper, 3-Speed Switch–Unit Mounted
Figure 56: Fan Coil Wiring Diagram – Typical Low Voltage Interface Board and PSC, Intermediate Electric Heat, F/A
Damper, 3-Speed Switch–Unit Mounted
Figure 57: Fan Coil Wiring Diagram – Typical Low Voltage Terminal Strip and ECM, Intermediate Electric Heat, F/A Damper,
3-Speed Switch–Unit Mounted
Figure 58: Fan Coil Wiring Diagram – Typical Low Voltage Terminal Strip and ECM, Intermediate Electric Heat, F/A Damper,
3-Speed Switch–Unit Mounted
Figure 59: Fan Coil Wiring Diagram – Typical MicroTech Controller with ECM and Economizer, Intermediate Electric Heat
Figure 60: Fan Coil Wiring Diagram – Typical MicroTech Controller with ECM and Economizer, Intermediate Electric Heat,
continued
Figure 61: Fan Coil Wiring Diagram – Unit Mounted 3 Speed Switch, Low Voltage Valves
57. Filter Status Sensor 68. Right Hand End Pocket Extension
• Y = none • 00 = none
• X = special • 04 = 4 inch extended length
58. Fan Status Sensor 69. Subbase (not applicable)
• Y = none 70. Discharge Air - Outlet
• X = special • BA = bottom discharge with double deflection
59. Future Control Function grille
• Y = none • BD = bottom discharge with duct collar
60. Future Control Function • BP = open bottom discharge
• BS = bottom discharge with stamped louver grille
• Y = none
• FA = front discharge with double deflection grille
61. Cabinet Style
• FD = front discharge with duct collar
• S = standard
• FP = open front discharge
• T = tamperproof
• FS = front discharge with stamped louver grille
• Y = none
• XX = special
62. Cabinet Gauge
71. Return Air Inlet
• 16 = 16 gauge
• BS = bottom inlet with stamped louver
• 18 = 18 gauge
• BD = bottom inlet with duct collar (plenum)
• YY = none
• RD = rear inlet with duct collar (plenum)
• XX = special
• RS = rear inlet with stamped louver
63. Cabinet Coating Type
• XX = special
• B = powder coat
• YY = no plenum (open return)
• Y = none
72. Filter
64. Color- Cabinet
• 1 = 1 inch Throwaway Filter
• I = antique ivory
• 3 = 1 inch Throwaway + (1) Extra
• W = off white
• G = soft gray
• C = cupola white
• P = putty beige
• Y = none
• X = special
65. Cabinet Depth Extension
• 00 = none
66. Unit Lineup Position
• S = standalone
67. Left Hand End Pocket Extension
• 00 = none
• 04 = 4 inch extended length
3 O M U
MT 155 Thermostat
Installation
DANGER 1. Install the thermostat with the two furnished mounting
screws to a standard 2" × 4" electrical box, 4-11/16" ×
READ THESE INSTRUCTIONS CAREFULLY BEFORE 21/8" square device box with a 2" x 4" adapter ring or
ATTEMPTING TO INSTALL, OPERATE OR SERVICE to a 4" × 4" box with accessory adapter plate.
THIS THERMOSTAT.
2. For wall installations, mount the thermostat on an
Failure to observe safety information and comply with inside wall approximately 5 feet above the floor. The
instructions could result in PERSONAL INJURY, DEATH location should provide circulation at average room
AND/ OR PROPERTY DAMAGE. temperature. Avoid direct sunlight or sources of hot or
To avoid electrical shock or damage to equipment, cold air in the room or wall.
disconnect power before installing or servicing. Use only 3. Remove the knob and then the cover. Mount
wiring with insulation rated for full thermostat operating thermostat base assembly to the outlet box using the
voltage. Use copper wire only. Insulate or wirenut all un- screws provided, tighten the screws evenly but do not
used leads. Any wiring, including the remote probe,may over tighten. Make wiring connections as noted.
carry the full operating voltage of the thermostat.
4. To use a remote sensor, remove jumper JP-1 to
To avoid potential fire and/ or explosion do not use in disable local sensing. See Figure 1. Failure to remove
potentially flammable or explosive atmospheres. Retain JP-1 when using a remote sensor will cause improper
these instructions for future reference. You must review operation of the thermostat. Some units do not have
your application and national and local codes to ensure remote sensing capability. See Application Notes.
that your installation will be functional and safe.
5. Reinstall the cover assembly. Install cover locking
screw provided. Reinstall the knob.
Figure 1: Removing Jumper JP-1
INSTALL COVER 6. Checkout: After wiring and installation are complete,
LOCKING SCREW
energize the system and check the operation. Adjust
the thermostat as necessary to complete at least one
cycle. Be sure the thermostat and all other equipment
are functioning correctly.
IM 1014 MTA/B 155 Thermostat
REMOVE JP1
JP1
WHEN USING A
REMOTE SENSOR
IM 1152-10 57
Addendum IM 1014 — MT155
Ratings
Table 1: Fan and system switches
58 IM 1152-10
Addendum IM 1014 — MT155
Wiring Diagrams
Figure 2: Units with remote sensing capability Figure 4: Units with no switches with local/remote sensing
capability
TB3-1 HEAT
OUTPUT
TB3-2 COOL
TB3-1 HEAT
TB3 OUTPUT OUTPUT
1
TB3-3
2 3
1
TB2
2 3
L2 or NEUTRAL TB1-4 TB2-2 FAN HIGH TB3-3
L1
1
CONNECT 5
TB2-3 FAN MED
2 3
CONTINUOUS
TB2-4 FAN LOW
2 3
L2 or NEUTRAL TB1-4
5
NO CONNECTION TB1-3
4
2 3
REMOTE PROBE 1 TB1-2
TB1
1
Figure 3: Units with switches used for local sensing only
Figure 5: Units with no switches used for local sensing
TB3-1 HEAT
only
OUTPUT
1
TB2
L2 or NEUTRAL TB2-2 FAN HIGH
2 3
TB1-4 TB3-3
1
CONNECT L1
TB2-3 FAN MED
2 3
CONTINUOUS
TB2-4 FAN LOW
1
L2 or NEUTRAL TB1-4
5
NO CONNECTION TB1-3
2
1
TB1
IM 1152-10 59
Addendum Material
General Installation
DANGER
Two-pipe system (Cooling or Heating)
READ THESE INSTRUCTIONS CAREFULLY BEFORE
To field wire a T*155 thermostat (either as wall-mounted or
ATTEMPTING TO INSTALL, OPERATE OR SERVICE
unit-mounted) and field-install valve package for a 2-pipe
THIS THERMOSTAT.
system the following accessories are required:
Failure to observe safety information and comply with
• Single-Pole Double-Throw Automatic Changeover
instructions could result in PERSONAL INJURY, DEATH
Switch (SPDT ACO Kit P/N 039398600)
AND/ OR PROPERTY DAMAGE.
• Thermostat TA155 (kit) – PN 107345302 or
To avoid electrical shock or damage to equipment, Thermostat TB155 (kit) – PN 107345304
disconnect power before installing or servicing. Use only
wiring with insulation rated for full thermostat operating • 10K Return Air Sensor - PN 107345501
voltage. Use copper wire only. Insulate or wire-nut all un-
Step 1: Installing NC (Normally Closed)
used leads. Any wiring, including the remote probe, may
carry the full operating voltage of the thermostat. To avoid valve packages
potential fire and/ or explosion do not use in potentially • Solder the appropriate inlet and outlet pipe
flammable or explosive atmospheres. Retain these connections from the valve package to the coil
instructions for future reference. You must review your connections. Refer to Figures 1, 2, 3 and 4.
application and national and local codes to ensure that • Snap-on the SPDT ACO Switch on the supply side of
your installation will be functional and safe. the valve package (SPDT ACO Kit P/N 039398600 to
be ordered as field-installed option)
CAUTION • Cut white wire 60 of the wiring harness leading from
Care should be used to avoid electrostatic discharge to the Low Voltage Interface Board terminal connection
the microprocessor. (see Fig. 1) prior to attaching the quick-connect
This unit has configuration dip switches and jumpers. connector of the On-Off valve actuator to the interface
You may need to reconfigure the thermostat for your board (Fig. 3). The white wire lead going to the
application. actuator will be connected to terminal No. 1 of the
ACO switch (see Fig. 5):
— Terminal No. 1: black wire - to be connected to
the valve side (G terminal) with white wire of the
terminal strip
— Terminal No. 2: red wire – to be connected to the
IM 1089 MT A/B Thermostat: Field Installation
IM 1152-10 61
Addendum IM 1089 — MT155 A/B
Figure 1: Automatic changeover connection between the valve actuator and the interface board
Cap the
wire
RED to TB3 - 1
WHITE 60 BLACK of T-stat WHITE
ACO to TB3 - 2 CLG +
BLUE of T-stat
G0 WHITE 61
CLG –
WHITE 62
COM
Valve
Acuator
Wiring Harness LV
Board
Figure 2: Low Voltage Interface Board shown with all additional support options
Line Voltage
Hi-Med-Lo Fan
motor control
FA
Clg. 24vac valve actuators inputs
Available in Stock
62 IM 1152-10
Addendum IM 1089 — MT155 A/B
Figure 3: Factory-installed and wired Low Voltage Interface Board (Wiring Diagram)
Figure 4: Thermostat TB155 autochangeover to be used with ON-OFF 24V valve packages, SPDT ACO and unit-mounted
Low Voltage Interface Board
IM 1152-10 63
Addendum IM 1089 — MT155 A/B
64 IM 1152-10
Addendum IM 1015 — MT158 A
Installation
DANGER 3. Remove the cover. Mount thermostat base assembly
to the outlet box using the screws provided, tighten
READ THESE INSTRUCTIONS CAREFULLY BEFORE the screws evenly but do not over tighten. Connect
ATTEMPTING TO INSTALL, OPERATE OR SERVICE wires as shown in the appropriate wiring diagram for
THIS THERMOSTAT. your thermostat style.
Failure to observe safety information and comply with 4. To use a remote sensor on units with local sensing
instructions could result in PERSONAL INJURY, DEATH capability, remove jumper JP-1 to disable local
AND/ OR PROPERTY DAMAGE. sensing. Failure to remove JP-1 will cause improper
To avoid electrical shock or damage to equipment, operation of the thermostat.
disconnect power before installing or servicing. Use only
wiring with insulation rated for full thermostat operating Figure 1: Wiring Diagram for ON/OFF Output
voltage. Use copper wire only. Insulate or wirenut all Configuration
unused leads. Any wiring, including the remote probe,may
C ONNE C T IONS
LINE V OLTAG E
L1 (HOT)
carry the full operating voltage of the thermostat. 1
To avoid potential fire and/ or explosion do not use in LO
2
potentially flammable or explosive atmospheres. MED L2 OR NEUTRAL
3 FAN
Retain these instructions for future reference. You must HIGH
review your application and national and local codes to 4
OR SINGLE SPEED FAN
ensure that your installation will be functional and safe.
24 VAC 1
5 24 VAC
CAUTION 24 VAC 2 XFMR
6
Care should be used to avoid electrostatic discharge to SETBACK INPUT
the microprocessor. 7
MAIN 1 MAIN 1
This unit has configuration jumpers. You may need to 10 OUTPUT
reconfigure this thermostat for your application. SEC 1 SECONDARY
11 1 OUTPUT
C ONNE C T IONS
LOW V OLTAG E
IM 1152-10 65
Addendum IM 1015 — MT158 A
Summer: OFF Summer: ON 6. Checkout: After wiring and installation are complete,
Secondary with heat demand with heat demand
(Terminal 11) energize the system and check the operation. Adjust the
Winter: Disabled Summer: Disabled
thermostat as necessary to complete at least one cycle.
Secondary 2
(Terminal 13)
NA NA Be sure the thermostat and all other equipment are
Note: * Operation determined by configuration. See Dip Switch Configuration Table. functioning correctly.
Thermostat Operation
These thermostats are designed to control ON-OFF, N.O. and Setback Operation
N.C. valves, relays and Erie® three wire floating valves. These
units may include a fan switch with one or more fan speed Connection of the Setback Input to 24 VAC 1 will force the
selections. control into unoccupied mode (see wiring diagram). Pressing
an arrow key or the mode button on the thermostat cover will
disable the setback input for one hour.
Mode Button Operation
OFF: All thermostat outputs are off, fan is still operational if Pipe Sensor Operation
connected to manual fan speed switch.
If cold water is detected, the system will operate in summer
AUTO: The thermostat automatically selects heating or cooling mode and the Main output will be cooling. If hot water is
mode depending on the set point and room temperature. The detected, the system will operate in winter mode, the Main
appropriate HEAT or COOL indicator is enabled in addition to output will be heating and First Stage Secondary Output will be
AUTO. A 3°F dead-band is provided to prevent short cycling disabled. In the case of an ambiguous reading, neither hot nor
between heating and cooling modes. After change-over the cold, the thermostat will initiate a purge cycle.
control points automatically shift so that the heating off-point or
the cooling off-point equals the setpoint temperature.
Ratings
COOL: The thermostat operates as a cooling-only thermostat.
by pressing the UP and DOWN arrows simultaneously. The Table 2: Fan and system switches
heating outputs are disabled.
Voltage Inductive Resistive Pilot Thermostatic
HEAT: The thermostat operates as a heating-only thermostat. Rating FLA LRA Amps Duty Switching
The cooling outputs are disabled. 24 VAC N.A. N.A. N.A. 24 VA 10 VA
120 VAC 5.8 34.8 6.0 125 VA NA
If constructed without a mode button, the thermostat operates
240 VAC 2.9 17.4 5.0 125 VA NA
in Auto mode, subject to configuration of the 2/4 pipe jumper
277 VAC 2.4 14.4 4.2 125 VA NA
and pipe sensor input.
66 IM 1152-10
Addendum IM 1015 — MT158 A
1
DIP S WIT C H
Menu Selection: Select 1 to 5 by pressing the mode button or
2 3 4 5 6
by pressing the UP▲ and DOWN▼ arrows simultaneously.
Adjust Value: Use UP▲ or DOWN▼ arrow.
AUTO J P4
Item # Function Range Default 10 11 12 13 15 16 17
1 Zone Temp Offset -5.1°F to 5.1°F 0°F 5 6 7 1 2 3 4
2 Valve Stroke Time 30 sec. to 5 min. 120 sec.
3 Fan Delay to OFF 0 to 10 minutes 0 sec.
Compressor
4 Minimum OFF 30 sec. to 10 min. 120 sec.
Time
J P1
0 = Time Based
5 Purge Cycle 1 = Temperature 1
Based
MAIN 1 OF F WIT H DE MAND MAIN 1 ON WIT H DE MAND JP1 Local Sensing Remote Sensing
C E NT IG R ADE DIS P LAY FAHR E NHE IT DIS P LAY JP4 2 Pipe System* 4 Pipe System
OP E R AT ING P OS IT ION N/A
Application Notes
OP E R AT ING P OS IT ION N/A
85 F / 60 F S E T B AC K 90 F / 50 F S E T B AC K
IM 1152-10 67
Addendum Material
DANGER Installation
READ THESE INSTRUCTIONS CAREFULLY BEFORE 1. Install the thermostat with the two furnished mounting
ATTEMPTING TO INSTALL, OPERATE OR SERVICE screws to a standard 4-11/16" × 2-1/8" square device
THIS THERMOSTAT. box with a 2" × 4" adapter ring.
Failure to observe safety information and comply with 2. For wall installations, mount the thermostat on an
instructions could result in PERSONAL INJURY, DEATH inside wall approximately 5 feet above the floor. The
AND/ OR PROPERTY DAMAGE. location should provide circulation at average room
To avoid electrical shock or damage to equipment, temperature. Avoid direct sunlight or sources of hot or
disconnect power before installing or servicing. Use only cold air in the room or wall.
wiring with insulation rated for full thermostat operating 3. Remove the cover. Mount thermostat base assembly
voltage. Use copper wire only. Insulate or wirenut all un- to the outlet box using the screws provided, tighten
used leads. Any wiring, including the remote probe,may the screws evenly but do not over tighten. Connect
carry the full operating voltage of the thermostat. wires as shown in the appropriate wiring diagram for
To avoid potential fire and/ or explosion do not use in your thermostat style.
potentially flammable or explosive atmospheres. 4. To use a remote sensor on units with local sensing
Retain these instructions for future reference. You must capability, remove jumper JP-1 to disable local
review your application and national and local codes to sensing. Failure to remove JP-1 will cause improper
ensure that your installation will be functional and safe. operation of the thermostat.
5. Remove the LCD plastic protective film. Reinstall
CAUTION the cover assembly. Install the cover locking screw
Care should be used to avoid electrostatic discharge to provided in the hole at the left side of the control
the microprocessor. enclosure to complete the installation.
This unit has configuration jumpers. You may need to 6. Checkout: After wiring and installation are complete,
reconfigure this thermostat for your application. energize the system and check the operation. Adjust
the thermostat as necessary to complete at least one
cycle. Be sure the thermostat and all other equipment
are functioning correctly.
IM 1152-10 69
Addendum IM 1016 — MT158 B
Thermostatic
LINE V OLTAG E
L1 (HOT) Voltage
1 Rating Inductive Resistive Switching
Amps Pilot Duty (Pilot Duty)
LO FLA LRA
2 24 VAC N.A. N.A. N.A. 24 VA 10 VA
MED L2 OR NEUTRAL
3 FAN 120 VAC 5.8 34.8 6.0 125 VA NA
HIGH 240 VAC 2.9 17.4 5.0 125 VA NA
4 277 VAC 2.4 14.4 4.2 125 VA NA
OR SINGLE SPEED FAN
24 VAC 1
5 24 VAC
6
24 VAC 2 XFMR Thermostat Operation
SETBACK INPUT These thermostats are designed to control ON-OFF, N.O.
7
and N.C. valves, relays and three-wire floating valves. These
MAIN 1 OPEN
10 MAIN units may include a fan switch with one or more fan speed
SEC 1 OPEN selections.
11
C ONNE C T IONS
LOW V OLTAG E
MAIN 2 CLOSE
12 Table 2: Main and Secondary Output Operation*
SEC 2 CLOSE SECONDARY
13 3-Wire OFF ON
Output Floating with Demand with Demand
OUTSIDE AIR
14 DAMPER OUTPUT Main 1 Powers main ON at temp ON at temp
(Terminal 10) valve open demand demand
15 REMOTE PROBE Main 2 Powers main Cycles ON with Cycles ON with
(Terminal 12) valve closed demand demand
16 PIPE SENSOR
Summer: OFF Summer: ON with
Secondary Powers secondary with heat demand heat demand
17 (Terminal 11) valve open
Winter: Disabled Winter: Disabled
L1 (HOT)
1
LO
Mode Button Operation
2
OFF: All thermostat outputs are off, fan is still operational if
MED L2 OR NEUTRAL
3 FAN connected to manual fan speed switch.
HIGH
4 AUTO: The thermostat automatically selects heating or cooling
OR SINGLE SPEED FAN
mode depending on the set point and room temperature. The
5
24 VAC 1 appropriate HEAT or COOL indicator is enabled in addition to
24 VAC
24 VAC 2 XFMR
AUTO. A 3°F dead-band is provided to prevent short cycling
6 between heating and cooling modes.
SETBACK INPUT
7 After change-over the control points automatically shift so that
MAIN 1 MAIN 1 the heating OFF-point or the cooling OFF-point equals the set
10 OUTPUT
SEC 1
point temperature.
SECONDARY
11 1 OUTPUT COOL: The thermostat operates as a cooling-only thermostat.
C ONNE C T IONS
LOW V OLTAG E
FAN DEMAND
12 OUTPUT
The heating outputs are disabled.
HEAT 2 2ND STAGE
13 HEAT: The thermostat operates as a heating-only thermostat.
HEAT
OUTSIDE AIR The cooling outputs are disabled.
14 DAMPER OUTPUT
If constructed without a mode button, the thermostat operates
15 REMOTE PROBE in Auto mode, subject to configuration of the 2/4 pipe jumper
16 PIPE SENSOR and pipe sensor input.
17
70 IM 1152-10
Addendum IM 1016 — MT158 B
1
DIP S WIT C H
2 3 4 5 6
Pipe Sensor Operation
If cold water is detected, the system will operate in summer
AUTO J P4
mode and the Main output will be cooling. If hot water is
10 11 12 13 15 16 17
detected, the system will operate in winter mode, the Main
output will be heating and First Stage Secondary Output will be
5 6 7 1 2 3 4
J P1
Open and Close outputs are used to position the valve.
Stroke time is factory set at two minutes. Outputs are off after
reaching full on or off position. Valves are periodically reset for Figure 4: Dip Switch Configuration
accuracy.
ON
Secondary 1 OFF with Demand Secondary 1 ON with Demand
1 2 3 4 5 6
Outside Air Damper Operation Main 1 OFF with Demand Main 1 ON with Demand
This output is ON any time the control is turned ON. Centigrade Display Fahrenheit Display
IM 1152-10 71
Addendum Material
Installation
DANGER 1. Install the thermostat with the two furnished mounting
screws to a standard 4-1/16" × 2-1/8" square device
READ THESE INSTRUCTIONS CAREFULLY BEFORE ATTEMPTING box with a 2" × 4" adapter ring.
TO INSTALL, OPERATE OR SERVICE THIS THERMOSTAT.
2. For wall installations, mount the thermostat on an
Failure to observe safety information and comply with instructions inside wall approximately 5 feet above the floor. The
could result in PERSONAL INJURY, DEATH AND/ OR PROPERTY location should provide circulation at average room
DAMAGE. temperature. Avoid direct sunlight or sources of hot or
To avoid electrical shock or damage to equipment, disconnect power cold air in the room or wall.
before installing or servicing. Use only wiring with insulation rated for 3. Remove the cover. Mount thermostat base assembly
full thermostat operating voltage. Use copper wire only. Insulate or to the outlet box using screws provided. Tighten the
wire-nut all un-used leads. Any wiring, including the remote probe, may screws evenly but do not overtighten. Connect wires
carry the full operating voltage of the thermostat. per wiring diagram.
To avoid potential fire and/ or explosion do not use in potentially 4. To use a remote sensor on units with local sensing
flammable or explosive atmospheres. capability, remove jumper JP-1 to disable local
Retain these instructions for future reference. You must review your sensing. Failure to remove JP-1 will cause improper
application and national and local codes to ensure that your installation operation of thermostat.
will be functional and safe. 5. Connecting a jumper between terminals 16 and 17
will disable the secondary output and change the
CAUTION main output to heat mode.
Care should be used to avoid electrostatic discharge to the 6. Connection of a 24 VAC set-back signal will force
microprocessor. the control into unoccupied mode (see diagram).
This unit has configuration dip switches and jumpers. You may need to Pressing an arrow key or the mode buttons on the
reconfigure the thermostat for your application. thermostat cover will disable the setback input for
one hour.
7. Remove the LCD plastic protective film to complete
the installation. Reinstall the cover assembly. Install
cover locking screw provided.
8. Checkout: After wiring and installation are complete,
energize the system and check the operation. Adjust
the thermostat as necessary to complete at least one
cycle. Be sure the thermostat and all other equipment
are functioning correctly.
IM 1152-10 73
Addendum IM 1017 — MT168
Figure 2: Typical Wiring* 4. The set point and operating mode will be retained on a
loss of power.
C O N N E C T IO N S
L1 (HOT)
1
wiring away from any electrical motors or power wiring.
LO FAN
2 6. The auxiliary heat output supplies a 24 VAC signal with
MED FAN L2 OR NEUTRAL
3 FAN call for heat. This output is shipped configured for staged
HIGH FAN heat.
4 OR SINGLE SPEED
7. The thermostat is shipped with all dip switches in the
24 VAC 1 “ON” (closed) position.
5 24 VAC
24 VAC 2 XFMR 8. The damper output is ON when mode is AUTO, HEAT or
6
COOL. Damper is OFF in set back.
SETBACK
7
MAIN 1
10
SECONDARY
0-10 VDC
OUTPUT Thermostat Operation
11 0-10 VDC
1 OUTPUT These thermostats are designed to control 0-10 VDC/4-0 mA
C O N N E C T IO N S
L O W V O LTA G E
FAN
12 OUTPUT valves. These units may include a fan switch with one or more
AUXILIARY fan speed selections.
13 HEAT
OUTPUT
DAMPER
14 OUTPUT Mode Button Operation
15 OPTIONAL REMOTE PROBE OFF: All thermostat outputs are off, fan is still operational if
16 connected to a manual fan switch.
AUTO: The thermostat automatically selects heating or cooling
17 OPTIONAL PIPE SENSOR
mode depending upon the relationship of the setpoint and the
room temperature. The appropriate HEAT or COOL indicator
is enabled in addition to AUTO. A 3°F dead band is provided
NOTE: Note: * Specific models may have fewer connections.
to prevent short cycling between heating and cooling modes.
After changeover, the control points automatically shift so that
Electrical Ratings the heating OFF-point equals the set point temperature or the
cooling OFF-point equals the set point temperature.
Table 1: Fan switch (terminals 1-4) line voltage
COOL: The thermostat operates as a cooling only thermostat.
connections
The heating outputs are disabled.
Voltage Inductive Resistive Pilot Thermostatic HEAT: The thermostat operates as a heating-only thermostat.
Rating FLA LRA Amps Duty Switching
The cooling outputs are disabled.
24 VAC N.A. N.A. N.A. 24 VA 10 VA
120 VAC 5.8 34.8 6.0 125 VA NA
240 VAC 2.9 17.4 5.0 125 VA NA
277 VAC 2.4 14.4 4.2 125 VA NA
74 IM 1152-10
Addendum IM 1017 — MT168
IM 1152-10 75
Addendum Material
T170 Thermostat
24 VAC/120–277 VAC
3-Speed Fan Control (Continuous or Cycling) or Staged Fan Control
WARNING
BEFORE ATTEMPTING TO INSTALL, OPERATE, OR
SERVICE THIS THERMOSTAT, CAREFULLY READ
THESE INSTRUCTIONS.
Failure to observe safety information and comply with
instructions could result in PERSONAL INJURY, DEATH,
AND/OR PROPERTY DAMAGE.
To avoid potential fire and/or explosion, do not use in
potentially flammable or explosive atmospheres.
Retain these instructions for future reference. This
product, when installed, is part of an engineered system
whose specifications and performance characteristics are
not designed or controlled by Daikin. You must review
your application and national and local codes to assure
that your installation is functional and safe.
US
DANGER
Hazardous voltage. To avoid electrical shock or damage
to equipment, disconnect power before installing or
servicing.
Failure to follow these instructions will result in death or
serious injury.
IM 846 T 170 Thermostat
IM 1152-10 77
Addendum IM 846 — MT170
Installation
Thermostat Model and Part Number The thermostat base mounts to a field provided 4" × 4" outlet
box with a 2" × 4" mud ring (Figure 1). The thermostat cover
Daikin offers two different thermostats depending on the fan assembly mounts to the thermostat base.
speed control used (Table 1).
1. Disconnect power before installing or servicing.
Table 1: Thermostat model and part numbers 2. Run line voltage wiring (and low voltage wiring if
applicable) into the field provided outlet box and mud
Model Number Part Number Fan Speed Control ring (Figure 1).
TA170-001 107345335 3-Speed Fan Control
TB170-001 107345336 Staged Fan 3. Locate all connections within the mud ring/connection
Note – For a list of thermostat features, refer to ED 3611. box and wire nut all unused wires.
4. Remove the thermostat cover assembly from its base to
Optional Occupancy Detection Sensors/ gain access to the circuit board (Figure 2).
Kits 5. On the circuit board, set the voltage selection switch
In addition to the T170 thermostat, Daikin offers optional (Figure 2) to the appropriate voltage for the application
occupancy detection sensors that can be ordered and used
• 24 V = 24 VAC
in conjunction with the thermostat. When ordering, use the
associated kit number(s) • 110–277 V = 120, 240, or 277 VAC.
NOTE: The circuit board is shipped with the voltage selection
switch in the 110-227 V position. For 24 VAC use, the
Table 2: Occupancy sensor model and kit numbers
switch must be in the 24 V position.
Model Number Kit Number
6. The circuit board is also equipped with configuration
SA200-001 6677877211
jumpers (JP1, JP3, and JP4 in Figure 2). Depending on
SB200-001 6677877311
the application, it may be necessary to reconfigure the
SD200-001 6677877411
following jumpers:
SB200-002 6677877511
• JP4: 2/4 Pipe Sensor Jumper - This jumper selects
between 2-pipe (jumper ON) and 4-pipe (jumper OFF)
Mounting and Wiring the Thermostat operation (Fan Operation).
• JP3: Door/Window Switch Jumper - This jumper is
CAUTION shipped normally open. Placement of a jumper allows
Before applying power, the voltage selection switch must be in for occupancy detection and door/window switch only
the appropriate position. Failure to select the correct voltage operation (Optional Occupancy Detection Equipment
can cause thermostat malfunction or permanently damage Operation).
the thermostat. • JP1: Removal of this jumper allows the sensor to be
located in a remote location.
CAUTION 7. Connect the color coded thermostat wires (Figure 3) to
To use a remote sensor on units with local sensing capability, the line voltage wires located in the mud ring/connection
remove jumper JP1 to disable local sensing. Failure to remove box and secure the connections with wire nuts.
JP1 can cause improper operation of the thermostat with a 8. Install the thermostat base to the mud ring/outlet box
remote probe installed. using two furnished mounting screws. Tighten the screws
evenly but do not over tighten.
CAUTION
NOTE: An output ratings chart (Table 3) is located on the
Use copper wire only. Insulate or wire nut all unused leads. inside of the base.
Avoid electrostatic discharge to the thermostat. Failure to do
9. With the base now secured, verify that the circuit board is
so can cause thermostat malfunction or permanently damage
firmly snapped into the cover and is not dislodged.
the thermostat.
10. Install the cover assembly to the base, pressing firmly to
DANGER engage the cover locking snaps.
Hazardous voltage. Combined load current is not to exceed
20 amps. Mount only to a grounded metallic box. Low voltage
wiring is Class 2. To avoid electrical shock or damage to
equipment, disconnect power before installing or servicing.
Failure to follow these instructions will result in death or
serious injury.
78 IM 1152-10
Addendum IM 846 — MT170
MODES:
AUTO
UP/DOWN
COOL ARROW
JP4 HEAT BUTTONS
OFF
JP3
JP1
White/Yellow
Remote Probe The System button (Figure 4) contains and displays the
LOW VOLTAGE
Accessories
following modes of operation:
THERMOSTAT CONNECTIONS
White/Violet
Circuit Common Available
from
Pipe Sensor SUNNE CONTROLS
OFF—All thermostat outputs are off. The fan is still operational
White/Blue
if FAN ON is selected.
Occupancy Detector
White/Gray
AUTO—The thermostat automatically selects heating
Yellow L2 / NEUTRAL or cooling mode depending on the set point and room
Blue
Cool temperature. If demand exists, the appropriate HEAT or COOL
(Main Output)
Heat
icon illuminates. A 3°F dead band is provided to prevent short
Red (Secondary Output)
cycling between heating and cooling modes. After changeover,
LINE VOLTAGE
White/Brown Fan Low the control point automatically shifts so that the control OFF
OUTPUTS
White/Red Fan Medium
See Ratings point equals the set point temperature.
IM 1152-10 79
Addendum IM 846 — MT170
80 IM 1152-10
Addendum IM 846 — MT170
6. Set back heat: When this function is selected, the Fan Operation
current temperature range adjustment, the SET BACK
icon, and the HEAT icon appear. To increase or decrease The thermostat may be factory configured for standard or
the value, press the up or down arrow button. staged fan operation.
7. Set back cool: When this function is selected, the Standard Fan Configuration (TA170-001)
current Cool setback value, the SET BACK icon, and the
COOL icon appear. To increase or decrease the value, Units with standard fan operation (Figure 7) have a selectable
press the up or down arrow button. fan Speed button.
are made in 1°F and 0.5°C. FAN AUTO: Fan cycles on with demand.
Set Point
into the service menu. To increase or decrease the value, TEMPERATURE DEMAND - HEAT
IM 1152-10 81
Addendum IM 846 — MT170
Fan Coil Operation 5. After the three minute purge cycle occurs, the thermostat
checks to see if the water temperature is more than 15°F
Fan Coil operation is either a 2-pipe or 4-pipe configuration from the set point, or above 80°F, or below 60°F.
which is determined by jumper selection JP4 (Mounting and
Wiring the Thermostat). If yes, normal HVAC operation occurs.
If no, the valve is left open and the thermostat continues
2-Pipe Operation to search for a valid reading.
In this configuration, the thermostat permanently disables NOTE: If at any time the demand goes away, the thermostat
the secondary output and disables the fan from cycling in an will stop the purge cycle.
invalid mode. The main output configuration is dependent
on the pipe sensor input. With a pipe sensor connected, the Table 4 shows output operation, depending on the sensed
thermostat automatically selects heating or cooling depending water temperature.
on the sensed water temperature. If the pipe sensor input is
open (unconnected), the main output only cools. If the pipe Table 4: Output operation
sensor input is shorted, the main output only heats. Normal
Output Operation
thermostat default is for 4-pipe operation. For 2-pipe operation, 2-Pipe/4-Pipe Water
Selection Temperature Secondary
install a jumper on JP4. Main Output Output
Cooling only
4-Pipe Operation Cold The fan does not Disabled
cycle ON with a
In this configuration, both the main output (COOL) and the 2-pipe heat demand.
secondary output (HEAT) are available. These both cycle ON JP4 ON Heating only
depending on the mode of the thermostat. With a pipe sensor Hot The fan does not Disabled
connected, the thermostat automatically changes the main cycle ON with a
cool demand.
output to heat and disables the secondary output if the main coil Cold Cooling Heating
water is hot. For 4-pipe operation, the JP4 jumper is removed. Heating only
4-pipe
JP4 OFF Hot The fan does not Disabled
Pipe Sensor Operation cycle ON with a
cool demand.
A pipe sensor can be connected when the thermostat is
configured for either 2-pipe or 4-pipe configuration. The pipe
sensor is used to determine the water temperature in the main
Setback Operation
coil, which should be connected to the primary output. In this configuration, the low level switch input normally is
open. To enable setback operation, the JP3 jumper is removed
Pipe sensor input—use a 10K Remote Probe or a standard
(Mounting and Wiring the Thermostat). The input will close and
ON-OFF Aquastat for summer/winter changeover.
the thermostat heating and cooling setback limits can then be
used as temperature control points. Fan operation in setback
Purge Cycle
is cycled with demand. Press any thermostat key to override
With a pipe sensor connected, the thermostat initiates a setback for one hour. Setback overrides any user setting except
purge cycle if the sensed water temperature is ambiguous if the control is turned to OFF.
(not adequately hot or cold). The sequence for purge cycle
operation is as follows:
1. The thermostat has a call for heat or cooling.
NOTE: If at any time the call goes away, the thermostat stops
the purge cycle.
2. The thermostat checks the pipe sensor to verify water
temperature.
3. If the water temperature is beyond 15°F of the set point,
normal HVAC control occurs.
4. If the water temperature is not beyond 15°F of the
set point, the thermostat checks to see if the water
temperature is above 80°F or below 60°F.
If yes, normal HVAC control occurs.
If no, the thermostat opens the main output (COOL) for
three minutes.
82 IM 1152-10
Addendum IM 846 — MT170
IM 1152-10 83
Addendum IM 846 — MT170
84 IM 1152-10
Addendum IM 846 — MT170
IM 1152-10 85
Addendum Material
IM 1152-10 87
Addendum IM 1019 — MT180
Table of ConTenTs
Table of ConTenTs
88 IM 1152-10
Addendum IM 1019 — MT180
InsTallaTIon InsTruCTIons
InsTallaTIon InsTruCTIons
WARNING
Applications and Features
READ THESE INSTRUCTIONS CAREFULLY BEFORE
ATTEMPTING TO INSTALL, OPERATE OR SERVICE THIS For 2 or 4 Pipe Fan Coil and ON/OFF Control
THERMOSTAT. Applications
Failure to observe safety information and comply with • 7 Day, 4 Event Programmability
instructions could result in PERSONAL INJURY, DEATH
AND/OR PROPERTY DAMAGE. • System Selection: OFF-Heat-Cool-Auto-Setback
• 6 Outputs: 1H, 1C, Up to 3 Fan, OA Damper
To avoid electrical shock or damage to equipment, disconnect
power before installing or servicing and use only wiring with • Fan Control: 1-3 Speeds
insulation rated for full thermostat operating voltage. — Cycling (Auto) or Continuous (ON)
Before installing this control, the Voltage Selection Switch — Automatic Fan Speed Staging (TB180 models only)
must be placed in the correct position. See instructions. To
avoid potential fire and/or explosion do not use in potentially
Connections for:
flammable or explosive atmospheres. • Fan Coil Pipe Sensor
Retain these instructions for future reference. This product, • Remote Temperature Probe
when installed, will be part of an engineered system whose • Occupancy Control
specifications and performance characteristics are not • Door Switch or Setback
designed or controlled by PECO. You must review your
• Condensate Overflow
application and national and local codes to assure that your
installation will be functional and safe.
CAUTION
• Use copper wire only, insulate or wire nut all unused
leads.
• Care should be used to avoid electrostatic discharge to
the T180 thermostat.
• This unit has configuration jumpers. You may need to
reconfigure this thermostat for your application
IM 1152-10 89
Addendum IM 1019 — MT180
InsTallaTIon InsTruCTIons
90 IM 1152-10
Addendum IM 1019 — MT180
InsTallaTIon InsTruCTIons
CAUTION
To use a remote sensor on units with local sensing capability,
remove jumper JP1 to disable local sensing. Failure to remove
JP1 can cause improper operation of the thermostat with a
remote probe installed.
CAUTION
• Use copper wire only. Insulate or wire nut all unused
leads.
• Avoid electrostatic discharge to the thermostat.
• Failure to do so can cause thermostat malfunction or
permanently damage the thermostat.
The thermostat should be used indoors only. It should be
mounted on an inner wall in a location with freely circulating
DANGER air, and where it will be responsive to changes in room
Hazardous voltage. Combined load current is not to exceed temperature. Avoid mounting near heat generating appliances
20 amps. Mount only to a grounded metallic box. Low voltage (i.e. TV, heater, refrigerator), or in direct sunlight.
wiring is Class 2. To avoid electrical shock or Damage to The thermostat base mounts to a field provided 4” × 4” outlet
equipment, disconnect power before installing or servicing. box with a 2” × 4” horizontal mud ring. The thermostat cover
Failure to follow these instructions will result in death or assembly mounts to the thermostat base.
serious injury
1. Disconnect power before installing or servicing.
Figure 2: Mounting the Thermostat 2. Run line voltage wiring (and low voltage wiring if
applicable) into the field provided outlet box and mud
ring (Figure 2).
3. Locate all connections within the mud ring/connection
box and wire nut all unused wires.
4. Remove the thermostat cover assembly from its base to
gain access to the circuit board (Figure 3).
5. On the circuit board, set the voltage selection switch
(Figure 3) to the appropriate position prior to application
of power.
• 24V = 24 VAC
• 110-277 V = 120, 240 or 277 VAC
IM 1152-10 91
Addendum IM 1019 — MT180
InsTallaTIon InsTruCTIons
6. The circuit board is also equipped with configuration Figure 4: Wiring Diagram
jumpers (JP1, JP3, and JP4 in Figure 3). Depending on
the application, it may be necessary to reconfigure the
following jumpers:
JP1 Jumper Selection – Remote Temperature Sensor
Local Sensing – Install JP1
Remote Sensing – Remove JP1 – Accessory sensors
are available in standard 60” lengths but can be
extended to meet application requirements.
JP3 Jumper Selection – HVAC Setback Systems
The JP3 jumper allows the T180 to be configured for
Setback, Occupancy Detection or Door Switch Only
Occupancy Operations. For further descriptions of these
conditions please see the Technical and Application
Notes‚ page 12.
• Setback Operation - Remove JP3
• Occupancy Detection - Install JP3
• Door Switch Only - Install JP3
JP4 Jumper Selection – 2 or 4 Pipe Operation
Connection of a pipe sensor will change the operation of
the outputs as shown in Table 4. (See Technical Notes
for further information on Pipe Sensor Operation‚ page Table 4: Jumper Activation
12)
Secondary
Pipe Sensor Main Output
• 2-Pipe Operation - Install JP4 - The thermostat will JP4 Section Water Temp Aqua Stat (Blue Wire) Output (Red
wire)
permanently disable the Secondary Output and
2-Pipe Cold Open Cooling Only Disabled
disables system and fan invalid modes.
JP4-ON Hot Closed Heating Only Disabled
• 4-Pipe Operation - Remove JP4 - Both the Main 2-Pipe Cold Open Cooling Heating
Output (COOL) and Secondary Output (HEAT) will be JP4-OFF Hot Closed Heating Only Disabled
available. NOTE: *Fan will not cycle on for disabled modes.
7. Connect the color coded thermostat wires (Figure 4) to
the line voltage wires located in the mud ring/connection
box and secure the connections with wire nuts. Table 5: Output Ratings
8. Install the thermostat base to the mud ring/outlet box Voltage FLA LRA RES Amps Pilot Duty HP
using two furnished mounting screws. Tighten the screws 24 VAC NA NA NA 24 VA NA
evenly but do not over tighten. 120 VAC 5.8 34.8 6.0 125 VA ¼
240 VAC 2.9 17.4 5.0 125 VA ¼
NOTE: Note: An output ratings chart (Table 5) is located on
the inside of the base. 277 VAC 2.4 14.4 4.2 125 VA ¼
Combined Load Current Not to Exceed 20 Amps
9. With the base now secured, verify that the circuit board is
firmly snapped into the cover and is not dislodged.
10. Install the cover assembly to the base, pressing firmly to
engage the cover locking snaps.
92 IM 1152-10
Addendum IM 1019 — MT180
operaTIon
operaTIon
The thermostat interface (Figure 5) contains buttons for 1. System Mode Display (See Table 6)
use in navigating to accompanying menus/screens and for
2. Temperature Display (See Table 7)
performing specific operations. These buttons and operations
are described below. 3. Time and Day Display (See Table 8)
1. Liquid Crystal Display with a blue backlight 4. Programming Commands (See Table 9)
2. UP .and DOWN .Buttons 5. Time Period Indicators
3. SYSTEM Button WAKE, DAY, EVE, and SLEEP are the names given to
the four time periods per day. Each time period has its
4. FAN Button
own unique setpoint temperatures as shown in Table 15.
5. PROGRAM Button. 6. Fan Operation Indicators (See Table 10)
7. Program Override Commands (See Table 11)
8. Service Indicator
The wrench symbol is displayed when there is a
temperature sensor error or condensate overflow error.
It indicates there is an open or a short connection to
the sensor switch. When this occurs, the thermostat will
disable all outputs and illuminate the wrench symbol.
A service technician should be called to determine the
cause of the error.
IM 1152-10 93
Addendum IM 1019 — MT180
operaTIon
94 IM 1152-10
Addendum IM 1019 — MT180
operaTIon
IM 1152-10 95
Addendum IM 1019 — MT180
operaTIon
96 IM 1152-10
Addendum IM 1019 — MT180
operaTIon
IM 1152-10 97
Addendum IM 1019 — MT180
operaTIon
98 IM 1152-10
Addendum IM 1019 — MT180
Fan Operation
The thermostat may be factory configured for standard or
staged fan operation.
Fan On: Fan is On continuously Fan Auto: Fan cycles On with demand Fan Medium
Fan On: Fan stays at lowest speed
Fan Low
Fan Low
Fan Auto: Fan cycles On with demand Fan On: Fan is On continuously
Fan On: Fan stays at lowest speed
Fan Medium
Fan High
Temperature Demand - Heat
Temperature Demand - Heat
Table 16: Standard Fan Operation Overview Table 17: Staged Fan Operation with Temperature Demand
Menu Description Overview
FAN ON Fan is on continuously and is not dependant on a heat or cool
demand Menu Description
Fan cycles on with a heat or cool temperature demand and FAN ON Fan stages from high to medium to low and stays continuously
FAN AUTO on in the lowest available speed
cycles off with the heat or cool output
FAN SPEED High, medium, or low is selected by the user FAN AUTO Fan stages from high to medium to low and cycles off at set
point
FAN SPEED selected by the thermostat program
IM 1152-10 99
Addendum IM 1019 — MT180
100 IM 1152-10
Addendum IM 1019 — MT180
IM 1152-10 101
Addendum IM 1019 — MT180
Operation
In an occupied mode, the thermostat operates normally
and looks for a door open signal. When the door opens, the
thermostat waits for a door close signal. If the door is open for
more than two minutes, the thermostat turns the HVAC system
outputs to OFF. During this two minute period, if any button
is pressed on the keypad, the time delay is extended to ten
minutes. The time delay can only be extended once. Once the
HVAC outputs transition to OFF, a door closure is required to
re-enable the outputs. When the door closes, the thermostat
starts a two minute timer and tries to detect occupancy. If the
timer expires and no occupancy is detected, the thermostat
transitions to an unoccupied state. If occupancy is detected
while the timer is running, the thermostat will remain in the
occupied mode.
In an unoccupied mode, the thermostat sets heating and
cooling set points to setback values as determined by factory
or user settings. The fan is automatically set to cycle with
demand. The thermostat continually monitors the occupancy
sensor and will enter into occupied mode if occupancy is
detected.
If the installation is only using a door/window switch, the
thermostat will disable the HVAC outputs if this output is open
for longer than two minutes.
102 IM 1152-10
Addendum IM 1019 — MT180
IM 1152-10 103
Addendum IM 1019 — MT180
annex I
annex I
Day Time Period Start Time Heat Setpoint Temperature Cool Setpoint Temperature
Wake
Day
Monday
Evening
Sleep
Wake
Day
Tuesday
Evening
Sleep
Wake
Day
Wednesday
Evening
Sleep
Wake
Day
Thursday
Evening
Sleep
Wake
Day
Friday
Evening
Sleep
Wake
Day
Saturday
Evening
Sleep
Wake
Day
Sunday
Evening
Sleep
104 IM 1152-10
Addendum IM 1019 — MT180
annex II
annex II
6 Setback Low 0-OFF 50–82°F, 11–27°C The temperature setpoint value you want the thermostat to Heat to when the
(55°F- Default) T180 is in the Setback mode.
0-OFF 50–90°F, 11–32°C The temperature setpoint value you want the thermostat to Cool to when the
7 Setback High (90°F- Default) T180 is in the Setback mode.
8 Zone Temp Offset +/- 9°F or +/- 4.5°C (0°F-Default) Zone Temperature offset adjusts the sensed Zone Temperature displayed,
allowing calibration in the field.
0-No keypad lockout (Default) This function blocks access to certain features of the device. The Service Menu
9 Keypad Lockout 1-Disables System/Fan/Program is still available if the keypad lockout is enabled.
2-Disables all buttons
1-ON ON-Fan is always on, regardless of demand. Auto-Fan is only ON with heating
10 Fan Mode 2-Auto or cooling demand. ON or Auto-User can choose either selection.
3-ON or Auto (Default)
1-High
11 Fan Speeds 2-Low, High Speeds which are selectable by the user.
3-Low, Med, High (Default)
OFF, Auto OFF, Heat, Cool, Auto (Default)
12 System Mode Sets the system modes the occupant is able to select.
OFF, Heat, Cool Heat, Cool, Auto
When enabled, the unit will control to the Setback setpoints. This function will
0-Disable (Default) also override the user mode setting of OFF if the room temperature is equal
13 Controlled OFF or OFF Override 1-Enable to or above the Cool Setback setpoint or equal to or below the Heat Setback
setpoint.
0-Disable (Default) When enabled, Setback is shown as an available system mode selection. If
14 Front Panel Setback Control Setback mode is selected, the thermostat will control to the current Setback
1-Enable Heat and Setback Cool setpoints.
The Outside Air output will cycle with heat or cool demand if Cycles mode is
0-Cycles (Default) chosen. The Outside Air output is active anytime the thermostat is out of the
15 Cycled Outside Air Damper 1-Continuous OFF mode when Continuous mode is chosen. When in Setback the Outside Air
output will turn OFF.
16 Temperature Based Purge Cycle 0-Time Based (Default) Determines if the Purge Cycle will be Temperature or Time Based.
1-Temperature Based
3°F (Default) A changeover deadband value prevents short cycling between Heating
17 Minimum Dead Band Adjustment 3–10°F, 1.5–5°C and Cooling modes. The value is adjustable to meet various HVAC system
requirements.
18 Factory Default Reset 0-Disable (Default) Toggles between OFF and DFLT. When factory default is desired, select DFLT.
1-Enable
25 Pre-Occupancy Purge 0 Hours (Default) Energizes Fan Low for selected number of hours (0-3) prior to events Wake
0–3 Hours (Occupied 1) and Day (Occupied 2)
30 Cycles Per Hour (CPH) Cooling 3 CPH (Default) Defines the number of cycles per hour for cooling. A selection of 0 disables
0–6 CPH cycling.
32 Cycles Per Hour (CPH) Heating 5 CPH (Default) Defines the number of cycles per hour for heating. A selection of 0 disables
0–12 CPH cycling.
35 Heat Recovery Rate 5°F/Hr (Default) Defines the rate in which the device achieves the comfort setpoint. 0 disables
0–18°F/Hr 0–10°C/Hr ramp recovery.
36 Cool Recovery Rate 5°F/Hr (Default) Defines the rate in which the device achieves the comfort setpoint. 0 disables
0–18°F/Hr 0–10°C/Hr ramp recovery.
40 Minimum OFF Time 4 Minutes (Default) Sets the minimum OFF time for both heat and cool output
1–10 Minutes
0-Disable (Default) If enable is selected, the intermittent fan will operate during setback operation.
45 Intermittent Fan 1-Enable (Default values will be used unless menu 46 and 47 are adjusted.)
5 Minutes (Default) Defines the duration in which fan low will be ON. Fan ON will be activated after
46 Intermittent Fan-ON Time 1–60 Minutes Fan OFF time has passed.
47 Intermittent Fan-OFF Time 25 Minutes (Default) Defines the duration in which fan low will be OFF. Fan OFF will be activated
0–60 Minutes after Fan ON time has passed. A selection of 0 will result in continuous Fan.
71 Revision — Upon menu selection, the firmware and configuration revision will be displayed.
If enable is selected, it will activate the main output (cool output) for 10 minutes.
80 System Test Main Output (Cool) 0-Disable (Default) Fan High will automatically turn ON. If a different menu is selected the output
1-Enable will be disabled.
If enable is selected, it will activate the secondary output (heat output) for 10
81 System Test Main Output (Heat) 0-Disable (Default) minutes. Fan High will automatically turn ON. If a different menu is selected the
1-Enable output will be disabled.
0-Disable (Default)
82 System Test Fan Output 1-Enable Fan Low Output If enable is selected, it will activate the fan output for 10 minutes. If a different
2-Enable Fan Medium Output menu or a different fan speed is selected the output will be disabled.
3-Enable Fan High Output
IM 1152-10 105
Addendum IM 1019 — MT180
Warranty
All Daikin equipment is sold pursuant to its standard terms and conditions of sale, including Limited
Product Warranty. Consult your local Daikin Applied representative for warranty details. To find your
local Daikin Applied representative, go to www.DaikinApplied.com.
Aftermarket Services
To find your local parts office, visit www.DaikinApplied.com or call 800-37PARTS (800-377-2787).
To find your local service office, visit www.DaikinApplied.com or call 800-432-1342.
This document contains the most current product information as of this printing. For the most up-to-date
product information, please go to www.DaikinApplied.com.
106 IM 1152-10
Addendum IM 1171 — Digitally Adjustable Display Sensor
Contents
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 Front Panel Button Operation .....................7
Sensor buttons & dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . .2 Occupied icon indicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Applications ...................................3 “OVERRIDE” on the display . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Sensor functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 Fan status & speed indicators . . . . . . . . . . . . . . . . . . . . . . . . . .7
Mounting, Maintenance, Terminations .............. 4 System mode “HEAT/COOL/AUTO/OFF/DHUM” indicators . . .7
Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 “ALARM” on the display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 “E-SAVE” word on the display . . . . . . . . . . . . . . . . . . . . . . . . . .7
Terminations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 “SETPOINT” word on the display . . . . . . . . . . . . . . . . . . . . . . . .7
Initial Start-up, Display Descriptions ............... 6 “STATUS” word & dot on the display . . . . . . . . . . . . . . . . . . . . .7
Terminal descriptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6 Front panel button operation . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Initial start-up occupied sequence . . . . . . . . . . . . . . . . . . . . . . .6 Optional Technician Adjustments..................9
Power fail start-up occupied sequence . . . . . . . . . . . . . . . . . . .6 Optional technician adjustments . . . . . . . . . . . . . . . . . . . . . . . .9
Display descriptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6 Diagnostics ................................... 11
Adjusting the setpoint . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6 Specifications .................................12
IM 1152-10 107
Addendum IM 1171 — Digitally Adjustable Display Sensor
Overview
The display sensor is used in conjunction with the MicroTech a digital display for Temperature, Humidity, Occupancy, Fan
III equipped units as described in the Application Section Speed, System Mode, Alarm, Setpoint and Status indication .
below . The same sensor is used for Water Source Heat Pump Controls include six buttons for Setpoint, System Mode, Fan
(WSHP) and for Fan Coil Units (FCU) with just a hardware Speed, Occupied/Unoccupied Request, and Override Reset .
jumper and menu change during configuration. The sensor has (Figure 1) .
1 .125 2 .784
4 .500
Fan Speed
Setpoint-Down
Setpoint-Up
Occupied/Unoccupied Request
Override Reset
System Mode
108 IM 1152-10
Addendum IM 1171 — Digitally Adjustable Display Sensor
ApplicAtiOns
The display sensor for water source heat pump applications is shown in Table 2 .
Table 2: Water source heat pump application guide
Applications
Water-
Cool- Heat- side
Dehumidification Electric Heat
ing ing Econo-
Units Product Models mizer
Smart Hu- Dehu-
3-Way
Dehu- Hot Gas Simpli- midistat midifi- Boil- Supple-
Stages Primary Valve
midifi- Reheat fied Con- cation erless mental
Control
cation trolled Only
Hori- W.CCH,
1 1 No No No No No No No No No
zontal W.CCW
W.VFC,
Vertical 1 1 No Yes No No No Yes1 Yes1 No No
W.VFW
Enfinity
Vertical
W.VHC 1 1 No No No No No No No No No
Stacked
W.MHC,
Water Console 1 1 No No No No No Yes1 Yes1 No No
W.MHW
Source
Heat Hori- Smart-
W.GSH,
Pumps zontal & Source 3 4 Yes Yes Yes Yes Yes Yes Yes Yes Yes
W.GSV
Vertical 1-Stage
Hori- Smart-
W.GTH,
zontal & Source 3 4 Yes Yes Yes Yes Yes Yes Yes Yes Yes
W.GTV
Vertical 2-Stage
Smart-
Vertical Source W.DFW NA NA No No No No No No No No No
Inverter
Note: 1With optional Boilerless controls
IM 1152-10 109
Addendum IM 1171 — Digitally Adjustable Display Sensor
Drywall mounting
1 . Place the base plate against the wall where you want to
mount the sensor .
2 . Mark out the two mounting holes where the unit will be
attached to the wall . Drill a 3/16" hole in the center of each
mounting hole and insert a drywall anchor into the holes .
3 . Drill one 1/2" hole in the middle of the marked wiring
through hole area .
4 . Pull the wire through the wall and out the 1/2" hole, leaving
about six inches free .
5 . Pull the wire through the hole in the base plate .
6 . Secure the base to the drywall anchors using the #6 × 1"
mounting screws provided .
7. Screw the plate firmly to the wall so the foam plate backing
is compressed about 50% .
110 IM 1152-10
Addendum IM 1171 — Digitally Adjustable Display Sensor
terMinAtiOns
All wiring must comply with the National Electric Code (NEC)
CAUTION and local codes . Do NOT run any of this device’s wiring in the
same conduit as other AC power wiring. Tests show that fluctu-
Combination of power wiring (R, 5, DH) and analog (1, 2, 3, 4, ating and inaccurate signal levels are possible when AC power
and 6 to ground) wiring in a common cable may cause signal wiring is present in the same conduit as the signal lines . If you
interference and must be avoided .
are experiencing any of these difficulties, please contact your
Daikin representative .
Figure 4: SmartSource MicroTech III board to digital room temperature sensor wiring
MicroTech III Board I/O Expan-
SmartSource Board
Base Board sion Module
Terminal Block Label TB2-1 TB1-1 TB1-2 TB1-3 TB1-4 TB1-5 TB3-1 TB3-2 TB1-1
Dehumidification
Sensor & Tenant
Shutdown Input
Setpoint Adjust
Room Temp
Unoccupied
Emergency
Unit Status
DC Signal
Common
Override
24VAC
Output
Mode
Input
Input
Description
Terminal Label R 1 2 3 4 5 E U 1
Typical Wiring
Emergency Shut-
Fan & Unit Mode
Dehumidification
Sensor & Tenant
Setpoint Adjust
Room Temp
Unoccupied
DC Signal
Common
Override
24VAC
down
Only
Description
Figure 5: Fan-Coil MicroTech III board to digital room temperature sensor wiring
MicroTech III Board
SmartSource Board
Base Board
Terminal Block Label TB2-2 TB1-5 TB1-4 TB1-3 TB1-2 TB1-1 TB1-6 TB2-1
Sensor & Ten-
ant Override
Room Temp
Unoccupied
Unit Status
Unit Mode
Fan Mode
DC Signal
Common
Setpoint
24VAC
Output
Adjust
Description
Terminal Label 24 VAC BO9 AI7 AI4 AI3 AI1 COM BI2
Typical Wiring
Room Temp
Unoccupied
Unit Status
Fan Speed
DC Signal
Common
Override
24VAC
Output
Description
Sensor Digitally Adjustable Room Temperature Sensor (Part No. 910113679) / 910152148, 910113575
IM 1152-10 111
Addendum IM 1171 — Digitally Adjustable Display Sensor
112 IM 1152-10
Addendum IM 1171 — Digitally Adjustable Display Sensor
IM 1152-10 113
Addendum IM 1171 — Digitally Adjustable Display Sensor
There should always be one indicator “ON” unless the sensor “Fan & 4 Wavy Lines & AUTO” - the fan runs on a
has no power or has a problem . The System Mode Analog Out- call for HEAT/COOL/DHUM . Otherwise the fan is off .
put voltage on Term . 2 will change based on the system mode .
“Fan & 4 Wavy Lines” - the fan runs continuously
Fan speed indication (FCU only) regardless of the system mode setting of HEAT/
COOL/AUTO/DHUM .
“AUTO/HIGH/MEDIUM/LOW” “Fan & No Wavy Lines” - the fan is Off when the
The Fan Speed Indicators on the display show the fan speed system mode is “Off” .
status (AUTO/HIGH/MEDIUM/LOW) and are changed by push-
ing the Fan Mode button . Override/Reset button (timed
“Fan & 4 Wavy Lines & AUTO” - the fan stages up override & alarm reset)
or down automatically depending on the demand for When the “Override/Reset” Button is pressed, the thermistor
HEAT/COOL . sensor is shorted . If held for more than 3 seconds but less than
“Fan & 4 Wavy Lines” - the fan runs continuously at 11 seconds, it puts the controller into a timed Occupied Over-
high speed regardless of the system mode setting of ride (the time is set by the controller) . If the unit is in alarm,
HEAT/COOL/AUTO . then holding the “Override/Reset” Button for more than 11 sec-
“Fan & 3 Wavy Lines” - the fan runs continuously onds will clear all alarms in the controller but only if the cause of
at medium speed regardless of the system mode the alarm has already returned to its non-alarm condition . Some
setting of HEAT/COOL/AUTO . alarms will not reset from the digital room sensor .
“Fan & 2 Wavy Lines” - the fan runs continuously at In this case, power to the unit must be cycled off for 5 seconds
low speed regardless of the system mode setting of to clear the alarm . Continuously resetting alarms from the
HEAT/COOL/AUTO . room sensor could damage the controller . Please call a service
technician when repeated alarm resets are required to keep
“Fan & No Wavy Lines” - Indicates the fan is Off . the unit operational .
There should always be one indicator “On” unless the sensor
has no power or has a problem . The Fan Speed Analog Output Occupied button (occupied/
voltage on Terminal 6 will change based on the fan speed unoccupied request)
selection . Note: Terminal “U” opens HI to source power on power-up
System mode indication (WSHP only) “Occcupied”
When the “Occupancy” Button is pushed, the current “Occu-
“HEAT/COOL/AUTO/OFF/DHUM” pied” or “Unoccupied” status of the sensor will be toggled to
The “HEAT/COOL/AUTO/OFF/DHUM” Mode Indicators on the the opposite condition for 20 seconds . Both the display and “U”
display show the mode status of the sensor and are changed terminal output reflect the new status during the 20 seconds.
by pushing the System Mode button . If a confirmation signal is received from the controller into
• “HEAT” on the display means the unit will only provide the Status Input terminal “1” within 20 seconds, then the new
heating . occupancy condition remains; otherwise the “U” terminal will
return to the original state and the “Occupied” Icon will flash the
• “COOL” on the display means unit will only provide cooling .
desired occupancy state every 8 seconds .
• “AUTO” on the display means the unit can switch
automatically to provide cooling or heating or Up & down setpoint buttons
dehumidification. ( temp or humidity)
• “OFF” on the display means the unit will not provide Press the Setpoint “Up/Down” Buttons once to enter the Set-
cooling, heating, dehumidification or fan operation (“E” point Adjustment Mode . View the display to see whether the
terminal goes Low) . unit is in Temperature or Humidity Setpoint mode . If needed,
• “DHUM” on the display means that only dehumidification press the “System Mode” Button once to toggle to the desired
will operate . Setpoint . The current setpoint value will display for 5 seconds .
There should always be one indicator “On” unless the sensor When the “Up/Down” Buttons are pressed in this mode, the
has no power or has a problem . The System Mode Analog temperature or humidity setpoint will change in one degree or
Output voltage on Terminal 2 will change based on the system percent (%) increments . It will only change within the tempera-
mode selection . ture setpoint range that was ordered (or the setpoint range that
was set via the Program Mode) .
Fan indication (WSHP only) The humidity setpoint is always between 40% to 90% . After 5
“AUTO/ON” seconds of no buttons being pushed, the sensor will go into the
standard display mode .
The Fan Indicators on the left side of the display show the fan
status (AUTO/ON) of the sensor and are changed by pushing
the Fan Mode button .
114 IM 1152-10
Addendum IM 1171 — Digitally Adjustable Display Sensor
IM 1152-10 115
Addendum IM 1171 — Digitally Adjustable Display Sensor
P1 in S2 Mode: No adjustment . Factory set to -5°F P9 Dehumidification Dead band (DB) (Factory set to
(-2 .8°C) . 2%), (WSHP Only) .
P1 in S3 Mode: No adjustment . Factory set to -3°F 2 “UP/DOWN” to set Dead band at 2% (On at setpoint
(-1.6°C) for Enfinity systems. SP, Off at SP-DB) .
P5 Setpoint High Range (Factory set to 95°F or 35°C 3 “UP/DOWN” to set Dead band at 3% (On at setpoint
depending on J50-°F/°C setting) . SP, Off at SP-DB) .
P1 in S1 Mode: Adjustment range 85 to 95°F or 29 to 4 “UP/DOWN” to set Dead band at 4% (On at setpoint
35°C . SP, Off at SP-DB) .
• “UP” to increase the high setpoint range up to 95°F 5 “UP/DOWN” to set Dead band at 5% (On at setpoint
or 35°C . SP, Off at SP-DB) .
• “DOWN” to decrease the high setpoint range down P10 Display Mode (Factory set to #16 for WSHP units,
to 85°F or 29°C . factory set to #4 or #3 for FCU Units) .
P1 in S2 Mode: No adjustment . Factory set to 5°F • “UP/DOWN” to set display mode.
(2 .8°C) . • Choose from numbered list below. Choices 5-16 will
P1 in S3 Mode: No adjustment . Factory set to 3°F not be shown if P12 = nOH .
(1.6°C) for Enfinity systems. 1 = No value on the main display (Blank) .
P6 Fan Lock Mode (Factory set to Unlocked “Unl”) 2 = Temperature Value (TV) .
• “UP/DOWN” to set Fan Lock mode. Choose from 3 = Temperature Setpoint (TSP) (FCU Default 910113575) .
list below: 4 = Temperature Value & Temperature Setpoint (FCU
All Models Unl Enables fan to be controlled by the Default 910152148, 910113679) .
Sensor Fan button 5 = Humidity Value (HV) .
All Models FA Locks fan to the Fan Auto position 6 = Temperature Value & Humidity Value .
(No Sensor Fan button control)
7 = Humidity Value & Temperature Setpoint .
WSHP Models FO Locks fan to the Fan On position
(No Sensor Fan button control) 8 = Temperature Value, Temp Setpoint & Humidity
Value .
FCU Models FH Locks fan to the Fan High speed
position (No Sensor Fan button control) 9 = Humidity Setpoint (HSP) .
FCU Models Fd Locks fan to the Fan Medium speed 10 = Temperature Value & Humidity Setpoint .
position (No Sensor Fan button control) 11 = Temperature Setpoint & Humidity Setpoint .
FCU Models FL Locks fan to the Fan Low speed 12 = Temperature Value & Temp Setpoint & Humidity
position (No Sensor Fan button control) Setpoint .
FCU Models Fo Locks fan to the Fan Off position 13 = Humidity Value & Humidity Setpoint .
(No Sensor Fan button control) 14 = Temperature Value, & Humidity Value & Humidity
P7 System Lock Mode (Factory set to Unlocked “Unl”) Setpoint .
• “UP/DOWN” to set System Lock mode. Choose 15 = Humidity Value & Temperature Setpoint & Humidity
from list below: Setpoint .
Unl Enables System to be controlled by the Sensor 16 = Temperature Value & Temperature Setpoint &
System Mode button . Humidity Value & Humidity Setpoint (WSHP Default) .
UH Locks System to the Heat mode (No Sensor P11 Setpoint Button Lockout (Factory set to “0”: Temp . &
System button control) . Humidity Setpoint Enabled .
UC Locks System to the Cool mode (No Sensor Note: 1. Selections in P11 will impact Menu P10).
System button control) . 2. After changing P11 option, remove PRG jumper on
UA Locks System to the Auto mode (No Sensor Sys- J50 to exit programming mode and refresh options.
tem button control) . In order to make additional programming changes,
UO Locks System to the Off mode (No Sensor Sys- PRG Jumper must be reinstalled to enter
tem button control) . programming mode.
Ud Locks System to the Dhum mode (No Sensor 0 Both Temperature & Humidity Setpoints are enabled
System button control) . (No Setpoint lockout, WSHP Units Only) .
P8 Display Resolution (Factory set to ±0 .5 resolution, “0 .5”) . 1 Humidity Setpoint Only is Enabled (Temperature
setpoint is locked out, WSHP Units Only) .
0.1 “UP/DOWN” to set resolution to ±0 .1, (Rounds up
at .05) . 2 Temperature Setpoint Only is Enabled (Humidity
setpoint is locked out) .
0.5 “UP/DOWN” to set resolution to ±0 .5, (Rounds up
at .08) . 3 Both Temperature & Humidity Setpoints are Disabled
(Full Setpoint lockout) .
1 “UP/DOWN” to set resolution to ±1 .0, (Rounds up at .5) .
116 IM 1152-10
Addendum IM 1171 — Digitally Adjustable Display Sensor
IM 1152-10 117
Addendum IM 1171 — Digitally Adjustable Display Sensor
speciFicAtiOns
IM 1171-7 ©2015 Daikin Applied (04/15) | (800) 432–1342 | www .DaikinApplied .com
118 IM 1152-10
Addendum IM 831 — Thermostat Conversion Kit
IM 1152-10 119
Addendum IM 831 — Thermostat Conversion Kit
Figure 1: Opening the Thermostat Cover Figure 3: Remove Plastic Fan Slide Switch Cap
Without 3-Speed
Switch Opening
120 IM 1152-10
Addendum IM 763 — Automatic Changeover Switch
CAUTION
Sharp edges and coil surfaces are a potential injury
hazards. Avoid contact with them
These line voltage changeover switches are designed to
switch a thermostat from heating to cooling based on a
change in supply water temperature. The switches can be
mounted on 5/8" or 7/8" O.D. copper tube or iron pipe.
Both models are easily mounted to the supply piping with a
simple spring clip included with the thermostat.
Models
The 039398600 model (Fig. 1) has 110 in. leads and is the
standard changeover switch. The 06361801 model (Fig. 2)
has the same operating characteristics and includes 18 in.
conduit and connector.
Both models are snap acting, SPDT switches.
Terminal No. 1 has a black wire and is the common (C)
connected to valve (valve cycle) or to the yellow wire of the
speed switch (fan cycle).
Terminal No. 2 has a red wire and is normally open (N.O.).
Connected to the heating (red) wire of the thermostat.
Terminal No. 3 has a blue wire and is normally closed
(N.C.). Connected to the cooling (blue) wire of the
thermostat.
At approximately 65°F, plus or minus 6°F, terminals 1 and
3 are closed and terminals 1 and 2 are open. At 95°F, plus
or minus 6°F, terminals 1 and 2 are closed and terminals 1
and 3 are open.
IM 763 Discharge Conversion Kit
IM 1152-10 121
Addendum IM 763 — Automatic Changeover Switch
Specifications
Table 26: Electrical Rating Figure 2: Automatic Changeover Switch
(Kit P/N 061361801)
Model Voltage FLA LRA Restive
039398600
24 – 240 15 – 5 90 – 30 25
061361801
Changeover Range: 65°F to 95°F (18°C to 35°C)
Maximum Operating 220°F Fluid Temperature @ 125°F Ambient
Temperature Limits (104°C Fluid Temperature @ 52°C Ambient)
Agency Approval UL Listed, CSA Approved
The specifications above are nominal and conform to generally acceptable
industry standards. Daikin is not responsible for damages resulting from
misapplication or misuse of its products.
122 IM 1152-10
Addendum OM 1111
IM 1152-10 123
Addendum OM 1111
124 IM 1152-10
Addendum OM 1111
IntroductIon
IntroductIon
IM 1152-10 125
Addendum OM 1111
IntroductIon
Input Description
Room or Return Air Temp & Tenant Override
Analog input may be used to measure Room or Return Air
temperature using a 10k NTC thermistor . The same analog
input is used to sense the position of the timed override switch
when a room sensor is applied . This sensor is mandatory in
the Fan Coil/Cabinet Unit Heater units unless the input value is
provided through network communications .
Condensate Overflow
Analog input may be used to detect the presence of water in
condensate pan . While the input is analog (microOhms), the
result of the algorithm is binary (dry or wet) . If the value is
below 2 .5 microOhms, the pan is dry . If the value is above 2 .5
microOhms, the pan is wet . Ultimately the pan is considered
dry for analog inputs above 1 .8 VDC .
126 IM 1152-10
Addendum OM 1111
MIcrotech BaseBoard
MIcrotech BaseBoard
switch is closed, the temperature in the air stream is above • Low Speed:
freezing (alarm inactive) . Must use “nciSoftJumpers” to enable This binary output is used to operate the fan at low
or disable this input . See Table 18 . Input span is 0 .0 to 3 .6 speed . If this output is energized, the fan operates at low
VDC, with a threshold of 1 .5 VDC . speed .
NOTE: Freezestat sensor should be provided from the • Medium Speed:
factory or field-supplied
This binary output is used to operate the fan at medium
Occupancy Sensor speed . If this output is energized, the fan operates at
Binary input may be used to detect the position of an medium speed .
occupancy sensor . This could be a motion detector or a time • High Speed:
clock . Open sensor contact represents occupied, closed
This binary output is used to operate the fan at high
sensor contact represents unoccupied . Network-effective
speed . If this output is energized, the fan operates at
occupancy has priority over position of this input . Input span
high speed .
is 0 .7 (unoccupied) to 5 .0 VDC (occupied), with a threshold of
2 .85 VDC .
Two-Position Damper Output
NOTE: Note: Occupancy sensor is field-supplied
Binary output may be used to open a fresh air ventilation
damper . If the output is de-energized, the damper is closed . If
Control Outputs the output is energized, the damper is open .
The MicroTech baseboard provides the following Binary
Outputs: Room Sensor Status Output
1 . Fan Low Speed Binary output may be used to energize and de-energize an
indicator located on the room sensor . See Room Sensor Status
2 . Fan Medium Speed Output Annunciation Table below .
3 . Fan High Speed
4 . Valve Output #1 Status Annunciation Tables
5 . Valve Output #2
Table 1: Room Sensor Status Output Annunciation Table
6 . Valve Output #3/Electric Heat S1
Condition * Indicator Indicator
7 . Valve Output #4 On Time (Sec) Off Time (Sec)
Alarm Active:
8 . Fresh (Outside) Air Damper – 2-Position only . Specific Alarm Determines 0 .3 0 .3
Number of Flashes (See (1 .3 Between Cycles)
9 . Room Sensor Status Output Alarms section)
Calibration or Network 3 .0 3 .0
Wink Active
Output Description
Service Test Mode 0 .0 Continually
Each binary output is either a relay with normally-open
Unoccupied Mode 0 .5 5 .5
contacts or a triac . A triac is treated like a relay with normally-
open contacts . In other words, energizing the triac is like Standby Mode 5 .5 0 .5
closing a normally-open contact . Occupied, Bypass Mode Continually 0 .0
* Annunciation conditions are listed in order of priority .
IM 1152-10 127
Addendum OM 1111
The I/O Expansion Module is an extension of the main board Input Description
and provides extra functionality to the MicroTech control
system . The MicroTech unit controller in combination with the
Outdoor(Fresh) Air Temperature (OAT)
I/O Expansion Module will be the standard control system for
ThinLine Fan Coils and Cabinet Unit Heaters . See Figure 2 . Analog input may be used to measure outdoor air temperature
using a 10k NTC thermistor .
Adding an I/O Expansion Module (with an interconnect cable)
to the main controller allows:
Dirty Air Filter
• Economizer Control
Binary input may be used to detect Dirty Filter2 condition . Dirty
• Second Fan Motor Control air filter alarm is active when the input contact opens. Must use
• Additional control inputs “nciSoftJumpers” to enable or disable this input . See Table 18
for details . Input span is 0 .0 to 3 .6 VDC, with a threshold of 1 .5
I/O Expansion Board Inputs & Outputs VDC .
2
Currently Dirty Filter input uses timer signal only .
I/O expansion Board accepts the following inputs:
1 . Outdoor Air Temperature (OAT) – analog Humidistat [future option]
2 . Dirty Air Filter – binary 1 Binary input may be used to detect humidistat position . Contact
closes when dehumidification is required. This feature is only
3 . Emergency Shutdown Detection – binary [Future option] allowed for 4-Pipe Heating & Cooling systems with modulating
4 . Humidistat – binary [Future option] valves and 2-Pipe Cooling-only systems . Input span is 0 .0 to
1
Currently Dirty Filter indication uses timer only 3 .6 VDC, with a threshold of 1 .5 VDC .
128 IM 1152-10
Addendum OM 1111
IM 1152-10 129
Addendum OM 1111
Figure 3: MicroTech Unit Controller & I/O Expansion Module Connectors Descriptions
130 IM 1152-10
Addendum OM 1111
IM 1152-10 131
Addendum OM 1111
Figure 4: MicroTech III Fan Coil I/O Expansion Board Connector Layout (not to scale)
132 IM 1152-10
Addendum OM 1111
IM 1152-10 133
Addendum OM 1111
134 IM 1152-10
Addendum OM 1111
The FCU primary operation depends on eight unit states of Possible FCU Machine States include:
operation . When power is applied or controller is reset, the • Off Alarm
unit controller will go through a boot-up sequence, then go to
the “Off” unit state . Refer to Table 8 and Table 9 for the state • Off
of every fan coil component in the Occupied and Unoccupied • Start (Actuator calibration occurs if applicable)
(Standby) Modes . • Fan Only (Fan is enabled, however may not be on)
• Heating
• Economizer
• Cooling (fan coils only)
• Dehumid [future option for Fan coils only: 2-Pipe
in Cooling mode or 4-Pipe Modulating Heat & Cool
Systems]
Off Alarm Off Start Fan Only Heating Economizer Cooling Dehumid
[future option]
Fan Off Off Off Controlled Controlled Controlled Controlled Controlled
Cooling Valve Note1 Closed2 Closed Closed Closed Closed Controlled Open
Heating Valve Note1 Closed2 Closed Closed Controlled Closed Closed Controlled
Electric Heat Off Off Off Off On Off Off Off
Damper Closed Closed Closed Controlled3 Open Open Open Open
IM 1152-10 135
Addendum OM 1111
nciBypassTime 0, 30 to 120 Min 120 m Amount of time controller operates is in the bypass occupancy mode when the user
activates the timed override function .
nciSetpoints:Occ_cool 50 to 95 °F 75 °F Occupied operating mode cooling setpoint .
nciSetpoints:Stby_cool 50 to 95 °F 77 °F Standby operating mode cooling setpoint .
nciSetpoints:Unoc_cool 50 to 95 °F 85 °F Unoccupied operating mode cooling setpoint .
nciSetpoints:Occ_heat 50 to 95 °F 70 °F Occupied operating mode heating setpoint .
nciSetpoints:Stby_heat 50 to 95 °F 66 °F Standby operating mode heating setpoint .
nciSetpoints:Unoc_heat 50 to 95 °F 60 °F Unoccupied operating mode heating setpoint .
Differential between the effective on and off setpoints when operating in the occupied
nciOccDiff 1 to 5 °F 1 °F mode .
nciUnoccDiff 2 to 10 °F 2 °F Differential between the effective on and off setpoints when operating in the unoccupied
mode .
nciEwtFlowTimer 60 to 600 Sec 120 s Length of time flow is allowed after opening a hydronic valve before sampling the EWT.
nciEwtSampleTmr 0, 20 to 120 Min 120 m Length of time between EWT sampling processes .
nciFanMinOffTmr 120 to 1200 Sec 180 s Minimum length of time the fan must remain off after it initially turns off .
nciFanMinOnTmr 120 to 1200 Sec 180 s Minimum length of time the fan must remain running after it initially turns on .
nciFltrChangeHrs 0, 360 to 4320 Hr 1440 hr Length of time the fan operates before a dirty air filter alarm is generated.
nciLocSptEnable Disable, Enable Enable Variable to enable or disable the use of the local setpoint adjustment input from the room
sensor .
nciSptAdjMax 55 to 95 °F 95 °F Long range setpoint adjust input maximum value .
nciSptAdjMin 55 to 95 °F 55 °F Long range setpoint adjust input minimum value .
Hydronic Heating Control
EWT must be warmer than the room temperature at least by this amount for hydronic
nciHeatEnDiff 2 to 10 °F 5 °F
heating to be allowed in two pipe systems .
nciHeatIntStgTmr 120 to 1200 Sec 300 s Inter stage time used between automatic heating capacity fan speed changes .
nciHeatKp 5 to 160 % 25 % Hydronic heating valve PI control loop proportional gain setting .
nciHeatKi 0 to 1200 Sec 20 s Hydronic heating valve PI control loop integral setting .
nciHeatDB 3 to 100 % 3% Hydronic heating valve actuator positioning deadband .
nciHeatVlvStroke 15 to 600 Sec 180 s Hydronic heating valve actuator full travel time .
Hydronic Cooling Control
EWT must be colder than the room temperature at least by this amount for hydronic cool-
nciCoolEnDiff 2 to 10 °F 5 °F ing to be allowed in two pipe systems .
nciCoolIntStgTmr 120 to 1200 Sec 300 s Inter stage time used between automatic cooling capacity fan speed changes .
nciCoolKp 5 to 160 % 40 % Hydronic cooling valve PI control loop proportional gain setting .
nciCoolKi 0 to 1200 Sec 30 s Hydronic cooling valve PI control loop integral setting .
nciCoolDB 3 to 100 % 3% Hydronic cooling valve actuator positioning deadband .
nciCoolVlvStroke 15 to 600 Sec 180 s Hydronic cooling valve actuator full travel time .
Economizer Cooling Control
nciDaSptKp 5 to 160 % 40 % Discharge air temperature setpoint PI control loop proportional gain setting .
nciDaSptKi 0 to 1200 Sec 20 s Discharge air temperature setpoint PI control loop integral setting .
Economizer PI control block setpoint maximum value when the discharge air PI control
nciMaxDaSpt 50 to 80 °F 75 °F loop output is at 0% .
nciMinDaSpt 50 to 80 °F 55 °F Economizer PI control block setpoint minimum value when the discharge air PI control
loop output is at 100% .
Outdoor air temperature must be colder than the room temperature at least by this
nciEconOaEnDiff 1 to 12 °F 2 °F amount for Economizer cooling to be allowed .
nciEconOaEnSpt 40 to 80 °F 50 °F Outdoor air temperature must be above this setpoint to allow Economizer cooling .
nciEconKp 5 to 160 % 90 % Economizer positioning PI control loop proportional gain setting .
nciEconKi 0 to 1200 Sec 10 s Economizer positioning PI control loop integral setting .
nciEconDB 3 to 100 % 3% Economizer actuator positioning deadband setting .
nciEconStroke 15 to 600 Sec 66 s Economizer actuator full travel time .
nciEconLowMin 0 to 100 % 10 % Economizer minimum position when the fan is operating at low speed .
nciEconMedMin 0 to 100 % 10 % Economizer minimum position when the fan is operating at medium speed .
nciEconHighMin 0 to 100 % 10 % Economizer minimum position when the fan is operating at high speed .
Note: Reference the ED15135 protocol information document for more details on configuration properties and other network variables.
136 IM 1152-10
Addendum OM 1111
IM 1152-10 137
Addendum OM 1111
If the temperature is above the Heating On Setpoint and 4-Pipe Modulating Heating & Cooling System:
the heating Interstage timer has expired, the fan will stage • Fan is on at speed determined by capacity and effective
from High to Medium speed . If the temperature is above fan mode/speed .
the Heating On setpoint and the heating Interstage timer
has expired, the fan will stage from Medium to Low speed . If • Heating valve is controlled .
the temperature remains above the Heating Off Setpoint for
longer than the heating stage time and the fan is at its lowest General Operation
fan speed the heating valve will close, electric heat will shut Unit status will change to the “Fan Only” state if all of the
off, and the unit will enter the Fan Only state . When the Fan following conditions exist:
Minimum On and the Fan On After Electric Heat timers have
• Dehumidification isn’t required or is not available, heating
expired, the fan will turn off if fan cycling is enabled .
or cooling capacity becomes required .
• The cooling valve has been driven closed .
Unoccupied Capacity Control • The 4-pipe system heating valve has been driven closed .
• Fan is running at the lowest possible speed based on:
Cooling
selected occupancy and fan mode/speed switch setting .
When the room temperature rises above the Unoccupied
Cooling On Setpoint, the fan will start in High speed and the Dehumid State Notes
cooling valve will fully open in an attempt to maintain room
• For dehumidification availability definition, see
temperature. When the temperature is satisfied (temperature
“Miscellaneous Control Definitions section”.
drops below the Unoccupied Cooling On Setpoint minus the
unoccupied differential) and the cooling Interstage timer has • When leaving “Dehumid” state, the 180 second fixed
expired, the valve will first close and then the fan will shut off. “dehumidification minimum off” timer will be started. This
prevents returning back to the “Dehumid” state too soon .
Heating
Total Electric Heat mode (2-pipe Cooling
When the room temperature falls below the Unoccupied
Heating On Setpoint, the fan will start in High speed and systems only)
the heating valve will fully open (or the electric heat will On an initial call for heating:
be enabled) in an attempt to maintain room temperature .
1 . The fan will start at Low speed in “Fan Only” state
When the temperature is satisfied (temperature rises above
the Unoccupied Heating On Setpoint plus the unoccupied 2 . Unit enters Heating state, electric heat is energized, and
differential) and the heating Interstage timer has expired, the heating Interstage timer is started
valve will first close, electric heat will shut off and then the fan 3 . If Heating Interstage Countdown Timer has expired and
will shut off . room temperature is below the Heating On Setpoint, fan
speed will be changed from Low to Medium, and Heating
Dehumidification Operation [future option] Interstage Countdown Timer is started again .
This fan coil state is allowed for: 2-Pipe in Cooling only or 4 . If Heating Interstage Countdown Timer has expired and
4-Pipe Modulating Heating & Cooling systems; and controller room temperature is below the Heating On Setpoint,
must be in the occupied or bypass mode . Modulating Cooling fan speed will be changed from Medium to High, and
valve is fully open . Electric heat is off . Fresh Air Damper (if Heating Interstage Countdown Timer is started again .
available) is open . Economizer, if available, will be fully open, Once room temperature reaches the Heating On Setpoint
otherwise at minimum position based on fan speed . the fan will be run at Medium and Low speed with Interstage
Countdown Timer started each time the fan speed is changed .
2-Pipe Cooling Only System: When the room setpoint conditions are satisfied, electric heat
• Fan is on at lowest available speed . will be de-energized and the fan will continue to operate at its
“fan only” setting when enabled, for continuous fan operation .
• Heating valve is non-existent .
If fan cycling is enabled, the fan will turn off after 30 seconds
• Dehumidification is only allowed when the effective space once room setpoint conditions are satisfied.
temperature is greater than the effective heating on
setpoint, and becomes disabled when space temperature
drops below the effective heating on setpoint minus a 2°F
fixed differential.
138 IM 1152-10
Addendum OM 1111
IM 1152-10 139
Addendum OM 1111
BACnet equivalent objects . Refer to the ED15135 protocol Translated DA temperature SP that is
Translator: nciMaxDaSpt (AV-11) sent to PI block #4 when the PI output
information document for more details pertaining to the fan coil is at 0% .
network variables . Translated DA temperature SP that is
Translator: nciMinDaSpt (AV-12) sent to PI block #4 when the PI output
is at 100% .
Table 13: PI Control Block #1 – Modulating Hydronic
Heating Valve Control Table 16: PI Control Block #4 – Economizer Position
Inputs / Outputs Interpretation Control
Polarity Type: Reverse Acting (Not Error is defined as: (Effective Heat SP Inputs / Outputs Interpretation
Adjustable) minus Room Temp)
Polarity Type: Direct Acting (Not Error is defined as: (DAT minus
SP: Effective Heating Setpoint The desired heating setpoint input . Adjustable) Discharge Air SP)
PV: nvoSpaceTemp (AV-22) Room temperature is used as the The desired DAT setpoint input . The
process variable input . SP: Discharge Air SP from PI Control
Block #3 Output PI block #3 output is translated into a
KP: nciHeatKp (Loop1:Proportional_ Proportional gain used in the PI discharge air temperature SP value .
Constant) control algorithm . Discharge air temperature is used as
PV: nvoDischAirTemp (AI-4) the process variable input .
KI: nciHeatKi (Loop1:Integral_ Integral time used in the PI control
Constant) algorithm . KP: nciDASptKp (Loop4:Proportional_ Proportional gain used in the PI
Output: nvoHeatVlvOut Heating valve position output Constant) control algorithm .
(Loop1:Present_Value) command . KI: nciDASptKi (Loop4:Integral_ Integral time used in the PI control
Deadband used to determine if the PI Constant) algorithm .
DB: nciHeatDB (AV-29) output is applied to the heating valve Output: nvoEconOut (Loop4:Present_
positioning control . Economizer position output command .
Value)
Deadband used to determine if the PI
Table 14: PI Control Block #2 – Modulating Hydronic DB: nciEconDB (AV-18) output is applied to the Economizer
positioning control .
Cooling Valve Control
Inputs / Outputs Interpretation
Polarity Type: Direct Acting (Not Error is defined as: (Room Temp
Adjustable) minus Effective Cool SP)
SP: Effective Cooling Setpoint The desired cooling setpoint input .
140 IM 1152-10
Addendum OM 1111
IM 1152-10 141
Addendum OM 1111
alarMs
alarMs
142 IM 1152-10
Addendum OM 1111
IM 1152-10 143
Addendum OM 1111
144 IM 1152-10
Addendum OM 1111
appendIx a
appendIx a
IM 1152-10 145
Addendum OM 1111
appendIx B
appendIx B
WARNING
When an optional wall-mounted room temperature
sensor is connected to the unit controller, the Return
Air Temperature (RAT) sensor must not be installed .
A wall-mounted room temperature sensor and the
return air temperature sensor must not be connected
simultaneously or the unit will not operate properly .
146 IM 1152-10
Addendum OM 1111
appendIx c
appendIx c
The unit controller is programmed and tested with all the logic
required to monitor and control the unit . An optional wall sensor
may be used with the communication module to provide limited
local control of the fan coils and cabinet unit heater unit . Room
sensor options include one with a setpoint adjustment, unit
mode, fan speed, and tenant override . See actual sensor to
make sure these options are present .
The unit controller monitors water and air temperatures and
passes information to the communication module . The module
communicates with the BAS, to provide network control of the
fan coils and cabinet unit heater unit .
IM 1152-10 147
Addendum OM 1111
appendIx d
appendIx d
148 IM 1152-10
Addendum OM 1111
appendIx d
Figure 10: 1 PSC Motor, No Electric Heat, 2 Position Actuators, 2 Position Valves – Page 2
IM 1152-10 149
Addendum OM 1111
appendIx d
Figure 11: 1 PSC Motor, No Electric Heat, Valve1 FLT, No Return Air Temperature – Page 1
150 IM 1152-10
Addendum OM 1111
appendIx d
Figure 12: 1 PSC Motor, No Electric Heat, Valve1 FLT, No Return Air Temperature – Page 2
IM 1152-10 151
Addendum OM 1111
appendIx d
152 IM 1152-10
Addendum OM 1111
appendIx d
IM 1152-10 153
Addendum OM 1111
Now that you have made an investment in modern, efficient Daikin equipment, its care should be a high
priority. For training information on all Daikin HVAC products, please visit us at www.DaikinApplied.com
and click on Training, or call 540-248-9646 and ask for the Training Department.
Warranty
All Daikin equipment is sold pursuant to its standard terms and conditions of sale, including Limited
Product Warranty. Consult your local Daikin Applied representative for warranty details. To find your
local Daikin Applied representative, go to www.DaikinApplied.com.
Aftermarket Services
To find your local parts office, visit www.DaikinApplied.com or call 800-37PARTS (800-377-2787).
To find your local service office, visit www.DaikinApplied.com or call 800-432-1342.
This document contains the most current product information as of this printing. For the most up-to-date
product information, please go to www.DaikinApplied.com.
OM 1111-2 (10/15) ©2015 Daikin Applied | (800) 432–1342 | www .DaikinApplied .com
154 IM 1152-10
Addendum—ED 19059
Overview
The constant CFM ECM when wired to with the ECM speed
adjustment board (EVO Board) allows the user the manually
adjust the airflow for each of the three fan speeds by turning
a dial. Each speed may be adjusted across the full RPM
range of the motor and once set the new flow rate will then be
maintained by the motor despite changes to the system static
pressure. The CFM for each speed setting may be determined
by measuring the airflow in the system or by measuring the DC
voltage between the adjusted terminal and the reference point
on the board. If desired, the motor may be used without speed
adjustment by replacing the wire harness from the EVO board
with the standard wire harness. In this case the motor will run
at the factory programmed flow rates.
IM 1152-10 155
Addendum—ED 19059
Overview
Overview
Connecting the Unit to Field Power Connecting the Unit to a 24V Thermostat
Line voltage power wires L1 and Com are connected to S2 or Controller
as shown. A factory provided step down transformer provides The factory provided 24VAC transformer should be used to
24VAC power for the ECM control and the EVO board and the provide power for the field mounted t-stat by connecting the
factory provided 16 pin wire harness connects the EVO board 24V input to TB2 terminal B and the common to TB2 terminal
to the ECM (Figure 7 and Figure 8). E. The three t-stat fan speed outputs are connected to the EVO
board spade terminals labeled Flo1, Flo2 and Flo3 (Figure 1).
When a t-stat fan speed output is energized, the fan will run
at the speed set at the corresponding flow dial until the speed
output is de-energized.
156 IM 1152-10
Addendum—ED 19059
Wiring
Wiring
Figure 2: Typical EVO Board Wiring for a Single Motor Large Cap Unit
IM 1152-10 157
Addendum—ED 19059
Wiring
Figure 3: Single Motor EVO Board Bypass Wiring Detail for Large Cap Unit
Figure 4: Two Motor EVO Board Bypass Wiring Detail for Large Cap Unit
158 IM 1152-10
Addendum—ED 19059
Wiring
Figure 5: Single Motor EVO Board Bypass Wiring Detail for ThinLine Unit
Figure 6: Two Motor EVO Board Bypass Wiring Detail for ThinLine Unit
IM 1152-10 159
Addendum—ED 19059
Wiring
160 IM 1152-10
Addendum—ED 19059
Table 10: Size 6 Voltage Table–ThinLine * These values are all approximates and based on testing with
the 3 row coil.
Speed Voltage* CFM*
LOW 1.40 VDC 340 @ 0.1ʺ WC ** MAX VDC is referring to the dial being turned to its
MED 2.1 VDC 522 @ 0.1ʺ WC MAXIMUM voltage output.
HIGH 2.75 VDC 711 @ 0.1ʺ WC
IM 1152-10 161
Addendum—ED 19059
Warranty
All Daikin equipment is sold pursuant to its standard terms and conditions of sale, including Limited
Product Warranty. Consult your local Daikin Applied Representative for warranty details. To find your
local Daikin Applied Representative, go to www.DaikinApplied.com.
Aftermarket Services
To find your local parts office, visit www.DaikinApplied.com or call 800-37PARTS (800-377-2787).
To find your local service office, visit www.DaikinApplied.com or call 800-432-1342.
This document contains the most current product information as of this printing. For the most up-to-date
product information, please go to www.DaikinApplied.com.
162 IM 1152-10
Daikin Applied Training and Development
Now that you have made an investment in modern, efficient Daikin Applied equipment, its care should
be a high priority. For training information on all Daikin Applied HVAC products, please visit us at
www.DaikinApplied.com and click on Training, or call 540-248-9646 and ask for the Training Department.
Warranty
All Daikin Applied equipment is sold pursuant to its standard terms and conditions of sale, including
Limited Product Warranty. Consult your local Daikin Applied Representative for warranty details. Refer
to Form 933-430285Y. To find your local Daikin Applied Representative, go to www.DaikinApplied.com.
Aftermarket Services
To find your local parts office, visit www.DaikinApplied.com or call 800-37PARTS (800-377-2787).
To find your local service office, visit www.DaikinApplied.com or call 800-432-1342.
This document contains the most current product information as of this printing. For the most up-to-date
product information, please go to www.DaikinApplied.com.