Chapter 19A:: All-Air Systems: Single Zone and Single Duct
Chapter 19A:: All-Air Systems: Single Zone and Single Duct
                           Introduction
– Large number of all-air system variations to fit different requirements for
  comfort in buildings, process applications and also for special
  applications requiring close control of temperature and humidity (clean
  rooms, computer rooms, hospital operating rooms, …)
– An all-air system provides complete sensible and latent cooling,
  preheating, and humidification capacity to the building supply air
– No additional cooling or dehumidification required at zone (but heating
  may be required)
                                                                                        1
                                                                                        6/2/22
- Operating principle of CAV and VAV under peak design cooling and heating conditions
- Operation of CAV under part load
- Operation of VAV under part load
                                                                                            2
                                                                                               6/2/22
                                          Supply
                                            fan
                                                                                                   3
                                                                                               6/2/22
                                                       Thermostat
              9 Recycled
                air                                                 Space        Qspace,cool
Outdoor                                                                5
                                                                        Supply
air                                 3            4                      air
     0        1        2
                                                           Supply
                  PH       CC           HC                 fan
  Fig. 19.1 Schematic diagram of the basic single zone HVAC system with
  some of the major energy equipment. The important psychrometric state
  points (0-9) and the return, supply, exhaust and ventilation flows are also
  shown.
                                                                                       8
                                                                                                   4
                                                                                                                 6/2/22
     A space is to be maintained at 78° F (25.5° C) dry-bulb temperature and 50% RH. The total
     cooling load (heat to be removed from the space to maintain comfort) is 120,000 Btu/h (35
     kW) of which 70% is sensible heat. Ventilation air at 1000 ft3/min (472 L/s) is required on
     the peak day when the outdoor conditions are 95° F (35° C) and 55% RH. The room supply
     air temperature is 20o F (11.1o C) below that of the room set point temperature (a typical
     value for commercial buildings at peak operating conditions). What are the space air supply
     flow rate and the cooling coil rating (total cooling capacity and SHR)?
   Fig. 19.3. The air-conditioning process diagram on a psychrometric chart. The state
   points correspond to those in Fig. 19.1 while the numerical values apply to Example
   19.1.
                                                                                                            10
                                                                                                                     5
                                                                                                                             6/2/22
          Solution
      1. Locate specified points 0 and 6 on the psychometric chart
1. Locate specified points 0 and 6 on the psychometric chart
      2. Locate supply air point 5. The conditioned space inlet and outlet conditions lie on line
2. Locate    supply
        3-6 in        air Condition
               Fig. 19.3.  point 5. The6 (78°  conditioned
                                                  F, 50% humidity)space isinlet  and known
                                                                            already   outlet from
                                                                                              conditions       lie on line
                                                                                                     the problem
   3-6 in  Fig. 19.3.
        statement.  TheCondition    6 (78°
                         slope of line    3-6 isF,determined
                                                      50% humidity) from theis inner
                                                                                already
                                                                                     scaleknown
                                                                                            of the from     the problem
                                                                                                    protractor    as
   statement.
        shown forTheSHR
                      slope   of line
                          = 0.7.  The 3-6       is determined
                                         location    of point 3 isfrom       the inner scale
                                                                       the intersection   of the of
                                                                                                  linethe
                                                                                                        3-6protractor
                                                                                                              and a     as
   shown    for SHR
        vertical        = 0.7.
                 line drawn     The
                             from      ,3 = 58° F.of
                                   Tdblocation         Thispoint    3 is thetointersection
                                                              corresponds       a RH value ofof80%.the line 3-6 and a
   vertical
    3. Findline
              the drawn   from airflow58°
                   space supply               rate.F.TheThis   corresponds
                                                            first               to a RHisvalue of 80%.
                                                                  law for this process
3. Find the space supply airflow   Q!            = m!
                                             rate. The
                                      space,cool      a ( h  - h
                                                           6 first)
                                                                 5 law for this process is
                                                                                                             (19.6)
        The enthalpies can be read from Fig. 13.6: h5 = h3 = 23 Btu / lba , h6 = 30 Btu / lba
                                                                                              (19.6)
        The air mass flow rate is thus
    The enthalpies can 120,000
                           be read Btu/h
                                      from Fig. 13.6:
                   m! a =                     = 17,140 lba /h (3770 ft 3 /min)
    The air mass flow     rate-is23)thus
                          (30         Btu/lba
     4. Locate mixed air point 1. The end points 0 and 9(6) are known, and so the inverse
        relation between mass flows and line segment lengths [Eq. (13.29)] is used to locate
        point 1 (see sec. 13.6.2). The outdoor air mass flow is
4. Locate mixed air point 1. The end 3 points 0 and 9(6) are known, and so the inverse
   relation between mass         V!0 60,000     ft / segment
                                                      h
                       m! a,,0 =flows= and line3
                                                                lengths
                                                        = 4,170 lb a /h
                                                                        [Eq. (13.29)] is used to locate
   point 1 (see sec. 13.6.2). The v0   14.4 ft   / lb
                                      outdoor aira mass flow is
         The ratio of air mass flows is (4,170/17,140) = 0.243. Therefore, point 1 is located 24.3
         percent of the distance from point 6 along line segment 6-0. The properties at point 1
         can be read from the psychrometric chart. They are Tdb = 82° F, Twb = 69° F, and moist
     The air
         ratio  of airhmass
             enthalpy        flows
                       a =33.4 Btu/lbisa. (4,170/17,140) = 0.243. Therefore, point 1 is located 24.3
     percent of the distance from point 6 along line segment 6-0. The properties at point 1
          This   allows point
          Alternatively,
                               1use
                                 to the
                                    be fixed
     can be   read fromwethecan         weighted
                              psychrometric      average
                                              chart. Theyrule
                                                            areto calculate
                                                                        82°the
                                                                            F, mixed air
                                                                                     69°humidity
                                                                                         F, and moist
                                                                                                 11
          ratio:
     air enthalpy ha =33.4 Btu/lba.
               W1 =[0.243 × 0.0197 lbw/lba + (1 – 0.243) × 0.0103 lbw/lba] = 0.01216 lbw/lba
     Alternatively, we can use the weighted average rule to calculate the mixed air humidity
     ratio:Similarly, assuming constant specific heats, the mixed air dry-bulb temperature is:
               T
               db,1  =[0.243 × 95° F + (1 – 0.243) ×78° F)] = 82° F (consistent with the chart
          W1 =[0.243
             reading).
                       × 0.0197 lbw/lba + (1 – 0.243) × 0.0103 lbw/lba] = 0.01216 lbw/lba
     Similarly, assuming constant specific heats, the mixed air dry-bulb temperature is:
          This allows point 1 to be fixed on the psychrometric chart.
         Tdb,1 =[0.243 × 95° F + (1 – 0.243) ×78° F)] = 82° F (consistent with the chart
      5. reading).
          Determine cooling coil load. Line 1-3 can now be constructed by connecting points 1
         and 3. The slope of the resulting line is transposed to the protractor, and the coil's
         sensible heat ratio SHRcc can be read off as 0.55. The corresponding relative humidity is
         80% and the humidity ratio is 0.0084 lbw/lba. Finally, the coil heat removal rate (or “coil
     Thiscooling
          allowsload”)
                  point can
                         1 tobebefound.
                                   fixed on the psychrometric chart.
5. Determine cooling coil load. Line 1-3 can now be constructed by connecting points 1
    and 3. The slope of the resulting line is transposed to the protractor, and the coil's
    sensible heat ratio SHRcc can be read off as 0.55. The corresponding relative humidity is
    80% and the humidity ratio is 0.0084 lbw/lba. Finally, the coil heat removal rate (or “coil
    cooling load”) can be found.
   Q! cc ,tot = m! a ( h1 - h3 ) = 17,140 lba /h ´ (33.4 - 23) Btu/lba
            = 178,300 Btu/h or 14.9 Tons (52.2 kW)
12
                                                                                                                                 6
                                                                                                            6/2/22
        For a pressure rise in a fan of 250 Pa (1.0 in-WG), the temperature rise with a 100%
efficient fan is 0.2o C (0.36° F).
For a 70% efficient fan, the temperature rise is 0.29o C (0.52° F).
        In commercial building HVAC systems, a pressure rise of several inches water gauge is common.
The resulting temperature rise can be 1.0 to 2.0o C (2 to 3° F) and must be considered when cooling coils
and central cooling plants are sized.
13
                                               6(7,8,9)
                                        4(5)
 Fig. 19.7 Process diagram for single duct CAV system to air-condition a single space with
 high latent loads. The state points correspond to Fig. 19.1 while the numerical values apply
 to Example 19.3. Note that the supply fan reheat is neglected.
14
                                                                                                                7
                                                                                                              6/2/22
        Example 19.1 illustrated the fact that the CAV system for a one-
zone space can be designed so as to only require cooling energy (without
any heating) under peak load conditions. This is not always possible. One
important instance where heating is needed even under peak load
conditions arises when the peak space latent load fraction is high such as
in hot and humid locations. This solved example will discuss why this
occurs, and illustrate how to analyze such cases.
                          !                 3
             =0.55, V 0= 1000 ft /min
             Cooling      coil leaving        air conditions:    Tdb,3 = 58°F,     and fand
                                                                          Tdb,3 = 58°F,      f3 = 0.8.
                                                                                        3 = 0.8.
                      Cooling       coil leaving      air conditions:
                                                      o              f
             SpaceSpace condition      Tdb,6 =T78
                                condition              F 78
                                                  db,7 =  andF and
                                                             o  = 0.5. 7 = 0.5.
          Lookup values: specific volume v0 = 14.4 ft3/lb, humidity ratio W0 = 0.0197 lbw/lba,
    h0 = 44.52 Btu/lba, W3 = 0.0082 lbw/lba, h3 = 22.85 Btu/lba, W7 = 0.0103 lbw/lba, h7 = 30 Btu/lba.
15
      SOLUTION
     1. Locate specified points 0, 3 and 7 on the psychrometric chart (see Fig. 19.7) which are
        specified from the problem statement.
     2. Locate supply air point 5.
        As previously, the slope of line 5-7 can be determined from the inner scale of the protractor.
        The location of point 6 is the intersection of the line drawn from point 7 with a slope equal
        to 0.5 and the horizontal line drawn from point 3. This is found to be
        Tdb,5 = 69.1o F and h5 = 25.5 Btu/lba and W5 = 0.0082 lbw /lba .
     3. Determine space supply airflow rate:
        The enthalpy balance equation (Eq. 19.7) is re-arranged to yield:
                                Q! space,cool
                                      120,000 Btu/h
                       m! a =    =                     = 26,667 lba / h
                         h7 - h5 (30 - 25.5) Btu/lba
     4. Determine mixed air condition point 1.
        The outdoor air mass flow is the same as before:    m! a,0 = 4,170 lba / h
      The ratio of air mass flows is (4,170/26,667) = 0.156. Therefore, point 1 is located 15.6 percent
      of the distance from point 7 along line segment 7-0.
16
                                                                                                                  8
                                                                                                               6/2/22
             Note:
             -substantial increase in supply air flow rate
             (from 17,140 lba/h to 26,667 lba/h
17
0                1        2          3          4                    5
                     PH        CC          HC
                                                           Steam
Fig. 19.5a Schematic diagram of the complete single-duct single zone CAV system
with ducted return. The preheater and the steam humidifier would operate during
winter while the cooling coil and the reheat coil would be active when cooling
loads are to be met.
18
                                                                                                                   9
                                                                                             6/2/22
       Consider the CAV system analyzed under peak cooling load condition in
                                                              o
previous
  Example example..
            19.1. The same space is to be maintained at 72 F and 50% RH. The
total heating load of the space is 150,000 Btu/hr with a sensible heat ratio of 0.8.
The outdoor design condition is 40 0F dry-bulb and 40% RH. The same amount of
ventilation air (1000 ft3 /min) is needed. Design the necessary heating and
humidification equipment assuming saturated steam at 200 0F is available and that
the supply air flow rate is kept at the summer design peak value of 17,140 lba/h.
The supply air dry-bulb temperature should not exceed 105 0F.
      Assumptions: The location is at sea level. The duct heat transfer and the fan
           air temperature rise are ignored for simplicity.
                  !
      Given: ma = 17,140 lba /h , SHRspace = 0.80, Q" space,tot = 150,000 Btu/h,
                                                                                 3
              outdoor air conditions: Tdb,o = 40 oF, fo =0.40, V" 0= 1000 ft /min,
              space condition T7 = 72 F and f7 = 0.5, Tdb,6 < 105 F.
                                         o                              o
              •
      Find: m steam , Q" ph and Q" hc
      Lookup values: specific volume v0 = 12.65 ft3/lb, humidity ratio W0 = 0.0021
           lbw/lba, W7 = 0.0084 lbw/lba, h7 = 26.4 Btu/lba, specific heat of air ca =
           0.24 Btu/lba oF, and enthalpy of steam hsteam= 1146 Btu/lbw.
19
Fig. 19.5
 (a) Schematic
     diagram
 (b) Psychrometric
    process
    diagram
                                                                                                10
                                                                                                     6/2/22
    SOLUTION
    We will illustrate the use of the graphical procedure as previously.
    1. Locate specified points 0 and 7 on the psychrometric chart (see Fig. 19.5b) which are
       specified from the problem statement.
    2. Determine outdoor air mass flow rate.
       The outdoor air mass flow is given by:
                              V!0 1,000 ft 3 / min´ 60 min/h
                   m! a,0 =      =                           = 4,743 lba / h
                              v0       12.65 ft 3 / lba
       Note that this mass flow rate is over 13% higher than the previous case which is
       attributed to the difference in the specific volumes of outdoor air between summer and
       winter conditions.
    3. Locate mixed air condition point 1.
       The inverse relation between mass flows and line segment lengths (Eq. 13.34) is used to
       locate 1. The ratio of air mass flows is (4,743/17,140) = 0.277. The dry-bulb
       temperature and humidity ratios can be calculated from the chart or just as simply using
       the weighted average rule; e.g.,
         The corresponding moist-air enthalpy is read from the psychrometric chart, h1 = 22.4
         Btu/lba.
                                                                                                21
1.
4. Determine supply air condition point 5.
   As previously, the slope of line 5-7 is equal to the inner scale of the protractor
   corresponding to SHRspace = 0.80. We determine enthalpy h5 of the specified supply air
   mass flow rate as follows:
                Q!                           150,000 Btu/h
      h5 = h7 + space,heat = 26.4 Btu/ lba +                = 35.15 Btu/ lba
                   m! a                       17,140 lba /h
   The intersection of the enthalpy line corresponding to 35.15 Btu/lba and the line 6-7
   yields a point whose corresponding dry-bulb value is Tdb,5 = 102o F (this is acceptable
   since it is lower than the stipulated maximum value of 105o F). The corresponding
   humidity ratio W5 = 0.0096 lbw/lba.
5.
2. Determine the amount of steam needed
   This is easily calculated since the entering and leaving humidity ratio of the air streams
   are known:
     "
    msteam = m
             ! a (W5 - W4 ) = 17,140 lba /h ´ (0.0096 - 0.00665) lb w /lb a = 50.56 lbw /h
     We draw a line from point 6 parallel to the outer scale of the protractor corresponding to
    1,146 ( since enthalpy of steam hsteam= 1,146 Btu/lbw.) which intersects the horizontal
    line from point 1 at point 2. This is determined to be: Tdb,2= 100.8o F and h2 = 31.6
    Btu/lba.
                                                                                                    6/2/22
     The intersection of the enthalpy line corresponding to 35.15 Btu/lba and the line 6-7
     yields a point whose corresponding dry-bulb value is Tdb,5 = 102o F (this is acceptable
     since it is lower than the stipulated maximum value of 105o F). The corresponding
     humidity ratio W5 = 0.0096 lbw/lba.
      We draw a line from point 6 parallel to the outer scale of the protractor corresponding to
     1,146 ( since enthalpy of steam hsteam= 1,146 Btu/lbw.) which intersects the horizontal
     line from point 1 at point 2. This is determined to be: Tdb,2= 100.8o F and h2 = 31.6
     Btu/lba.
23
Alternative system:
Not requiring a
steam boiler
Fig. 19.8
(a) Schematic of the winter
heating and humidification
system with injection of
liquid water. The cooling
coil is not shown.
                                                                                                       12
                                                                                                        6/2/22
25
                                              Return fan
            8                    7            (optional)   6
      Exhaust                   Return
      air                       air
                                                           Thermostat
                  9 Recycled
                    air                                                 Space        Qspace,cool
     Outdoor                                                               5
                                                                            Supply
     air                                 3           4                      air
          0        1        2
                                                               Supply
                       PH       CC           HC                fan
26
                                                                                                           13
                                                                                                                                           6/2/22
           SOLUTION
       1. Calculate outdoor air mass flow rate
                       V! 1, 000 ft 3 / min´ 60 min/h
               m! a,0 = 0 =                           = 4,320 lba / h
                       v0          13.9 ft 3 / lba
       2. Calculate supply air temperature point 5 using sensible heat balance
          since the room thermostatic control is based on dry-bulb temperature.
                    Using sensible heat balance equation:
               "              "
              Q space, sen = ma .ca .(Tdb,6 - Tdb,5 )
                                   "
                                  Q space, sen                               49,000 Btu/h
              Tdb,5 = Tdb,6 -          "
                                                        = 78 o F -                                      = 66.10 F
                    ma ´ c a                                         17,140 lba /h × 0.24 Btu/lba . o F
    3. Verify indoor comfort.
       Calculate humidity ratio of air leaving room using a latent heat balance
  SOLUTION
                                           "                "
              or Tdb,1 = 78.5 0F
  This corresponds  to humidity
        Similarly the  an indoor isrelative  humidity
                                     determined       of ==45%,
                                                  as: W    0.0103which
                                                                  lbw/lbalong with a dry-bulb
                                                        1                a
  temperature of 78 0F is satisfactory for indoor human comfort.
 4. 5. Determine
    Calculate mixedcooling coil loads
                    air condition point(process
                                         1.     1-3)
              Using the simplified, we have
       A common assumption which simplifies the analysis is to assume a constant specific heat
           - Sensible load:
       of moist air ca. The energy balance equation can then be expressed as:
                              !                         !       !          !
                             ma ,1 Tdb,1 = (m a ,1 - mo )Tdb,7 + mo Tdb,o
                   17,140 lba /h×Tdb,1 =(17,140-4,320) lba /h ×78 o F+4,320 lba /h × 80 o F
       or
       or Tdb,1 = 78.5 0F
       Similarly the humidity is determined as: W1 = 0.0103 lbw/lba
       -      Latent load:
               !
               Qcc,lat =17,140 lba /h × 1075 Btu/lb w × (0.0103-0.0082) lbw /lba =38,931 Btu/h =3.24 Tons
                                  !
                                  Q cc ,tot = 84,329 + 38,931 = 123,260 Btu/h =10.27 Tons
              - Total load:
                                                                                                                    Note:
6.2.       Determine reheat coil load
           Using the sensible heat equation:                                                                        Energy penalty
                       !                                                                                            due to reheat
                      Qrc,tot =17,140 lb/h×0.24 Btu/lba . o F ×(66.1-58) o F =73,320
                                                                               33,320Btu/h
                                                                                      Btu/h
 Reheat load:
28
                                                                                                                                              14
                                                                                                 6/2/22
(VAV) Systems
                                                                                 VAV box
                                                                              with reheat coil
                                                          PC      CC
 Fig. 19.10 (a) Terminal reheat configuration for a VAV system for a single zone ducted
 return system for a small laboratory
29
             Example
  Consider previous    19.5 where a CAV system was assumed. We will solve this
                     example
  problem for the case when a VAV system is used.
30
                                                                                                    15
                                                                                                                                        6/2/22
     SOLUTION
       1. Calculate supply air mass flow rate with supply air temperature
    1. assumed to be equal to that of the cooling coil set temperature. From a
       sensible heat balance equation :
                                 !
                  !          Qspace,sen  49,000 Btu/h
              ma =             =                                   =10,208.3 lba /h
             (Tdb,6 -Tdb,5 )×ca (78-58) o F × 0.24 Btu/(lba . o F)
    2. Verify indoor comfort, calculate humidity ratio of air leaving room using
       a latent heat balance
                                     !
                   Q                                    70,000 Btu/h×(1-0.7)
        W6 = W5 + ! space ,lat =0.0082 lb w /lb a +                                  =0.0101 lb w /lb a
       SOLUTION m a ´ h                             10,208.3 lb a /h×1075 Btu/lb w
                              v
         1. Calculate supply air mass flow rate with supply air temperature
      1. assumed to be equal to that of the cooling coil set temperature.      From a
                                                                      fo =49%, which along
         sensible heat balance equation :
This condition corresponds to an indoor relative humidity of
with a dry-bulb  temperature
                    !
                                   of 75 0F which is within the indoor human comfort
          !        Qspace,sen                49,000 Btu/h
range. ma =                        =                                 =10,208.3 lba /h
               (Tdb,6 -Tdb,5 )×ca (78-58) o F × 0.24 Btu/(lba . o F)
      2. Verify indoor comfort, calculate humidity ratio of air leaving room using
         a latent heat
   3. Calculate         balance
                    mixed       air condition
                             !                           !       !               !
                            ma,1´! Tdb,1 = (ma,1 - mo ) ´ Tdb,7 + mo ´ Tdb,o                                                       31
                                         Q space ,lat                              70,000 Btu/h×(1-0.7)
              OrW6 = W5 +                 !
                                                        =0.0082 lb w /lb a +                                  =0.0101 lb w /lb a
                                         m a ´ hv                              10,208.3 lb a /h×1075 Btu/lb w
        10,208.3 lba /h × Tdry,1 = (10,208.3-4,320) lba /h × 78 o F+ 4,320lba /h × 80 o F
       or Tdb,1 = 78.85 0F                                       fo =49%, which along
       Similarlycorresponds
  This condition  the humidity to is
                                   andetermined   as: humidity
                                      indoor relative W1 = 0.0114
                                                               of lbw/lba
  with a dry-bulb temperature of 75 0F which is within the indoor human comfort
  range.
    4. Determine cooling coil loads
              Using the simplified equation, we have
      3.- Calculate
               Sensible load
                    mixed air condition
          !                      !                           !   !               !
                    ma,1´ Tdblb,1a=/h(m
      Qcc , sen = 10,208.3              ,1 - moBtu/(lb
                                      ×a0.24   ) ´ Tdb,7 a+. om o ´ Tdb ,o
                                                              F)×(78.85-58) o
                                                                              F=51,082 Btu/h =4.26 Tons (down from 7.03 T)
                      Or                   !
                                          Qcc,lat = 10,208.3 lba /h×1075 Btu/lb w ×(0.0114-0.0082)lb w /lba
      -
          Latent load:lba /h × Tdry,1 = (10,208.3-4,320) lba /h × 78 o F+ 4,320lba /h × 80 o F
            10,208.3           =35,116 Btu/h =2.93 Tons (down from 3.24 T)
                      or Tdb,1 = 78.85 0F
              - Similarly
                      Total
                          theload:
                              humidity is determined as: W1 = 0.0114 lbw/lba
          !
      Q cc,tot = 51,082 + 35,116 = 86,198 Btu/h =7.18 Tons (down from 10.27 T)
      4. Determine cooling coil loads
         Using the simplified equation, we have
                      -      Sensible load
                  !
              Qcc , sen = 10,208.3 lba /h × 0.24 Btu/(lba . o F)×(78.85-58) o F=51,082 Btu/h =4.26 Tons (down from 7.03 T)
                                               !
                                                                                                                For CAV = 7.03 T
                                              Qcc,lat = 10,208.3 lba /h×1075 Btu/lb w ×(0.0114-0.0082)lb w /lba
              -
                  Latent load:
                                                        =35,116 Btu/h =2.93 Tons (down from 3.24 T)
                                                                       For CAV = 3.24 T
                      -      Total load:
                  !
              Q cc,tot = 51,082 + 35,116 = 86,198 Btu/h =7.18 Tons (down from 10.27 T)
                                                                          For CAV =10.27 T
                  No reheat needed
                                                                                                                                   32
                                                                                                                                           16
                                                                                                       6/2/22
Comments:
   In the above example, the reduced airflow has eliminated the need for
   reheat but has somewhat compromised occupant comfort due to the
   slightly elevated humidity in the space (RH increased from 45% to
   49%).
33
     Supply
       air
    flowrate                                                                     Minimum air
                                                                                 flowrate
                                                                                 (~ 60% design)
                       Hot air               Reheat           Cold air
           100%                                                             100%
        Heating load                                                     Cooling load
Fig. 19.9 Modulation of room supply air flow for a single zone VAV system as space
loads vary over the year. Note the three modes of operation: (a), (b) and (c).
                                                                                                          17
                                                                                             6/2/22
                                                                   •   Small commercial
        + Simple to build and operate                              •   Strip malls
        + Lower initial cost                                       •   Elementary
                                                                   •   Small health clinic
        -   Higher energy costs during operation                   •   Auditoriums
Cons:
35
Single-zone VAV
                                                                   •   Small commercial
        + Simple to build (inexpensive) and operate                •   Strip malls with
                                                                       different types of
                                                                       stores
        -   Requires reheat if rooms with different conditioning   •   Small health clinic
            requirements since supply air cannot be reduced
Cons:
                                                                                                18
                                                                        6/2/22
                           Outcomes
• Understanding of the common all-air system types used for air
  distribution in buildings
• Understanding the operation of the basic CAV and VAV systems for
  single zone buildings
• Knowledge of air stream heating across fans
• Familiarity with different configurations of CAV and VAV systems
• Be able to analyze single zone CAV with reheat, CAV without reheat,
  and VAV under summer and winter design conditions
• Be able to analyze the performance of CAV and VAV under part-load
  operation
• Understanding of the various control issues and energy efficiency
  benefits of using VAV system
37
19