TECHNICAL DATA
DIESEL GENERATING SET
50HZ
500 KVA
Standard Features
• Compact structure with high-strength chassis; • Top lifting, Forklift bottom hole design, easy to
• Easy operation and maintenance, Low cost; transport;
• Excellent performance damping system; • Industrial muffler;
• Compliance with international electrical safety standards of • Noise reduction structure,Low noise;
electrical system; • Convenient power output interface;
• 8 hours base tank; • Deepsea Module for control system
• High-performance maintenance-free batteries with isolation • Customized design for user
switch
• 50℃Radiator;
Genset Technical Data
Output frequency 50 HZ
Rated speed 1500 Rpm
Prime power 500 KVA / 400 kW
Standby power 550 KVA / 440 kW
Rated voltage 380/220 V
Phase 3
Noise dB(A) @7m 85 (Max)
Fuel consumption of 100% load 101 Litres/h
Fuel consumption of 75% load 74.2 Litres/h
Dimension and Weight (Approximate)
Generating set model Open Type Silent Type
Length(L) (mm) 3900 4550
Width(W) (mm) 1300 1850
Height(H) (mm) 2300 2350
Dry weight (k g) 4250 5296
Tank capacity ( L ) 400 400
Page: 1/4
500 KVA
Engine Specifications
Engine manufacturer CUMMINS
Number of cylinders 6
Cylinder arrangement Vertical in-line
Cycle Four stroke
Aspiration Turbocharged and Aftercooled
Bore Stroke (mm mm) 130 x 163
Displacement (Liter) 13.0
Compression Ratio 17.0 : 1
Prime power/speed 450 KW / 1500rpm
Standby power/speed 470 KW / 1500rpm
Speed governor Electrical / Cummins PTM
Cooling system Jacket Water Aftercooled
Steady speed droop (%) 5%
Total lubrication system capacity (L) 45.2
Coolant capacity (L) 23.1
Fuel consumption at 100% load(Ltr/H) 101 (at 1500RPM)
Starter motor DC 24V
Alternator DC 24V
Alternator Specifications
Alternator Brand / Model STAMFORD
Rated output prime power 500 kVA
AVR Type SX440
Rated speed 1500 RPM
Rated frequency 50 Hz
Phase 3
Rated voltage 380/220 V
Exciter type Self excitation, Brushless
Power factor 0.8
Voltage adjust range ≥5%
Voltage regulation ± 1.0 %
Insulation grade H
Protection grade IP23
Winding Stator Double Layer Lap
Winding Pitch Two Third
Winding Leads 12
Waveform Distortion No Load < 1.5% Non Distorting Balanced Linear Load < 5.0%
Maximum Overspeed 2250 rev/min
Optional
Optional Alternator brand N/A
Optional Alternator model N/A
Rated output prime power N/A
Page: 2/4
500 KVA
Control System
Deepsea
Main Features
• AMF and ATS and communication and expansion function
• Designed to work with electronic or non-electronic or gas
engine simultaneously. (support many kinds of engines
ECU).
• Manual, Automatic, Test and remote control mode
selectable.
• Monitoring and measuring operational parameters of the
mains supply and genset.
• Indicating operation status, fault conditions, all
parameters and alarms
• Multiple protections and multiple parameters display.
• Includes 12 inputs and eight outputs. 8 inputs are
configurable and 4 outputs are configurable.
• Can be programmed using the front panel or by using the
PC software.
• Support twelve languages. The language was edited by
customer.
• Graded protection: pre-alarm, shutdown and electrical Protecting Functions
trip, flexible setting.
• Over frequency / under frequency
• The module can be pre-set for four operating modes and
• Over voltage / under voltage
protecting parameters.
• Over current
• The firmware can be updated automatically, so customer • Over speed /under speed
can have the latest version.
• Emergency stop
• Low oil pressure
• High water temperature
• Failure to start/Failure to stop
• Battery charger failure
• Comprehensive shutdown or warning on fault
condition
Page: 3/4