PAXICR Product Manual - 2
PAXICR Product Manual - 2
PAXICR-H
Drawing No. LP0896
Released 07/2024
C UL
R US LISTED
E179259
PROCESS CONTROL EQUIPMENT
GENERAL DESCRIPTION computer to directly control the outputs of the meter. With an RS232 or RS485
The PAX Digital Input Panel Meters offer many features and performance card installed, it is possible to configure the meter using Red Lion’s Crimson
capabilities to suit a wide range of industrial applications. Available in three software. The configuration data can be saved to a file for later recall.
different models, PAXC Counter/Dual Counter, PAXR Rate Meter and the PAXI A linear DC output signal is available as an option card for the PAXI only. The
which offers both counting and rate in the same package. Refer to pages 4 - 5 for card provides either 20 mA or 10 V signals. The output can be scaled independent
the details on the specific models. The PAXC and PAXR offer only the Setpoint of the input range and can track any of the counter or rate displays.
Option, while the PAXI is the fully featured version offering all the capabilities Once the meters have been initially configured, the parameter list may be
as outlined in this bulletin as well as a slave display feature. The option cards locked out from further modification in its entirety or only the setpoint values
allow the opportunity to configure the meter for present applications, while can be made accessible.
providing easy upgrades for future needs. The meters have been specifically designed for harsh industrial environments.
The meters employ a bright 0.56" LED display. The meters are available with With NEMA 4X/IP65 sealed bezel and extensive testing of noise effects to CE
a red sunlight readable LED display. The intensity of the display can be adjusted requirements, the meter provides a tough yet reliable application solution.
from dark room applications up to sunlight readable, making it ideal for viewing
in bright light applications. SAFETY SUMMARY
The meters accept digital inputs from a variety of sources including switch All safety related regulations, local codes as well as instructions that appear
contacts, outputs from CMOS or TTL circuits, magnetic pickups and all in this document or on equipment must be observed to ensure personal safety
standard RLC sensors. The meter can accept directional, uni-directional or and to prevent damage to either the device or equipment connected to it.
Quadrature signals simultaneously. The maximum input signal varies up to 34 Do not use these products to replace proper safety interlocking. No software-
KHz depending on the count mode and function configurations programmed. based device (or any other solid-state device) should ever be designed to be
Each input signal can be independently scaled to various process values. responsible for the maintenance of personnel safety or consequential equipment
The Rate Meters provide a MAX and MIN reading memory with programmable not equipped with safeguards. Red Lion disclaims any responsibility for
capture time. The capture time is used to prevent detection of false max or min damages, either direct or consequential, that result from the use of this
readings which may occur during start-up or unusual process events. equipment in a manner not consistent with these specifications.
Optional digital output cards provide the meter with up to four setpoint
outputs. The cards are available as dual relay, quad relay, quad sinking
transistor, quad sourcing transistor/SSR drive, or dual triac/dual SSR drive
outputs. The setpoint alarms can be configured to suit a variety of control and
alarm requirements. CAUTION: Risk of Danger. CAUTION: Risk of electric shock.
Communication and Bus Capabilities are also available as option cards for Read complete instructions prior to
the PAXI only. These include RS232, RS485, Modbus, DeviceNet, and installation and operation of the unit.
DIMENSIONS In inches [mm] Note: Recommended minimum clearance (behind the panel) for mounting clip installation is
2.1" [53.4] H x 5" [127] W.
12 16 20
A
13 17 21
B 14 18 22
C 1.95 1.75 15 19 23 1.75
SP1 SP2 SP3 SP4 [49.5] [44.5] 1 2 3 4 5 6 7 8 9 10 11
24
25 [44.5]
DSP PAR F1 F2 RST
.10 4.10
3.80 3.60 [91.4]
[2.5] [104.1]
[96.5]
1
Table Of Contents
Ordering Information. . . . . . . . . . . . . . . . . . . . 2 3.0 Installing Option Cards. . . . . . . . . . . . . . . 8
General Meter Specifications . . . . . . . . . . . . . 3 4.0 Wiring the Meter. . . . . . . . . . . . . . . . . . . . 9
Model PAXC - 1/8 DIN Counter . . . . . . . . . . . 4 5.0 Reviewing the Front Buttons and Display.11
Model PAXR - 1/8 DIN Rate Meter. . . . . . . . . 4 6.0 Programming the Meter . . . . . . . . . . . . . 11
Model PAXI - 1/8 DIN Counter/Rate Meter. . . 5 6.9 Factory Service Operations (). . . . . 28
Option Cards. . . . . . . . . . . . . . . . . . . . . . . . . . 6 Troubleshooting. . . . . . . . . . . . . . . . . . . . . . . 29
Crimson Programming Software. . . . . . . . . . . 7 Parameter Value Chart. . . . . . . . . . . . . . . . . 30
1.0 Installing the Meter. . . . . . . . . . . . . . . . . . 7 Programming Quick Overview. . . . . . . . . . . . 32
2.0 Setting the Jumper and DIP Switches . . . 8
Ordering Information
Meter Part Numbers
PAX 0 0
C - Counter/Dual Counter
R - Rate Meter
I - Counter/Dual Counter/
Rate Meter/Slave Display
2 - 85 to 250 VAC
3 - 11 to 36 VDC, 24 VAC
2
General Meter Specifications
1. DISPLAY: 6 digit, 0.56" (14.2 mm) red sunlight readable or LED 8. CERTIFICATIONS AND COMPLIANCES:
2. POWER: CE Approved
AC Versions: EN 61326-1 Immunity to Industrial Locations
AC Power: 85 to 250 VAC, 50/60 Hz, 18 VA Emission CISPR 11 Class A
Isolation: 2300 Vrms for 1 min. to all inputs and outputs. (300 V working) Safety requirements for electrical equipment for measurement control, and
DC Versions: laboratory use:
DC Power: 11 to 36 VDC, 14 W EN 61010-1: General Requirements
(derate operating temperature to 40° C if operating <15 VDC and three EN 61010-2-030: Particular Requirements for Testing and Measuring
option cards are installed) Circuits
AC Power: 24 VAC, ± 10%, 50/60 Hz, 15 VA RoHS Compliant
Isolation: 500 Vrms for 1 min. to all inputs and outputs (50 V working). UL Listed: File #E179259
3. SENSOR POWER: 12 VDC, ±10%, 100 mA max. Short circuit protected Type 4X Enclosure rating (Face only)
4. KEYPAD: 3 programmable function keys, 5 keys total IP65 Enclosure rating (Face only)
5. USER INPUTS: Three programmable user inputs IP20 Enclosure rating (Rear of unit)
Max. Continuous Input: 30 VDC Refer to EMC Installation Guidelines section of the bulletin for additional
Isolation To Sensor Input Commons: Not isolated information.
Logic State: Jumper selectable for sink/source logic 9. ENVIRONMENTAL CONDITIONS:
Operating Temperature Range: 0 to 50°C (0 to 45°C with all three cards
installed)
SINKING INPUTS SOURCING INPUTS Vibration to IEC 68-2-6: Operational 5 to 150 Hz, 2 g.
INPUT STATE
5.1 KΩ pull-up to +12 V 5.1 KΩ pull-down
Shock to IEC 68-2-27: Operational 25 g (10 g relay).
Active VIN < 0.9 VDC VIN > 2.4 VDC Storage Temperature Range: -40 to 60°C
Inactive VIN > 2.4 VDC VIN < 0.9 VDC Operating and Storage Humidity: 0 to 85% max. RH non-condensing
Altitude: Up to 2000 meters
Response Time: 6 msec. typical; function dependent. Certain resets, stores 10. CONNECTIONS: High compression cage-clamp terminal block
and inhibits respond within 25 µsec if an edge occurs with the associated Wire Strip Length: 0.3" (7.5 mm)
counter or within 6 msec if no count edge occurs with the associated Wire Gage: 30-14 AWG copper wire
counter. These functions include , , , , Torque: 4.5 inch-lbs (0.51 N-m) max.
, , and . Once activated, all functions are latched for 11. CONSTRUCTION: This unit is rated for NEMA 4X/IP65 outdoor use.
IP20 Touch safe. Installation Category II, Pollution Degree 2. One piece
50 msec min. to 100 msec max. After that period, another edge/level may
bezel/case. Flame resistant. Synthetic rubber keypad. Panel gasket and
be recognized.
mounting clip included.
6. OUTPUT:
12. WEIGHT: 10.1 oz. (286 g)
Response Time: 25 µsec.; add 6 msec (typical) if a relay card is installed
Timed Output Accuracy: Counter = ± 0.01% + 10 msec.
Rate = ± 0.01% + 20 msec.
7. MEMORY: Nonvolatile memory retains all programmable parameters and
display values when power is removed.
3
Model PAXC - 1/8 DIN Counter
6-DIGIT LED DISPLAY (Alternating 8 digits for counting)
DUAL COUNT QUAD INPUTS
UP TO 3 COUNT DISPLAYS
SETPOINT ALARM OUTPUTS (W/Option card)
PAXC SPECIFICATIONS
MAXIMUM SIGNAL FREQUENCIES: ANNUNCIATORS:
To determine the maximum frequency for the input(s), first answer the A - Counter A
questions with a yes (Y) or no (N). Next determine the Count Mode to be B - Counter B
used for the counter(s). If dual counters are used with different Count Modes, C - Counter C
then the lowest frequency applies to both counters. - Upper significant digit display of counter
SP1 - setpoint 1 output state
FUNCTION QUESTIONS Single: Counter A or B Dual: Counter A & B SP2 - setpoint 2 output state
Are any setpoints used? N N Y Y N N Y Y SP3 - setpoint 3 output state
SP4 - setpoint 4 output state
Is Counter C used? N Y N Y N Y N Y
COUNT MODE (Values are in KHz) (Values are in KHz) COUNTER DISPLAYS:
Maximum display: 8 digits: ± 99999999 (greater than 6 digits, display
Count x1 34 25 18 15 13 12 9 7.5 alternates between high order and low order.)
Count x2 17 13 9 7 9 7 5 4
INPUTS A and B:
Quadrature x1 22 19 12 10 7 6 4 3.5
DIP switch selectable to accept pulses from a variety of sources including
Quadrature x2 17 13 9 7 7 6 4 3.5 switch contacts, TTL outputs, magnetic pickups and all standard RLC
sensors.
Quadrature x4 8 6 4 3
LOGIC: Input trigger levels VIL = 1.5 V max.; VIH = 3.75 V min.
Notes: Current sinking: Internal 7.8 KΩ pull-up to +12 VDC, IMAX = 1.9 mA.
1. Counter Modes are explained in the Module 1 programming section. Current sourcing: Internal 3.9 KΩ pull-down, 7.3 mA max. @ 28 VDC,
2. Listed values are with frequency DIP switch set on HI frequency. VMAX = 30 VDC.
Filter: Damping capacitor provided for switch contact bounce. Limits
input frequency to 50 Hz and input pulse widths to 10 msec. minimum.
DUAL COUNT MODES:
When any dual count mode is used, then User Inputs 1 and/or 2 will accept
the second signal of each signal pair. The user inputs do not have the
Logic/Mag, HI/LO Freq, and Sink/Source input setup switches. The user
inputs are inherently a logic input with no low frequency filtering. Any
mechanical contacts used for these inputs in a dual count mode must be
debounced externally. The user input may only be selected for sink/source
by the User Jumper placement.
PAXR SPECIFICATIONS
ANNUNCIATORS: INPUT A:
- Rate DIP switch selectable to accept pulses from a variety of sources including
- Maximum (High) Rate TTL outputs, magnetic pickups and all standard RLC sensors.
- Minimum (Low) Rate LOGIC: Input trigger levels VIL = 1.5 V max.; VIH = 3.75 V min.
SP1 - setpoint 1 output state Current sinking: Internal 7.8 KΩ pull-up to +12 VDC, IMAX = 1.9 mA.
SP2 - setpoint 2 output state Current sourcing: Internal 3.9 KΩ pull-down, 7.3 mA max. @ 28 VDC,
SP3 - setpoint 3 output state VMAX = 30 VDC.
SP4 - setpoint 4 output state MAGNETIC PICKUP:
Sensitivity: 200 mV peak
RATE DISPLAY: Hysteresis: 100 mV
Accuracy: ±0.01% Input impedance: 3.9 KΩ @ 60 Hz
Minimum Frequency: 0.01 Hz Maximum input voltage: ±40 V peak, 30 Vrms
Maximum Frequency: 34 KHz
Maximum Display: 5 Digits: 99999
Adjustable Display (low) Update: 0.1 to 99.9 seconds
Over Range Display: “ ”
4
Model PAXI - 1/8 DIN Counter/Rate Meter
COUNT, RATE AND SLAVE DISPLAY
6-DIGIT 0.56" RED SUNLIGHT READABLE DISPLAY
VARIABLE INTENSITY DISPLAY
10 POINT SCALING (FOR NON-LINEAR PROCESSES)
FOUR SETPOINT ALARM OUTPUTS (W/OPTION CARD)
RETRANSMITTED ANALOG OUTPUT (W/OPTION CARD)
COMMUNICATION AND BUS CAPABILITIES (W/OPTION CARD)
BUS CAPABILITIES; DEVICENET, MODBUS, AND PROFIBUS-DP
CRIMSON PROGRAMMING SOFTWARE
PAXI SPECIFICATIONS
MAXIMUM SIGNAL FREQUENCIES TABLE
To determine the maximum frequency for the input(s), first answer the
questions with a yes (Y) or no (N). Next determine the Count Mode to be used
for the counter(s). If dual counters are used with different Count Modes, then
the lowest frequency applies to both counters.
FUNCTION QUESTIONS Single: Counter A or B (with/without rate) or Rate only Dual: Counter A & B or Rate not assigned to active single counter
Are any setpoints used? N N N N Y Y Y Y N N N N Y Y Y Y
Is Prescaler Output used? N N Y Y N N Y Y N N Y Y N N Y Y
Is Counter C used? N Y N Y N Y N Y N Y N Y N Y N Y
COUNT MODE (Values are in KHz) (Values are in KHz) (Values are in KHz) (Values are in KHz)
Count x1 34 25 21 17 18 15 13 11 13 12 13 11 9 7.5 9 7
Count x2 17 13 16 12 9 7 8 7 9* 7* 9* 7* 5* 4* 5* 4*
Quadrature x1 22 19 20 17 12 10 11 10 7* 6* 6* 5* 4* 3.5 * 3.5 * 3*
Quadrature x2 17 13 16 12 9 7 8 6 7* 6* 6* 5* 4* 3.5 * 3.5 * 3*
Quadrature x4 8 6 8 6 4 3 4 3
Rate Only 34 N/A 21 N/A 34 N/A 21 N/A
Notes:
1. Counter Modes are explained in the Module 1 programming section.
2. If using Rate with single counter with direction or quadrature, assign it to Input A for the listed frequency.
3. * Double the listed value for Rate frequency.
4. Listed values are with frequency DIP switch set on HI frequency.
5. Derate listed frequencies by 20% during serial communications. (Placing a 5 msec. delay between serial characters will eliminate the derating.)
5
Option Cards
WARNING: Disconnect all power to the unit before installing Contact Rating:
option cards. One Relay Energized: 5 amps @ 120/240 VAC or 28 VDC (resistive load).
Total current with both relays energized not to exceed 5 amps
Life Expectancy: 100 K cycles min. at full load rating. External RC snubber
extends relay life for operation with inductive loads
Adding Option Cards
The PAX and MPAX series meters can be fitted with up to three option cards. QUAD RELAY CARD: PAXCDS20
The details for each option card can be reviewed in the specification section Type: Four FORM-A relays
below. Only one card from each function type can be installed at one time. The Isolation To Sensor & User Input Commons: 2300 Vrms for 1 min.
function types include Setpoint Alarms (PAXCDS), Communications (PAXCDC), Contact Rating:
and Analog Output (PAXCDL). The option cards can be installed initially or at a One Relay Energized: 3 amps @ 250 VAC or 30 VDC (resistive load).
later date. Total current with all four relays energized not to exceed 4 amps
Life Expectancy: 100K cycles min. at full load rating. External RC snubber
PAXI COMMUNICATION CARDS (PAXCDC) extends relay life for operation with inductive loads
A variety of communication protocols are available for the PAX and MPAX QUAD SINKING OPEN COLLECTOR CARD: PAXCDS30
series. Only one of these cards can be installed at a time. When programming Type: Four isolated sinking NPN transistors.
the unit via Crimson, a Windows® based program, the RS232, RS485 or USB Isolation To Sensor & User Input Commons: 500 Vrms for 1 min.
Cards must be used. Note: For Modbus communications use RS485 Not Isolated from all other commons.
Communications Output Card and configure Communication Type Rating: 100 mA max @ VSAT = 0.7 V max. VMAX = 30 V
parameter (tYPE) for Modbus.
QUAD SOURCING OPEN COLLECTOR CARD: PAXCDS40
SERIAL COMMUNICATIONS CARD: PAXCDC1_ and PAXCDC2_ Type: Four isolated sourcing PNP transistors.
Type: RS485 or RS232 Isolation To Sensor & User Input Commons: 500 Vrms for 1 min.
Communication Type: RLC Protocol (ASCII), Modbus RTU, and Modbus Not Isolated from all other commons.
ASCII Rating: Internal supply: 24 VDC ± 10% , 30 mA max. total
Isolation To Sensor & User Input Commons: 500 Vrms for 1 min. External supply: 30 VDC max., 100 mA max. each output
Not Isolated from all other commons. DUAL TRIAC/DUAL SSR DRIVE CARD: PAXCDS50
Data: 7/8 bits Triac:
Baud: 1200 to 38,400 Type: Isolated, zero crossing detection
Parity: no, odd or even Voltage: 260 VAC max., 20 VAC min.
Bus Address: Selectable 0 to 99 (RLC Protocol), or 1 to 247 (Modbus Max Load Current: 1 Amp @ 25°C
Protocol), Max. 32 meters per line (RS485) 0.75 Amp @ 50°C
Transmit Delay: Selectable for 0 to 0.250 sec (+2 msec min) Total load current with both triacs ON not to exceed 1.5 Amps
DEVICENET® CARD: PAXCDC30 Min Load Current: 5 mA
Compatibility: Group 2 Server Only, not UCMM capable Off State Leakage Current: 1 mA max @ 60 Hz
Baud Rates: 125 Kbaud, 250 Kbaud, and 500 Kbaud Operating Frequency: 20-400 Hz
Bus Interface: Phillips 82C250 or equivalent with MIS wiring protection per SSR Drive:
DeviceNet® Volume I Section 10.2.2. Type: Two isolated sourcing PNP Transistors.
Node Isolation: Bus powered, isolated node Isolation To Sensor & User Input Commons: 500 Vrms for 1 min.
Host Isolation: 500 Vrms for 1 minute between DeviceNet® and meter input Not Isolated from all other commons.
common. Rating:
Output Voltage: 18/24 VDC (unit dependent) ± 10%, 30 mA max.
PAXUSB PROGRAMMING CARD: PAXUSB00 total both outputs
Type: USB Virtual Comms Port
Connection: Type mini B QUAD FORM C RELAY CARD: PAXCDS60
Isolation To Sensor & User Input Commons: 500 Vrms for 1 min. Type: Four FORM-C relays
Not Isolated from all other commons. Isolation To Sensor & User Input Commons: 500 Vrms for 1 min.
Baud Rate: 1200 to 38,400 Contact Rating:
Unit Address: Selectable 0 to 99 (RLC Protocol), or 1 to 247 (Modbus Rated Load: 3 Amp @ 30 VDC/125 VAC
Protocol) Total Current With All Four Relays Energized not to exceed 4 amps
Life Expectancy: 100 K cycles min. at full load rating. External RC snubber
PROFIBUS-DP CARD: PAXCDC50 extends relay life for operation with inductive loads
Fieldbus Type: Profibus-DP as per EN 50170, implemented with Siemens
SPC3 ASIC
Conformance: PNO Certified Profibus-DP Slave Device
PAXI LINEAR DC OUTPUT CARD (PAXCDL)
Either a 0(4)-20 mA or 0-10 V retransmitted linear DC output is available
Baud Rates: Automatic baud rate detection in the range 9.6 Kbaud to 12 Mbaud
from the analog output option card. The programmable output low and high
Station Address: 0 to 125, set by rotary switches.
scaling can be based on various display values. Reverse slope output is possible
Connection: 9-pin Female D-Sub connector
by reversing the scaling point positions.
Network Isolation: 500 Vrms for 1 minute between Profibus network and
sensor and user input commons. Not isolated from all other commons. ANALOG OUTPUT CARD: PAXCDL10 - Self-Powered Output (Active)
Types: 0 to 20 mA, 4 to 20 mA or 0 to 10 VDC
SETPOINT CARDS (PAXCDS) Isolation To Sensor & User Input Commons: 500 Vrms for 1 min.
The PAX and MPAX series has 6 available setpoint alarm output option Not Isolated from all other commons.
cards. Only one of these cards can be installed at a time. (Logic state of the Accuracy: 0.17% of FS (18 to 28°C); 0.4% of FS (0 to 50°C)
outputs can be reversed in the programming.) Resolution: 1/3500
Compliance: 10 VDC: 10 KΩ load min., 20 mA: 500 Ω load max.
DUAL RELAY CARD: PAXCDS10 Response Time: 50 msec. max., 10 msec. typ.
Type: Two FORM-C relays
Isolation To Sensor & User Input Commons: 2000 Vrms for 1 min.
6
Crimson Programming Software
Crimson software is a Windows® based program that allows configuration of
the PAX meter from a PC. Crimson offers standard drop-down menu commands,
that make it easy to program the meter. The meter’s program can then be saved
in a PC file for future use. A PAX serial option card or PAX USB programming
card is required to program the meter using the software. Crimson can be
downloaded at www.redlion.net.
PANEL
MOUNTING
SCREWS
7
2.0 Setting the Jumper and DIP Switches
To access the jumper and switches, remove the meter base from the meter Warning: Exposed line voltage exists on the circuit boards.
case by firmly squeezing and pulling back on the side rear finger tabs. This Remove all power to the meter and load circuits before
should lower the latch below the case slot (which is located just in front of the accessing inside of the meter.
finger tabs). It is recommended to release the latch on one side, then start the
other side latch.
2.1 SETTING THE JUMPER 2.2 SETTING THE INPUT DIP SWITCHES
The meter has one jumper for user input logic. When using the user inputs The meter has six DIP switches for Input A and Input B terminal set-up that
this jumper must be set before applying power. The Main Circuit Board figure must be set before applying power. Note: The PAXR only uses switches 1-3.
shows the location of the jumper and DIP switch.
The user input jumper determines signal logic for the user inputs, when they Input B LO Freq. 6 HI Freq.
are used with user functions or for input signal direction. All user inputs are set Input B SRC. 5 SNK.
by this jumper. Input B MAG. 4 Logic
Input A LO Freq. 3 HI Freq.
FRONT DISPLAY
Input A SRC. 2 SNK.
Input A MAG. ON 1 Logic
USER
Finger DIP SWITCHES SRC.: Adds internal 3.9 KΩ pull-down resistor, 7.3 mA max. @ 28 VDC,
INPUT Finger
Tab JUMPER Tab VMAX = 30 VDC.
SRC
SNK SNK.: Adds internal 7.8 KΩ pull-up resistor to +12 VDC, IMAX = 1.9 mA.
SWITCHES 3 and 6
HI Frequency: Removes damping capacitor and allows max. frequency.
LO Frequency: Adds a damping capacitor for switch contact bounce. Also
REAR TERMINALS limits input frequency to 50 Hz and input pulse widths to 10 msec.
Finger Finger
Hold Hold
8
4.0 Wiring the Meter
WIRING OVERVIEW EMC INSTALLATION GUIDELINES
Electrical connections are made via screw-clamp terminals located on the Visit http://www.redlion.net/emi for more information on EMI guidelines,
back of the meter. All conductors should conform to the meter’s voltage and Safety and CE issues as they relate to Red Lion products.
current ratings. All cabling should conform to appropriate standards of good
installation, local codes and regulations. It is recommended that the power
supplied to the meter (DC or AC) be protected by a fuse or circuit breaker.
When wiring the meter, compare the numbers embossed on the back of the
meter case against those shown in wiring drawings for proper wire position.
Strip the wire, leaving approximately 0.3" (7.5 mm) bare lead exposed (stranded
wires should be tinned with solder.) Insert the lead under the correct screw-
clamp terminal and tighten until the wire is secure. (Pull wire to verify
tightness.) Each terminal can accept up to one #14 AWG (2.55 mm) wire, two
#18 AWG (1.02 mm), or four #20 AWG (0.61 mm).
+ -
USER2
USER3
USER3
USER2
USER1
COMM
resistance. The input is active when it is The user inputs of the meter are internally
pulled low (<0 .9 V). pulled down to 0 V with 5.1 K resistance.
The input is active when a voltage greater
7 8 9 10 than 2.4 VDC is applied. 7 8 9 10
+ -
V SUPPLY (30V max.)
9
4.3 INPUT WIRING
CAUTION: Sensor input common is NOT isolated from user input common. In order to preserve the safety of the meter application, the sensor input
common must be suitably isolated from hazardous live earth referenced voltage; or input common must be at protective earth ground potential.
If not, hazardous voltage may be present at the User Inputs and User Input Common terminals. Appropriate considerations must then be given
to the potential of the user input common with respect to earth ground; and the common of the isolated option cards with respect to input common.
If you are wiring Input B, connect signal to Terminal 6 instead of 5, and set DIP switches 4, 5, and 6 to the positions shown for 1, 2, and 3.
Magnetic Pickup Input A AC Inputs From Tach Generators, Etc. Two Wire Proximity, Current Source
Input A
Input A
Switch or Isolated Transistor; Current Sink Switch or Isolated Transistor; Current Source Emitter Follower; Current Source
Input A Input A
Input A
Current Sink Output; Quad/Direction Current Sink Output; Quad/Direction Current Sink Output; Quad/Direction
Single Counter A Counter A Counter A &
& Rate B Counter B
Switch position is application dependent. Shaded areas not recommended for counting applications.
10 11
- +
10
5.0 Reviewing the Front Buttons and Display
Counter
A
Readout
Legends*
B
C 8.8.8.8.8.8
SP1 SP2 SP3 SP4
Setpoint Alarm
Annunciators
DSP PAR F1 F2 RST
PAR
PROGRAMMING MENU
NO User Input/ Display/
Counter A Function Program Rate Setpoint* Serial* Analog* Factory
& B Input Key Lock-out Input Counter C (Alarm) Communication Output Service
Parameters Parameters Parameters Parameters Parameters Parameters Parameters Parameters Operations
Pro F1/F2
Keys
PAR PAR PAR PAR PAR PAR PAR PAR PAR
Shaded areas represent program access that is model dependent. * Only accessible with appropriate option card.
PROGRAMMING MODE ENTRY (PAR KEY) PROGRAMMING MODE EXIT (DSP KEY or at PAR KEY)
The meter normally operates in the Display Mode. No parameters can be The Programming Mode is exited by pressing the DSP key (from anywhere
programmed in this mode. The Programming Mode is entered by pressing the in the Programming Mode) or the PAR key (with displayed). This will
PAR key. If it is not accessible then it is locked by either a security code, or a commit any stored parameter changes to memory and return the meter to the
hardware lock. Display Mode. If a parameter was just changed, the PAR key should be pressed
Two types of programming modes are available. Quick Programming Mode to store the change before pressing the DSP key. (If power loss occurs before
permits only certain parameters to be viewed and/or modified. All meter returning to the Display Mode, verify recent parameter changes.)
functions continue to operate except the front panel keys change to Programming
Mode Operations. Quick Programming Mode is configured in Module 3. Full PROGRAMMING TIPS
Programming Mode permits all parameters to be viewed and modified. In this It is recommended to start with Module 1 for counting and Module 4 for rate.
mode, incoming counts may not be recognized correctly, the front panel keys If lost or confused while programming, press the DSP key and start over. When
change to Programming Mode Operations and certain user input functions are programming is complete, it is recommended to record the parameter
disabled. Throughout this document, Programming Mode (without Quick in programming on the Parameter User Chart and lock out parameter programming
front) always refers to “Full” Programming. with a user input or lock-out code.
stores and activates the displayed selection/value. This also advances the meter Factory Settings are shown.
to the next parameter.
For numeric values, the RST key may be used to select a specific digit to be
changed. Once a digit is selected, the arrow keys are used to increment or
decrement that digit to the desired number.
11
6.1 MODULE 1 - Count A & B Input Parameters ()
PAXC & I PARAMETER MENU
x = Counter A or Counter B
Module 1 is the programming for Counter A, Counter B and the Prescaler Output. Counter B parameters follow the Prescaler parameters. For
maximum input frequency, the counters should be set to mode NONE and the Prescaler to NO when they are not in use. When set to NONE
or NO, the remaining related parameters are not accessible. A corresponding annunciator indicates the counter being shown in the Display
Mode. An Exchange Parameter Lists feature for scale factors and count load values is explained in Module 2.
to
Select the operating mode for Counter A. The number of input counts is multiplied by the scale factor and the scale
SELECTION MODE DESCRIPTION multiplier to obtain the desired process value. A scale factor of 1.00000 will
Does not count. result in the display of the actual number of input counts. (Details on scaling
calculations are explained at the end of this section.)
Count X1 Adds Input A falling edge.
12
PAXI: PRESCALER SCALE VALUE COUNTER B COUNT LOAD VALUE
to to
The prescaler output frequency When reset to count load action is selected, Counter B will reset to this value.
is the Input A frequency times the
prescaler scale value.
COUNTER B RESET POWER-UP
Counter B may be programmed to reset at each meter power-up.
COUNTER B OPERATING MODE
8 DIGIT COUNT VALUES
Any counter display value below -99999 or above 999999 (less decimal
point) will consist of a two part display. This display alternates between the
least 6 significant digits and the remaining most significant digits beginning
Select the operating mode for Counter B. with “” in the display. If the display exceeds ± 99999999 the display will roll
SELECTION MODE DESCRIPTION
to zero and continue counting. Outputs cannot be set to counter values above 6
Does not count.
digits. The annunciator, indicating the counter being displayed, will flash when
Count X1 Adds Input B falling edge. the value is above 6 digits.
d Count X1 Adds Input B falling edge if User 2 is high. Subtracts
w/direction Input B falling edge if User 2 is low.
Quad X1 Adds Input B rising edge when User 2 is high. SCALING CALCULATIONS
Subtracts Input B falling edge when User 2 is high. Each counter has the ability to scale an input signal to a desired display
Quad X2 Adds Input B rising edge when User 2 is high and value. This is accomplished by the counter mode (x-), scale factor (x),
Input B falling edge when User 2 is low. Subtracts
Input B falling edge when User 2 is high and Input B scale multiplier (x) and decimal point (x). The scale factor is
rising edge when User 2 is low. calculated using:
Count X2 Adds Input B rising and falling edges.
SF (x) = Desired Display Decimal DDD
d Count X2 Adds Input B rising and falling edges if User 2 is (Number of pulses per ‘single’ unit x CM x SM)
w/direction high. Subtracts Input B rising and falling edge if User
2 is low. Where:
Desired
Display x Counter Decimal Selection
COUNTER B RESET ACTION Decimal DDD
1
10
0
0.0
None
Tenths
100
1000
0.00
0.000
Hundredths
Thousandths
When Counter B is reset, it returns to zero or Counter B count load value. 10000 0.0000 Ten Thousandths
This reset action affects all Counter B resets, except the Setpoint Counter Auto 100000 0.00000 Hundred Thousandths
Reset Action in Module 6. Number of pulses per ‘single’ unit: pulses per unit generated by the
process (i.e. # of pulses per foot)
CM: Counter Mode(x-) times factor of the mode 1,2 or 4.
COUNTER B DECIMAL POSITION SM: Scale Multiplier (x) selection of 1, 0.1 or 0.01.
Example:
1. Show feet to the hundredths (0.00) with 100 pulses per foot:
Scale Factor would be 100 / (100 x 1 x 1) = 1
This selects the decimal point position for Counter B and any setpoint value (In this case, the scale multiplier and counter mode factor are 1)
assigned to Counter B. The selection will also affect Counter B scale factor 2. Show feet with 120 pulses per foot: Scale Factor would be 1 / (120 x 1 x 1)
calculations. = 0.0083333. (In this case, the scale multiplier of 0.01 could be used: 1 / (120
x 1 x 0.01) = 0.83333 or show to hundredths (0.00): 100 / (120 x 1 x 1) =
0.8333.)
COUNTER B SCALE FACTOR
General Rules on Scaling
to 1. It is recommended that, the scale factor be as close as possible to, but not
exceeding 1.00000. This can be accomplished by increasing or decreasing
the counter decimal point position, using the scale multiplier, or selecting a
The number of input counts is multiplied by the scale factor and the scale
different count mode.
multiplier to obtain the desired process value. A scale factor of 1.00000 will
result in the display of the actual number of input counts. (Details on scaling 2. To double the number of pulses per unit, use counter modes direction X2 or
calculations are explained at the end of this section.) quad X2. To increase it by four times, use counter mode quad X4. Using
these modes will decrease the maximum input frequency.
3. A scale factor greater than 1.00000 will cause Counter display rounding. In
COUNTER B SCALE MULTIPLIER this case, digit jumps could be caused by the internal count register rounding
the display. The precision of a counter application cannot be improved by
using a scale factor greater than 1. 00000.
4. The number of pulses per single unit must be greater than or equal to the
DDD value for the scale factor to be less than or equal to one.
The number of input counts is multiplied by the scale multiplier and the scale 5. Lowering the scale factor can be accomplished by lowering the counter
factor to obtain the desired process value. A scale multiplier of 1 will result in decimal position. (Example: 100 (Hundredths)/10 pulses = 10.000 lowering
only the scale factor affecting the display. (Details on scaling calculations are to 10 (Tenths)/10 = 1.000.)
explained at the end of this section.)
13
6.2 MODULE 2 - User Input and Front Panel Function Key
Parameters ()
PARAMETER MENU
Module 2 is the programming for rear terminal user inputs and front panel EXCHANGE PARAMETER LISTS
function keys.
Three rear terminal user inputs are individually programmable to perform
specific meter control functions. While in the Display Mode, the function is
executed when the user input transitions to the active state. (Refer to the user
input specifications for active state response times.) Certain user input functions Two lists of values are available for , , , , , ,
are disabled in “full” Programming Mode. , , , . The two lists are named and .
Three front panel function F1, F2 and RST keys are also individually If a user input is used to select the list then is selected when the user
programmable to perform specific meter control functions. While in the Display input is not active and and is selected when the user input is active,
Mode, the primary function is executed when the key is pressed. Holding the (maintained action). If a front panel key is used to select the list then the list will
F1 and F2 function keys for three seconds executes a secondary function. It is toggle for each key press, (momentary action). The meter will suspend ALL
possible to program a secondary function without a primary function. The front operations for approximately 1 msec. while the new values are loaded. The
panel key functions are disabled in both Programming Modes. display will only indicate which list is active when the list is changed or when
In most cases, if more than one user input and/or function key is programmed entering any Programming Mode.
for the same function, the maintained (level trigger) actions will be performed To program the values for and , first complete the programming
while at least one of those user inputs or function keys are activated. The of all the parameters. Exit programming and switch to the other list. Re-enter
momentary (edge trigger) actions are performed every time any of those user programming and enter the values for , , , , , ,
inputs or function keys transition to the active state. All functions are available , , , . If any other parameters are changed then the
to both user inputs and function keys. other list values must be reprogrammed.
Some of the user functions have a sublist of parameters. The sublist is
accessed when PAR is pressed at the listed function. The function will only be Shaded parameters do not apply to the PAXR.
performed for the parameters entered as . If a user input or function key is
configured for a function with a sublist, then that sublist will need to be scrolled
through each time to access the following user inputs or function keys PAXI: PRINT REQUEST
parameters.
NO FUNCTION
The meter issues a block print through the serial port when activated. The
data transmitted during the print request is configured in Module 7. If the user
input is still active after the transmission is complete (about 100 msec.), an
With this selection, NO function is performed. This is the factory setting for additional transmission will occur. Only one transmission will take place with
all user inputs and function keys except the Reset (RST) Key. each function key depression. This selection will only function when a serial
communications option card is installed in the meter.
Note: When a user input is used to accept a quad or directional input
signal, then that user input should be programmed for NO function.
14
MAINTAINED (LEVEL) RESET AND INHIBIT DEACTIVATE SETPOINT MAINTAINED (LEVEL)
The meter performs a reset and inhibits the displays configured as , as The meter deactivates the setpoints configured as , as long as activated
long as activated (maintained action). (maintained action). This action only functions with a Setpoint card installed.
DISPLAY DESCRIPTION FACTORY DISPLAY DESCRIPTION FACTORY
Counter A Setpoint 1
Counter B Setpoint 2
Counter C Setpoint 3
Maximum Setpoint 4
Minimum
DEACTIVATE SETPOINT MOMENTARY (EDGE)
PAXR: MAINTAINED (LEVEL) RESET AND INHIBIT
When activated (momentary action), the meter deactivates the setpoints
The meter performs a reset and inhibits the displays configured as , as configured as . This action only functions with a Setpoint card installed.
long as activated (maintained action).
DISPLAY DESCRIPTION FACTORY
DISPLAY DESCRIPTION FACTORY
Setpoint 1
Maximum Setpoint 2
Minimum Setpoint 3
Setpoint 4
MOMENTARY (EDGE) RESET
Module 3 is the programming for Display lock-out and “Full” and “Quick” SETPOINT 1 to 4 ACCESS LOCK-OUT
Program lock-out.
When in the Display Mode, the available displays can be read consecutively
by repeatedly pressing the DSP key. An annunciator indicates the display being
shown. These displays can be locked from being visible. It is recommended that
the display be set to when the corresponding function is not used.
The setpoint displays can be programmed for , , or (See the
SELECTION DESCRIPTION following table). Accessible only with the Setpoint option card installed.
Visible in Display Mode
Not visible in Display Mode COUNT LOAD A B C ACCESS LOCK-OUT
“Full” Programming Mode permits all parameters to be viewed and
modified. This Programming Mode can be locked with a security code and/or
user input. When locked and the PAR key is pressed, the meter enters a Quick
Programming Mode. In this mode, setpoint, count load, scale factor values, and
the Display Intensity Level () parameter can still be read and/or changed The Count Load Values can be programmed for , , or .
per the selections below.
SELECTION DESCRIPTION SCALE FACTOR A B C ACCESS LOCK-OUT
Visible but not changeable in Quick Programming Mode
Visible and changeable in Quick Programming Mode
Not visible in Quick Programming Mode LOC
The Scale Factor values can be programmed for , , or .
COUNTER A B C DISPLAY LOCK-OUT
RATE DISPLAY LOCK-OUT
DISPLAY INTENSITY ACCESS LOCK-OUT
MAX. MIN. DISPLAY LOCK-OUT
d-LEV The Display Intensity Level can be programmed for
LOC , , or .
SECURITY CODE
to
These displays can be programmed for or . Entry of a non-zero value will cause the prompt to appear when trying to
access the “Full” Programming Mode. Access will only be allowed after entering
a matching security code or universal code of . With this lock-out, a user input
Shaded areas are model dependent. would not have to be configured for Program Lock-out. However, this lock-out is
overridden by an inactive user input configured for Program Lock-out.
Throughout this document, Programming Mode (without Quick in front) always refers to “Full” Programming (all meter parameters are accessible).
16
6.4 MODULE 4 - Rate Input Parameters () - PAXR & I
PARAMETER MENU
Module 4 is the programming for the Rate parameters. For maximum input Non-linear Application – Up to 10 Scaling Points
frequency, Rate assignment should be set to when not in use. When set to Non-linear processes may utilize up to nine segments (ten scaling points) to
, the remaining related parameters are not accessible. The Rate value is provide a piece-wise linear approximation representing the non-linear function.
shown with an annunciator of ‘’ in the Display Mode. The Rate display will be linear throughout each individual segment (i.e.
Note: For PAXR, is actually on the unit’s display and between sequential scaling points). Thus, the greater the number of segments,
is actually on the unit’s display. the greater the conformity accuracy. Several linearization equations are
available in the software.
PAXI: RATE ASSIGNMENT
About Scaling Points
Each Scaling Point is specified by two programmable parameters: A desired
Rate Display Value () and a corresponding Rate Input Value ().
Scaling points are entered sequentially in ascending order of Rate Input Value.
Two scaling points must be programmed to define the upper and lower
For measuring the rate (speed) of pulses on Input A, select . For Input endpoints of the first linear segment. Setting , automatically factory sets
B select . This assignment is independent of the counting modes. the first scaling point to 0.0 for typical single segment, zero based applications.
When multiple segments are used, the upper scaling point for a given segment
LOW UPDATE TIME (DISPLAY UPDATE) becomes the lower scaling point for the next sequential segment. Thus, for each
additional segment used, only one additional scaling point must be programmed.
to seconds The following chart shows the Scaling Points, the corresponding Parameter
mnemonics, and the Factory Default Settings for each point.
SCALING DISPLAY DISPLAY INPUT INPUT
The Low Update Time is the minimum amount of time between display SEGMENT
POINT PARAMETER DEFAULT PARAMETER DEFAULT
updates for the Rate display. Values of 0.1 and 0.2 seconds will update the
1 000000 00000.0
display correctly but may cause the display to appear unsteady. The factory
1 2 001000 01000.0
setting of 1.0 will update the display every second minimum.
2 3 002000 02000.0
3 4 003000 03000.0
HIGH UPDATE TIME (DISPLAY ZERO)
4 5 004000 04000.0
to seconds
5
6
6
7
005000
006000
05000.0
06000.0
7 8 007000 07000.0
The High Update Time is the maximum amount of time before the Rate 8 9 008000 08000.0
display is forced to zero. (For more explanation, refer to Input Frequency 9 10 009000 09000.0
Calculation.) The High Update Time must be higher than the Low Update Time
and higher than the desired slowest readable speed (one divided by pulses per PAXI: RATE DISPLAY VALUE FOR SCALING POINT 1
second). The factory setting of 2.0, will force the display to zero for speeds
below 0.5 Hz or a pulse every 2 seconds. to
RATE DECIMAL POSITION
Confirm the Rate Display Value for the first Scaling Point is 0. This parameter
is automatically set to 0 and does not appear when . (See Note)
PAXI: RATE INPUT VALUE FOR SCALING POINT 1
This selects the decimal point position for Rate, Minimum and Maximum
rate displays and any setpoint value assigned to these displays. This parameter
does not affect rate scaling calculations.
to
PAXI: LINEARIZER SEGMENTS Confirm the Rate Input Value for the first Scaling Point is 0.0. (See Note)
to Note: For all linear and most non-linear applications, the Scaling Point
1 parameters ( and ) should be set to 0 and 0.0
respectively. Consult the factory before using any non-zero values for
Scaling Point 1. These parameters are automatically set to 0 and do
This parameter specifies the number of linear segments used for the Rate Scaling
not appear when .
function. Each linear segment has two scaling points which define the upper and
lower endpoints of the segment. The number of segments used depends on the
linearity of the process and the display accuracy required as described below. RATE DISPLAY VALUE FOR SCALING POINT 2
17
RATE INPUT VALUE FOR SCALING POINT 2 RATE SCALING
To scale the Rate, enter a Scaling Display value with a corresponding Scaling
to Input value. (The Display and Input values can be entered by Key-in or Applied
Methods.) These values are internally plotted to a Display value of 0 and Input
value of 0 Hz. A linear relationship is formed between these points to yield a
Enter the corresponding Rate Input Value for the second Scaling Point by rate display value that corresponds to the incoming input signal rate. The PAXI
using the arrow keys. Rate Input values for scaling points can be entered by and PAXR are capable of showing a rate display value for any linear process.
using the Key-in or the Applied method described below.
KEY-IN SCALING METHOD CALCULATION
Key-in Method: If a display value versus input signal (in pulses per second) is known, then
Enter the Rate Input value () that corresponds to the entered Rate those values can be entered into Scaling Display (x) and Scaling Input
Display value () by pressing the F1 or F2 keys. This value is always in (x). No further calculations are needed.
pulses per second (Hz). If only the number of pulses per ‘single’ unit (i.e. # of pulses per foot) is
known, then it can be entered as the Scaling Input value and the Scaling Display
Applied Method: value will be entered as the following:
Apply an external rate signal to the appropriate input terminals. At the Rate
Input Value () press and hold the F1 and F2 keys at the same time. The NOTES:
RATE PER DISPLAY (x) INPUT (x)
applied input frequency (in Hz) will appear on the display. (To verify correct
Second 1 # of pulses per unit
reading wait for at least the length of the Low Update Time. Then press and
hold the F1 and F2 keys at the same time again. The new value should be ± Minute 60 # of pulses per unit
0.1% of the previous entered value.) Press PAR to enter the displayed Hour 3600 # of pulses per unit
frequency as the Rate Input value. To prevent the displayed value from being
entered, press DSP. This will take the meter out of Programming Mode and the 1. If # of pulse per unit is less than 10, then multiply both Input and
previous Rate Input value will remain. Display values by 10.
2. If # of pulse per unit is less than 1, then multiply both Input and
Display values by 100.
RATE DISPLAY ROUND
3. If the Display value is raised or lowered, then Input value must be
raised or lowered by the same proportion (i.e. Display value for per
hour is entered by a third less (1200) then Input value is a third less
of # of pulses per unit). The same is true if the Input value is raised
or lowered, then Display value must be raised or lowered by the
Rounding values other than one round the Rate display to the nearest same proportion.
increment selected (e.g. rounding of ‘5’ causes 122 to round to 120 and 123 to 4. Both values must be greater than 0.0.
round to 125). Rounding starts at the least significant digit of the Rate display.
EXAMPLE:
1. With 15.1 pulses per foot, show feet per minute in tenths. Scaling Display
LOW CUT OUT = 60.0 Scaling Input = 15.1.
2. With 0.25 pulses per gallon, show whole gallons per hour. (To have greater
to accuracy, multiply both Input and Display values by 10.) Scaling Display
= 36000 Scaling Input = 2.5.
The Low Cut Out value forces the Rate display to zero when the Rate display INPUT FREQUENCY CALCULATION
falls below the value entered. The meter determines the input frequency by summing the number of falling
edges received during a sample period of time. The sample period begins on the first
falling edge. At this falling edge, the meter starts accumulating time towards Low
MAXIMUM CAPTURE DELAY TIME Update and High Update values. Also, the meter starts accumulating the number of
falling edges. When the time reaches the Low Update Time value, the meter looks
to seconds for one more falling edge to end the sample period. If a falling edge occurs (before
the High Update Time value is reached), the Rate display will update to the new
value and the next sample period will start on the same edge. If the High Update
When the Rate value is above the present Maximum rate value for the Time value is reached (without receiving a falling edge after reaching Low Update
entered amount of time, the meter will capture that Rate value as the new Time), then the sample period will end but the Rate display will be forced to zero.
Maximum value. A delay time helps to avoid false captures of sudden short The High Update Time value must be greater than the Low Update Time value.
spikes. Maximum detection will only function if Rate is assigned to Input A or Both values must be greater than 0.0. The input frequency calculated during the
B. The Maximum rate value is shown with an annunciator of ‘’ in the display sample period, is then shown as a Rate value determined by either scaling method.
and will continue to function independent of being displayed.
18
6.5 MODULE 5 - Counter C Input Parameters ()
PAXC & I PARAMETER MENU
Module 5 is the programming for Counter C. For maximum input frequency, COUNTER C DECIMAL POSITION
the counter operating mode should be set to when not in use. When set to
the remaining related parameters are not accessible. The C annunciator
indicates that Counter C is being shown in the Display Mode. An Exchange
Parameter List feature for scale factor and count load values is explained in
Module 2. This selects the decimal point position for Counter C and any setpoint value
assigned to Counter C. The selection will also affect Counter C scale factor
COUNTER C OPERATING MODE calculations.
Note: When using or , Counter A, B and C must all be reset at
the same time for the math to be performed on the display values. COUNTER C COUNT LOAD VALUE
19
6.6 MODULE 6 - Setpoint (Alarm) Parameters ()
6-SPt PARAMETER MENU Pro
PAR
PAR
Module 6 is the programming for the setpoint (alarms) output parameters. To have setpoint outputs, a setpoint option card needs to
be installed into the PAX (see Ordering Information). Depending on the card installed, there will be two or four setpoint outputs
available. For setpoint hardware and wiring details, refer to the bulletin shipped with the option card. For maximum input frequency,
unused Setpoints should be configured for action.
The setpoint assignment and the setpoint action determine certain setpoint feature availability. The chart below illustrates this.
20
SETPOINT ACTION SETPOINT STANDBY OPERATION
: When not using a setpoint, it should be set to (no action). Selecting will disable low acting setpoints at a power up until the display
For Counter Assignments: value crosses into the alarm “off” area. Once in the alarm “off” area, the
setpoint will function according to the configured setpoint parameters.
With Timed Out action, the setpoint output activates when the
count value equals the setpoint value and deactivates after the
Time Out value. This action is not associated with Boundary types.
With boundary action, the setpoint output activates when the count PAXI & R: SETPOINT HYSTERESIS
value is greater than or equal to (for = ) or less than or equal
to (for = ) the setpoint value. The setpoint output will
deactivate when the count value is less than (for = ) or
to
greater than (for = ) the setpoint value.
With Latch action, the setpoint output activates when the count The hysteresis value is added to (for = ), or subtracted from (for =
value equals the setpoint value. The output remains active until ), the setpoint value to determine at what value to deactivate the associated
reset. This action is not associated with Boundary types.
setpoint output. Hysteresis is only available for setpoints assigned to the Rate
with boundary action.
For Rate Assignments:
With Timed Out action, the setpoint output cycles when the rate
value is greater than or equal to (for = ) or less than or equal
to (for = ) the setpoint value. The Setpoint Time Out
PAXI & R: SETPOINT OFF DELAY
() and Setpoint On Delay () values determine the
cycling times. to seconds
With Boundary action, the setpoint output activates when the rate
value is greater than or equal to (for = ) or less than or equal
to (for = ) the setpoint value. The setpoint output will This is the amount of time the Rate display must meet the setpoint
deactivate (Auto reset) as determined by the hysteresis value. deactivation requirements (below hysteresis for high acting and above
With Latch action, the setpoint output activates when the rate value hysteresis for low acting) before the setpoint’s output deactivates.
is equal to the setpoint value. The setpoint output remains active
until reset. If after reset, the rate value is greater than or equal to
(for = ) or less than or equal to (for = ) the setpoint
value, the output will reactivate. PAXI & R: SETPOINT ON DELAY
SETPOINT TRACKING
PAXC & I: COUNTER AUTO RESET
If a selection other than NO is chosen, then the value of the setpoint being
programmed (“n”) will track the entered selection’s value. Tracking means that This automatically resets the display value of the Setpoint Assignment
when the selection’s value is changed, the “n” setpoint value will also change () counter each time the setpoint value is reached. This reset may be
(or follow) by the same amount. different than the Counter’s Reset Action (x) in Module 1 or 5.
SELECTION ACTION
No auto reset.
SETPOINT BOUNDARY TYPE
Reset to zero at the start of output activation.
Reset to count load value at the start of output activation.
Reset to zero at the end of output activation. ( action only).
activates the output when the assigned display value ( ) equals or Reset to count load value at the end of output activation. (
exceeds the setpoint value. activates the setpoint when the assigned display action only).
value is less than or equal to the setpoint.
21
PAXC & I: SETPOINT RESET WITH DISPLAY RESET PAXC & I: SETPOINT RESET WHEN SPn+1 DEACTIVATES
Select , so the setpoint output will deactivate (reset) when the Setpoint Select , so the setpoint output will deactivate (reset) when SPn +1
Assignment () counter display resets. The only exception is if the activates and then times out (deactivates). This function may only be used if the
assigned counter is reset by a Counter Auto reset generated by another setpoint. SPn+1 is programmed for Setpoint Action of . (Example SP1 deactivates
when SP2 is activated and then times out.) The last setpoint will wrap around
to the first.
PAXC & I: SETPOINT RESET WHEN SPn+1 ACTIVATES
Select , so the setpoint output will deactivate (reset) when SPn +1
activates. (Example: SP1 deactivates when SP2 activates and SP4 when SP1
activates.) The last setpoint will wrap around to the first.
22
6.7 MODULE 7 - Serial Communications Parameters ()
PAR
7-SrL
PAXI Only PARAMETER MENU Pro
NO
tYPE bAUd dAtA PAr Addr dELAY AbrV OPt
Comms Baud Data Bit Parity Bit Meter Transmit Abbreviated Print
Type Rate Address Delay Printing Options
YES
PAR
Module 7 is the programming module for the Serial Communications METER ADDRESS
Parameters. These parameters are used to match the serial settings of the PAXI
with those of the host computer or other serial device, such as a terminal or 1 to 247 - Modbus
printer. This programming module can only be accessed if an RS232 or RS485 0 to 99 - RLC Protocol
Serial Communications card is installed. 247
This section also includes an explanation of the commands and formatting Enter the serial meter (node) address. The address range is dependent on the
required for communicating with the PAXI. In order to establish serial parameter. With a single unit, configured for RLC protocol ( =
communications, the user must have host software that can send and receive ), an address is not needed and a value of zero can be used. With multiple
ASCII characters or Modbus protocol. Red Lion’s Crimson software can be units (RS485 applications), a unique 2 digit address number must be assigned
used for configuring the PAXI (See Ordering Information). For serial hardware to each meter.
and wiring details, refer to the bulletin shipped with the option card.
This section does NOT apply to the DeviceNet or Profibus-DP communication TRANSMIT DELAY
cards. For details on the operation of the Fieldbus cards, refer to the bulletin
shipped with each card.
0 to seconds
COMMUNICATIONS TYPE Following a transmit value (‘*’ terminator) or Modbus command, the PAXI
will wait this minimum amount of time before issuing a serial response.
u
C
- Modbus RTU
- Modbus ASCII
rtu - RLC Protocol (ASCII) Parameters below only appear when Communications Type parameter
Select the desired communications protocol. Modbus protocol provides () is set to .
access to all meter values and parameters. Since Modbus is included within the
ABBREVIATED PRINTING
PAXI, the PAX Modbus option card, PAXCDC4, should not be used. The
PAXCDC1 (RS485), or PAXCDC2 (RS232) card should be used instead.
BAUD RATE
Select for full print or Command T transmissions (meter address,
2400 4800 parameter data and mnemonics) or for abbreviated print transmissions
(parameter data only). This will affect all the parameters selected in the print
384 9600 19200 38400 options. (If the meter address is 0, it will not be sent during a full transmission.)
Set the baud rate to match the other serial communications equipment on the
serial link. Normally, the baud rate is set to the highest value that all the serial PRINT OPTIONS
equipment is capable of transmitting and receiving.
DATA BIT
- Enters the sub-menu to select the meter parameters to appear during a
print request. For each parameter in the sub-menu, select for that parameter
information to be sent during a print request or for that parameter information
8 not to be sent. A print request is sometimes referred to as a block print because
Select either 7 or 8 bit data word lengths. Set the word length to match the more than one parameter information (meter address, parameter data and
other serial communications equipment on the serial link. mnemonics) can be sent to a printer or computer as a block.
PARAMETER DESCRIPTION FACTORY MNEMONIC
23
SERIAL MODBUS COMMUNICATIONS 3. If a multiple write includes read only registers, then only the write registers
will change.
Modbus Communications requires that the Serial Communications Type
4. If the write value exceeds the register limit (see Register Table), then that
Parameter (tYPE) be set to Modbus RTU (Mbrtu) or Modbus ASCII (MbASC).
register value changes to its high or low limit.
PAXI CONFIGURATION USING CRIMSON AND SERIAL FC08: Diagnostics
COMMUNICATIONS CARD The following is sent upon FC08 request:
1. Install Crimson software. Module Address, 08 (FC code), 04 (byte count), “Total Comms” 2 byte count,
2. Install RS232 or RS485 card and connect communications cable from “Total Good Comms” 2 byte count, checksum of the string
PAXI to PC. “Total Comms” is the total number of messages received that were addressed
3. Supply power to PAXI. to the PAXI. “Total Good Comms” is the total messages received by the
4. Configure serial parameters to Modbus RTU (Mbrtu), 38,400 baud, PAXI with good address, parity and checksum. Both counters are reset to
address 247. (Note: These are the factory default settings.) 0 upon response to FC08 and at power-up.
5. Create a new file (File, New) or open an existing PAXI V3.0+ database.
6. Configure Crimson Link options (Link, Options) to the serial port which FC17: Report Slave ID
the communication cable is attached (in step 2). The following is sent upon FC17 request:
RLC-PAXI_V3 <a><b><0300h><0040h><0040h><0010h>
SUPPORTED FUNCTION CODES <a> = SP Card Status. “0”-None, “2”-Dual, “4”-Quad
<b> = Linear Card Status. “0”-Not Installed, “1”-Installed
FC03: Read Holding Registers
<0300h> = Software Version Number (e.g. 3.00)
1. Up to 64 registers can be requested at one time.
<0040h><0040h> = Max Register Reads/Writes (64)
2. HEX <8000> is returned for non-used registers.
<0010h> = Number of GUID/Scratch Pad Registers (16)
FC04: Read Input Registers
1. Up to 64 registers can be requested at one time. SUPPORTED EXCEPTION CODES
2. Block starting point can not exceed register boundaries. 01: Illegal Function
3. HEX <8000> is returned in registers beyond the boundaries. Issued whenever the requested function is not implemented in the meter.
4. Input registers are a mirror of Holding registers.
02: Illegal Data Address
FC06: Preset Single Register Issued whenever an attempt is made to access a single register that does not
1. HEX <8001> is echoed back when attempting to write to a read only register. exist (outside the implemented space) or to access a block of registers that falls
2. If the write value exceeds the register limit (see Register Table), then that completely outside the implemented space.
register value changes to its high or low limit. It is also returned in the
response. 03: Illegal Data Value
Issued when an attempt is made to read or write more registers than the meter
FC16: Preset Multiple Registers can handle in one request.
1. No response is given with an attempt to write to more than 64 registers at
a time. 07: Negative Acknowledge
2. Block starting point cannot exceed the read and write boundaries (40001- Issued when a write to a register is attempted with an invalid string length.
41280).
24
REGISTER FACTORY
REGISTER NAME LOW LIMIT HIGH LIMIT ACCESS COMMENTS
ADDRESS SETTING
40027 Setpoint 2 Value (Hi word)
-199999 999999 200 Read/Write Active List (A or B)
40028 Setpoint 2 Value (Lo word)
40029 Setpoint 3 Value (Hi word)
-199999 999999 300 Read/Write Active List (A or B)
40030 Setpoint 3 Value (Lo word)
40031 Setpoint 4 Value (Hi word)
-199999 999999 400 Read/Write Active List (A or B)
40032 Setpoint 4 Value (Lo word)
Manual Mode Registers
Bit State: 0 = Auto Mode, 1 = Manual Mode Bit 4 = S1, Bit 3
40036 Manual Mode Register (MMR) 0 31 0 Read/Write
= S2, Bit 2 = S3, Bit 1 = S4, Bit 0 = Linear Output
Linear Output Card written to only if Linear Output is in
40037 Analog Output Register (AOR) 0 4095 0 Read/Write
Manual Mode (MMR bit 0 = 1).
Status of Setpoint Outputs. Bit State: 0=Off, 1=On.
Bit 3 = S1, Bit 2 = S2, Bit 1 = S3, Bit 0 = S4.
40038 Setpoint Output Register (SOR) 0 15 N/A Read/Write
Outputs can only be activated/reset with this register when the
respective bits in the Manual Mode Register (MMR) are set.
Bit State: 1= Reset Output, bit is returned to zero following
40039 Reset Output Register 0 15 0 Read/Write
reset processing; Bit 3 = S1, Bit 2 = S2, Bit 1 = S3, Bit 0 = S4
25
RECEIVING DATA FROM THE METER AUTO/MANUAL MODE REGISTER (MMR) ID: U
Data is transmitted by the meter in response to either a transmit command (T), This register sets the controlling mode for the outputs. In Auto Mode (0) the
a print block command (P) or User Function print request. The response from meter controls the setpoint and analog output. In Manual Mode (1) the outputs
the meter is either a full field transmission or an abbreviated transmission. The are defined by the registers SOR and AOR. When transferring from auto mode
meter response mode is established in Module 7. to manual mode, the meter holds the last output value (until the register is
changed by a write). Each output may be independently changed to auto or
Full Field Transmission (Address, Mnemonic, Numeric data) manual. In a write command string (VU), any character besides 0 or 1 in a field
Byte Description
1, 2 2 byte Node (meter) Address field [00-99] will not change the corresponding output mode.
3 <SP> (Space) U abcde
4-6 3 byte Register Mnemonic field e = Analog Output
7-18 12 byte data field, 10 bytes for number, one byte for sign, one byte for
d = SP4
decimal point
19 <CR> carriage return c = SP3
20 <LF> line feed b = SP2
21 <SP>* (Space) a = SP1
22 <CR>* carriage return
23 <LF>* line feed Example: VU00011* places SP4 and Analog in manual.
* These characters only appear in the last line of a block print.
The first two characters transmitted (bytes 1 and 2) are the unit address. If the ANALOG OUTPUT REGISTER (AOR) ID: W
address assigned is 00, two spaces are substituted. A space (byte 3) follows the This register stores the present signal value of the analog output. The range
unit address field. The next three characters (bytes 4 to 6) are the register of values of this register is 0 to 4095, which corresponds to the analog output
mnemonic. The numeric data is transmitted next. range per the following chart:
The numeric field (bytes 7 to 18) is 12 characters long. When the requested Register Output Signal* *Due to the absolute accuracy rating
value exceeds eight digits for count values or five digits for rate values, an * Value 0-20 mA 4-20 mA 0-10 V and resolution of the output card, the
(used as an overflow character) replaces the space in byte 7. Byte 8 is always a 0 0.00 4.00 0.000 actual output signal may differ 0.15%
space. The remaining ten positions of this field (bytes 9 to 18) consist of a minus 1 0.005 4.004 0.0025 FS from the table values. The output
sign (for negative values), a floating decimal point (if applicable), and eight 2047 10.000 12.000 5.000 signal corresponds to the range selected
positions for the requested value. The data within bytes 9 to 18 is right-aligned 4094 19.995 19.996 9.9975 (0-20 mA, 4-20 mA or 0-10 V).
with leading spaces for any unfilled positions. 4095 20.000 20.000 10.000
The end of the response string is terminated with <CR> (byte 19), and <LF>
(byte 20). When a block print is finished, an extra <SP> (byte 21), <CR> (byte Writing to this register (VW) while the analog output is in the Manual Mode
22), and <LF> (byte 23) are used to provide separation between the transmissions. causes the output signal level to update immediately to the value sent. While in
the Automatic Mode, this register may be written to, but it has no effect until the
Abbreviated Transmission (Numeric data only) analog output is placed in the manual mode. When in the Automatic Mode, the
Byte Description meter controls the analog output signal level. Reading from this register (TW)
1-12 12 byte data field, 10 bytes for number, one byte for sign, one byte for will show the present value of the analog output signal.
decimal point
Example: VW2047* will result in an output of 10.000 mA, 12.000 mA or
13 <CR> carriage return
14 <LF> line feed 5.000V depending on the range selected.
15 <SP>* (Space)
16 <CR>* carriage return SETPOINT OUTPUT REGISTER (SOR) ID: X
17 <LF>* line feed This register stores the states of the setpoint outputs. Reading from this
* These characters only appear in the last line of a block print. register (TX) will show the present state of all the setpoint outputs. A “0” in the
setpoint location means the output is off and a “1” means the output is on.
Meter Response Examples:
1. Address = 17, full field response, Count A = 875 X abcd
17 CTA 875 <CR><LF> d = SP4
2. Address = 0, full field response, Setpoint 2 = -250.5 c = SP3
SP2 -250.5<CR><LF> b = SP2
3. Address = 0, abbreviated response, Setpoint 2 = 250, last line of block print a = SP1
250<CR><LF><SP><CR><LF> In Automatic Mode, the meter controls the setpoint output state. In Manual
Mode, writing to this register (VX) will change the output state. Sending any
character besides 0 or 1 in a field or if the corresponding output was not first in
manual mode, the corresponding output value will not change. (It is not
necessary to send least significant 0s.)
Example: VX10* will result in output 1 on and output 2 off.
COUNTER C SLAVE COMMUNICATIONS numerical characters are received, then the numeric value will be zero. The
Counter C may be programmed for , to act as a serial slave display. By numeric display can be used for setpoint (boundary action only) and analog
doing this, the carriage return <CR> is added as a valid command terminator output functions. When using this display for setpoint and analog output values,
character for all serial command strings. The <CR> as a terminator may be very the decimal point position must match the programming entered through the
useful for standard serial commands, even if Counter C is never displayed or front panel. The numeric value is retained in Counter C memory until another
sent a slave message. The $ terminator should not be used in the slave mode. If Numeric transmission is received.
numeric values are not to be saved to memory, then send the value as a literal Recognized Numbers = 0, 1, 2, 3, 4, 5, 6, 7, 8, 9
transmission with <CR> terminator. Recognized Punctuation = period, comma, minus
The Counter C slave display is right aligned. It has a capacity of displaying
six characters. When less than six characters are received, blank spaces will be Literal Transmissions
placed in front of the characters. If more than six characters are sent, then only When a string that begins with # is received, the meter processes it as a Literal
the last six are displayed. The meter has a 192 character buffer for the slave transmission. In this case, any unrecognized characters will be replaced with a
display. If more than 192 characters are sent, the additional characters are space. A Literal display will replace a Numeric value in the Counter C display.
discarded until a terminator is received. Counter C processes numeric and literal However, it will not remove a previous Numeric value from Counter C memory
transmissions differently. or prevent the Counter C outputs from functioning with the Numeric value.
Literal transmissions are only possible when using RS232 or RS485 cards.
Numeric Transmissions
When a string that does not begin with #, T, V, P or R is received, the meter Recognized Characters = a, b, c, d, e, f, g, h, i, j, l, n, o, p, q, r, s, t, u,
processes it as a Numeric transmission. In this case, only the recognized y, z (in upper or lower case)
numbers and punctuation are displayed. All other characters in the string are Recognized Numbers = 0, 1, 2, 3, 4, 5, 6, 7, 8, 9
discarded. If a negative sign appears anywhere in the string the resulting number Recognized Punctuation = period, comma, minus, blank
will be negative. Only the most significant decimal point is retained. If no
26
COMMAND RESPONSE TIME Timing Diagrams
The meter can only receive data or transmit data at any one time (half-duplex
operation). During RS232 transmissions, the meter ignores commands while NO REPLY FROM METER
transmitting data, but instead uses RXD as a busy signal. When sending
commands and data to the meter, a delay must be imposed before sending Command Unit
another command. This allows enough time for the meter to process the String Response
command and prepare for the next command. Transmission Time
At the start of the time interval t1, the computer program prints or writes the
string to the com port, thus initiating a transmission. During t1, the command Ready t1 t2 Ready
characters are under transmission and at the end of this period, the command
terminating character (*, $ or slave only <CR>) is received by the meter. The Command
time duration of t1 is dependent on the number of characters and baud rate of Terminator
the channel. Received
t1 = (10 times the # of characters) / baud rate
At the start of time interval t2, the meter starts the interpretation of the
command and when complete, performs the command function. This time RESPONSE FROM METER
interval t2 varies from 2 msec to 15 msec. If no response from the meter is
expected, the meter is ready to accept another command. Command Unit
If the meter is to reply with data, the time interval t2 is controlled by the use String Response
of the command terminating character and the Serial Transmit Delay parameter Transmission Time
(dELAY). The ‘*’ or ‘<CR>’ terminating character results in a response time Ready t1 t2 t3 Ready
window of the Serial Transmit Delay time (dELAY) plus 15 msec. maximum. The
dELAY parameter should be programmed to a value that allows sufficient time for Command First Reply
the release of the sending driver on the RS485 bus. Terminating the command Terminator Character Transmission
line with “$” results in a response time window (t2) of 2 msec minimum and 15 Received of Reply Time
msec maximum. The response time of this terminating character requires that
sending drivers release within 2 msec after the terminating character is
received.
At the beginning of time interval t3, the meter responds with the first
character of the reply. As with t1, the time duration of t3 is dependent on the
number of characters and baud rate of the channel. At the end of t3, the meter is
ready to receive the next command.
t3 = (10 times the # of characters) / baud rate
The maximum serial throughput of the meter is limited to the sum of the
times t1, t2 and t3.
COMMUNICATION FORMAT
Data is transferred from the meter through a serial communication channel.
In serial communications, the voltage is switched between a high and low level
at a predetermined rate (baud rate) using ASCII encoding. The receiving device
reads the voltage levels at the same intervals and then translates the switched
levels back to a character.
The voltage level conventions depend on the interface standard. The table
lists the voltage levels for each standard.
LOGIC INTERFACE STATE RS232* RS485*
1 mark (idle) TXD,RXD; -3 to -15 V a-b < -200 mV
0 space (active) TXD,RXD; +3 to +15 V a-b > +200 mV
* Voltage levels at the Receiver
Data is transmitted one byte at a time with a variable idle period between
Character Frame Figure
characters (0 to ∞). Each ASCII character is “framed” with a beginning start bit,
an optional parity bit and one or more ending stop bits. The data format and
baud rate must match that of other equipment in order for communication to
take place. The figures list the data formats employed by the meter.
Parity bit
After the data bits, the parity bit is sent. The transmitter sets the parity bit to
a zero or a one, so that the total number of ones contained in the transmission
Start bit and Data bits
(including the parity bit) is either even or odd. This bit is used by the receiver
Data transmission always begins with the start bit. The start bit signals the
to detect errors that may occur to an odd number of bits in the transmission.
receiving device to prepare for reception of data. One bit period later, the least
However, a single parity bit cannot detect errors that may occur to an even
significant bit of the ASCII encoded character is transmitted, followed by the
number of bits. Given this limitation, the parity bit is often ignored by the
remaining data bits. The receiving device then reads each bit position as they are
receiving device. The PAX meter ignores the parity bit of incoming data and
transmitted.
sets the parity bit to odd, even or none (mark parity) for outgoing data.
Stop bit
The last character transmitted is the stop bit. The stop bit provides a single bit
period pause to allow the receiver to prepare to re-synchronize to the start of a
new transmission (start bit of next byte). The receiver then continuously looks
for the occurrence of the start bit. If 7 data bits and no parity is selected, then 2
stop bits are sent from the PAXI.
27
6.8 MODULE 8 - Analog Output Parameters ()
PAXI Only 8-AnA PARAMETER MENU Pro
PAR
Module 8 is the programming for the analog output parameters. To have an ANALOG LOW SCALE VALUE
analog output signal, an analog output option card needs to be installed (See
Ordering Information). For analog output hardware and wiring details, refer to
the bulletin shipped with the option card.
to
Enter the display value within the selected Analog Assignment that
ANALOG TYPE corresponds to the low limit of the type selected.
The decimal point is determined by the decimal point setting of the assigned
SELECTION
RANGE
0 to 20 mA
counter or rate. The scale value can not be set to read values with more than 6
digits. Reverse acting output is possible by reversing the scaling values.
4 to 20 mA
0 to 10 V
Enter the analog output type. For voltage output use terminals 16 and 17. For ANALOG HIGH SCALE VALUE
current output use terminals 18 and 19. Only one range can be used at a time.
to
ANALOG ASSIGNMENT
Enter the display value within the selected Analog Assignment that
corresponds to the high limit of the type selected.
The decimal point is determined by the decimal point setting of the assigned
counter or rate. The scale value can not be set to read values with more than 6
digits. Reverse acting output is possible by reversing the scaling values.
Select the display that the analog output is to follow:
d-LEV COdE
Display Factory
Intensity Level Service Code
28
UNIT TYPE AND VERSION PAXI: CALIBRATION
COdE The meter briefly displays the unit type followed by the
current firmware version (UEr x.x), and then returns to
The only item in the PAXI meter that can be calibrated
is the Analog Output. The Count A and B values are scaled
51 COdE 50. This information is also displayed during the using the parameters in Module 1, Counter C value is scaled
meter power-up sequence. using Module 5 and the Rate value is scaled using Module
4. If the meter appears to be indicating incorrectly or inaccurately, refer to the
Troubleshooting section.
When Analog Out recalibration is required (generally every 2 years), it
INPUT A AND B LOGIC SELECTION should be performed by qualified technicians using appropriate equipment.
Calibration does not change any user programmed parameters.
COdE Calibration may be aborted by disconnecting power to the meter before
55 exiting Module 9. In this case, the existing calibration settings remain in effect.
The Count Inputs A and B are factory configured for falling edge triggered Note: Allow a 30 minute warm-up period before staring calibration.
(active low) operation in single edge count modes. The Counter Operating Mode
descriptions in the Input programming section reflect this logic. If an application
is better suited to use rising edge triggered (active high) operation, the Input
Logic for Input A and/or Input B can be changed by entering Code 55. Analog Output Card Calibration
Before starting, verify that a precision meter with an accuracy of 0.05% or
better (voltmeter for voltage output and/or current meter for current output) is
INP A connected and ready. Then perform the following procedure:
LO-ACt LO-ACt HI-ACt 1. Use the arrow keys to display and press PAR.
2. is displayed. Use the arrow keys to select and press PAR.
Selecting HI-ACt sets the Input A logic to rising edge triggered (active high) 3. Using the chart below, step through the five selections to be calibrated. At
operation. Be advised that all references to Input A falling edge and Input A each prompt, use the PAXI arrow keys to adjust the output so that the
rising edge will be reversed for the Counter Operating Mode descriptions. external meter display matches the selection being calibrated. When the
external reading matches, or if the range is not being calibrated, press PAR.
INP b SELECTION EXTERNAL METER ACTION
4. When appears, press PAR twice and remove the external meters.
TROUBLESHOOTING
PROBLEM REMEDIES
NO DISPLAY CHECK: Power level, power connections
CHECK: Active (lock-out) user input
PROGRAM LOCKED-OUT
ENTER: Security code requested
CERTAIN DISPLAYS ARE LOCKED OUT CHECK: Module 3 programming
CHECK: Input wiring, DIP switch setting, input programming, scale factor calculation,
INCORRECT DISPLAY VALUE or NOT COUNTING
input signal level, user input jumper, lower input signal frequency
USER INPUT NOT WORKING CORRECTLY CHECK: User input wiring, user input jumper, user input being used for signal, Module 2
OUTPUT DOES NOT WORK CHECK: Corresponding option card installation, output configuration, output wiring
CHECK: Wiring is per EMC installation guidelines, input signal frequency, signal quality,
JITTERY DISPLAY
scaling, update time, DIP switch setting
“ ” RATE CHECK: Lower input signal frequency, reduce rate scaling
MODULES or PARAMETERS NOT ACCESSIBLE CHECK: Corresponding option card installation, related controlling parameter selected
ERROR CODE ( ) PRESS: Reset key (if unable to clear contact factory.)
SERIAL COMMUNICATIONS CHECK: Wiring, connections, meter and host settings
29
PARAMETER VALUE CHART Programmer ________________ Date ________
PAX Model Number _________ Meter# _____________ Security Code __________
Counter A & B Input Parameters - PAXC & I only Rate Input Parameters - PAXI & R only
FACTORY FACTORY
DISPLAY PARAMETER USER SETTING DISPLAY PARAMETER USER SETTING
SETTING SETTING
COUNTER A OPERATING MODE RATE ASSIGNMENT
COUNTER A RESET ACTION LOW UPDATE TIME
COUNTER A DECIMAL POSITION HIGH UPDATE TIME
COUNTER A SCALE FACTOR (A) RATE DECIMAL POINT
COUNTER A SCALE FACTOR (B) * LINEARIZER SEGMENTS
COUNTER A SCALE MULTIPLIER SCALING PT. 1 - DISPLAY VALUE
COUNTER A COUNT LOAD VALUE (A) SCALING PT. 1 - INPUT VALUE
COUNTER A COUNT LOAD VALUE (B)* SCALING PT. 2 - DISPLAY VALUE
COUNTER A RESET POWER-UP SCALING PT. 2 - INPUT VALUE
PRESCALER OUTPUT ENABLE SCALING PT. 3 - DISPLAY VALUE
PRESCALER SCALE VALUE SCALING PT. 3 - INPUT VALUE
COUNTER B OPERATING MODE SCALING PT. 4 - DISPLAY VALUE
COUNTER B RESET ACTION SCALING PT. 4 - INPUT VALUE
COUNTER B DECIMAL POSITION SCALING PT. 5 - DISPLAY VALUE
COUNTER B SCALE FACTOR (A) SCALING PT. 5 - INPUT VALUE
COUNTER B SCALE FACTOR (B)* SCALING PT. 6 - DISPLAY VALUE
COUNTER B SCALE MULTIPLIER SCALING PT. 6 - INPUT VALUE
COUNTER B COUNT LOAD VALUE (A) SCALING PT. 7 - DISPLAY VALUE
COUNTER B COUNT LOAD VALUE (B)* SCALING PT. 7 - INPUT VALUE
COUNTER B RESET POWER-UP SCALING PT. 8 - DISPLAY VALUE
SCALING PT. 8 - INPUT VALUE
* See Module 2, Exchanging Parameter Lists, for details on programming this value.
SCALING PT. 9 - DISPLAY VALUE
Shaded areas are model dependent. SCALING PT. 9 - INPUT VALUE
SCALING PT. 10 - DISPLAY VALUE
SCALING PT. 10 - INPUT VALUE
User Input and Function Key Parameters RATE DISPLAY ROUNDING
MINIMUM LOW CUT OUT
FACTORY
DISPLAY PARAMETER USER SETTING MAX CAPTURE DELAY TIME
SETTING
USER INPUT 1 MIN CAPTURE DELAY TIME
USER INPUT 2 Shaded areas are model dependent.
USER INPUT 3
FUNCTION KEY 1
FUNCTION KEY 2 Counter C Input Parameters - PAXC & I only
RESET KEY
2nd FUNCTION KEY 1 DISPLAY PARAMETER
FACTORY
USER SETTING
2nd FUNCTION KEY 2 SETTING
COUNTER C OPERATING MODE
COUNTER C RESET ACTION
COUNTER C DECIMAL POSITION
Display and Program Lockout Parameters COUNTER C SCALE FACTOR (A)
FACTORY COUNTER C SCALE FACTOR (B)*
DISPLAY PARAMETER USER SETTING
SETTING COUNTER C SCALE MULTIPLIER
COUNTER A DISPLAY LOCK-OUT COUNTER C COUNT LOAD VALUE (A)
COUNTER B DISPLAY LOCK-OUT COUNTER C COUNT LOAD VALUE (B)*
COUNTER C DISPLAY LOCK-OUT COUNTER C RESET POWER-UP
RATE DISPLAY LOCK-OUT
MAX DISPLAY LOCK-OUT * See Module 2, Exchanging Parameter Lists, for details on programming this value.
MIN DISPLAY LOCK-OUT
SETPOINT 1 ACCESS LOCK-OUT
SETPOINT 2 ACCESS LOCK-OUT
SETPOINT 3 ACCESS LOCK-OUT
SETPOINT 4 ACCESS LOCK-OUT
COUNT LOAD A ACCESS
COUNT LOAD B ACCESS
COUNT LOAD C ACCESS
SCALE FACTOR A ACCESS
SCALE FACTOR B ACCESS
SCALE FACTOR C ACCESS
d-LEV DISPLAY INTENSITY ACCESS LOC
SECURITY CODE
Shaded areas are model dependent.
30
Setpoint (Alarm) Parameters
FACTORY FACTORY FACTORY FACTORY
DISPLAY PARAMETER USER SETTING USER SETTING USER SETTING USER SETTING
SETTING SETTING SETTING SETTING
SETPOINT ANNUNCIATORS
SETPOINT OUTPUT LOGIC
SETPOINT POWER UP STATE
SETPOINT ACTION
SETPOINT ASSIGNMENT
SETPOINT VALUE (A)
SETPOINT VALUE (B)*
SETPOINT TRACKING
SETPOINT BOUNDARY TYPE
STANDBY OPERATION
SETPOINT HYSTERESIS (rate)
SETPOINT OFF DELAY
SETPOINT ON DELAY
SETPOINT TIME OUT
COUNTER AUTO RESET ACTION
SETPOINT RESET WITH DISPLAY
RESET WHEN SPn+1 ACTIVATES
RESET WHEN SPn+1 DEACTIVATES
* See Module 2, Exchanging Parameter Lists, for details on programming this value.
Shaded areas are model dependent.
Serial Communication Parameters - PAXI only Analog Output Parameters - PAXI only
FACTORY FACTORY
DISPLAY PARAMETER USER SETTING DISPLAY PARAMETER USER SETTING
SETTING SETTING
tYPE COMMUNICATIONS TYPE Mbrtv ANALOG TYPE
BAUD RATE 384 ANALOG ASSIGNMENT
DATA BIT 8 ANALOG LOW SCALE VALUE
PARITY BIT NO ANALOG HIGH SCALE VALUE
METER ADDRESS 247
dELAY TRANSMIT DELAY 0.010
ABBREVIATED PRINTING
PRINT COUNTER A Factory Service Parameters
PRINT COUNTER B FACTORY
DISPLAY PARAMETER USER SETTING
SETTING
PRINT COUNTER C
PRINT RATE DISPLAY INTENSITY LEVEL
PRINT MAX & MIN
PRINT SCALE FACTORS
PRINT COUNT LOAD VALUES COPYRIGHT
PRINT SETPOINT VALUES © 2024 Red Lion Controls, Inc. All Rights Reserved. The terms Red Lion,
the Red Lion logo, PAX and Crimson are registered trademarks of Red Lion
Controls. All other marks are the property of their respective owners.
LIMITED WARRANTY
(a) Red Lion Controls Inc. (the “Company”) warrants that all Products shall be free from defects in material and
workmanship under normal use for the period of time provided in “Statement of Warranty Periods” (available at
www.redlion.net) current at the time of shipment of the Products (the “Warranty Period”). EXCEPT FOR THE
ABOVE-STATED WARRANTY, COMPANY MAKES NO WARRANTY WHATSOEVER WITH RESPECT TO THE
PRODUCTS, INCLUDING ANY (A) WARRANTY OF MERCHANTABILITY; (B) WARRANTY OF FITNESS FOR
A PARTICULAR PURPOSE; OR (C) WARRANTY AGAINST INFRINGEMENT OF INTELLECTUAL PROPERTY
RIGHTS OF A THIRD PARTY; WHETHER EXPRESS OR IMPLIED BY LAW, COURSE OF DEALING, COURSE
OF PERFORMANCE, USAGE OF TRADE OR OTHERWISE. Customer shall be responsible for determining that a
Product is suitable for Customer’s use and that such use complies with any applicable local, state or federal law.
(b) The Company shall not be liable for a breach of the warranty set forth in paragraph (a) if (i) the defect is a
result of Customer’s failure to store, install, commission or maintain the Product according to specifications; (ii)
Customer alters or repairs such Product without the prior written consent of Company.
(c) Subject to paragraph (b), with respect to any such Product during the Warranty Period, Company shall, in its
sole discretion, either (i) repair or replace the Product; or (ii) credit or refund the price of Product provided that,
if Company so requests, Customer shall, at Company’s expense, return such Product to Company.
(d) THE REMEDIES SET FORTH IN PARAGRAPH (c) SHALL BE THE CUSTOMER’S SOLE AND EXCLUSIVE
REMEDY AND COMPANY’S ENTIRE LIABILITY FOR ANY BREACH OF THE LIMITED WARRANTY SET
FORTH IN PARAGRAPH (a).
BY INSTALLING THIS PRODUCT, YOU AGREE TO THE TERMS OF THIS WARRANTY, AS WELL AS ALL OTHER
DISCLAIMERS AND WARRANTIES IN THIS DOCUMENT.
31
Counter parameters apply to the PAXC and PAXI, while the rate
parameters apply to the PAXR and PAXI.
F1/F2 Keys
x x x x x x x
Counter x Counter x Counter x Counter x Counter x Counter x Counter x Prescaler Prescaler
Operating Reset Decimal Scale Scale Count Load Reset at Output Scale
Mode Action Position Factor Multiplier Value Power-up Enable Value
# #
Rate Low Update High Update Rate Decimal Linearizer Rate Scaling Rate Scaling Rate Display Min. Low Max. Capture Min. Capture
Assignment Time Time Position Segments Display Input Rounding Cut-out Delay Time Delay Time
32
Setpoint Setpoint Output Power-up Setpoint Setpoint Setpoint Setpoint Boundary
Select Annunciators Logic State Action Assignment Value Tracking Type
tYPE dELAY
Comms Baud Data Bit Parity Bit Meter Transmit Abbreviated Print Print
PROGRAMMING QUICK OVERVIEW