0% found this document useful (0 votes)
77 views33 pages

Mir90 03 A

The document is an instruction manual for the MIR90 electronic control panel, detailing its front panel controls, programming parameters, and alarm signals. It provides step-by-step procedures for accessing and modifying parameters, as well as a comprehensive list of parameters and their functions. Additionally, it outlines the use of digital inputs, alarm outputs, and connections for the device.

Uploaded by

AndonLaza
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
77 views33 pages

Mir90 03 A

The document is an instruction manual for the MIR90 electronic control panel, detailing its front panel controls, programming parameters, and alarm signals. It provides step-by-step procedures for accessing and modifying parameters, as well as a comprehensive list of parameters and their functions. Additionally, it outlines the use of digital inputs, alarm outputs, and connections for the device.

Uploaded by

AndonLaza
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 33

UK

I nstruction manual E

electronic control panel F

G ebrauchsanleitungen RUS

Elektronische Steuerung

L ibro de instrucciones
centralita electrónica

M ode d’emploi
Panneau électronique

L ibretto istruzioni
centralina

Р У КО В ОД С Т В О по
эксплуатации
ýëåêòðîííîé ïàíåëè

MIR90

release 03 - A
1. FRONT PANEL CONTROLS UK

SET : SET POINT display: By pressing and releasing this key the set point is displayed.
SET POINT change: By pressing the key for 3s the set point value is displayed and the set point change mode is entered: the SET
led blinks. In order to change the value use the and keys.
Then, the new value can be stored either by pressing the “SET” key (the instrument restores temperature display)
or by waiting the programming exit timeout (15s).

UP : In the programming mode or in the “Function Menu” it browses the parameter codes or increases the value of the
variable displayed. Keep pressed for a faster change.
Manual defrost: by pressing it for 5s the defrost cycle will start.

DOWN : In programming mode or in “Function Menu” it browses the parameter codes or decreases the value of the variable
displayed. Keep pressed for a faster change.

LIGHT : It switches on and off the light.

ON/OFF : It activates and deactivates the card stand-by.

KEY COMBINATIONS

+ If the keys are pressed and released, the probe values are displayed.

+ When pressed for 3s, the Pr1 or PR2 parameter Menu is entered.

+ Programming end and room temperature display once again.

USE OF LEDS

A series of light points on keyboard is used to monitor the loads controlled by the instrument. Each LED function is described in the
following table:

LED MODE FUNCTION

ON Compressor enabled

BLINKING Anti-short cycle delay enabled

ON Fan enabled

BLINKING Drain enabled

ON Defrost enabled

BLINKING Drain time in progress

ON • ALARM signal
• In “Pr2” indicates the parameter is also present in “Pr1”

ON Auxiliary exit ON

BLINKING The set point is displayed and it is modifiable

ON The set point is displayed

ON The instrument is on standby

2. PROGRAMMING OF THE PARAMETERS

The parameters that control the electronic control panel working are divided into 2 different levels. The parameters more used lie at the first
level (Pr1), whereas at the second one (Pr2) there those which need to be changed very rarely.

ACCESS PROCEDURE TO “Pr1”

1 Press the keys + for 3s: the code of the first parameter will be displayed.
2 To run trough the menu use the or keys.
3 To select the function desired press the key .

ACCESS PROCEDURE TO “Pr2”

To enter the parameters of the Pr2 level it necessary to write a password.

3
UK 1 Enter the Pr1 user Menu.
2 Select through or the Pr2 label and press .
3 Use the or buttons to program the correct number on the blinking digit.
4 Confirm this number by pushing : this digit will stop blinking, the chosen number will still be displayed and
the following digit will blink.
5 Repeat operations 3 and 4 for the other digits.
6 If the password is correct, the “Pr2” is entered by pressing on the last digit, otherwise the password input
process restarts from the beginning.

Ü If no key is pressed within 15 seconds, the instrument displays the cold room temperature again. Û
Tu r n t o t h e s u p p l i e r f o r t h e PA S S W O R D .

N.B.: each parameter in “Pr2” can be removed or put into “Pr1” (user level) by pressing the + keys. When you are
in "Pr2" and a parameter is present in “Pr1”, the LED is lit up.

CHANGE OF THE PARAMETER VALUE

Each parameter is identified by a special alphanumeric code.


To change the parameter value operate as follows:
1 Enter the parameter mode (Pr1 or Pr2).
2 Browse the parameter list using or until the required parameter is displayed.
3 Press the key to display its value.
4 Use or to change its value.
5 Press to store the new value and to pass to the following parameter.

Exit: Press + when a label is displayed, or wait 15s without pressing any key.

N.B.: The set value is stored, even when the parameter change procedure is left without pressing the key.

3. LIST OF PARAMETERS

HY Differential: (0,1÷25,5°C; 1÷25°F) Intervention differential for set point, always positive. The compressor Cuts IN when the
temperature reaches the Set Point Plus + Hy value. The Compressor Cuts OUT when the temperature reaches again the set point value.

LS Minimum set point: (-50°C÷SET; -58°F÷SET) Sets the minimum acceptable value for the set point.

US Maximum set point: (SET÷110°C; SET÷230°F) Sets the maximum acceptable value for the set point.

OdS Output activation delay at start-up: (0÷255min) At start-up the activation of any load is hindered for the programmed time.

AC Anti-short cycle delay: (0÷30 min) minimum interval between the compressor stop and the following restart.

Con Compressor ON time with faulty probe: (0÷255min) time during which the compressor is active in case of faulty probe.
With "Con=0" the compressor is always OFF. N.B.: If “Con”=0 e “CoF”=0 the compressor is OFF.

CoF Compressor OFF time with faulty probe: (0÷255min) time during which the compressor is off in case of faulty probe.
With "CoF=0" the compressor is always active.

CF Temperature measurement unit: °C = Celsius; °F = Fahrenheit.

rES Resolution (of °C): (in = 1°C; de = 0,1°C) it allows the display with the decimal point.

tdF Defrost type: rE = by heaters (Compressor OFF). rt = time defrost with temperature control. The defrost duration is equal to
the Mdf value, and during this time, the heaters are controlled by a thermostat so that the dtE temperature value is kept in the
evaporator. in = by hot gas (Compressor ON).

EdF Defrost mode: in = the defrost takes place only during fixed time intervals set by the idF parameters.
sd = Smart Defrost. The idF defrost interval time is counted only at compressor ON.

dtE Defrost termination temperature: (-50,0÷110,0°C; -58÷230°F) sets the temperature measured by the evaporator probe,
which causes the end of defrost.

IdF Interval between defrost cycles: (1÷120 hours) determines the time interval between the beginning of two defrost cycles.

MdF Maximum defrost duration: (0÷255min) When P2P = n (evaporator probe not present) sets the defrost duration,
when P2P = y (evaporator probe present) it sets the maximum length of time for defrost.

dFd Temperature displayed during defrost: rt = real temperature; it = defrost start temperature; Set = set point;
dEF = “dEF” label; dEG = “dEg” label.

4
dAd MAX display delay after defrost: (0÷255min): Sets the maximum time between the end of the defrost and the restarting of UK
the real room temperature display.

Fdt Drain time: (0÷60min) Time interval between reaching defrost termination temperature and the restoring of the control normal operation.

FnC Fans operating mode: C-n: runs with compressor/OFF during defrost; C-y: runs with compressor/ON during defrost;
O-n: continuous mode/OFF during defrost; O-y: continuous mode/ON during defrost.

Fnd Fan activation delay after defrost: (0÷255min) time interval between the defrost termination and the restoring of the fan
normal operation.

FSt Fan stop temperature: (-50÷110°C; -58÷230°F) If the temperature detected by evaporator probe is higher than “FSt” the
fans stop. It is used to let air cold enough in the cold room.

ALC Set point alarm configuration: (rE= depends on the set point; Ab= absolute) determines if temperature alarms concern the
setpoint or if alarms are referred to absolute temperatures.

ALU Maximum temperature alarm: (If ALC = rE: 0÷50°C ;0÷90°F. If ALC = Ab: ALL÷110°C; ALL÷230°F) when this
temperature is reached the alarm is enabled after the ALd delay time.

ALL Minimum temperature alarm: (If ALC = rE: 0÷50°C ;0÷90°F. If ALC = Ab: ALU÷-50°C; ALU÷-58°F) when this temperature
is reached the alarm is enabled after the ALd delay time.

AFH Alarm and fan Set differential: (0,1 ÷ 25,5 °C; 1÷25°F). It indicates the differential for the fan and temperature alarm regulation.

ALd Temperature alarm delay: (0÷255 min) time interval between the detection of an temperature alarm condition and the alarm signalling.

dAo Temperature alarm delay at start-up: (from 0min÷23h 50min) time interval between the detection of the temperature
alarm condition after instrument power on and the alarm signalling.

EdA Temperature alarm delay at defrost end: (0÷255min) time interval between the detection of the temperature alarm
condition at the end of the defrost and the alarm signalling.

dot Door opening alarm override: (0÷255min) It is the time that determines the alarm override duration after door closing.

doA Open door alarm delay: (0÷255min) time interval between the detection of the open door alarm condition and the alarm signalling.

tbA Buzzer and alarm relay switching off: n = Buzzer and relay are independent; y = Buzzer and relay are switched off
through the same key.

nPS Maximum number of pressure switch trippings: (0÷15) It establishes how many time the pressure switch has to trip in
the interval times set at the "did" parameter in order to cause the alarm signalling.

ot Thermostat probe calibration: (-12÷12°C; -21÷21°F) allows to calibrate the thermostat probe.

oE Evaporator probe calibration: (-12÷12°C; -21÷21°F) allows to calibrate the evaporator probe.

P2P Presence of the Probe 2: n: probe not present, time defrost. y: probe present, temperature controlled defrost.

odc Opened door control: It determines the compressor and fan state at open door: no = Fans and compressor operate normally;
Fan = Fans OFF; CPr = Compressor OFF; F_C = Compressor and fans OFF.

did Digital input alarm delay: (0÷255 min.) When the digital input is set as pressure switch input, it determines the interval time
during which the pressure switch has to trip a "nps" number of time to cause an alarm signalling.

LdE Light switching off delay after door closing: (0÷255s) It settles the light switching on after the door closing.

Adr Serial address RS485: (1÷247) It allows to identify the instrument when it is inserted into a control or monitoring system like the XJ500.

rEL Release software: (reading only).

Ptb Parameter table: (reading only) Through it , it is possible to look up the list of the parameters set in the factory.

4. DIGITAL INPUTS

The MIR90 electronic control panel has two digital inputs (clean contact). The first digital input acts as door microswitch and the second
one as pressure switch.

INPUT 1: DOOR MICROSWITCH

It signals to the device the cold room door opening. When the door is opened, the compressor and the fans work according to the "odc"
parameter value.
After the time interval programmed at the dOA parameter, the opened door alarm is activated and on the display the "dA" message

5
UK appears. The alarm reset is automatic as soon as the digital input is deactivated. The temperature alarms are off when the door is opened
and after its closing for the time interval set at the "dot" parameter.
The LIGHT output is active at the door opening and during the "Lde" interval time after its closing.

INPUT 2: PRESSURE SWITCH

If during the time interval programmed at the "did" parameter, the pressure switch trips a number of times equal to those set at the "nPS"
parameter the alarm is actuated. The "PAL" message is displayed, the compressor stops and the regulation is suspended. To restore the nor-
mal functioning, switch off the instrument or put it on Standby through the ON/OFF key.

5. TTL SERIAL LINE

Thanks to the TTL serial line, the MIR90 can connect to a monitoring and supervising system by an external TTL/RS485 module. The com-
munication protocol is the ModBUS-RTU.

6. ALARM SIGNALS

Message - Mode Cause Outputs

“EE” Flashing Data failure Alarm output ON; Other outputs unchanged

“P1” Flashing Thermostat probe failure; Alarm output ON; Compressor output according to
parameters “Con” and “CoF”

P2” Alternating with Evaporator probe failure; Alarm output ON; Other outputs unchanged,
room temperature Time controlled end defrost

“HA” Alternating with Maximum temperature alarm Alarm output ON; Other outputs unchanged
room temperature

“LA” Alternating with Minimum temperature alarm Alarm output ON; Other outputs unchanged
room temperature

“dA” Alternating with Open door alarm Alarm output ON; Outlets according to the parameter “odc”
room temperature

“PAL” Alternating with Pressure switch alarm Alarm output ON; All outputs OFF
room temperature

“noL” Fixed or lighting Comunication alarm keyboard – mainboard All the outlets OFF

!!! All the signals different from the ones specified in this manual indicate a serious damage to the electronic control panel.

7. ALARM OUTPUT

When an alarm condition occurs, the alarm signal is displayed till this condition does not disappears. It is possible to inhibit the alarm out-
put deactivation by setting the “tbA” parameter at "n"; in this case the alarm output remains active till the alarm condition lasts.

ALARM RECOVERY

Probe alarm “P1” starts 30 seconds after the fault in the related probe; it stops automatically 30 seconds after the probe restarts nor-
mal operation. Check connections before replacing the probe.
The “HA” and “LA” temperature alarms automatically stop as soon as the thermostat temperature returns to normal values, at defro-
st starting or at door opening.
The “dA” open door alarm stops automatically at the door closing.
The "PAL" pressure switch alarm can be restarted manually, by switching off the instrument or by putting it on Standby.

8. CONNECTIONS
(3) NEUTRAL

(2) NEUTRAL

(1) NEUTRAL
(10) ON-OFF
(17) DEF-NC

(15) DEF NA
(16) DEF-C
(19) LIGHT

(9) PHASE
(7) PHASE

(6) COMP

(5) COMP
(14) FAN

AL +

AL -
-
Keyboard
+
Input1 (27)
Gnd (24)
Input2 (25)
Gnd (26)

Gnd (28)
Evap (29)

Gnd (30)
Room (31)

6
9. PARAMETER DEFAULT VALUES UK

defrost by defrost by defrost by


AIR HOT GAS HEATERS
Label Description Range level H-A M-N B-K M-N B-K

REGULATION
Set Set point LS ÷ US Pr 1 --- --- --- --- ---
HY Differential SET (principal) 0,1 ÷ 25,5 °C/°F Pr 1 2 2 2 2 2
LS Minimum set point -50,0 °C/°F ÷ Set Pr 1 5 -5 -25 -5 -25
US Maximum set point Set ÷ 110,0 °C/°F Pr 1 15 5 -18 5 -18
OdS Output activation delay at start-up 0 ÷ 255 min Pr 1 0 0 0 0 0
AC Anti-short cycle delay 0 ÷ 30 min Pr 2 2 2 2 2 2
Con Compressor ON time with faulty probe 0 ÷ 255 min Pr 2 0 0 0 0 0
CoF Compressor OFF time with faulty probe 0 ÷ 255 min Pr 2 0 0 0 0 0
PROBES AND DISPLAYS
CF Display Celsius/Fahrenheit °C ÷ °F Pr 2 °C °C °C °C °C
rES Resolution (of °C): integer, decimal in ÷ de Pr 2 In In In In In
DEFROST
tdF Defrost type rE, rt, in Pr 1 rE In In rE rE
EdF Defrost mode: hour, interval, Smart-def in ÷ Sd Pr 2 Sd Sd Sd Sd Sd
dtE Defrost termination temperature -50,0 ÷ +110,0 °C/°F Pr 1 110 20 20 30 30
IdF Defrost Interval 1 ÷ 120 h Pr 1 3 3 3 3 3
MdF Maximum defrost duration 0 ÷ 255 min Pr 1 20 20 20 30 30
dFd Display during defrost rt, it, Set, dEF, dEG Pr 2 rt rt rt rt rt
dAd Temperature display delay after defrost 0 ÷ 255 min Pr 2 0 0 0 0 0
Fdt Drain time 0 ÷ 60 min Pr 1 0 2 2 2 2
FANS
FnC Fans operating mode C_n, C_y, O_n, O_y Pr 1 O_y O_n O_n O_n O_n
Fnd Fan activation delay after defrost 0 ÷ 255 min Pr 1 0 3 3 3 3
FSt Fan stop temperature -50,0 ÷ +110,0 °C/°F Pr 1 40 40 40 40 40
ALARMS
ALC Alarm configuration: relative / absolute rE ÷ Ab Pr 2 rE rE rE rE rE
ALU Maximum temperature alarm -50,0 ÷ +110,0 °C/°F Pr 2 5 5 5 5 5
ALL Minimum temperature alarm -50,0 ÷ +110,0 °C/°F Pr 2 5 5 5 5 5
AFH Alarm and fan set differential 0,1 ÷ 25,5 °C; 1 ÷ 25 °F Pr 2 2 2 2 2 2
ALd Temperature alarm delay (normal operating) 0 ÷ 255 min Pr 2 0 0 0 0 0
dAo Temperature alarm delay at start-up 0 ÷ 24 h Pr 1 3 3 4 3 4
EdA Temperature alarm delay at defrost end 0 ÷ 255 min Pr 2 60 60 60 60 60
dot Door opening alarm override 0 ÷ 255 min Pr 2 60 60 60 60 60
doA Open door alarm delay 0 ÷ 255 min Pr 2 10 10 10 10 10
tbA Alarm relay switching off n÷y Pr 2 y y y y y
nPS No. of pressure switch trippings (did time) 0 ÷ 15 Pr 2 10 10 10 10 10
ANALOG INPUTS
ot Probe 1 calibration -12,0 ÷ +12,0 °C/°F Pr 2 0 0 0 0 0
oE Probe 2 calibration -12,0 ÷ +12,0 °C/°F Pr 2 0 0 0 0 0
P2P Probe 2 presence n÷y Pr 1 n y y y y
DIGITAL INPUTS
odc Open door control: fans and compressor no, Fan, CPr, F_C Pr 2 F_C F_C F_C F_C F_C
did Digital input 1 counting interval time 0 ÷ 255 min Pr 2 60 60 60 60 60
LdE Light switching off delay after deactivation 0 ÷ 255 min Pr 2 0 0 0 0 0
OTHER
Adr Address 1 RS485 0 ÷ 247 Pr 1 1 1 1 1 1
rEL Firmware release code (reading only) --- Pr 2 --- --- --- --- ---
Ptb Parameter table --- Pr 2 --- --- --- --- ---

10. GENERAL DESCRIPTION

The MIR90 electronic control panel has two inputs for probes which control the cold room temperature and the defrost. It has also two free
digital inputs not to be supplied that act as door microswitch and pressure switch. The alarm conditions are signalled by an output of
0-12V/20mA.

7
1. STEUERUNGEN AM STIRNBRETT

D SET : SET POINT–SICHTBARMACHUNG: indem man sie drückt und wieder losläßt, wird das Set Point sicht- bar gemacht.
SET POINT–ÄNDERUNG: Wenn man auf die Taste 3 s drückt, wird die Taste sichtbar gemacht und kann man in Set Point-Ände-
rungs-Modus kommen: das SET Led blinkt. Um den Wert zu ändern, drücken Sie auf die Tasten und .
Nachdem die Änderungen ausgeführt worden sind, kann der neue Wert gespeichert werden, indem man auf SET drückt (das Gerät
macht die Temperatur wieder sichtbar) oder indem man das Ausgangs-Timeout von der Programmierung (15 s) erwartet.

UP : Während der Programmierung oder im “Menü der Funktionen” dient sie dazu, die Codes der Parameter zu
überfliegen oder den Wert der sichtbar gemachten Variable zu erhöhen. Wenn man auf diese Taste dauernd drückt,
wird die Erhöhung schneller.
Manuelle Abtauung: wenn man auf diese Taste für 5 s drückt, fängt der Abtauungszyklus an.

DOWN : Während der Programmierung oder im “Menü der Funktionen” dient sie dazu, die Codes der Parameter zu
überfliegen oder den Wert der sichtbar gemachten Variable herabzusetzen. Wenn man auf diese Taste dauernd drückt,
wird die Herabsetzung schneller.

LICHT : Durch diese Taste wird das Licht an- und ausgemacht.

ON/OFF : Durch diese Taste wird das Stand-By der Karte in Betrieb gesetzt und dann auch unterbrochen.

ZUSAMMENSTELLUNG DER TASTEN

+ Wenn die Drucktasten zuerst gedrückt und nachher losgelassen werden, wird der Wert der Sensoren sichtbar gemacht.

+ Wenn man auf diese Tasten für 3 s drückt, ist es möglich ins “Menü der Parameter Pr1 oder Pr2” zu kommen.

+ Ausgang von Programmierung und Wiedersichtbarmachung der Kühlraumtemperatur.

FUNKTIONEN DER LEDS

Auf der Tastatur liegen Leuchtflecke, die die vom Gerät kontrollierten Lasten überwachen. Die Funktion von jedem LED wird in der nach-
stehenden Tabelle beschrieben:

LED MODALITÄTEN FUNKTION

LEUCHTEND Der Kompressor läuft

BLINKEND Laufende Mindestzeit vom Kompressor- Stehenbleiben

LEUCHTEND Der Lüfter läuft

BLINKEND Laufendes Tropfen

LEUCHTEND Laufende Abtauung

BLINKEND Laufende Tropfenzeit

LEUCHTEND • Alarmsignal
• Während der “Pr2” Programmierung bedeutet es, daß der Parameter auch in “Pr1” anwesend ist

LEUCHTEND Hilfsausgang AN

BLINKEND Das Set Point wird sichtbar gemacht und es ist möglich es zu ändern

LEUCHTEND Das Set Point wird sichtbar gemacht

LEUCHTEND Das Gerät ist in Stand-By

2. PROGRAMMIERUNG DER PARAMETER

Die Parameter, die den Betrieb des Steuergehäuses führen, sind in 2 verschiedenen Niveau unterteilt. Auf erstem Niveau (Pr1) liegen die
mehr gebrauchten Parameter, während die, die selten geändert werden müssen, auf zweitem Niveau (Pr2) liegen.

ZUGRIFFSVERFAHREN IN “Pr1”

1 3 Sekunden auf die Tasten + drücken: der Code des ersten Parameters wird erscheinen.
2 Auf die Tasten oder drücken, um innerhalb des Menüs vor- oder zurückrücken.
3 Um die gewünschte Funktion auszuwählen, auf die Taste drücken.

8
ZUGRIFFSVERFAHREN IN “Pr2”

Um die in “Pr2” enthaltenen Parameter zu erreichen, geben Sie ein Kennwort ein. D
1 Betreten Sie das Menü des Benutzers Pr1.
2 Wählen Sie die Etikette “Pr2” durch die Tasten oder und drücken Sie auf die Taste .
3 Drücken Sie auf oder , um die richtige Ziffer auf das blinkende Digit zu programmieren.
4 Bestätigen Sie solche Ziffer beim Drücken auf die Taste : das Digit wird nicht mehr blinken, aber die gewähl-
te Ziffer wird immer sichtbar sein. Dann wird das folgende Digit blinken.
5 Wiederholen Sie nochmals die Handlungen 3 und 4 für die übrigen Digits.
6 Wenn das Kennwort korrekt ist, kann man “Pr2” beim Drücken auf die Taste auf das letzte Digit betreten, sonst
wird das Kennwort-Eingabe-Verfahren von Anfang wieder beginnen.

Ü Wenn keine Taste innerhalb 15 Sekunden gedrückt wird, macht das Gerät die Kühlraumtemperatur wieder sichtbar. Û
Man soll den Lieferanten um das KENNWORD ersuchen.

N.B.: Jeder Parameter, der im “Pr2” anwesend ist, kann in “Pr1” hineingegeben oder vom “Pr1” genommen werden
(Benutzer-Niveau), indem man auf die Tasten + drückt. Wenn man im “Pr2” ist und wenn ein Parameter im
“Pr1” anwesend ist, leucht das LED .

ÄNDERUNG DES PARAMETERWERTS

Jeder Parameter entspricht einem alphanumerischen Code.


Um den Wert des Parameters zu ändern, verfahren Sie, wie folgt:
1 Betreten Sie den Programmierungs-Modus (Pr1 oder Pr2).
2 Lesen Sie flüchtig die Liste der Parameter durch die Tasten oder , bis der Code des Parameters, an dem
man interessiert ist, sichtbar gemacht wird.
3 Drücken Sie auf die Taste , um seinen Wert sichtbar zu machen.
4 Durch und ändern Sie seinen Wert.
5 Drücken Sie auf die Taste , um den neuen Wert zu speichern und dann gehen Sie zum Code des folgenden
Parameters über.

Ausgang: drücken Sie einfach auf + , wenn eine Etikette sichtbar gemacht wird oder drücken Sie auf keine Taste
für 15 Sekunden.

N.B.: Der neue programmierte Wert wird gespeichert , auch wenn man aus dem Änderungsverfahren ausgeht , ohne auf
die Taste zu drücken.

3. LISTE DER PARAMETER

HY Hysterese: (0,1÷25,5°C; 1÷25°F) Ansprechdifferential vom Set Point (immer positiv). Der Kompressor setzt sich in Betrieb,
wenn die Temperatur steigert und das Set Point + Hy erreicht. Der Kompressor wird halten, wenn die Temperatur gleich dem Wert
vom Set Point wieder wird.

LS Mindestes Set Point: (-50°C÷SET; -58°F÷SET) Es setzt den Mindestwert fest , der als Set Point programmiert werden kann.

US Höchstes Set Point: (SET÷110°C; SET÷230°F) Es setzt den Höchstwert fest, der als Set Point programmiert wer den kann.

OdS Ausgänge-Inbetriebsetzungs-Verzögerung beim Einschalten: (0÷255 min) Beim Einschalten wird die
Inbetriebsetzung irgendwelcher Belastung für die programmierte Zeit verhindert.

AC Mindestzeit vom Kompressor-Stehenbleiben: (0÷30 min) Es ist der mindeste Zeitraum zwischen dem Anhalten des
Kompressors und seiner folgenden Wiederinbetriebnahme.

Con Zeit mit Kompressor ON bei beschädigtem Sensor: (0÷255 min) Dauer vom Kompressorbetrieb beim
beschädigten Sensor. Bei “Con”=0 steht der Kompressor immer still. N.B.: Falls “Con”=0 und “CoF”=0 steht der Kompressor still.

CoF Zeit mit Kompressor OFF bei beschädigtem Sensor: (0÷255 min) Dauer vom Kompressorstillstand beim beschädigten
Sensor. Falls “CoF”=0, ist der Kompressor immer in Betrieb.

CF Temperatur-Maßeinheit: °C = Celsius; °F = Fahrenheit.

rES Genauigkeitsgrad (für °C): (in = 1°C; de= 0,1°C) es erlaubt die Sichtbarmachung mit dem Dezimalpunkt.

tdF Abtauungsart: rE = elektrisch (mit Widerständen) (Kompressor OFF). rt = zeitgeregelte Abtauung mit Temperaturkontrolle. Die
Abtauung dauert so lange wie den Wert des Parameters Mdf. Während dieses Zeitabstands werden die Widerstände durch
den Thermostat kontrolliert, so daß der Temperaturwert dtE im Verdampfer gehalten wird. in = mit Heißgas (Kompressor ON).

EdF Abtauungsmodalität: in = die Abtauung geschieht in festen Zeitabständen, die durch Parameter Idf eingestellt werden.
sd = Smart Defrost-Abtauung. Der Zeitabstand IdF wird nur bei laufendem Kompressor gezählt.

dtE Abtauungsende-Temperatur: (-50,0÷110,0°C; -58÷230°F) Es setzt die vom Verdampfersensor gemessene Temperatur fest,

9
die das Ende der Abtauung verursacht.

D IdF Intervall zwischen Abtauungszyklen: (1÷120 ore) Es setzt den Zeitraum zwischen dem Beginn von zweien btauungszyklen fest.

MdF Maximale Abtauungs-Dauer: (0÷255min) Bei P2P = n (abwesende Verdampfersensor) setzt er die Dauer der Abtauung fest,
bei P2P = y (anwesende Verdampfersensor) wird er die längste Dauer der Abtauung.

dFd Sichtbarmachung der Temperatur während Abtauung: rt = reelle Temperatur. it = Abtauungsbeginn-Temperatur.


Set = Set Point. dEF = Etikette “dEF”. dEG = Etikette “dEg”.

dAd Maximale Sichtbarmachungs-Verzögerung nach Abtauung: (0÷255min) Es setzt die Höchstzeit zwi schen dem
Ende der Abtauung und der Wiedersichtbarmachung der reellen Temperatur des Kühlraums fest.

Fdt Abtropfzeit: (0÷60min) Es ist der Zeitraum zwischen der Erreichung der Abtauungsende-Temperatur und der fol genden
normalen Wiederinbetriebnahme des Reglers.

FnC Betriebsmodalitäten der Ventilatoren: C-n: im Nebenschluß mit dem Kompressor, OFF während Abtauung.
C-y: im Nebenschluß mit dem Kompressor, ON während Abtauung. O-n: andauernd, OFF während Abtauung.
O-y: andauernd, ON während Abtauung.

Fnd Ventilatoren-Inbetriebnahme-Verzögerung nach Abtauung: (0÷255min) Es ist der Zeitraum zwischen dem
Abtauungsende und der folgenden normalen Wiederinbetriebnahme der Ventilatoren.

FSt Ventilatoren-Sperre-Temperatur: (-50÷110°C; -58÷230°F) Wenn die vom Verdampfersensor gemessene Temperatur
höher als die durch Parameter “FSt” programmierte ist, halten die Ventilatoren. Es dient dazu, warme genug Luft in die Kühlzelle einzulassen.

ALC Konfiguration der Alarme vom Set Point: (rE=Differentialwerte im Vergleich zu dem Wert vom Set Point Ab=absolute Werte)
Es stellt fest, ob die Temperaturalarme Differentialwerte im Vergleich zu dem Wert vom Set Point oder absolute Temperaturwerte sind.

ALU Höchsttemperaturalarm: (wenn ALC = rE: 0÷50°C ;0÷90°F. Wenn ALC = Ab: ALL÷110°C; ALL÷230°F) Wenn diese
Temperatur erreicht wird, wird der Alarm in Betrieb gesetzt (eventuell nach der Zeit ALd).

ALL Mindesttemperaturalarm: (wenn ALC = rE: 0÷50°C ;0÷90°F. Se ALC = Ab: ALU÷-50°C; ALU÷-58°F) Wenn diese
Temperatur erreicht wird, wird der Alarm in Betrieb gesetzt (eventuell nach der Zeit ALd).

AFH Alarme-und Ventilatoren-Differential: (0,1 ÷ 25,5 °C; 1÷25°F). Es zeigt das Differential für die Einstellung der Ventilatoren und der Temperatur-Alarme.

ALd Temperaturalarm-Verzögerung: (0÷255 min) Es ist der Zeitraum zwischen dem Aufnehmen von einem
Temperaturalarmsignal und seiner Meldung.

dAo Temperaturalarm-Verzögerung beim Einschalten: (von 0min÷23h 50min) Es ist der Zeitraum zwischen
dem Aufnehmen des Temperaturalarmzustands beim Einschalten des Geräts und seiner Meldung.

EdA Temperaturalarm-Verzögerung am Abtauungsende: (0÷255min) Es ist der Zeitraum zwischen dem Aufnehmen des
Temperaturalarmzustands am Abtauungsende und seiner Meldung.

dot Temperaturalarm-Ausschaltung bei offener Tür: (0÷255min) Nach der Schließung der Tür wird der
Temperaturalarm während der im diesem Parameter programmierten Zeit ausgeschaltet.

doA Alarm-Verzögerung bei offener Tür: (0÷255min) Es ist die Verzögerung zwischen dem Aufnehmen der offener Tür und der
entsprechenden Meldung.

tbA Summer- und Alarmrelais-Abschalten: n = Summer und Relais sind unabhängig. y = Summer und Relais werden beide
durch eine Taste abgeschaltet.

nPS Höchstansprechzahl vom Druckwächter: (0÷15) Es setzt die Ansprechzahl, die der Druckwächter während des am
Parameter “did” programmierten Zeitraums ausführen soll, nach der der Alarm ausgelößt wird.

ot Eichung vom Thermostatsensor: (-12÷12°C; -21÷21°F) Durch diesen Parameter kann man den
Thermostatsensor eichen.

oE Eichung vom Verdampfersensor: (-12÷12°C; -21÷21°F) Durch diesen Parameter kann man den
Verdampfersensor eichen.

P2P Anwesenheit vom Sensor 2: n: Sensor abwesend, Zeitabtauung. y: Sensor anwesend, Temperaturabhängige Abtauung.

odc Kontrolle bei offener Tür: Es bestimmt den Zustand vom Kompressor und von Ventilatoren bei offener Tür:
no = Ventilatoren und Kompressor laufen regelmäßig. Fan = Ventilatoren OFF. CPr = Kompressor OFF.
F_C = Kompressor und Ventilatoren OFF.

did Digitaleingang-Alarmverzögerung: (0÷255 min.) Wenn der Digitaleingang als Druckwächtereingang abgestaltet wird,
setzt es den Zeitraum fest, in dem eine “nPS” Ansprechzahl ausgeführt werden soll, damit der Alarm ausgelößt wird.
Wenn der Eingang als Außenalarm abgestaltet wird, setzt es den Zeitraum fest, nach dem der Alarm gemeldet wird.

10
LdE Licht-Ausschaltung-Verzögerung nach Tür-Schließung: (0÷255 s) Es is der Zeitraum, in dem das Licht an nach der Tür-Schließung ist.

Adr Serienadresse RS485: (1÷247) Es dient dazu, dieses Gerät zu identifizieren, wenn es in ein Kontroll- oder D
Überwachungssystem wie das XJ500 eingesetzt wird.

rEL Release software: (nur Ablesung).

Ptb Tabelle der Parameter: (nur Ablesung) Es dient dazu, die im Werk eingestellte Parameterliste zu identifizieren.

4. DIGITALEINGÄNGE

Die elektronische Steuerung MIR90 hat zwei Digitaleingänge (potentialfreier Kontakt). Der erste Eingang ist als Tür-Mikroschalter abge-
staltet, während der zweite als Druckwächter.

EINGANG 1: TÜR-MIKROSCHALTER

Es meldet der Vorrichtung die Öffnung der Kühlraumtür. Wenn die Tür geöffnet wird, funktionieren der Kompressor und die Ventilatoren
dem Wert vom Parameter “odc” gemäß.
Nach der am Parameter “dOA” eingestellten Zeit wird der “Tür-Öffnungs”-Alarm ausgelößt und wird die Meldung “dA” sichtbar gemacht.
Der Alarm wird automatisch nach dem Ausschalten des Digitaleingangs wiedereingeschaltet. Die Temperaturalarme werden bei offener Tür
und nach der Tür-Schließung für den am Parameter “dot” programmierten Zeitraum ausgeschaltet.
Der LICHT-Ausgang wird beim Öffnung der Tür und für den am Parameter “Lde” programmierten Zeitraum nach der Tür-Schließung aktiviert.

EINGANG 2: DRUCKWÄCHTER

Wenn die am Parameter “nPS” eingestellte Ansprechzahl vom Druckwächter während des am Parameter “did” eingestellten Zeitraums
erreicht wird, wird der Alarm ausgelößt. Die Meldung “PAL” wird sichtbar gemacht, der Kompressor hält und die Einstellung wird unter-
brochen. Um den normalen Betrieb wiederzuherstellen, ist das Gerät auszuschalten oder in Standby durch die ON/OFF zu setzen.

5. SERIENWEISE LEITUNG TTL

Die elektronische Steuerung MIR90 hat eine serienweise Leitung TTL, dank der sie durch einem Außenmodul TTL/RS485 mit einem
Überwachungssystem in Verbindung gesetzt werden kann. Das Verbindungsprotokoll ist das ModBUS-RTU.

6. ALARMMELDUNG

Meldung - Modalität Ursache Ausgänge

“EE” Blinkend Anomalie bezüglich der Daten Alarm-Ausgang ON;


Andere ausgänge werden nicht geändert

“P1” Blinkend Beschädigter Thermostatsensor Alarm-Ausgang ON; Kompressor-Ausgang


nach Parametern “Con” und “CoF”

“P2” Im Wechsel mit Beschädigter Verdampfersensor Alarm-Ausgang ON


Kühlraumtemperatur Andere Ausgänge werden nicht geändert
Zeitabtauungsende

“HA” Im Wechsel mit Höchsttemperaturalarm Alarm-Ausgang ON


Kühlraumtemperatur Andere Ausgänge werden nicht geändert

“LA” Im Wechsel mit Mindesttemperaturalarm Alarm-Ausgang ON


Kühlraumtemperatur Andere Ausgänge werden nicht geändert

“dA” Im Wechsel mit Tür-Öffnungs-Alarm Alarm-Ausgang ON


Kühlraumtemperatur Ausgänge nach dem Parameter “odc”

“PAL” Im Wechsel mit Druckwächter-Alarm Alarm-Ausgang ON


Kühlraumtemperatur Alle Ausgänge OFF

“noL” Fest oder blinkernd Alarm bzgl. Übertragungsprobleme Alle Ausgänge OFF
zwischen Tastatur und Steuerungskarte

Sämtliche Anzeigen, die sich von denen unterscheiden, die in dieser Anleitung aufgeführt werden, sind auf eine
!!! schwere Störung der Steuerung zurückzuführen.

7. ALARM-AUSGANG

Wenn ein Alarmzustand festgestellt wird, dauert die Meldung am Sichtgerät, bis der Alarmzustand verschwunden ist. Es ist möglich das
Ausschalten vom Alarm-Ausgang zu beseitigen, indem man den Parameter “tbA” auf “n” eingestellt wird. Auf diesen Fall bleibt der Alarm-
Ausgang eingeschaltet, solange der Alarmzustand dauert.

11
MODALITÄT DER ALARME-ABSCHALTUNG

D Der Sensoralarm “P1” spricht zirka 30 s nach der Festellung vom Sensorschaden an. Wenn der Sensor gut zu funktionieren wieder-
beginnt, schaltet der Alarm sich automatisch nach 30 s aus. Bevor Sie den Sensor auswechseln, prüfen Sie die Anschlüsse.
Die Temperaturalarme “HA” und “LA” schalten sich automatisch aus:
- sobald die Thermostattemperatur wieder normal wird,
- wenn eine Abtauung beginnt und
- wenn die Tür geöffnet wird.
Der Tür-Öffnungs-Alarm “dA” schaltet sich automatisch aus, wenn die Tür geschlossen wird.
Der Druckwächter-Alarm “PAL” soll manuell wiederhergestellt werden, indem man das Gerät ausschaltet oder es in Stand-By stellt.

8. ANSCHLUßPLÄNE

(3) NEUTRAL

(2) NEUTRAL

(1) NEUTRAL
(10) ON-OFF
(17) DEF-NC

(15) DEF NA
(16) DEF-C
(19) LIGHT

(9) PHASE
(7) PHASE

(6) COMP

(5) COMP
(14) FAN

AL +

AL -
-
Keyboard
+
Input1 (27)
Gnd (24)
Input2 (25)
Gnd (26)

Gnd (28)
Evap (29)

Gnd (30)
Room (31)

9. DEFAULT-WERTE DER PARAMETER

Luftabtauung Abtauung mit ELEKTRISCHE


HEIßGAS Abtauung
Label Beschreibung Regelungsbereich Niveau H-A M-N B-K M-N B-K

EINSTELLUNG
Set Set point LS ÷ US Pr 1 --- --- --- --- ---
HY Hysterese 0,1 ÷ 25,5 °C/°F Pr 1 2 2 2 2 2
LS Mindestes Set Point -50,0 °C/°F ÷ Set Pr 1 5 -5 -25 -5 -25
US Höchstes Set Point Set ÷ 110,0 °C/°F Pr 1 15 5 -18 5 -18
OdS Ausgänge-Inbetriebsetzungs-Verzögerung beim Einschalten 0 ÷ 255 min Pr 1 0 0 0 0 0
AC Mindestzeit vom Kompressor-Stehenbleiben 0 ÷ 30 min Pr 2 2 2 2 2 2
Con Zeit mit Kompressor ON bei beschädigtem Sensor 0 ÷ 255 min Pr 2 0 0 0 0 0
CoF Zeit mit Kompressor OFF bei beschädigtem Sensor 0 ÷ 255 min Pr 2 0 0 0 0 0
SENSOREN UND SICHTBARMACHUNGEN
CF Sichtbarmachung Celsius / Fahrenheit °C ÷ °F Pr 2 °C °C °C °C °C
rES Genauigkeitsgrad (für °C): ganz , dezimal in ÷ de Pr 2 In In In In In
ABTAUUNG
tdF Abtauungsart rE, rt, in Pr 1 rE In In rE rE
EdF Abtauungsmodalität: Zeit, Zeitraum, Smart-def in ÷ Sd Pr 2 Sd Sd Sd Sd Sd
dtE Abtauungsende-Temperatur -50,0 ÷ +110,0 °C/°F Pr 1 110 20 20 30 30
IdF Intervall zwischen Abtauungszyklen 1 ÷ 120 h Pr 1 3 3 3 3 3
MdF Maximale Abtauungs-Dauer 0 ÷ 255 min Pr 1 20 20 20 30 30
dFd Sichtbarmachung während Abtauung rt, it, Set, dEF, dEG Pr 2 rt rt rt rt rt
dAd Temperatur-Sichtbarmachungs-Verzögerung nach Abtauung 0 ÷ 255 min Pr 2 0 0 0 0 0
Fdt Abtropfzeit 0 ÷ 60 min Pr 1 0 2 2 2 2
VENTILATOREN
FnC Ventilatoren-Betriebsmodalität C_n, C_y, O_n, O_y Pr 1 O_y O_n O_n O_n O_n
Fnd Ventilatoren-Inbetriebnahme-Verzögerung nach Abtauung 0 ÷ 255 min Pr 1 0 3 3 3 3
FSt Ventilatoren-Sperre-Temperatur -50,0 ÷ +110,0 °C/°F Pr 1 40 40 40 40 40
ALARME
ALC Konfiguration der Alarme: relativ oder absolut rE ÷ Ab Pr 2 rE rE rE rE rE
ALU Höchsttemperaturalarm -50,0 ÷ +110,0 °C/°F Pr 2 5 5 5 5 5
ALL Mindesttemperaturalarm -50,0 ÷ +110,0 °C/°F Pr 2 5 5 5 5 5
AFH Alarme-und Ventilatoren-Differential 0,1 ÷ 25,5 °C; 1 ÷ 25 °F Pr 2 2 2 2 2 2
ALd Temp.-Verzögerung (während normalen Betriebs) 0 ÷ 255 min Pr 2 0 0 0 0 0
dAo Temperaturalarm-Verzögerung beim Einschalten 0 ÷ 24 h Pr 1 3 3 4 3 4
EdA Temperaturalarm-Verzögerung am Abtauungsende 0 ÷ 255 min Pr 2 60 60 60 60 60
dot Temperaturalarm-Ausschaltung bei offener Tür 0 ÷ 255 min Pr 2 60 60 60 60 60
doA Alarm-Verzögerung bei offener Tür 0 ÷ 255 min Pr 2 10 10 10 10 10
tbA Alarmrelais-Abschalten n÷y Pr 2 y y y y y
nPS Druckwächter-Ansprechzahl (Zeitraum did) 0 ÷ 15 Pr 2 10 10 10 10 10

12
Luftabtauung Abtauung mit ELEKTRISCHE
HEIßGAS Abtauung
Label Beschreibung Regelungsbereich Niveau H-A M-N B-K M-N B-K D

ANALOGEINGÄNGE
ot Eichung vom Sensor 1 -12,0 ÷ +12,0 °C/°F Pr 2 0 0 0 0 0
oE Eichung vom Sensor 2 -12,0 ÷ +12,0 °C/°F Pr 2 0 0 0 0 0
P2P Anwesenheit vom Sensor 2 n÷y Pr 1 n y y y y
DIGITALEINGÄNGE
odc Kontrolle bei offener Tür: Ventilatoren und Kompressor no, Fan, CPr, F_C Pr 2 F_C F_C F_C F_C F_C
did Zählungszeitraum vom Digitaleingang1 0 ÷ 255 min Pr 2 60 60 60 60 60
LdE Licht-Ausschaltung-Verzögerung nach Türschließung 0 ÷ 255 min Pr 2 0 0 0 0 0
ANDERES
Adr Serienadresse 1 RS485 0 ÷ 247 Pr 1 1 1 1 1 1
rEL Release software Code: (nur Ablesung) --- Pr 2 --- --- --- --- ---
Ptb Tabelle der Parameter --- Pr 2 --- --- --- --- ---

10. ALLGEMEINE DATEN

Die Elektronik MIR90 hat zwei Eingänge NTC für Sensoren, die die Kühlraumtemperatur und die Abtauung kontrollieren. Sie hat auch
zwei nicht zu speisenden Digitaleingänge, die als Tür-Mikroschalter und Druckwächter fungieren. Die Alarmzustände werden duch einen
Ausgang 0-12V/20mA gemeldet.

13
1. MANDOS DEL FRONTAL

SET : Visualización del SET POINT: presionando y soltando el pulsador se accede a la visualización del set point.
Modificación del SET POINT: presionando durante tres segundos el pulsador se visualiza y se accede al modo de
E variación del set point: el led Set se ilumina intermitentemente. Para modificar el valor actuar en los pulsadores y .
Efectuada la modificación, es posible memorizar el nuevo valor sea presionando SET (El instrumento vuelve a visualizar
la temperatura) o esperando el timeout de salida de la programación (15s).

UP : En modo de programación o en “Menú Funciones” desplaza los códigos de los parámetros o incrementa el valor de la
variable visualizada. Manteniéndola presionada se producirá un incremento veloz.
Desescarche manual: manteniéndolo presionado durante 5 seg. efectuará el ciclo de desescarche.

DOWN : En modo programación o en “Menú Funciones” desplaza los códigos de los parámetros o disminuye el valor de la
variable visualizada. Manteniéndolo presionado se producirá una disminución veloz.

LUZ : Activa y desactiva la luz.

ON/OFF : Activa y desactiva el funcionamiento de la placa.

COMBINACIONES DE LOS PULSADORES

+ Si se presionan y se desenganchan visualizan el valor de la sonda.

+ Presionados durante 3 seg. permiten el acceso al Menú de Parámetros Pr1 o Pr2.

+ Salida de programación y retorno a la visualización de la temperatura de la cámara.

FUNCIONES DE LOS LEDS

En la placa de pulsadores existen una serie de puntos luminosos que efectúan una acción de señalización de las cargas (compresor, ven-
tiladores, etc) controladas por el instrumento. La función de cada LED se indica en la siguiente tabla:

LED MODALIDAD FUNCIÓN

ILUMINADO Compresor activo

INTERMITENTE Retardo protección compresor

ILUMINADO Ventilador activo

INTERMITENTE Goteo activo

ILUMINADO Desescarche activo

INTERMITENTE En curso el tiempo de goteo

ILUMINADO • Señalización ALARMA


• En “Pr2” indica que el parámetro está presente también en “Pr1”

ILUMINADO Salida auxiliar ON

INTERMITENTE Se visualiza el set point y es modificable

ILUMINADO Se visualiza el set point

ILUMINADO El instrumento está en Stand By

2. PROGRAMACION DE LOS PARAMETROS

Los parámetros que gestionan el funcionamiento de la centralita estás subdivididos en 2 niveles distintos. El primer nivel (Pr1) se encuentran
los parámetros de mayor utilización, el segundo nivel (Pr2) están los que raramente necesitan modificarse.

PROCEDIMIENTO ACCESO A “Pr1”

1 Presionar durante 3 sec. los pulsadores + : aparecerá el código del primer parámetro.
2 Para moverse en el interior del menú utilizar los pulsadores o .
3 Para seleccionar la función deseada presionar el pulsador .

PROCEDIMIENTO ACCESO A “Pr2”

Para acceder a los parámetros contenidos en “Pr2” es necesario introducir un password “contraseña”.

14
1 Entrar en el Menú Usuario Pr1.
2 Seleccionar con o la etiqueta Pr2 y presionar .
3 Actuar con o para seleccionar en los dígitos intermitente la cifra correcta.
4 Confirmar tal cifra presionando el pulsador : los dígitos dejar de estar intermitentes manteniendo la visualización de la
cifra seleccionada y la intermitencia se situará en el dígito siguiente. E
5 Repetir las operaciones 3 y 4 para los siguientes dígitos.
6 Si la contraseña es correcta presionando el pulsador en el ultimo dígito se obtiene el acceso a “Pr2” en caso contrario
el procedimiento de introducción de la contraseña se repetirá desde el principio.

Ü Si no se presiona ningún pulsador durante 15 segundos el instrumento vuelve a visualizar la temperatura de la cámara. Û
E l PA S S W O R D “ c o n t r a s e ñ a ” s e t i e n e q u e s o l i c i t a r a l d i s t r i b u i d o r.

NOTA: Cada parámetro presente en “Pr2” puede quitarse o introducirse en “Pr1” (nivel usuario) presionando los pulsadores
+ . Cuando se está en “Pe2” y hay un parámetro presente en “Pr1” el LED se ilumina.

MODIFICACIÓN VALORES PARAMETROS

Cada parámetro está identificado por un adecuado código alfanumerico.


Para modificar el valor del parámetro actuar como se explica a continuación:
1 Acceder al modo de programación (Pr1 o Pr2).
2 Desplazar con los pulsadores o la lista de los parámetros hasta visualizar el código del parámetro interesado.
3 Presionar el pulsador para visualizar el valor.
4 Con o modificar el valor.
5 Presionar para memorizar el nuevo valor y pasar al código del parámetro siguiente.

Salida: Presionar + , cuando se visualiza una etiqueta , o esperar 15 segundos sin presionar ningún pulsador.

NOTA: El nuevo valor seleccionado también se memoriza cuando se sale del procedimiento de modificación de parámetros
sin tener que presionar el pulsador .

3. LISTA DE LOS PARAMETROS

HY Isteresis: (0,1 ÷ 25,5°C; 1 ÷ 25°F) Diferencial de actuación del set point, siempre positivo. El compresor se activa cuando la
temperatura aumenta hasta alcanzar el set point + Hy, para pararse cuando se alcanza el valor del set point.

LS Set point mínimo: (-50°C ÷ SET; -58°C ÷ SET) Fija el valor mínimo de selección para el set point.

US Set point máximo: (SET ÷ 110°C; SET ÷ 230°F) Fija el valor máximo de selección para el set point.

Ods Retardo activación salidas al encendido: (0 ÷ 255 min) Al encenderse la activación de cualquier carga está inhabilitada por el tiempo seleccionado.

AC Retardo protección compresor: (0 ÷ 30 min) Intervalo mínimo entre el paro del compresor y la siguiente partida del mismo.

Con Tiempo compresor ON con la sonda averiada: (0 ÷ 255 min) Tiempo en el que el compresor permanece activo en el
caso de avería de sonda. Con “Con” = 0 el compresor permanece siempre apagado. Nota: si “CoF”= 0 el compresor permanece apagado.

CoF Tiempo compresor OFF con sonda averiada: (0 ÷ 255 min) Tiempo en el cual el compresor permanece parado en el
caso de sonda averiada. Con “CoF” = 0 el compresor permanece siempre activado.

CF Unidad medida temperatura: °C = Celsius; °F Fahrenheit.

rES Resolución (para °C): (en = 1°C; de = 0,1°C) Permite la visualización del punto decimal.

tdF Tiempo de desescarche: rE = con resistencias (compresor OFF). rt = desescarche termostatado, El desescarche tiene la duración de Mdf y la
resistencia durante este tiempo efectúan cortes termostáticos sobre el valor de temperatura dtE. in = con gas caliente (compresor ON).

EdF Modalidad de desescarche: in = desescarches a intervalos de tiempo fijo seleccionado en el parámetro idF.
sd = Desescarche Smart Defrost. El intervalo del desescarche idF se cuenta solo con el compresor en funcionamiento.

dtE Temperatura final desescarche: (-50,0 ÷ 110,0°C; -58 ÷ 230°F) fija la temperatura detectada por la sonda del
evaporador, que determina el final de desescarche.

IdF Intervalos entre los ciclos de desescarche: (1 ÷ 120 horas) Determina el intervalo entre el inicio de dos ciclos de desescarche.

MdF Duración (MAX) desescarche: (0 ÷ 255 min) Con P2P = n (sonda de evaporador ausente) establece la duración del
desescarche, con P2P = y (sonda evaporador presente) se convierte en duración máxima de desescarche.

dFd Temperatura visualizada durante el desescarche: rt = temperatura real. it = temperatura inicio desescarche.
Set = set point. dEF = etiqueta “dEF”. dEG = etiqueta “dEg”.

dAd Retardo MAX visualización después del desescarche: (0 ÷ 255 min) Establece el tiempo máximo entre el fin de
desescarche y continuación de la visualización de la temperatura real de la cámara.

15
Fdt Tiempo de goteo: (0 ÷ 60 min) intervalo de tiempo entre la temperatura del final de desescarche y la continuación del funcionamiento normal del regulador.

FnC Modalidad funcionamiento ventiladores: C-n: en paralelo al compresor, parados en el desescarche. C-y: en paralelo
al compresor, funcionando en el desescarche. O-n: en continuo, parados en el desescarche. O-y: en continuo, funcionando en el desescarche.
E
Fnd Retardo activación ventiladores después del desescarche: (0 ÷ 255 min) Tiempo que discurre entre el final del
desescarche y la continuación del funcionamiento normal de los ventiladores.

FSt Temperatura bloqueo ventiladores: (-50 ÷ 110°C; -58 ÷ 230°F) Si la temperatura detectada por la sonda del
evaporador es mayor a “FSt” los ventiladores se paran. Sirve para meter aire suficientemente frío en la cámara.

ALC Configuración alarmas set point: (rE = relativas al set point; Ab = absolutos) establece si las alarmas de temperatura son
relativas al set point o son a la temperatura absoluta.

ALU Alarma Máxima temperatura: (si ALC = rE: 0 ÷ 50°C ; 0 ÷ 90°F ,si ALC = Ab; ALL ÷ 110°C; ALL ÷ 230°F) al alcanzar
tal temperatura se activa la alarma, eventualmente después del tiempo de retardo Ald.

ALL Alarma Mínima temperatura: (si ALC = rE: 0 ÷ 50°C ; 0 ÷ 90°F si ALC = Ab; ALU ÷ 50°C; ALU ÷ 58°F) al alcanzar tal
temperatura se activa la alarma, eventualmente después del tiempo de retardo Ald.

AFH Diferencial set Alarma y ventiladores: (0,1 ÷ 25,5°C; 1 ÷ 25°F) Indica el diferencial para la regulación del ventilador y las alarmas de temperatura.

ALd Retardo alarmas de temperatura: (0 ÷ 255 min) intervalo de tiempo entre la detección de una señal de alarma temperatura y su señalización.

dAo Retardo alarma temperatura al encendido: (de 0 min ÷ 23h 50min) intervalo de tiempo entre la detección de las
condiciones de alarmas temperatura al encendido del instrumento y su regulación.

EdA Retardo alarma temperatura final desescarche: (0 ÷ 255 min) intervalo de tiempo que transcurre entre la detección
de las condiciones de alarma temperatura al final del desescarche y su señalización.

dot Exclusión alarma temperatura puerta abierta: (0 ÷ 255 min) después de cerrar la puerta la alarma de temperatura
queda excluida durante el tiempo seleccionado en este parámetro.

doA Retardo alarma puerta abierta: (0 ÷ 255 min) retardo entre la detección de las condiciones de puerta abierta y su señalización.

tbA Silenciar zumbador con relé de alarma: n = zumbador y relé son independientes. y = zumbador y relé son silenciados ambos por el pulsador.

nPS Número max intervenciones presostato: (0 ÷ 15) establece el número de intervenciones que tiene que efectuar el
presostato en el intervalo de tiempo del parámetro “did” para generar la alarma.

ot Calibración sonda termostato: (-12 ÷ 12°C; -21 ÷ 21°F) permite tarar la sonda termostato.

oE Calibración sonda evaporador: (-12 ÷ 12°C; -21 ÷ 21°F) permite tarar la sonda evaporador.

P2P Presencia sonda 2: n: sonda ausente, desescarche por tiempo. y: sonda presente, desescarche por temperatura.

odc Control para puerta abierta: Determina el estado del compresor y de los ventiladores con la puerta abierta:
no = ventilador y compresor regulados normalmente. Fan = ventilador OFF. CPr = compresor OFF.
F_C = compresor y ventilador OFF.

did Retardo alarma ingreso digital: (0 ÷ 255 min.) Cuando el ingreso digital está configurado como ingreso presostato
establece el intervalo de tiempo en el cual se tiene que identificar un número “nPS” de intervenciones para generar la alarma.
Si el ingreso está seleccionado como alarma externa establece el tiempo después del cual señala la alarma.

LdE Retardo apagado luces después de cierre de puerta: (0 ÷ 255 min.) Determina el tiempo de encendido de la luz después de cerrar la puerta.

Adr Dirección serial RS485: (1 ÷ 247) Identifica el instrumento cuando es insertado en un sistema de control o de monitor como la XJ500.

rEL Release software: (solo lectura).

Ptb Tabla parámetros: (solo lectura) sirve para identificar el mapa de parámetros seleccionados en fábrica.

4. ENTRADAS DIGITALES

La MIR90 está dotada de dos entradas digitales (contacto limpio). La primera entrada digital está configurada como micro de puerta, la segunda como presostato.

ENTRADA 1 MICRO PUERTA

Señala al dispositivo la apertura de la puerta de la cámara. Cuando la puerta se abre el compresor y los ventiladores actúan en base al valor del parámetro “odc”:
Después del tiempo en el parámetro “dOA”, se activa la alarma de puerta abierta y se visualiza en el display el mensaje “dA”. El rear-
me de la alarma es automático e inmediato en el momento en que la entrada digital es desactivada. Las alarmas de temperatura son
excluidas con la puerta abierta y después de cerrarla durante un tiempo del parámetro “dot”.
La salida LUZ se activa a la apertura de la puerta y por el tiempo “Lde” después de cerrarla.

16
ENTRADA 2 PRESOSTATO

Si en el intervalo de tiempo establecido en el parámetro “did” se detectan un número de intervenciones del presostato igual al parámetro
“nPS” dispara la alarma. Se visualiza el mensaje “PAL”, y se para el compresor y suspendida la regulación. Para volver a funcionar nor-
malmente se tiene que apagar el instrumento o ponerlo en estado STAND BY con el pulsador ON/OFF. E

5. LINEA SERIAL TTL

La MIR90 tiene una línea serial TTL que permite mediante un modulo externo TTL/RS485 conectarse con un sistema de control informático y
supervisión. El protocolo de comunicación es el ModBUS-RTU.

6. SEÑALIZACIONES DE ALARMAS

Mensaje - Modalidad Causa Salida

“EE” Intermitente Anomalía en los datos Salida alarma ON; otras salidas no
modificadas

“P1” Intermitente Sonda termostato averiada Salida alarma ON; salida compresor según
parámetros “Con” y “CoF”

“P2” Alternado con la Sonda evaporador averiada Salida alarma ON; Otras salidas no modificadas;
temperatura de la cámara el desescarche termina por tiempo

“HA” Alternado con la Alarma de máxima temperatura Salida alarma ON; Otras salidas no
temperatura de la cámara modificadas

“LA” Alternado con la Alarma de mínima temperatura Salida alarma ON; Otras salidas no
temperatura de la cámara modificadas

“dA” Alternado con la Alarma puesta abierta Salida alarma ON; Salidas según el
temperatura de la cámara parámetro “odc”

“PAL” Alternado con la Alarma presostato Salida alarma ON; todas las salidas OFF
temperatura de la cámara

“noL” Fijo o intermitente Alarma comunicación panel de mandos – tarjeta Todas las salidas OFF

!!! Todas las señalizaciones diferentes de las especificadas en este manual indican una avería seria a la centralita electrónica.

7. SALIDAS ALARMAS

Una vez advertida la alarma la señalización permanece en el display hasta que las condiciones de alarma
han finalizado. Es posible inhibir la desconexión de la salida de alarma, seleccionando el parámetro “tbA” a “n” en este caso la salida
alarma permanece activa mientras duren las condiciones de alarma.

MODALIDAD REARME DE LAS ALARMAS

La alarma sonda “P1” aparece después de 30 segundos de la avería de la sonda; desaparece automáticamente 30 segundos después
de que la sonda vuelve a funcionar regularmente. Antes de sustituir la sonda se aconseja verificar las conexiones.
Las alarmas de temperatura “HA” y “LA” aparecen automáticamente casi inmediatamente cuando el termostato detecta la tem-
peratura, al iniciarse un desescarche o al abrir una puerta.
La alarma de puerta abierta “dA” finaliza automáticamente al cerrar de la puerta.
La alarma presostato “PAL” tiene el rearme manual apagando el instrumento o poniéndolo en estado Stand by.

8. ESQUEMAS DE CONEXION
(3) NEUTRAL

(2) NEUTRAL

(1) NEUTRAL
(10) ON-OFF
(17) DEF-NC

(15) DEF NA
(16) DEF-C
(19) LIGHT

(9) PHASE
(7) PHASE

(6) COMP

(5) COMP
(14) FAN

AL +

AL -
-
Keyboard
+
Input1 (27)
Gnd (24)
Input2 (25)
Gnd (26)

Gnd (28)
Evap (29)

Gnd (30)
Room (31)

17
9. VALORES DEFAULT DE LOS PARAMETROS

Desec. AIRE Desec. GAS CALIENTE Desec. ELECTRICO


Etiqueta Descripción Campo de regulación Nivel H-A M-N B-K M-N B-K
E
REGULACION
Set Set point LS ÷ US Pr 1 --- --- --- --- ---
HY Diferencial SET (principal) 0,1 ÷ 25,5 °C/°F Pr 1 2 2 2 2 2
LS Set mínimo -50,0 °C/°F ÷ Set Pr 1 5 -5 -25 -5 -25
US Set máximo Set ÷ 110,0 °C/°F Pr 1 15 5 -18 5 -18
OdS Retardo activación salidas power-on 0 ÷ 255 min Pr 1 0 0 0 0 0
AC Retardo protección compresor 0 ÷ 30 min Pr 2 2 2 2 2 2
Con Tiempo de On del compresor para sonda averiada 0 ÷ 255 min Pr 2 0 0 0 0 0
CoF Tiempo de OFF del compresor para sonda averiada 0 ÷ 255 min Pr 2 0 0 0 0 0
SONDAS Y VISUALIZACIONES
CF Visualización celsius/fahrenheit °C ÷ °F Pr 2 °C °C °C °C °C
rES Resolución (para °C): enteros, decimales in ÷ de Pr 2 In In In In In
DESESCARCHE
tdF Tipo de desescarche rE, rt, in Pr 1 rE In In rE rE
EdF Modalidad desescarche: horario , intervalos, Smart def in ÷ Sd Pr 2 Sd Sd Sd Sd Sd
dtE Temperatura final desescarche -50,0 ÷ +110,0 °C/°F Pr 1 110 20 20 30 30
IdF Intervalos desescarche 1 ÷ 120 h Pr 1 3 3 3 3 3
MdF Tiempo final desescarche 0 ÷ 255 min Pr 1 20 20 20 30 30
dFd Visualización durante el desescarche rt, it, Set, dEF, dEG Pr 2 rt rt rt rt rt
dAd Retardo visualización temp. después del desescarche 0 ÷ 255 min Pr 2 0 0 0 0 0
Fdt Tiempo goteo 0 ÷ 60 min Pr 1 0 2 2 2 2
VENTILADORES
FnC Modalidad funcionamiento ventiladores C_n, C_y, O_n, O_y Pr 1 O_y O_n O_n O_n O_n
Fnd Retardo ventiladores después del desescarche 0 ÷ 255 min Pr 1 0 3 3 3 3
FSt Temperatura bloqueo ventiladores -50,0 ÷ +110,0 °C/°F Pr 1 40 40 40 40 40
ALARMAS
ALC Configuración alarmas: relativas o absolutas rE ÷ Ab Pr 2 rE rE rE rE rE
ALU Alarma de máxima -50,0 ÷ +110,0 °C/°F Pr 2 5 5 5 5 5
ALL Alarma de mínimo -50,0 ÷ +110,0 °C/°F Pr 2 5 5 5 5 5
AFH Diferencial set alarma ventiladores 0,1 ÷ 25,5 °C; 1 ÷ 25 °F Pr 2 2 2 2 2 2
ALd Retardo alarma temp. (en funcionamiento normal) 0 ÷ 255 min Pr 2 0 0 0 0 0
dAo Retardo alarma al Power on 0 ÷ 24 h Pr 1 3 3 4 3 4
EdA Retardo alarma al final del desescarche 0 ÷ 255 min Pr 2 60 60 60 60 60
dot Exclusión alarma apertura puerta 0 ÷ 255 min Pr 2 60 60 60 60 60
doA Retardo alarma puerta abierta 0 ÷ 255 min Pr 2 10 10 10 10 10
tbA Silenciar relé alarma n÷y Pr 2 y y y y y
nPS Número intervenciones presostato (tiempo did) 0 ÷ 15 Pr 2 10 10 10 10 10
ENTRADAS ANALOGICAS
ot Calibración sonda 1 -12,0 ÷ +12,0 °C/°F Pr 2 0 0 0 0 0
oE Calibración sonda 2 -12,0 ÷ +12,0 °C/°F Pr 2 0 0 0 0 0
P2P Presencia sonda 2 n÷y Pr 1 n y y y y
ENTRADAS DIGITALES
odc Control con puerta abierta; ventilador y compresor no, Fan, CPr, F_C Pr 2 F_C F_C F_C F_C F_C
did Intervalo contador entrada digital 1 0 ÷ 255 min Pr 2 60 60 60 60 60
LdE Retardo apagado luz después de la desactivación 0 ÷ 255 min Pr 2 0 0 0 0 0
OTROS
Adr Dirección 1 RS485 0 ÷ 247 Pr 1 1 1 1 1 1
rEL Código relacionado a firmware (solo lectura) --- Pr 2 --- --- --- --- ---
Ptb Tabla de parámetros --- Pr 2 --- --- --- --- ---

10. DATOS GENERALES

La MIR90 tiene dos entradas para sonda NTC una para control de termostato y otra para el final de desescarche y dos entradas
digitales libres de tensión para la función de micro de puerta y de presostato. Las condiciones de alarma son señaladas por una salida
de 0-12V/20mA.

18
1. TOUCHES EN FAÇADE

SET : Affichage du POINT DE CONSIGNE: en pressant et en lâchant cette touche, le point de consigne est affiché.
Modification du POINT DE CONSIGNE: en appuyant sur la touche pendant 3 secondes, le point de consigne est affiché
et on peut le modifier; la led SET clignote. Pour changer la valeur, appuyer sur les touches et .
Après avoir effectué les modifications, il est possible de mémoriser la nouvelle valeur aussi bien enappuyant sur SET
(l’instrument affiche à nouveau la température) qu’en attendant la fin de la programmation (15 secondes). F

UP : En mode programmation ou en “Menu fonctions”, il permet de parcourir les codes des paramètres ou d’augmenter la valeur de
la variable affichée. En tenant cette touche pressée, on aura une augmentation rapide.
Dégivrage manuel: en appuyant sur cette touche pendant 5 secondes, le cycle de dégivrage démarre.

DOWN : En mode programmation ou en “Menu fonctions”, il permet de parcourir les codes des paramètres ou de réduire la
valeur de la variable affichée. En tenant cette touche pressée, on aura une réduction rapide.

ECLAIRAGE: Pour allumer et éteindre la lumière.

ON/OFF : Pour activer et désactiver le stand-by du panneau.

COMBINAISONS DE TOUCHES

+ Si on les presse, puis on les lâche, la valeur des sondes est affichée.

+ Pressées pendant 3 s, elles permettent d’accéder au Menu paramètres Pr1 ou Pr2.

+ Sortie de la programmation et retour à l’affichage température chambre.

FONCTIONS DES LEDS

Le clavier est doté d’une série de points lumineux qui exercent une action de monitorage des charges côntrolées par l’instrument.
La fonction de chaque LED est indiquée dans la table suivante:

LED MODALITÉ FONCTION

ALLUMÉE Compresseur activé

CLIGNOTE Retard empêchant des démarrages rapprochés du compresseur

ALLUMÉE Ventilateur activé

CLIGNOTE Egouttement activé

ALLUMÉE Dégivrage activé

CLIGNOTE Égouttement en cours

ALLUMÉE • Signalisation ALARME


• En programmation “Pr2” elle indique que le paramètre est présent aussi en “Pr1”

ALLUMÉE Sortie auxiliaire ON

CLIGNOTE Affichage du point de consigne; il est possible de le modifier

ALLUMÉE Affichage du point de consigne

ALLUMÉE L’instrument est en Stand-By

2. PROGRAMMATION DES PARAMÈTRES

Les paramètres qui contrôlent le fonctionnement du panneau sono divisés en 2 niveaux. Au premier niveau (Pr1) se trouvent les paramètres
qu’on utilise le plus, au deuxième niveau (Pr2) ceux qui nécessitent moins souvent de modifications.

PROCÉDURE D’ACCÈS À “Pr1”

1 Appuyer sur les touches + pendant 3 s: le code du premier paramètre sera affiché.
2 Pour parcourir le menu, utiliser les touches ou bien .
3 Pour sélectionner la fonction voulue, appuyer sur la touche .

PROCÉDURE D’ACCÈS À “Pr2”

Pour accéder aux paramètres contenus en “Pr2” il faut introduire un mot de passe.

19
1 Entrez en Menu Utilisateur Pr1.
2 Sélectionnez avec ou l’étiquette “Pr2” et appuyez sur la touche .
3 Appuyez sur ou pour programmer le chiffre correct sur le digit clignotant.
4 Confirmez ce chiffre en appuyant sur : le digit cessera de clignoter et continuera à afficher le chiffre choisi et le digit
suivant commencera à clignoter.
5 Répétez les opérations 3 et 4 pour les autres digits.
F 6 Si le mot de passe est correct, en pressant sur le dernier digit on pourra accéder à “Pr2”, sinon la phase d’introduction du
mot de passe recommencera du début.

Ü Si, pendant 15 secondes, on n’appuie sur aucune touche, l’instrument affichera encore la température de la chambre. Û
L e M O T D E PA S S E d o i t ê t r e d e m a n d é a u f o u r n i s s e u r.

N.B.: chaque paramètre présent en “Pr2” peut être introduit ou bien ôté de ”Pr1” (niveau utilisateur) en appuyant sur les
touches + Lorsqu’on est en “Pr2”, si un paramètre est présent en ”Pr1”, la LED est allumée.

MODIFICATION VALEUR PARAMÈTRE

Chaque paramètre est caractérisé par un code alphanumérique spécifique.


Pour changer la valeur du paramètre, se tenir aux indications suivantes:
1 Accéder au mode programmation (Pr1 ou Pr2).
2 Parcourir avec les touches ou la liste des paramètres jusqu’à afficher le code du paramètre que l’on veut changer.
3 Appuyer sur la touche pour en afficher la valeur.
4 Modifier la valeur du paramètre au moyen des touches ou .
5 Appuyer sur pour mémoriser la nouvelle valeur et passer au code du paramètre suivant.

Sortie: Appuyer sur + quand un label est affiché, ou bien attendre 15 secondes sans appuyer sur aucune touche.

N.B.: la nouvelle valeur programmée est mémorisée même quand on sort de la phase de modification sans avoir appuyé sur .

3. LISTE DES PARAMÈTRES

HY Hystérésis: (0,1÷25,5°C; 1÷25°F) Différentiel d’intervention du point de consigne, toujours positif. Le compresseur se met en marche quand
la température augmente jusqu’à atteindre le point de consigne + Hy; il s’arrête quand la température est ramenée à la valeur du point de consigne.

LS Point de consigne minimum: (-50°C÷ SET; -58°F÷SET). Valeur minimum qu’il est possible de choisir pour le point de consigne.

US Point de consigne maximum: (SET÷110°C; SET÷230°F). Valeur maximum qu’il est possible de choisir pour le point de consigne.

Ods Retard démarrage sorties lors de la mise en marche: (0÷255 min) Lors de la mise en marche, la mise en service de
toute charge est empêchée pour le temps programmé.

AC Retard empêchant des démarrages rapprochés du compress.: (0÷30 min) intervalle minimum entre l’arrêt du
compresseur et la mise en marche suivante.

Con Temps compresseur ON avec sonde en panne: (0÷255 min) Temps pendant lequel le compresseur reste en marche en cas de
dérangement de la sonde. Lorsque “Con” = 0, le compresseur est toujours arrêté. N.B.: Si “Con” = 0 et “CoF” = 0, le compresseur reste arrêté.

CoF Temps compresseur OFF avec sonde en panne: (0÷255 min) Temps pendant lequel le compresseur est arrêté en cas de
dérangement de la sonde. Lorsque “CoF” = 0, le compresseur est toujours allumé.

CF Unité de mesure de la température: °C = Celsius; °F = Fahrenheit.

rES Résolution (pour °C): (in = 1°C; de = 0,1°C) Permettant l’affichage avec point décimal.

tdF Type de dégivrage: rE = électrique (Compresseur OFF). rt = thermostaté. La durée du dégivrage est égale à Mdf et les
résistances, pendant cette intervalle, sont contrôlées par un thermostat, afin que dans l’évaporateur soit maintenue une valeur de
température dtE. in = par gaz chaud (Compresseur ON).

EdF Modalité de dégivrage: in = dégivrage à intervalles de temps fixes programmés à l’aide du paramètre idF. sd = dégivrage
Smart Defrost. L’intervalle de dégivrage idF est calculé seulement lorsque le compresseur est allumé.

dtE Température fin dégivrage: (-50,0÷110,0°C / -58÷230°F) il fixe la température mesurée par la sonde de l’évaporateur, qui entraîne la fin du dégivrage.

IdF Intervalle entre les cycles de dégivrage: (1÷120 h) Il établit l’intervalle entre le début de deux cycles de dégivrage.

MdF Durée (MAX) dégivrage: (0÷255 min) si P2P = n (Sonde évaporateur absente), il établit la durée du dégivrage, si
P2P = y (Sonde évaporateur présente), il indique la durée maximum du dégivrage.

dFd Température affichée pendant le dégivrage: rt = température réelle; it = température début dégivrage; Set = point de
consigne; dEF = étiquette “dEF”; dEG = étiquette “dEG”.

dAd Retard MAX affichage après le dégivrage: (0÷255 min) Il établit le temps maximum entre la fin du dégivrage et la

20
reprise de l’affichage de la température réelle de la chambre.

Fdt Temps d’égouttement: (0÷60 min) Intervalle de temps entre le moment où l’on atteint la température de fin dégivrage et la remise en marche normale du régulateur.

FnC Modalité de fonctionnement des ventilateurs: C-n = en parallèle au compresseur, arrêtés pendant le dégivrage;
C-y = en parallèle au compresseur, en marche pendant le dégivrage; O-n = fonctionnement continu, arrêtés pendant le dégivrage;
O-y = fonctionnement continu, en marche pendant le dégivrage. F

Fnd Retard mise en marche des ventilateurs après le dégivrage: (0÷255 min) Intervalle de temps entre la fin du
dégivrage et la remise en marche normale des ventilateurs.

FSt Température arrêt ventilateurs: (-50÷110°C / -58÷230°F) Si la température mesurée par la sonde de l’évaporateur
dépasse “FSt”, les ventilateurs s’arrêtent. Il sert à introduire de l’air suffisamment froid dans la chambre.

ALC Configuration alarmes point de consigne: (rE=relatives au point de consigne; Ab=absolues) il permet d’établir si les
alarmes de température sont relatifs au point de consigne ou bien s’il s’agit de températures absolues.

ALU Alarme température maximum: (si ALC = rE: 0÷50°C / 0÷90°F; si ALC = Ab ALL÷110°C / ALL÷230°F) lorsqu’on atteint
cette température l’alarme est activée, éventuellement après le retard ALd.

ALL Alarme température minimum: (si ALC = rE: 0÷50°C / 0÷90°F; si ALC = Ab ALU÷50°C / ALU÷58°F) lorsqu’on atteint
cette température l’alarme est activée, éventuellement après le retard ALd.

AFH Différentiel Point de consigne Alarme et ventilateurs: (0,1÷25,5°C; 1÷25°F) Il indique le différentiel pour le réglage
des ventilateurs et les alarmes de température.

ALd Retard alarme température: (0÷255 min) intervalle de temps entre la détection d’un signal d’alarme et sa signalisation.

dAo Retard alarme température lors de l’allumage: (de 0 min à 23 h 50 min) intervalle de temps entre la détection de
l’alarme de température lors de l’allumage et sa signalisation.

EdA Retard alarme température à fin dégivrage: (0÷255 min) intervalle de temps entre la détection de l’alarme de
température à la fin du dégivrage et sa signalisation.

dot Exclusion alarme température porte ouverte: (0÷255 min) Après la fermeture de la porte l’alarme de température est
désactivée pendant l’intervalle de temps programmé.

doA Retard alarme porte ouverte: (0÷255 min) Retard entre la détection de la condition de porte ouverte et sa signalisation.

tbA Désamorçage avertisseur et relais alarme: n = Avertisseur et relais sont indépendants. y = Avertisseur et relais sont désamorcés tous les deux par les touches.

nPS Nombre maximum d’interventions du pressostat: (0÷15 min) Il établit le nombre de mises en marche que le
pressostat doit effectuer dans l’intervalle de temps “did” pour déclencher l’alarme.

ot Étalonnage sonde thermostat: (-12÷12°C; -21÷21°F) il permet d'étalonner la sonde thermostat.

oE Étalonnage sonde évaporateur: (-12÷12°C; -21÷21°F) il permet d'étalonner la sonde évaporateur.

P2P Présence sonde 2: n: sonde absente, dégivrage à temps. y: sonde présente, dégivrage à température.

odc Contrôle porte ouverte: Il établit l’état du compresseur et des ventilateurs lorsque la porte est ouverte: no = Ventilateurs et
compresseur fonctionnent normalement; Fan = Ventilateurs OFF; CPr = Compresseur OFF; F_C = Compresseur et ventilateurs OFF.

did Retard alarme entrée numérique: (0÷255 min) Lorsque l’entrée numérique est programmée comme entrée pressostat, ce paramètre établit l’intervalle de temps pendant lequel un
nombre “nPS” de démarrages doit se produire pour déclencher l’alarme. Si l’entrée est programmée comme alarme externe, il établit le temps après lequel l’alarme est signalé.

LdE Retard extinction lumière après la fermeture de la porte: (0÷255 s) Il établit le temps d’allumage de la lumière après la fermeture de la porte.

Adr Adresse sérielle RS485: (1÷247) Elle identifie l’instrument lorsque celui-ci est inséré dans un système de contrôle ou de monitorage comme le XJ500.

rEL Version logiciel: (à lecture seule)

Ptb Table paramètres: (à lecture seule) servant à identifier la séquence des paramètres programmée en usine.

4. ENTRÉES NUMÉRIQUES

Le panneau électronique MIR90 a deux entrées numériques (contact non alimenté). La première est programmée comme micro-interrup-
teur porte, tandis que la deuxième est programmée comme pressostat.

ENTRÉE 1: MICRO-INTERRUPTEUR PORTE

Il signale au dispositif que la porte de la chambre est ouverte. Quand on ouvre la porte, le fonctionnement du compresseur et des

21
ventilateurs dépend de la valeur du paramètre “odc”.
Après le temps “dOA”, l’alarme porte ouverte se déclenche et le message “dA” est affiché. Le rétablissement de l’alarme se produit auto-
matiquement dès que l’entrée numérique est désactivée. Les alarmes de température sont débranchées lorsque la porte est ouverte et après
sa fermeture pour l’intervalle de temps prévu par le paramètre “dot”.
La sortie ÉCLAIRAGE est activée lors de l’ouverture de la porte et pour le temps “Lde” après sa fermeture.

F ENTRÉE 2: PRESSOSTAT

Si, dans l’intervalle de temps établit par le paramètre “did”, on atteint un nombre d'interventions du pressostat égal au paramètre “nPS”,
l’alarme se déclenche. Le message “PAL” est affiché, le compresseur s’arrête et le réglage est interrompu. Pour rétablir le fonctionnement
normal, il faut débrancher l’instrument ou le mettre en STAND-BY en utilisant la touche ON/OFF.

5. LIGNE SÉRIELLE TTL

Le panneau électronique MIR90 a une ligne sérielle TTL lui permettant, à l’aide d’un module externe TTL/RS485 de se connecter à un
système de monitorage et de supervision. Le protocole de communication est le ModBUS-RTU.

6. SIGNALISATION ALARMES

Message - Modalité Cause Sorties

“EE” Clignote Anomalie des données Sortie alarme ON; Autres sorties inchangées

“P1” Clignote Sonde thermostat en panne Sortie alarme ON; Sortie compresseur suivant
paramètres “Con” et “CoF”

“P2” Alterné à la temp. chambre Sonde évapor. en panne Sortie alarme ON; Autres sorties inchangées;
Le dégivrage se termine à temps

“HA” Alterné à la temp. chambre Alarme températ. maximum Sortie alarme ON; Autres sorties inchangées

“LA” Alterné à la temp. chambre Alarme températ. minimum Sortie alarme ON; Autres sorties inchangées

“dA” Alterné à la temp. chambre Alarme porte ouverte Sortie alarme ON; Sorties suivant paramètre “odc”

“PAL” Alterné à la temp. chambre Alarme pressostat Sortie alarme ON; Toutes les sorties OFF

“noL” Allumé ou clignotant Alarme dialogue clavier – platine Toutes les sorties OFF

!!! Tout affichage ne figurant pas parmi ceux qui sont décrits dans le présent mode d’emploi indique une panne grave de la platine électronique.

7. SORTIE ALARME

Après la détection de l'alarme, l’affichage dure jusqu’à ce que la condition d’alarme se termine. Il est possible d’empêcher le désamorçage
de la sortie alarme en programmant la valeur de “n” pour le paramètre “tbA”. Dans ce cas-là, la sortie alarme reste activée pendant toute
la durée de la condition d’alarme.

MODALITÉ DE REMISE À ZÉRO DES ALARMES

L’alarme sonde “P1” se déclenche environ 30 secondes après le dérangement de la sonde; il se rétablit automatiquement 30 secondes
après la reprise régulière du fonctionnement de la sonde. Avant de remplacer la sonde, on conseille d’en contrôler les branchements.
Les alarmes de température “HA” et “LA” se rétablissent automatiquement dès que la température du thermostat redevient normale,
au démarrage d’un dégivrage ou à l’ouverture de la porte.
L’alarme porte ouverte “dA” se rétablit automatiquement lorsqu'on ferme la porte.
L’alarme pressostat “PAL” se rétablit manuellement, en débranchant l’instrument ou en le mettant en état de Stand By.

8. SCHÉMAS DE BRANCHEMENT
(3) NEUTRAL

(2) NEUTRAL

(1) NEUTRAL
(10) ON-OFF
(17) DEF-NC

(15) DEF NA
(16) DEF-C
(19) LIGHT

(9) PHASE
(7) PHASE

(6) COMP

(5) COMP
(14) FAN

AL +

AL -
-
Keyboard
+
Input1 (27)
Gnd (24)
Input2 (25)
Gnd (26)

Gnd (28)
Evap (29)

Gnd (30)
Room (31)

22
9. VALEURS IMPLICITES DES PARAMÈTRES

Dégivr. AIR Dég. GAZ CHAUD Dég. ÉLECTRIQUE


Label Description Champ de réglage Niveau H-A M-N B-K M-N B-K

RÉGLAGE
Set Point de consigne LS ÷ US Pr 1 --- --- --- --- --- F
HY Différentiel SET (principal) 0,1 ÷ 25,5 °C/°F Pr 1 2 2 2 2 2
LS Point de consigne minimum -50,0 °C/°F ÷ Set Pr 1 5 -5 -25 -5 -25
US Point de consigne maximum Set ÷ 110,0 °C/°F Pr 1 15 5 -18 5 -18
OdS Retard démarrage sorties lors de la mise en marche 0 ÷ 255 min Pr 1 0 0 0 0 0
AC Retard empêchant des démarrages rapprochés du compress. 0 ÷ 30 min Pr 2 2 2 2 2 2
Con Temps compr.ON avec sonde en panne 0 ÷ 255 min Pr 2 0 0 0 0 0
CoF Temps compr. OFF avec sonde en panne 0 ÷ 255 min Pr 2 0 0 0 0 0
SONDES ET AFFICHAGES
CF Affichage celsius/fahrenheit °C ÷ °F Pr 2 °C °C °C °C °C
rES Résolution (°C) entier, décimal in ÷ de Pr 2 In In In In In
DÉGIVRAGE
tdF Type de dégivrage rE, rt, in Pr 1 rE In In rE rE
EdF Mod.dégivr.:horaire,interv.,Smart-defrost in ÷ Sd Pr 2 Sd Sd Sd Sd Sd
dtE Temp. fin dégivrage -50,0 ÷ +110,0 °C/°F Pr 1 110 20 20 30 30
IdF Intervalle dégivrage 1 ÷ 120 h Pr 1 3 3 3 3 3
MdF Délai dégivrage 0 ÷ 255 min Pr 1 20 20 20 30 30
dFd Affichage pendant le dégivr. rt, it, Set, dEF, dEG Pr 2 rt rt rt rt rt
dAd Retard affich.temp.après dégivr. 0 ÷ 255 min Pr 2 0 0 0 0 0
Fdt Temps égouttement 0 ÷ 60 min Pr 1 0 2 2 2 2
VENTILATEURS
FnC Mod. fonctionn.ventilateurs C_n, C_y, O_n, O_y Pr 1 O_y O_n O_n O_n O_n
Fnd Retard vent. après dégivrage 0 ÷ 255 min Pr 1 0 3 3 3 3
FSt Tempér. arrêt ventil. -50,0 ÷ +110,0 °C/°F Pr 1 40 40 40 40 40
ALARMES
ALC Config.alarmes: relatives ou absolues rE ÷ Ab Pr 2 rE rE rE rE rE
ALU Alarme temp.maximum -50,0 ÷ +110,0 °C/°F Pr 2 5 5 5 5 5
ALL Alarme temp. minimum -50,0 ÷ +110,0 °C/°F Pr 2 5 5 5 5 5
AFH Différ.point de consigne alarmes et ventil. 0,1 ÷ 25,5 °C; 1 ÷ 25 °F Pr 2 2 2 2 2 2
ALd Retard alarme temp. (fonct.norm.) 0 ÷ 255 min Pr 2 0 0 0 0 0
dAo Retard alarme lors de l’allumage 0 ÷ 24 h Pr 1 3 3 4 3 4
EdA Retard alarme à fin dégivrage 0 ÷ 255 min Pr 2 60 60 60 60 60
dot Excl. alarme ouvert. porte 0 ÷ 255 min Pr 2 60 60 60 60 60
doA Retard alarme porte ouverte 0 ÷ 255 min Pr 2 10 10 10 10 10
tbA Désamorçage relais alarme n÷y Pr 2 y y y y y
nPS N° démarr. pressostat (temps did) 0 ÷ 15 Pr 2 10 10 10 10 10
ENTRÉES ANALOGIQUES
ot Étalonnage sonde 1 -12,0 ÷ +12,0 °C/°F Pr 2 0 0 0 0 0
oE Étalonnage sonde 2 -12,0 ÷ +12,0 °C/°F Pr 2 0 0 0 0 0
P2P Présence sonde 2 n÷y Pr 1 n y y y y
ENTRÉES NUMÉRIQUES
odc Contr.porte ouv.: vent. et compr. no, Fan, CPr, F_C Pr 2 F_C F_C F_C F_C F_C
did Interv.comptage entrée numér. 1 0 ÷ 255 min Pr 2 60 60 60 60 60
LdE Retard extinc.lum.après débranchement 0 ÷ 255 min Pr 2 0 0 0 0 0
AUTRES
Adr Adresse 1 RS485 0 ÷ 247 Pr 1 1 1 1 1 1
rEL Version logiciel (à lecture seule) --- Pr 2 --- --- --- --- ---
Ptb Table paramètres --- Pr 2 --- --- --- --- ---

10. DONNÉES GÉNÉRALES

Le panneau électronique MIR90 a deux entrées de sonde NTC pour thermostatation et fin dégivrage et deux entrées numériques non ali-
mentées pour les fonctions de micro-interrupteur porte et de pressostat. Les conditions d’alarme sont signalées par une sortie 0-12V/20mA.

23
1. COMANDI DA FRONTALE

SET : Visualizzazione del SET POINT: premendo e rilasciando il tasto si accede alla visualizzazione del set point.
Modifica del SET POINT: premendo per tre secondi il tasto si visualizza e si accede al modo variazione set point: il led
Set lampeggia. Per modificare il valore agire sui tasti e .
Eseguite le modifiche, è possibile memorizzare il nuovo valore sia premendo SET (lo strumento ritorna a visualizzare la
temperatura), sia attendendo il timeout di uscita dalla programmazione (15s).

I UP : In modo programmazione o in “Menù Funzioni” scorre i codici dei parametri o incrementa il valore della
variabile visualizzata. Tenendolo premuto si avrà un incremento veloce.
Sbrinamento manuale: tenendolo premuto per 5s avvia il ciclo di sbrinamento.

DOWN : In modo programmazione o in “Menu Funzioni” scorre i codici dei parametri o decrementa il valore della variabile
visualizzata. Tenendolo premuto si avrà un decremento veloce.

LUCE : Attiva e disattiva la luce.

ON/OFF : Attiva e disattiva lo stand-by della scheda.

COMBINAZIONI DI TASTI

+ Premuti e rilasciati visualizzano il valore delle sonde.

+ Premuti per 3 s permettono l’accesso al Menu parametri Pr1 o Pr2.

+ Uscita programmazione e ritorno visualizzazione temperatura cella.

FUNZIONI DEI LED

Sulla tastiera esistono una serie di punti luminosi che svolgono un’azione di monitoraggio dei carichi controllati dallo strumento. La fun-
zione di ogni LED è data dalla tabella seguente:

LED MODALITÀ FUNZIONE

ACCESO Compressore attivo

LAMPEGGIANTE Ritardo antipendolazione attivo

ACCESO Ventilatore attivo

LAMPEGGIANTE Sgocciolamento attivo

ACCESO Sbrinamento attivo

LAMPEGGIANTE In corso tempo di sgocciolamento

ACCESO • Segnalazione ALLARME


• In “Pr2” indica che il parametro è presente anche in “Pr1”

ACCESO Uscita ausiliaria ON

LAMPEGGIANTE E’ visualizzato il set point ed è modificabile

ACCESO E’ visualizzato il set point

ACCESO Lo strumento è in Stand By

2. PROGRAMMAZIONE PARAMETRI

I parametri che gestiscono il funzionamento della centralina vengono suddivisi su 2 distinti livelli. Al primo livello (Pr1) si trovano i parametri
di maggiore utilizzo, al secondo livello (Pr2) ci sono invece quelli che più raramente necessitano di modifica.

PROCEDURA ACCESSO A “Pr1”

1 Premere per 3 sec. i tasti + : apparirà il codice del primo parametro.


2 Per spostarsi all’interno del menù utilizzare i tasti o .
3 Per selezionare la funzione che interessa premere il tasto .

PROCEDURA ACCESSO A “Pr2”

Per accedere ai parametri contenuti in “Pr2” è necessario immettere una password.

24
1 Entrare nel Menù Utente Pr1.
2 Selezionare con o la label Pr2 e premere .
3 Agire con o per impostare sul digit lampeggiante la cifra corretta.
4 Confermare tale cifra con la pressione di : il digit cesserà di lampeggiare mantenendo la visualizzazione della cifra
scelta e il lampeggio si sposterà sul digit successivo.
5 Ripetere le operazioni 3 e 4 per i restanti digit.
6 Se la password è corretta con la pressione di sull’ultimo digit si ottiene l’accesso a “Pr2” altrimenti la procedura di
immissione password ripartirà da principio.
I
Ü Se non si premono tasti entro 15 secondi lo strumento torna a visualizzare la temperatura della camera. Û
L a PA S S W O R D d e v e e s s e r e r i c h i e s t a a l f o r n i t o r e .

NOTA: ogni parametro presente in “Pr2” può essere tolto o immesso in “Pr1” (livello utente) premendo i tasti + .
Quando si è in “Pr2” se un parametro è presente in “Pr1” il LED appare illuminato.

MODIFICA VALORE PARAMETRO

Ogni Parametro è identificato da un opportuno codice alfanumerico.


Per modificare il valore del parametro agire come segue:
1 Accedere al modo programmazione (Pr1 o Pr2).
2 Scorrere con i tasti o la lista parametri fino a visualizzare il codice del parametro che interessa.
3 Premere il tasto per visualizzarne il valore.
4 Con o modificarne il valore.
5 Premere per memorizzare il nuovo valore e passare al codice del parametro successivo.

Uscita: Premere + , quando si visualizza una label, o attendere 15s senza premere alcun tasto.

NOTA: il nuovo valore impostato viene memorizzato anche quando si esce dalla procedura di modifica parametro senza
aver premuto il tasto .

3. LISTA DEI PARAMETRI

HY Isteresi: (0,1÷25,5°C; 1÷25°F) Differenziale di intervento del set point, sempre positivo. Il compressore si attiva quando la
temperatura aumenta fino a raggiungere il set point + Hy, per poi spegnersi quando viene riportata al valore del set point.

LS Set point minimo: (-50°C÷SET; -58°F÷SET) Fissa il valore minimo impostabile per il set point.

US Set point massimo: (SET÷110°C; SET÷230°F) Fissa il valore massimo impostabile per il set point.

OdS Ritardo attivazione uscite all’accensione: (0÷255min) All’accensione l’attivazione di qualsiasi carico è inibita per il tempo impostato.

AC Ritardo antipendolazione: (0÷30min) intervallo minimo tra lo spegnimento del compressore e la successiva riaccensione.

Con Tempo compressore ON con sonda guasta: (0÷255min) tempo in cui il compressore rimane attivo nel caso di guasto
sonda. Con “Con”=0 il compressore rimane sempre spento. Nota: Se “Con”=0 e “CoF”=0 il compressore rimane spento.

CoF Tempo compressore OFF con sonda guasta: (0÷255min) tempo in cui il compressore rimane spento in caso di guasto
sonda. Con “CoF”=0 il compressore rimane sempre acceso.

CF Unità misura temperatura: °C = Celsius; °F = Fahrenheit.

rES Risoluzione (per °C): (in = 1°C; de= 0,1°C) permette la visualizzazione col punto decimale.

tdF Tipo di sbrinamento: rE = a resistenza (Compressore OFF). rt = sbrinamento termostatato. Lo sbrinamento ha la durata di
Mdf e le resistenze durante questo tempo termostatano sul valore di temperatura dtE. in = a gas caldo (Compressore ON).

EdF Modalità di sbrinamento: in = sbrinamento a intervalli di tempo fissi impostati da parametri idF. sd = sbrinamento Smart
Defrost. L’intervallo di sbrinamento idF viene conteggiato solo a compressore acceso.

dtE Temperatura fine sbrinamento: (-50,0÷110,0°C; -58÷230°F) fissa la temperatura rilevata dalla sonda di evaporatore, che
determina la fine dello sbrinamento.

IdF Intervallo fra i cicli di sbrinamento: (1÷120 ore) Determina l’intervallo tra l’inizio di due cicli di sbrinamento.

MdF Durata (MAX) sbrinamento: (0÷255min) Con P2P = n (Sonda evaporatore assente) stabilisce la durata dello sbrinamento,
con P2P = y (Sonda evaporatore presente) diventa durata massima di sbrinamento.

dFd Temperatura visualizzata durante lo sbrinamento: rt = temperatura reale. it = temperatura di inizio sbrinamento.
Set = set point. dEF = etichetta “dEF”. dEG = etichetta “dEg”.

dAd Ritardo MAX visualizzazione dopo lo sbrinamento: (0÷255min) Stabilisce il tempo massimo tra la fine dello
sbrinamento e la ripresa della visualizzazione della temperatura reale della cella.

25
Fdt Tempo sgocciolamento: (0÷60min) Intervallo di tempo tra il raggiungimento della temperatura di fine sbrinamento e la
ripresa del funzionamento normale del regolatore.

FnC Modalità funzionamento ventilatori: C-n: In parallelo al compressore, spente in sbrinamento. C-y: In parallelo al
compressore, accese in sbrinamento. O-n: In continuo, spente in sbrinamento. O-y: In continuo, accese in sbrinamento.

Fnd Ritardo attivazione ventilatori dopo sbrinamento: (0÷255min) tempo che intercorre tra il termine dello sbrinamento e
la ripresa del funzionamento normale dei ventilatori.
I
FSt Temperatura blocco ventole: (-50÷110°C; -58÷230°F) Se la temperatura rilevata dalla sonda di evaporatore è maggiore di
“FSt” le ventole vengono fermate. Serve per immettere aria sufficientemente fredda nella cella.

ALC Configurazione allarmi set point: (rE=relativi al set point; Ab=assoluti) stabilisce se gli allarmi di temperatura sono relativi
al set point o sono delle temperature assolute.

ALU Allarme MASSIMA temperatura: (se ALC = rE: 0÷50°C ;0÷90°F. Se ALC = Ab: ALL÷110°C; ALL÷230°F) al raggiungimento
di tale temperatura viene attivato l’allarme, eventualmente dopo il tempo di ritardo ALd.

ALL Allarme minima temperatura: (se ALC = rE: 0÷50°C ;0÷90°F. Se ALC = Ab: ALU÷-50°C; ALU÷-58°F) al raggiungimento
di tale temperatura viene attivato l’allarme, eventualmente dopo il tempo di ritardo ALd.

AFH Differenziale Set Allarme e ventole: (0,1 ÷ 25,5 °C; 1÷25°F). Indica il differenziale per la regolazione delle ventole e gli
allarmi di temperatura.

ALd Ritardo allarme temperatura: (0÷255 min) intervallo di tempo tra la rilevazione di un segnale di allarme temperatura e la sua segnalazione.

dAo Ritardo allarme temperatura all’accensione: (da 0min÷23h 50min) Intervallo di tempo tra la rilevazione della
condizione di al-larme temperatura all’accensione dello strumento e la sua segnalazione.

EdA Ritardo allarme temperatura a fine sbrinamento: (0÷255min) Intervallo di tempo che intercorre tra la rilevazione della
condizione di al-larme temperatura alla fine dello sbrinamento e la sua segnalazione

dot Esclusione allarme temperatura a porta aperta: (0÷255min) dopo la chiusura della porta l’allarme di temperatura viene
escluso per il tempo impostato in questo parametro.

doA Ritardo allarme porta aperta: (0÷255min) ritardo tra la rilevazione della condizione di porta aperta e la sua segnalazione.

tbA Tacitazione buzzer e relè allarme: n = Buzzer e relay sono indipendenti. y = Buzzer e relay vengono tacitati entrambi da tasto.

nPS Numero MAX interventi pressostato: (0÷15) Stabilisce il numero di interventi che deve effettuare il pressostato
nell’intervallo di tempo di parametro “did” per generare l’allarme.

ot Calibrazione sonda termostato: (-12÷12°C; -21÷21°F) permette di tarare la sonda termostato.

oE Calibrazione sonda evaporatore: (-12÷12°C; -21÷21°F) permette di tarare la sonda evaporatore.

P2P Presenza sonda 2: n: sonda assente, sbrinamento a tempo. y: sonda presente, sbrinamento a temperatura.

odc Controllo per porta aperta: Determina lo stato del compressore e delle ventole a porta aperta: no = Ventole e
compressore regolano normalmente. Fan = Ventole OFF. CPr = Compressore OFF. F_C = Compressore e ventole OFF.

did Ritardo allarme ingresso digitale: (0÷255 min.) Quando l’ingresso digitale è configurato come ingresso pressostato
stabilisce l’intervallo di tempo nel quale si devono verificare un numero “nPS” di interventi per generare l’allarme.
Se l’ingresso è impostato come allarme esterno stabilisce il tempo dopo il quale segnala l’allarme.

LdE Ritardo spegnimento luce dopo chiusura porta: (0÷255sec.) Determina il tempo di accensione della luce dopo la chiusura della porta.

Adr Indirizzo seriale RS485: (1÷247) Identifica lo strumento quando viene inserito in un sistema di controllo o monitoraggio come l’XJ500.

rEL Release software: (sola lettura).

Ptb Tabella parametri: (sola lettura) serve ad identificare la mappa parametri impostata in fabbrica.

4. INGRESSI DIGITALI

La MIR90 è dotata di due ingressi digitali (contatto pulito). Il primo ingresso digitale è configurato come microporta, il secondo invece
come pressostato.

INGRESSO 1: MICROPORTA

Segnala al dispositivo l’apertura della porta della cella. Quando la porta viene aperta il compressore e le ventole regolano in base al
valore del parametro “odc” :
Dopo il tempo impostato nel parametro “dOA”, viene attivato l’allarme di porta aperta e visualizzato a display il messaggio “dA”.

26
Il ripristino dell’allarme è automatico appena l’ingresso digitale viene disattivato. Gli allarmi di temperatura sono esclusi a porta aperta e
dopo la chiusura per un tempo di parametro “dot”.
L’uscita LUCE si attiva all’apertura della porta e per il tempo “Lde” dopo la chiusura.

INGRESSO 2: PRESSOSTATO

Se nell’ intervallo di tempo stabilito da parametro “did” viene raggiunto un numero di interventi pressostato pari al parametro “nPS” scat-
ta l’allarme. Viene visualizzato il messaggio “PAL”, viene spento il compressore e sospesa la regolazione. Per riprendere il funzionamen-
to normale si deve spegnere lo strumento o metterlo in stato di STAND BY con il tasto ON/OFF. I

5. LINEA SERIALE TTL

La MIR90 ha una linea seriale TTL che le permette tramite un modulo esterno TTL/RS485 di interfacciarsi con un sistema di monitoraggio
e supervisione. Il protocollo di comunicazione è il ModBUS-RTU.

6. SEGNALAZIONE ALLARMI

Messaggio - Modalità Causa Uscite

“EE” Lampeggiante Anomalia nei dati Uscita allarme ON; Altre uscite non modificate

“P1” Lampeggiante Sonda termostato guasta Uscita allarme ON; Uscita compressore secondo
parametri “Con” e “CoF”

“P2” Alternato a Sonda evaporatore guasta Uscita allarme ON; Altre uscite non modificate;
temperatura cella Lo sbrinamento termina a tempo

“HA” Alternato a Allarme di massima temperatura Uscita allarme ON; Altre uscite non modificate
temperatura cella

“LA” Alternato a Allarme di minima temperatura Uscita allarme ON; Altre uscite non modificate
temperatura cella

“dA” Alternato a Allarme porta aperta Uscita allarme ON; Uscite secondo parametro “odc”
temperatura cella

“PAL” Alternato a Allarme pressostato Uscita allarme ON; Tutte le uscite OFF
temperatura cella

“noL” Fisso o lampeggiante Allarme comunicazione Tastiera – Scheda Tutte le uscite OFF

!!! Tutte le segnalazioni diverse da quelle specificate nel presente manuale indicano un guasto grave alla centralina elettronica.

7. USCITA ALLARME

Una volta rilevato l’allarme la segnalazione a display permane finché la condizione di allarme non è rientrata. É possibile inibire la disattivazione
dell uscita allarme, impostando il parametro “tbA” a “n” in questo caso l’uscita allarme rimane attiva finché dura la condizione di allarme.

MODALITA’ DI RIENTRO DEGLI ALLARMI

L’allarme sonda “P1” scatta dopo circa 30 secondi dal guasto della sonda; rientra automaticamente 30 secondi dopo che la sonda
riprende a funzionare regolarmente. Prima di sostituire la sonda si consiglia di verificarne le connessioni.
Gli allarmi di temperatura “HA” e “LA” rientrano automaticamente non appena la temperatura del termostato rientra nella nor-
malità, alla partenza di uno sbrinamento o all’apertura della porta.
L’ allarme di porta aperta “dA” rientra automaticamente alla chiusura della porta.
L’ allarme pressostato “PAL” è a ripristino manuale spegnendo lo strumento o ponendolo in stato di Stand by.

8. SCHEMI DI COLLEGAMENTO
(3) NEUTRAL

(2) NEUTRAL

(1) NEUTRAL
(10) ON-OFF
(17) DEF-NC

(15) DEF NA
(16) DEF-C
(19) LIGHT

(9) PHASE
(7) PHASE

(6) COMP

(5) COMP
(14) FAN

AL +

AL -
-
Keyboard
+
Input1 (27)
Gnd (24)
Input2 (25)
Gnd (26)

Gnd (28)
Evap (29)

Gnd (30)
Room (31)

27
9. VALORI DI DEFAULT DEI PARAMETRI

sbr. ARIA sbr. GAS CALDO sbr. ELETTRICO


Label Descrizione Campo di regolazione livello H-A M-N B-K M-N B-K

REGOLAZIONE
Set Set point LS ÷ US Pr 1 --- --- --- --- ---
HY Differenziale SET (principale) 0,1 ÷ 25,5 °C/°F Pr 1 2 2 2 2 2
I LS Set minimo -50,0 °C/°F ÷ Set Pr 1 5 -5 -25 -5 -25
US Set massimo Set ÷ 110,0 °C/°F Pr 1 15 5 -18 5 -18
OdS Ritardo attivazione uscite al power-on 0 ÷ 255 min Pr 1 0 0 0 0 0
AC Ritardo antipendolazione 0 ÷ 30 min Pr 2 2 2 2 2 2
Con Tempo di On del compressore per sonda guasta 0 ÷ 255 min Pr 2 0 0 0 0 0
CoF Tempo di OFF del compressore per sonda guasta 0 ÷ 255 min Pr 2 0 0 0 0 0
SONDE E VISUALIZZAZIONI
CF Visualizzazione celsius/fahrenheit °C ÷ °F Pr 2 °C °C °C °C °C
rES Risoluzione (per °C): intero, decimale in ÷ de Pr 2 In In In In In
SBRINAMENTO
tdF Tipo di sbrinamento rE, rt, in Pr 1 rE In In rE rE
EdF Modalità sbrinamento: orario, intervallo, Smart-def in ÷ Sd Pr 2 Sd Sd Sd Sd Sd
dtE Temperatura fine sbrinamento -50,0 ÷ +110,0 °C/°F Pr 1 110 20 20 30 30
IdF Intervallo sbrinamento 1 ÷ 120 h Pr 1 3 3 3 3 3
MdF Time_out sbrinamento 0 ÷ 255 min Pr 1 20 20 20 30 30
dFd Visualizzazione durante lo sbrinamento rt, it, Set, dEF, dEG Pr 2 rt rt rt rt rt
dAd Ritardo visualizz. temperatura dopo sbrinamento 0 ÷ 255 min Pr 2 0 0 0 0 0
Fdt Tempo sgocciolamento 0 ÷ 60 min Pr 1 0 2 2 2 2
VENTOLE
FnC Modalità funzionamento ventilatori C_n, C_y, O_n, O_y Pr 1 O_y O_n O_n O_n O_n
Fnd Ritardo ventilatori dopo sbrinamento 0 ÷ 255 min Pr 1 0 3 3 3 3
FSt Temperatura blocco ventole -50,0 ÷ +110,0 °C/°F Pr 1 40 40 40 40 40
ALLARMI
ALC Configurazione allarmi: relativi o assoluti rE ÷ Ab Pr 2 rE rE rE rE rE
ALU Allarme di massima -50,0 ÷ +110,0 °C/°F Pr 2 5 5 5 5 5
ALL Allarme di minima -50,0 ÷ +110,0 °C/°F Pr 2 5 5 5 5 5
AFH Differenziale set allarme e ventole 0,1 ÷ 25,5 °C; 1 ÷ 25 °F Pr 2 2 2 2 2 2
ALd Ritardo allarme temperatura (in funz. normale) 0 ÷ 255 min Pr 2 0 0 0 0 0
dAo Ritardo allarme al Power-on 0 ÷ 24 h Pr 1 3 3 4 3 4
EdA Ritardo allarme a fine sbrinamento 0 ÷ 255 min Pr 2 60 60 60 60 60
dot Esclusione allarme apertura porta 0 ÷ 255 min Pr 2 60 60 60 60 60
doA Ritardo allarme porta aperta 0 ÷ 255 min Pr 2 10 10 10 10 10
tbA Tacitazione relè allarme n÷y Pr 2 y y y y y
nPS Numero interventi pressostato (tempo did) 0 ÷ 15 Pr 2 10 10 10 10 10
INGRESSI ANALOGICI
ot Calibrazione sonda 1 -12,0 ÷ +12,0 °C/°F Pr 2 0 0 0 0 0
oE Calibrazione sonda 2 -12,0 ÷ +12,0 °C/°F Pr 2 0 0 0 0 0
P2P Presenza sonda 2 n÷y Pr 1 n y y y y
INGRESSI DIGITALI
odc Controllo per porta aperta: ventole e compressore no, Fan, CPr, F_C Pr 2 F_C F_C F_C F_C F_C
did Intervallo conteggio ingresso digitale 1 0 ÷ 255 min Pr 2 60 60 60 60 60
LdE Ritardo spegnimento luce dopo disattivazione 0 ÷ 255 min Pr 2 0 0 0 0 0
ALTRO
Adr Indirizzo 1 RS485 0 ÷ 247 Pr 1 1 1 1 1 1
rEL Codice release firmware (solo lettura) --- Pr 2 --- --- --- --- ---
Ptb Tabella parametri --- Pr 2 --- --- --- --- ---

10. DATI GENERALI

La MIR90 ha due ingressi da sonda NTC per termostatazione e fine sbrinamento e due ingressi digitali liberi da tensione per la funzio-
ne di microporta e di pressostato. Le condizioni di allarme sono segnalate da un’uscita 0-12V/20mA.

28
1. “€‚‹ ˆ   „ ‰ € ‹œž

SET : Показ контрольной точки: Кратковременным нажатием этой кнопки.


Изменение контрольной точки: При нажатием кнопки на 3 секунды, выводится значение контрольной точки и
включается режим ее изменения: мигает индикатор у кнопки "SET". Чтобы ее изменить, используйте кнопки
" "и" ". Затем новое значение можно запомнить либо нажатием кнопки "SET" (прибор вернется в режим
показа температуры) либо подождав около 15 сек.

îëüøå : В режиме программирования или в "Меню функций" показывает коды параметров или увеличивает значение
выведенной переменной. Держите кнопку нажатой для ускорения изменения.
ó÷íàß îòòàéêà: при нажатии на 5 сек запускается цикл оттайки.
RUS
Œåíüøå : В режиме программирования или в "Меню функций" показывает коды параметров или уменьшает значение
выведенной переменной. Держите нажатой для ускорения изменения.

‘âåò : Включает и выключает освещение в камере.

ON/OFF : Включает и отключает для прибора режим "сон".

ŠŽŒˆ€–ˆˆ ŠŽŽŠ

+ Кратковременным нажатием этих кнопок, выводится показание датчика.

+ При нажатии на 3 сек выводится меню параметров PR1 или Pr2.

+ Прекращает программирование и опять выводит температуру камеры.

ˆ‘Ž‹œ‡Ž‚€ˆ ˆ„ˆŠ€’ސނ

ˆíäèêàòîð åæèì ”óíêöèß

горит Компрессор включен

мигает Включена задержка от короткого цикла

горит Вентиляторы включены

мигает Идет слив талой воды

горит Оттайка включена

мигает Идет отсчет времени слива талой воды

горит • Сигнал тревоги


• В "Pr2" показывает, что параметр также есть и в "Pr1"

горит Вспомогательный выход включен

мигает Выведена контрольная точка и она может быть изменена

горит Выведена контрольная точка

горит Прибор находится в режиме "сон"

2. Žƒ€ŒŒˆŽ‚€ˆ €€Œ ’Ž‚

Параметры, которые управляют работой электронной панелью управления, разделены на 2 разных уровня. Более часто используемые
параметры находятся в первом уровне (Pr1), в то время как во втором уровне (Pr2) находятся параметры изменяемые очень редко.

Ž– „“€ „Ž‘’“€ Š "Pr1"

1 Нажать кнопки " " +" " на 3 сек: будет выведен код первого параметра.
2 Используя кнопки " "и" " переходить по меню.
3 Выбрать требуемую функцию, нажав кнопку " ".

Ž– „“€ „Ž‘’“€ Š "Pr2"

Для входа в параметры уровня "Pr2" необходимо ввести пароль.


1 Войти в меню уровня "Pr1".
2 Используя кнопки " "и" " перейти к метке "Pr2" и нажать " ".
3 Используя кнопки " "и" " набрать нужный номер мерцающей цифры.
4 Ввести набранный номер, нажав кнопку " ": набранная цифра перестанет мигать, введенное значение будет на дисплее,
станет мигать следующая цифра.
5 Повторить операции 3 и 4 для остальных цифр пароля.
6 Если пароль введен верно, то после ввода последней цифры произойдет переход к параметрам уровня "Pr2", иначе процедура
ввода пароля повторяется с начала.

29
Ü ñëè íè îäíà èç êíîïîê íå áûëà íàæàòà â òå÷åíèå 15 ñåê, ïðèáîð âîçâðàùàåòñß â ðåæèì ïîêàçà òåìïåðàòóðû â êàìåðå. Û
‡ í à ÷ å í è å ï à ð î ë ß Вы може те пол у чить у св оего По с т авщика (Продавца)

Любой параметр уровня "Pr2" может быть удален или перемещен на уровень "Pr1" нажатием кнопок
" "+" ". Если Вы находитесь на уровне "Pr2" и текущий параметр присутствует на уровне "Pr1", то горит
индикатор " ".

ˆ‡Œ  ˆ ‡€— ˆŸ €€Œ ’€

RUS Каждый параметр имеет свой код из букв (латинских) и цифр.


Для изменения его значения поступайте следующим образом:
1 Войдите в режим параметров (Pr1 или Pr2).
2 Пролистайте список параметров с помощью кнопок " " или " ", пока не будет выведен код требуемого параметра.
3 Нажмите кнопку " " для вывода значения параметра.
4 С помощью кнопок " " или " " измените его значение.
5 Нажмите кнопку " " для записи нового значения и перехода к следующему параметру.

‚ûõîä Нажмите кнопки " "+" ", если выведена метка параметра, или подождите 15 сек, не нажимая никаких кнопок.

‡íà÷åíèå параметра будет запомнено, даже если процедура его изменения была завершена без нажатия кнопки " ".

3. ‘ˆ‘ŽŠ €€Œ ’Ž‚

SET Šîíòðîëüíàß òî÷êà: (LS...US) температура, которую должен поддерживать агрегат.

HY „èôôåðåíöèàë (ãèñòåðåçèñ):(0,1...25,5°С) Всегда положителен.Компрессор включается,когда температура превысит значение контрольной


точки (Set) плюс дифференциал Hy.Компрессор отключится,когда температура достигнет значения контрольной точки.

LS Œèíèìóì êîíòðîëüíîé òî÷êè: (-50°С...Set) Задание минимально возможного значения контрольной точки.

US Œàêñèìóì êîíòðîëüíîé òî÷êè: (Set...+110°С) Задание максимально возможного значения контрольной точки.

OdS ‡àäåðæêà âûâîäîâ ïðè çàïóñêå: (0...255 мин) При запуске включение любой нагрузки зарерживается на заданное время.

AC ‡àäåðæêà ïðîòèâ "êîðîòêîãî öèêëà": (0...30 мин) Минимальный интервал времени между остановкой компрессора и его
последующим запуском.

Con àáîòà êîìïðåññîðà ïðè ñáîå äàò÷èêà: (0...255 мин) Время, в течение которого на компрессор подано напряжение в
случае поломки датчика., При Con = 0 компрессор выключен всегда.

CoF ‘òîßíêà êîìïðåññîðà ïðè ñáîå äàò÷èêà: (0...255 мин) Время, в течение которого на компрессор не подано напряжение
в случае поломки датчика., При CoF = 0 компрессор включен всегда. Если и Con=0 и CoF=0, то компрессор выключен.

CF äèíèöû èçìåðåíèß òåìïåðàòóðû: (°C/°F) C - шкала Цельсия, F - шкала Фаренгейта.

rES ’î÷íîñòü ïîêàçàíèé (â °‘): (in=1°C, de=0,1°C) Позволяет выводить значения с десятичной точкой.

tdF ‘ïîñîá (òèï) îòòàéêè (îïðåäåëßåòñß êîíñòðóêöèåé àãðåãàòà !): rE - нагревателями (ТЭНами) (Компрессор выключен).
rt - время оттайки с контролем температуры. Длительность оттайки равна значению параметра MdF и в течение этого времени
нагреватели управляются термостатом так, что температура батареи испарителя была равной значению параметра dtE.
in - горячим хладагентом от компрессора (Компрессор включен).

EdF €ëãîðèòì îòòàéêè: in - оттайка происходит через фиксированные интервалы времени, заданные параметром idF. rt - время
оттайки с контролем температуры. Длительность оттайки равна значению параметра MdF и в течение этого времени нагреватели
управляются термостатом так, что температура батареи испарителя поддерживается равной значению параметра dtE. Sd - хитрая
оттайка: интервал времени IdF отсчитывается только во время работы компрессора.

dtE ’åìïåðàòóðà ïðåêðàùåíèß îòòàéêè: (-50,0°С...110°С) Температура, измеренная датчиком батареи испарителя, при
достижении которой прекращается оттайка.

IdF ˆíòåðâàë ìåæäó öèêëàìè îòòàéêè: (0...120 час) Интервал времени между началами двух последовательных циклов оттайки.

MdF Œàêñèìàëüíàß äëèòåëüíîñòü îòòàéêè: (0...255 мин) Если датчик батареи испарителя отсутствует (параметр P2P=n), то
это длительность оттайки; если этот датчик имеется (параметр P2P=y), то это максимальная длительность оттайки.

dFd —òî âûâîäèòñß íà äèñïëåé âî âðåìß îòòàéêè: rt - реальная температура. it - температура на момент начала оттайки.
Set - значение контрольной точки. dEF - метка "dEF", dEG - метка "dEG".

dAd ‡àäåðæêà âûâîäà ïîñëå îòòàéêè: (0...255 мин) Установка максимального времени между окончанием оттайки и
возобновлением вывода температуры в камере.

Fdt ‚ðåìß ñëèâà:(0...60 мин) Интервал времени между достижением температуры окончания оттайки и возобновлением нормальной работы.

FnC åæèì ðàáîòû âåíòèëßòîðîâ: C_n: одновременно с компрессором/во время оттайки - отключен. C_y: одновременно с
компрессором/во время оттайки - включен. O_n: непрерывная работа/во время оттайки - отключен. O_y: непрерывная работа/во
время оттайки - включен.

Fnd ‡àäåðæêà âêëþ÷åíèß âåíòèëßòîðîâ ïîñëå îòòàéêè: (0...255 мин) Интервал времени между окончанием оттайки и

30
возобновлением нормальной работы вентиляторов.

FSt ’åìïåðàòóðà îñòàíîâêè âåíòèëßòîðîâ: (-50,0°С...110°С) Если температура от датчика батареи испарителя, превышает
значение FSt, то вентиляторы останавливаются.

ALC €ëãîðèòì îòñ÷åòà äëß òðåâîãè: (rE=от контрольной точки; Ab=абсолютное значение, т.е. от нуля) определяет, будут ли
температурные тревоги задаваться в виде отклонений от контрольной точки или в виде абсолютный значений.

ALU ’ðåâîãà ïî âûñîêîé òåìïåðàòóðå: (Если ALC=rE:то 0...50°С. Если ALC=Ab то ALL...110°С) Когда достигается эта
температура, то с задержкой, заданной параметром ALd, включается тревога по высокой температуре.

ALL ’ðåâîãà ïî íèçêîé òåìïåðàòóðå: (Если ALC=rE:то 0...50°С. Если ALC=Ab то -50°С...ALU) Когда достигается эта RUS
температура, то с задержкой, заданной параметром ALd, включается тревога по низкой температуре.

AFH „èôôåðåíöèàë òðåâîãè è âåíòèëßòîðîâ: (0,1...25,5°С) Указывает дифференнциал (гистерезис) для управления
вентиляторами и температурными тревогами.

ALd ‡àäåðæêà òåìïåðàòóðíîé òðåâîãè: (0...255 мин) Интервал времени между обнаружением условий температурной
тревоги и подачей сигнала тревоги.

dAo ‡àäåðæêà òåìïåðàòóðíîé òðåâîãè ïðè çàïóñêå: (0 мин ...23 час 50 мин) Интервал времени между обнаружением
условий температурной тревоги после включения и подачей сигнала тревоги.

EdA ‡àäåðæêà òåìïåðàòóðíîé òðåâîãè ïîñëå îêîí÷àíèß îòòàéêè: (0...255 мин) Интервал времени между обнаружением
условий температурной тревоги после окончания оттайки и подачей сигнала тревоги.

dot åðåíîñ òðåâîãè ïðè îòêðûâàíèè äâåðè: (0...255 мин) Это время, которое определяет длительность переноса тревоги
после закрытия двери.

doA ’ðåâîãà ïðè îòêðûòîé äâåðè: (0...255 мин) Интервал времени между обнаружением тревоги по открытой двери и подачей
сигнала тревоги.

tbA ‚ûêëþ÷åíèå çóììåðà è ðåëå òðåâîãè: n - зуммер и реле независимы. y - зуммер и реле отключается одновременно.

nPS Œàêñèìàëüíîå ÷èñëî ñðàáàòûâàíèé ïðåññîñòàòà: (0...15) Устанавливает, как много раз может сработать прессостат в
течение интервала времени, заданного параметром did, прежде чем будет подан сигнал тревоги.

ot Šàëèáðîâêà äàò÷èêà òåìïåðàòóðû â êàìåðå: (-12...+12°С) Позволяет установить постоянный сдвиг показаний
датчика температуры (калибровать его).

oE Šàëèáðîâêà äàò÷èêà òåìïåðàòóðû áàòàðåè èñïàðèòåëß: (-12...+12°С) Позволяет установить постоянный сдвиг
показаний датчика температуры (калибровать его).

P2P àëè÷èå âòîðîãî äàò÷èêà òåìïåðàòóðû: n - датчика нет, оттайка прекращается по времени. y - датчик присутствует,
оттайка контролируется по температуре

odc àáîòà ñ îòêðûòîé äâåðüþ: Определяет состояние компрессора и вентиляторов при открытой двери: no - Вентиляторы и
компрессор работают как обычно. Fan - Вентиляторы отключены. CPr - Компрессор отключен. F_C - Компрессор и
вентиляторы отключены.

did ˆíòåðâàë êîíòðîëß ñðàáàòûâàíèé ïðåññîñòàòà: (0...255 мин) Когда к цифровому входу подключен прессостат, этот
параметр определяет интервал времени в течение которого подсчитывается число его срабатываний и если оно превысит
значение nPS то подается сигнал тревоги.

LdE ‡àäåðæêà âûêëþ÷åíèß îñâåùåíèß ïîñëå çàðûâàíèß äâåðè: (0...255 сек) Устанавливает, сколько времени еще горит
свет в камере после закрывания двери.

Adr ‘åòåâîé àäðåñ RS485: (1...247) Позволяет идентифицировать прибор при подключении его к сети управления и
мониторинга подобной XJ500.

rEL ‚åðñèß ïðîãðàììû: (только для чтения).

Ptb ’àáëèöà ïàðàìåòðîâ: (только для чтения) Позволяет посмотреть значения параметров, установленных на заводе-изготовителе.

4. –ˆ”Ž‚› ‚•Ž„›

Электронная панель управления MIR90 имеет два цифровых входа (контакта). Первый цифровой вход действует как микровыключатель
в двери, а второй для подключения прессостата.

‚•Ž„ 1: ŒˆŠŽ‚›Š‹ž—€’ ‹œ „‚ ˆ

Он подает сигнал прибору о том, что дверь открыта. При открытой двери компрессор и вентиляторы работают в соответствии со
значением параметра "odc".
После интервала времени, заданного параметром "dOA", включается сигнал тревоги открытой двери и выводится сообщение "dA". Тревога
автоматически снимается (перезапускается) как только цифровой выход дезактивируется. Температурные тревоги отключены когда дверь
открыта и после ее закрытия в течение интервала времени, заданного параметром "dot".
Выход на освещение камеры включается при открывании двери и остается активным в течение интервала времени "Lde" после ее закрытия.

31
‚•Ž„ 2:  ‘‘Ž‘’€’

Если в течение интервала времни, заданного параметром "did", прессостат срабатывает число раз равное значению параметра "nPS", то
включается тревога. Выводится сообщение "PAL", компрессор останавливается и управление агрегатом прерывается. Для восстановления
нормальной работы отключите прибор или переведите его в режим сна, надав кнопку ON/OFF (предварительно выяснив причину частого
срабатывания прессостата и устранив ее).

5. €Ž’€ ‚ ‘ ’ˆ

Благодаря серийной линии (сети) TTL, прибор MIR90 может быть подключен к системе наблюдения и мониторинга с помощью внешнего
модуля TTL/RS485. Коммуникационный протокол связи в такой сети - ModBUS-RTU.
RUS
6. ‘ˆƒ€‹› ’ ‚Žƒˆ

Šîä åæèì ðè÷èíà ‚ûõîäû (’ðåâîãà âñåãäà âêëþ÷åíà !)

EE ìèãàåò Сбой в данных Без изменений

P1 ìèãàåò Датчик температуры камеры Выход на компрессор согласно Con и CoF

P2 ìèãàåò Датчика температуры в/о Без изменений. Оттайка по времени.

HA ïîî÷åðåäíî Высокая температура Без изменений.

LA ñ Низкая температура Без изменений.

dA òåìïåðàòóðîé Открытая дверь Без изменений. Выходы согласно “odc”

PAL â êàìåðå Прессостат давления Все выходы отключены.

noL ãîðèò èëè ìèãàåò Сообщение между клавиатурой и панелью Все выходы отключены.

!!! ‚ñå ñèãíàëû òðåâîãè, íå âêëþ÷åííûå â íàñòîßùåå ðóêîâîäñòâî ïîêàçûâàþò ñåðüåçíóþ íåèñïðàâíîñü ýëåêòðîííîé ïàíåëè.

7. ‚›•Ž„› ’ ‚Žƒˆ

При возникновении тревоги, на дисплей выводится сигнал тревоги и сохраняется, пока эти условия тревоги не прекратятся. Возможно
подавление отключения выхода тревоги установкой параметра "tbA" на значение "dS"; в этом случае выход тревоги остается активным все
время тревоги.

Ž’Š‹ž— ˆ ’ ‚Žƒˆ

Тревога датчика "P1" включается через 30 сек после сбоя датчика (разрыв цепи, короткое замыкание, показания датчика выходят за
допустимые пределы); она автоматически прекращается через 30 сек после возврата датчика к нормальной работе. Перед заменой датчика
проверьте его соединения.
Температурные сигналы тревоги "HA" и "LA" автоматически останавливаются как только температура возвращается к нормальным
значениям, включается оттайки или открывается дверь.
Сигнал тревоги открытия двери "dA" автоматически прекращается при закрытии двери.
Сигнал тревоги прессостата "PAL" можно снять (перезапустить) вручную, отключив панель управления или переключив ее в состояние сна.

8. Ž„Š‹ž— ˆ
(14) ‚E’ˆ‹Ÿ’.

(3) HE‰’A‹œ

(2) HE‰’A‹œ

(1) HE‰’A‹œ
(10) ‚Š‹-Ž’Š
(17) DEF-NC

(15) DEF NA

(6) ŠŽŒ.

(5) ŠŽŒ.
(16) DEF-C
(19) CBET

(9) ôaça
(7) ôaça

‚›XO„ AL +
CˆƒA‹A
T ‚ŽƒˆAL -
- öèôðîâûå âxîäû äaò÷èêè òåìïåðàòóðû
A AHE‹œ
+
‚XŽ„2 (25)
Gnd (24)

Gnd (26)

Gnd (28)

Gnd (30)
‚XŽ„1 (27)

aòað. (29)

Šaìåða (31)

32
9. ‘’€„€’› ‡€— ˆŸ €€Œ ’Ž‚

Œåòêà Žïèñàíèå ïàðàìåòðà „èàïàçîí “ðî- сушка оттайка газом оттайка ТЭНом
çíà÷åíèé âåíü H-A M-N B-K M-N B-K

Set Контрольная точка LS ÷ US Pr1 — — — — —


HY Дифференциал (гистерезис) 0,1...25,5°C Pr1 2 2 2 2 2
LS Минимум контрольной точки -50,0°C...SEt Pr1 5 -5 -25 -5 -25
US Максимум контрольной точки SEt...+110°C Pr1 15 5 -18 5 -18
OdS Задержка выходов при запуске 0...255 мин Pr1 0 0 0 0 0
AC Задержка от "короткого цикла" 0...30 мин Pr2 2 2 2 2 2
Con Работа компр. при сбое датчика 0...255 мин Pr2 0 0 0 0 0 RUS
CoF Стоянка компр. при сбое датчика 0...255 мин Pr2 0 0 0 0 0
ДАТЧИКИ
CF Шкала температур (°C/°F) °C, °F Pr2 °C °C °C °C °C
rES Показания: целые/десятичные In, dE Pr2 In In In In In
ОТТАЙКА
tdF Тип (способ) оттайки rE, rt, In Pr1 rE In In rE rE
EdF Алгоритм оттайки In, Sd Pr2 Sd Sd Sd Sd Sd
dtE Температура остановки оттайки -50,0°C...+110°C Pr1 110 20 20 30 30
IdF Интервал (шаг) оттайки 1...99 час Pr1 3 3 3 3 3
MdF Максим. длительность оттайки 0...255 мин Pr1 20 20 20 30 30
dFd Вывод на дисплей при оттайке rt, It, Set, dEF, dEG Pr2 rt rt rt rt rt
dAd Задержка показа после оттайки 0...255 мин Pr2 0 0 0 0 0
Fdt Время на слив талой воды 0...60 мин Pr1 0 2 2 2 2
ВЕНТИЛЯТОРЫ
FnC Режим работы C_n, C_y, O_n, O_y Pr1 O_y O_n O_n O_n O_n
Fnd Задержка запуска после оттайки 0...255 мин Pr1 0 3 3 3 3
FSt Температура остановки -50,0°C...+110°C Pr1 40 40 40 40 40
ТРЕВОГА
ALC Отчет: относительно Set, абсол. rE, Ab Pr2 rE rE rE rE rE
ALU По высокой температуре -50,0°C...+110°C Pr2 5 5 5 5 5
ALL По низкой температуре -50,0°C...+110°C Pr2 5 5 5 5 5
AFH Дифференц. тревоги и вентилят. 0,1°C...25,5°C Pr2 2 2 2 2 2
ALd Задержка температурной тревоги 0...255 мин Pr2 0 0 0 0 0
dAO Задержка тревоги при запуске 0...24 час Pr1 3 3 4 3 4
EdA Задержка тревоги после оттайки 0...255 мин Pr2 60 60 60 60 60
dot Перенос тревоги из-за двери 0...255 мин Pr2 60 60 60 60 60
doA Тревога при открытой двери 0...255 мин Pr2 10 10 10 10 10
tbA Выключение зуммера и тревоги n, y Pr2 y y y y y
nPS Макс. число сбоев прессостата 0...15 Pr2 10 10 10 10 10
АНАЛОГОВЫЕ ВХОДЫ
ot Калибровка 1 датчика -12°C...+12°C Pr2 0 0 0 0 0
oE Калибровка 2 датчика -12°C...+12°C Pr2 0 0 0 0 0
P2P Наличие 2-го датчика n, y Pr1 n y y y y
ЦИФРОВЫЕ ВХОДЫ
odc Откр. дверь: вентилят. и компрес. no, Fan, CPr, F_C Pr2 F_C F_C F_C F_C F_C
did Интервал подсчета прессостата 0...255 мин Pr2 60 60 60 60 60
LdE Свет горит после закрытия двери 0...255 сек Pr2 0 0 0 0 0
ДРУГИЕ
Adr Адрес в сети (RS485) 0...247 Pr1 1 1 1 1 1
rEL Версия прибора (для чтения) — Pr2 — — — — —
Ptb Таблица параметров (для чтения) — Pr2 — — — — —

10. ށ™ Žˆ‘€ˆ

Электронная панель управления MIR90 имеет два входа для датчиков, которые контролируют температуру в камере и оттайку. Она также
имеет два свободных цифровых входа без напряжения для подключения микроконтакта двери и прессостата.
Условия тревоги передаются на выход 0...12 В / 20 mA.

33
4MANUALE15

You might also like