Transformer Desigm
Transformer Desigm
Introduction
Transformer is static device which converts the voltage or current from one level to
another level keeping the power and frequency constant. The transformer are required to
transport the power from the generating station to load center which is far away from the
generating station. Its based on the faraday’s law of electromagnetic induction which states
whenever the coil experiences the changing flux and emf is induced .
𝒅∅
𝒆 = −𝑵
𝒅𝒕
Where N is number of turns in the coil . The negative sign implies that the nature of the
induced emf is such that it opposes the cause which produced it.
When a sinusoidal voltage is applied to the primary winding of a practical transformer on an iron
core with the secondary winding open, a small current In called the exciting current flows. The
major component of this current is called the magnetizing current , which corresponds to the
current through the magnetizing susceptance Bm . The magnetizing current produces the flux in
the core. The much smaller component of Ih+e which accounts for losses in the iron core, leads
the magnetizing current by 90° . The core losses occur due , first, to the fact that the cyclic
changes of the direction of the flux in the iron require energy which is dissipated as heat and is
called hysteresis loss . The second loss is due to the fact that circulating currents are induced in
the iron due to the changing flux, and these current produce an I2R loss in the iron called eddy-
current loss . Hysteresis loss is reduced by the use of certain high grades of alloy steel for the
core and Eddy current loss is reduced building the core with laminated sheet When the
secondary is open then small amount of primary current will flow to establish the flux in core .
The Equivalent circuit consist only magnetising inductance and resistance for the core loss
component .The no load condition and its phasor diagram is shown in below figure
In a well -designed transformer the maximum flux density in the core occurs at the knee of the
B-H or saturation curve of the transformer. So, flux density is not linear with respect to field
intensity . The magnetizing current cannot be sinusoidal if it is to produce sinusoidally varying
flux required for inducing sinusoidal voltages e1 and e2 when the applied voltage is sinusoidal .
The exciting current Inwill have a third harmonic content as high as 40% and lesser amounts of
higher harmonics..
Where equivalent resistance and reactance referred the primary side are
𝑹𝟎𝟏 = 𝑹𝒑 + 𝒂𝟐 𝑹𝒔 𝒂𝒏𝒅 𝑿𝟎𝟏 = 𝑿𝒑 + 𝒂𝟐 𝑿𝒔
Emf Equation
Its based on the faraday’s law of electromagnetic induction which states whenever the coil
experiences the changing flux and emf is induced .
𝒅∅
𝒆 = −𝑵
𝒅𝒕
Where N is number of turns in the coil . The negative sign implies that the nature of the
induced emf is such that it opposes the cause which produced it.
Let the
=m Cost
𝒅𝐦 𝐂𝐨𝐬𝐭
𝒆 = −𝑵 = 𝐍𝐦𝐒𝐢𝐧𝐭 = 𝟐𝛑𝐟𝐍𝐦𝐒𝐢𝐧𝐭
𝒅𝒕
Hence the rms value of the induced emf
𝟐𝛑𝐟𝐍𝐦𝐒𝐢𝐧𝐭
𝒆= = 𝟒. 𝟒𝟒𝒇𝑵
√𝟐
So the induced emf lags the main flux by 900
Phasor Diagram
The complete phasor diagram of the transformer for the lagging load representing all
components will be as shown below
2
I1
E2
I2/a
-E1
V2
I2
V1
Where
𝑬𝟐 = 𝑽𝟐 + 𝑰𝟐 (𝑹𝟐 + 𝒋𝑿𝟐 )
𝑰𝟐
𝑰𝟏 = + 𝑰𝒏
𝒂
𝑽𝟏 = 𝑬𝟏 + 𝑰𝟏 (𝑹𝟏 + 𝒋𝑿𝟏 )
Types of Transformer
According two the construction the transformer are two types one is core type whereas other
is shell type . In the core type the core is inside and the winding are outside . But in shell type
the windings are in side and the core is out side as shown in below figure
Output Equation
It gives the relationship between electrical rating and physical dimensions of the machines.
Let
V1 = Primary voltage say LV
V2 = Secondary voltage say HV
I1 = Primary current
I2 = Secondary current
N1= Primary no of turns
N2= Secondary no of turns
I
a1 = Sectional area of LV conductors (m2) = 1
I
a1 = Sectional area of HV conductors (m2) = 2
2
= Permissible current density (A/m )
Q = Rating in KVA
We place first half of LV on one limb and rest half of LV on other limb to reduce leakage flux.
So arrangement is LV insulation then half LV turns then HV insulation and then half HV turns.
H L Window
L H H L L H
V V V V V V V V
2I1 N1
( For IdealTransformer I1N1 I 2 N 2 )
Aw
So
K w Aw
N1 I 1 ( 2)
2
Put equation value of N1I1 form equation (2) to equation (1)
K w Aw
Q 4.44 f A i Bm 10 3 KVA
2
Q 2.22 f A i Bm K w Aw 10 3 KVA (3) Window
a1 N1 a2 N 2 LV LV
Kw
Aw
HV HV
( I / ) N1 ( I 2 / ) N 2
1 ( a1 I /1 & a2 I / 2 ) LV LV
Aw
Window
H L L H H L L H H L L H
V V V V V V V V V V V V
a1 N1 a2 N 2
Kw
Aw
( I / ) N1 ( I 2 / ) N 2
1 ( a1 I /1 & a2 I / 2 )
Aw
I N I N
1 1 2 2
Aw
2I N
1 1 ( For Ideal Transforme r I1 N1 I 2 N 2 )
Aw
So 3-phase shell type transformer
K w Aw with sandwich windings
N1 I 1 (9 )
2
Put equation value of N1I1 form equation (9) to equation (6)
K w Aw
Q 3 4.44 f A i Bm 10 3 KVA
2
Q 6.66 f A i Bm K w Aw 10 3 KVA (10)
We know
V1 4.44 fm N1 (1)
V1
So EMF / Turn Et 4.44 fm (2)
N1
and
Or Et K t Q Volts / Turn
3
Where Kt 4.44 f r 10 is a constant and value depend upon service type , construction
and cooling system For same cooling / current density / same type – three phase distribution
transformer will be more heated than power transformer ( distribution transformer are
continuously loaded) so the value of K will be more in case of power transformer Similarly for
same cooling system and current density / for Shell type cooling system is more effective
compared to core type so larger K can be chosen in shell type compared to core type
Core Cross-section
Small core type of transformer gas rectangular core limbs with rectangular coils as shown
below figure however for the larger power transformer economic use of the core material
required so the circular core limb is needed since the circular core has less periphery
than rectangular core which reduced the length of copper . The circular core needs
large no of different size of laminated sheet . Hence the two step or multistep core are
generally used .
We know
Et K t Q (1)
Et 4.44 f m
Or Et 4.44 f Ai Bm ( 2)
Et
So Ai (3)
4.44 f Bm
a
Two Step Core:
Two Step core is also called cruciform Core . b
Let d is the diameter of the circumscribing circle then
Here a = d cos and b - dsin
Gross Area of the iron Ag=2ab-b2 = 2d2SinCos-d2sin2
Hence for Maximum Gross area =0 Ө
0 b
Which gives = 31.45
Hence a=dCos31.450 =0.81d and b= dSin31.450 =0.53d
Maximum Gross iron area =2ab-b2=0.618d2
Let stacking factor K=0.9
Then Net iron Area = 0.9Ag= 0.9x0.618d2=0.56d2 2-Step
Ratio
.
= = 0.71 𝑎𝑛𝑑 =
.
= 0.79
d d/√2
Window Dimension
The leakage reactance is affected by the distance between adjacent limbs . if this distance
is relatively small width of the winding is limited this must be counter balance by
increasing the height of the window or winding ,thus windings are long and thin . This
arrangement give low value of the leakage reactance. If the height is limited then width of
the window must increase to accommodate windings this results short and wide coils
resulting high value of leakage . Hence the height and width of the window can be
adjusted for the suitable arrangement of windings as well as low value of the leakage
The area of the window depends upon the total copper area and window space factor
Let D is the Distance Between the Adjcent Limbs Then D must includes width of iron
,winding, insulation , clearance and ducts for cooling D= width of iron + width of copper
+ width of insulation + width of ducts + width of clearance .let m is the width occupied by
insulation ,ducts and clearance
Design of yoke
The area of the yoke is taken as 15-20% larger than that of core for the transformer using
hot rolled silicon steel . This reduces the value of the dlux density in yoke which reduces
iron losses and magnetizing current . For the transformer made of cold rolled grain oriented
sheet the yoke area is equal to core area
The section of the yoke can be either rectangular or stepped . if the yoke is rectangular
the depth of the yoke is equal to depth of the core . This depth of core is equal to width
of largest stamping size when square and stepped core are used
For rectangular yoke : Area of Yoke = Depth of Yoke x Height of yoke Dyx Hy where
Dy is equal to width of largest stamping
Window Dimension
Design of insulation
i) Electrical insulation: depends on the operating voltage
ii) Eddy current loss in the conductors and tank walls
iii) Mechanical considerations: high mechanical forces during fault
iv) Thermal considerations: depends on cooling
High conductivity
Low-temperature coefficient
High thermal conductivity
Light weigh
Types of Windings
individual cylindrical layers are placed axially one over the other.
used in transformer with high current and low voltage rating
Rectangular conductor are used for the voltage upto 500 V and 10 – 600A
Circular conductor are used for a current rating of 80 A
Uses of Cylindrical Windings
Cylindrical windings are low voltage windings used up to 6.6 kV for kVA up to 600-750, and
current rating between 10 to 600 A.
These windings are used in high voltage windings of small transformers. The conductors are
paper-covered round wires or strips. The windings are divided into several coils to reduce
voltage between adjacent layers. These coils are axially separated by 0.5 to 1 mm, with the
voltage between adjacent coils kept within 800 to 1000 V.
Transposition of windings
The no load current should not exceed 5% of the full the load current.
Q 103
Primary current I1
3V1
Q 103 N
Secondary current I2 OR 1 I1
3V2 N2
I1
Sectional area of primary winding a1
I2
Sectional area of secondary winging a2
Where is current the density.
Now we can use round conductors or strip conductors for this see the IS codes and ICC (Indian
Cable Company) table.
3I ( R R )
2
1 1
'
2
3 I12 R p
R01 R p R1 R2'
Where
Total resis tan ce referred to primary side
Note: On No load, there is magnetic field around connecting leads etc which causes additional
stray losses in the transformer tanks and other metallic parts. These losses may be taken as 7% to
10% of total cu losses.
Determination of EFFICIENCY:
Output Power
Efficiency
Input Power
Output Power
Output Power Losses
Output Power
100 %
Output Power Iron Loss Cu loss
MMF at distance x
N1 I1
Mx x
b1
Permeance of this elementary cylinder
A
o
L
Lmt dx a b2
b1
o (Lc =Length of winding)
Lc dx
Lc
1 L 1 x
S & Permeance
o A S
Leakage flux lines associated with elementary cylinder
dx M x Permeance
NI L dx
1 1 x o mt
b1 Lc
Flux linkage due to this leakage flux
d x No of truns with which it is associated d x N1I1=N2I2
N1 x N1I1 L dx
x o mt
b1 b1 Lc
2
L x
o N mt I1 dx
1
2 x
Lc b1 MMF Distribution
Flux linkages (or associated) with primary winding
b 2
L 1
x 2 L b
o N mt I 1 dx o N1 mt I1 1
'
1 1
2
Lc 0 b1 Lc 3
Flux linkages (or associated) with the space ‘a’ between primary and secondary windings
Lmt
o o N12 I1a
Lc
We consider half of this flux linkage with primary and rest half with the secondary winding. So
total flux linkages with primary winding
1 1' o
2
L b a
1 o N12 mt I1 1
Lc 3 2
Similarly total flux linkages with secondary winding
2 2' o
2
L b a
2 o N 22 mt I 2 2
Lc 3 2
Primary & Secondary leakage inductance
L b a
L1 1 o N 12 mt 1
I1 Lc 3 2
2 Lmt b2 a
L2 o N 22
I2 Lc 3 2
Primary & Secondary leakage reactance
L b a
X 1 2fL1 2fo N12 mt 1
Lc 3 2
Lmt b2 a
X 2 2fL2 2fo N 22
Lc 3 2
Total Leakage reactance referred to primary side
L b b
X 01 X P X 1 X 2' 2f o N 12 mt 1 2 a
Lc 3
Total Leakage reactance referred to secondary side
L b b2
X 02 X S X 1' X 2 2f o N 22 mt 1 a
Lc 3
It must be 5% to 8% or maximum 10%
Note:-How to control XP?
If increasing the window height (L), Lc will increase and following will
decrease b1, b2& Lmt and so we can reduce the value of XP.
I 2 Ro 2Cos 2 I 2 X o 2 Sin2
V .R. 100
E2
R Cos2 X Sin2
o2 100 o 2 100
E2 / I 2 E2 / I 2
% Ro 2Cos2 % X o 2 Sin2
hy
L H
Ww
(D-d)
D D
a
lt
De
b a b
Wt
h
W
Ht
H
h
Optimum design:
Optimum transformer design is a complex process that involves minimizing one or more of the
following quantities: Total weight, Total volume, Total cost, and Total loss. The ratio r=фm/AT
is a controlling factor for these quantities. A higher value of results in higher flux, which
requires a larger cross section. This increases the weight, volume, and cost of iron, and also
increases iron loss. A lower value of AT decreases the weight, volume, and cost of copper, and
also decreases copper losses
Design for maximum efficiency ( that occur for load current in which iron loss equal to
core losses )
Design for minimum cost ( that occur when cost of iron is equal to cost of copper
For minimum losses current density chosen for both primary and secondary should
be equal
Cooling Transformer
No transformer is truly an 'ideal transformer' and hence each will incur some losses, most of
which get converted into heat. If this heat is not dissipated properly, the excess temperature in
transformer may cause serious problems like insulation failure.
The temperature rise is given by the relationship 𝜃 = . So the temperature rise can be
decreased and brought within limits by two means.
Increasing the S heat dissipating area
Decreasing the cooling coefficient
Since the temperature rise is inversely proportional to surface are of the tank . Thus if the
area of the tank is increased the temperature can be controlled within limit. The surface
areaof the tanks can be increased by adopting fins , Corrugation as well as tubes .In high
power transformer forced cooling methods are used .
It is obvious that transformer needs a cooling system. Transformers can be divided in two types
as
dry type transformers and
oil immersed transformers.
Air cooling is not sufficient and effective for the medium and large size transformer. Oil
has main advantage of high thermal conductivity and high coefficient of volume expansion
with temperature . Hence all transformer are immersed in oil and heat generated in windings
and core are dissipated to the oil by conduction and oil transfer heat by convection .
During convection the heat is transferred to tank wall by convection .During this processes
heated oil gets cool and fall back to the bottom .There fore natural thermal head is
created which further transfer heat from heated part to wall
d= 5 Cm
Let
Wi = Weight of Iron in core and yoke (core volume* density + yoke volume* density) Kg
Wc= Weight of copper in winding (volume* density) Kg
(density of cu = 8900 Kg/m3)
Weight of Oil
= Volume of oil * 880 Kg
Add 20% of (Wi+Wc) for fittings, tank etc.
Total weight is equal to weight of above all parts.
Design for maximum efficiency ( that occur for load current in which iron loss equal to
core losses )
Design for minimum cost ( that occur when cost of iron is equal to cost of copper)
Area of the core affected by weight of copper and iron
1. A 25 KVA ,11000/433 V , 50 hz three phase delta star core type transformer has full load
copper loss 720Watt and over all core dimensions are
For limb For Yoke
Cross-section area A = 0.01035m2 Cross-section area A= 0.01216m2
Height H = 0.3m Length = 0.624m
Flux density Bm =1web/m2 Flux density Bm =0.833Web/m2
The magnetizing and specific core loss characteristics are given below table
Bm(Web/m2) 0.8 0.9 1 1.1
Iron loss (W/kg) 0.85 1.05 1.2 1.4
Mmf(A/m) 75 100 120 125
Determine no load current ,Efficiency at full load and identify whether it is distribution or
power transformer
2. Why Large Transformers requires elaborate cooling system? Show that by increasing linear
dimension of transformer n times , the KVA rating is increased by n 4 times and losses to be
dissipated per unit surface area is increased by n times
3. The tank of 575KVA On type transformer has dimensions length , width and height are 105
cm , 65 cm and 150 cm respectively . The full load losses is 6.5 KW .Design suitable
arrangement of 5 cm diameter tubes spaced 7.5 cm and average length of each tubes are
127.5 cm and temperature rise of the wall is limited at 35 0C .
Assume Watt/m2-0C due to convection =6.5, Watt/m2-0C due to radiation =6.5 and
improvement in convection due to provision of tubes =35%
4. Show the path of leakage flux in three phase core type transformer having concentric
cylindrical winding of equal length. What simplifying assumption are made in the derivation
of the formula for leakage reactance calculation .
5. A 750 ,6600V , 50hz three phase delta star core type transformer has following data : width
of l.v. winding 30mm , width of the high voltage winding 25mm , width of the duct between
high voltage and low voltage winding 15mm , height of winding 0.4m , length of the mean
turn 1.5m , h,v winding turns 217 and l.v winding turns is 15 . Estimate leakage reactance of
the transformer referred to h.v side .
6. A transformer has 1500W and 1100W hysterysis and eddy current losses at normal voltage
and frequency . Calculate the both losses when voltage and frequency are raised by 15%
7. Calculate the approximate overall dimension for a 200KVA ,6600/440V ,50 hz 3- phase core
type transformer . The following data may be assumed :Emf per turn =10V , maximum flux
density Bm=1.3Web/m2 , current density = 2.5amp/mm2 , window space factor =0.3 ,
overall height = overall width , Stacking factor =0.9 .
Use three step cores.
For three step core
Width of the largest stamping =0.9d
Net iron area =0.9d2 where d is diameter of the circumscribing circle
8. Full Load at 0.8 lagging P.F. regulation of power transformer was estimated from its
designed data to be 2.5% against the desire value 2%. What adjustment are necessary in
design to obtain require regulation. Justify your procedure
9. A 15 MVA transformer has iron loss of 80KW and copper loss of 120 KW at full load . The
tank dimensions are 3.5X3X1.4 meter .The transformer oil is cooled by three liter of oil per
second passed through cooling coil .Estimate average temperature rise of tank if the
difference of temperature of water at inlet and outlet is 150C . The specific heat dissipation
from the tank wall is 10W/m2-0C