MR Chapter4appx
MR Chapter4appx
Market Rules
               Chapter 4
Grid Connection
 Requirements -
     Appendices
          Related Documents
            Library Record No.               Document Title                 Version
            MDP_RUL_0002                     Market Rules for the Ontario   88.0
                                             Electricity Market
Document Control
        Authorities
          Prepared by
          Market Rules
          Reviewed by
          Technical Panel
          Legal Affairs
          Approved by
          IESO Board
        Distribution List
          Name                Organization
          Table of Contents
                                                                                                  Table of Contents
                                                                                                                      4
          Appendix 4.1 – IESO-Controlled Grid Performance Standards ...................... 1
.................................................................................................................... 31
                                                                                                                                4
            Ref              Item                         Requirement
                             Transmission System
            1                Frequency variations         All equipment shall be capable of continuously operating in the range
                                                          between 59.5 Hz and 60.5 Hz.
            2                Voltage variations           Under normal conditions voltages are maintained within the range below.
                                                          Transmission Voltage:
                                                          Nominal (kV)                 500       230       115
                                                          Maximum Continuous (kV)      550       250*      127*
                                                          Minimum Continuous (kV)      490       220       113
                                                          *In northern Ontario, the maximum continuous voltage for the 230 and 115
                                                          kV systems can be as high as 260 kV and 132 kV respectively
            3                [Intentionally left blank]
            4                [Intentionally left blank]
            5                [Intentionally left blank]
            6                [Intentionally left blank]
            7                [Intentionally left blank]
            8                [Intentionally left blank]
         These performance requirements shall also apply to electricity storage units at all
         times while connected to the IESO-controlled grid, unless the IESO identifies specific
         performance requirements that are not applicable to an electricity storage unit for those with
         a connection assessment finalized after January 18, 2021. Due consideration will be given to
         inherent limitations.
         Each facility that was authorized to connect to the IESO-controlled grid prior to September
         21, 2020 shall remain subject to the performance requirements in effect for each associated
         system at the time its authorization to connect to the IESO-controlled grid was granted or
         agreed to by the market participant and the IESO (i.e. the “original performance
         requirements”). These original performance requirements shall prevail until the main
         elements of an associated system (e.g. governor control mechanism, main exciter, power
         inverter) are replaced or substantially modified. At that time, the associated system that is
         replaced or substantially modified shall meet the applicable performance requirements
         detailed below. All other systems, not affected by replacement or substantial modification,
         shall remain subject to the original performance requirements.
            Category
            1. Off-Nominal Frequency
            Operation
                                                                                               Grid Connection Requirements - Appendices
            8. Power System Stabilizer   Provide (a) A change of power and speed input configuration; (b) Positive and negative output limits not
            (PSS) for Synchronous        less than ±5% of rated AVR voltage; (c) Phase compensation adjustable to limit angle error to within 30°
            Machines within Facilities   between 0.2 Hz and 2.0 Hz under conditions specified by the IESO, and (d) Gain adjustable up to an
            Greater than 75 MVA          amount that either increases damping ratio above 0.1 or elicits poorly damped exciter modes of
                                         oscillation at maximum active output unless otherwise specified by the IESO. Due consideration will be
                                         given to inherent limitations.
                                         For electricity storage units, Power System Stabilizer shall be disabled while withdrawing.
            9. Phase Unbalance           Provide an open circuit phase voltage unbalance not more than 1% and operate continuously with a
                                         phase voltage unbalance as high as 2% at the high-voltage terminal of its main output transformer.
            10. Armature and Field       Provide short-time capabilities specified in IEEE/ANSI 50.13 and continuous capability determined by
            Limiters                     either maximum field current, maximum stator current, core-end heating, or minimum field
                                         current. More restrictive limiting functions, such as steady state stability limiters, shall not be enabled
                                         without IESO approval.
             11. Technical
             Characteristics
                                                                                                                                              MDP_RUL_0002_04A
                                               Exhibit, at the high-voltage terminal of its main output transformer, performance comparable to an
                                               equivalent synchronous generation unit with characteristic parameters within typical ranges. Inertia,
                                               unsaturated transient impedance, transient time constants, and saturation coefficients shall be within
                                               typical ranges (e.g. H > 1.2 Aero-derivative, H > 1.2 Hydroelectric units less than 20 MVA, H > 2.0
                                               Hydroelectric units 20 MVA or larger, H > 4.0 Other synchronous units, X’d < 0.5, T’d0 > 2.0, and S1.2 <
                                               0.5) except where permitted by IESO approval.
             12. Reactive Power                For a constant voltage at the high-voltage terminal of the main output transformer, achieve a sustained
             Response to Voltage               reactive power change of 30% of generation facility or electricity storage facility rated apparent power at
             Changes of Inverter-Based         the low-voltage terminal of the main output transformer within 3s following a step change no larger than
             Units                             4% to the AVR voltage reference. AVR response to the voltage error signal must be consistent over the
                                               entire operating range.
         1
             A main output transformer steps up the voltage from the generation unit/facility to the transmission voltage level.
                                                                                                                                                   4
          Distributors Connected to the IESO-
          Controlled Grid
          The performance requirements set out below shall apply to connected wholesale customers
          and distributors that are connecting equipment or facilities to the IESO-controlled grid or to
          their distribution systems after January 18, 2021.
            Category                        Requirement
            1. Power Factor                 Connected wholesale customers and distributors connected to the IESO-controlled grid shall operate at a
                                            power factor within the range of 0.9 lagging to 0.9 leading as measured at the defined meter point.
            2. Under Frequency Load    Connected wholesale customers and distributors connected to the IESO-controlled grid may be required to
            Shedding                   participate in under frequency load shedding
            3. Remedial Action Schemes Connected wholesale customers and distributors connected to the IESO-controlled grid may be required to
                                       participate in remedial action schemes.
            4. Voltage Reduction            Distributors connected to the IESO-controlled grid with directly connected load facilities of aggregated
                                            rating above 20 MVA and with the capability to regulate distribution voltages under load, shall install and
                                            maintain facilities and equipment to provide voltage reduction capability.
            5. [Intentionally left blank]
            6. [Intentionally left blank]
            7. [Intentionally left blank]
            8. [Intentionally left blank]
            9. Testing and Compliance       Connected wholesale customers and distributors connected to the IESO-controlled grid shall test and
            Monitoring                      maintain their equipment in accordance with all applicable reliability standards.
            10. Metering                    Connected wholesale customers and distributors connected to the IESO-controlled grid shall comply with
                                            metering codes and standards set by the IESO.
            11. Voltage Ride-Through        Equipment connected within a connected wholesale customer’s or a distributor’s facility or distribution
                                            system that is connected to the IESO-controlled grid shall ride through routine switching events and
                                            design criteria contingencies on the transmission system assuming standard fault detection, auxiliary
                                            relaying, communication, and rated breaker interrupting times unless either disconnected by
                                            configuration or a failure to do so has been assessed and confirmed by the IESO as having no material
                                            adverse effect on the operation of the IESO-controlled grid.
                                      Any generation unit or electricity storage unit connected within a connected wholesale customer’s or a
                                      distributor’s facility or distribution system that is connected to the IESO-controlled grid shall meet, at a
                                      minimum, the performance requirements for Off-Nominal Frequency Operation (category 1),
                                      Speed/Frequency Regulation (category 2), and Voltage Ride-Through (category 3) specified in Appendix
                                      4.2.
                                      If a connected wholesale customer injects active power into the IESO-controlled grid, all performance
                                      requirements specified in Appendix 4.2 are applicable to the generation units and electricity storage units
                                      installed within their facility.
                                      Note: These performance requirements shall apply to electricity storage units and generation units at all
                                      times while connected within a connected wholesale customer’s or distributor’s facilities or distribution
                                      system that is connected to the IESO-controlled grid, unless the IESO identifies specific performance
                                      requirements that are not applicable to an electricity storage unit or generation unit for those with a
                                      connection assessment finalized after January 18, 2021. Due consideration will be given to inherent
                                      limitations.
                                                  Voltage changes shall not normally exceed 4% of steady state rms for capacitor switching
                                                                                                                                              4
                      Changes                     operations. Voltage changes shall not normally exceed 10% of steady state rms for line switching
                                                  operations
            2         Frequency                   All equipment shall be capable of continuous operation within the range of 59.5 to 60.5 Hz and
                      Variations                  have the capability to operate for 10 minutes in the range 58 to 61.5 Hz.
            3         Load Shedding               Each transmitter shall comply with IESO requirements for automatic under-frequency load
                      Facilities                  shedding in accordance with its operating agreement. Each transmitter shall be able to manually
                                                  drop up to 50% of its load within 10 minutes.
            4         Automatic Reclosure         Transmission circuits shall be equipped with timed, single-shot automatic re-closing facilities.
                                                  Reclosure shall only be initiated by protections that operate when it is highly likely that the fault is
                                                  not permanent. Reclosure within 5 seconds of fault detection is allowed only in exceptional
                                                  circumstances. Angle supervision shall be provided on all breakers rated at 230 kV and above.
                                                  Automatic reclosure shall remain enabled only for a limited period of time, usually about 40
                                                  seconds, following initiation.
            5         Thermal Ratings             •      Market participants that own and operate transmission equipment shall provide the IESO
                                                         with the continuous and limited time thermal ratings for their transmission circuits and
                                                         transformers.
                                                  •      Market participants shall provide this information to the IESO via a data link with a minimum
                                                         update rate of 5 minutes or as agreed to by the IESO. For backup and pre-dispatch
                                                         purposes, market participants shall provide a thermal rating table in a suitable format to
                                                         facilitate IESO applications to perform thermal rating interpolation.
                                                  •      Where other equipment (e.g. wavetraps) is more limiting, market participants shall provide
                                                         the IESO with the thermal rating of the most restrictive element.
                                                  •      Generators and connected wholesale customers that own and operate transmission
                                                         equipment that is part of the IESO-controlled grid shall provide the IESO with the continuous
                                                         and limited time thermal ratings for their transmission circuits and transformers only if
                                                         required by the IESO to maintain reliable operation of the IESO-controlled grid.
                                                  •      Limited time thermal ratings shall be 15-minute ratings, unless mutually agreed by the IESO
                                                         and market participant.
            6         Protective System           Protection systems shall be constructed and maintained in accordance with all applicable
                      Requirements                reliability standards.
            7         IESO Information            The transmitter shall provide any information that the IESO deems necessary to direct the
                      Requirements                operation of the IESO-controlled grid. This Information, including, but not limited to, voltages,
                                                  flows, and equipment status shall be telemetered continually to the IESO.
            8         Voltage Reduction           Transmitters with the ability to regulate distribution voltages under load shall install and maintain
                                                  facilities and equipment to provide voltage reduction capability.
            9         Telecommunications          Communication channels shall have a level of reliability that is consistent with the required
                                                  performance of the associated protection system. Telecommunications shall be designed to
                                                  assure adequate signal transmission during transmission disturbances and may be provided with
                                                  means to verify proper signal performance. Equipment may be monitored to assess its readiness
                                                  and be powered by batteries or other sources independent of the IESO.
            10        Testing and                 Transmitters shall test and maintain their equipment in accordance with all applicable reliability
                      Compliance                  standards.
                      Monitoring
            11        Metering                    Transmitters shall comply with the metering codes and standards set by the IESO.
                                                                                                                                        4
          The following information, as a minimum, shall be available on a continual basis to the IESO
          from:
          (a) any generator (i) whose generation facility is connected to the IESO-controlled grid, or
          (ii) that is participating in the IESO-administered markets; and
          (b) any embedded generator (i) that is not a market participant or whose embedded
          generation facility is not a registered facility; (ii) whose embedded generation facility
          includes a generation unit rated at greater than 20 MVA or that comprises generation units
          the ratings of which in the aggregate exceeds 20 MVA; and (iii) that is designated by the
          IESO for the purposes of section 7.3.1 of this Chapter as being required to provide such data
          in order to enable the IESO to maintain the reliability of the IESO-controlled grid.
                                            (i) the standard requirement as defined in part a) shall be provided as an aggregated total, and
                                                an aggregated total gross MW and gross MX or net MX shall be provided if designated by the
                                                IESO as required using the criteria listed above in part a); or
                                            (ii) if so designated by the IESO as required for determination of operating security limits or to
                                                 maintain reliable operation of the IESO-controlled grid or for dispatch compliance monitoring
                                                 purposes, the standard requirement as defined in part a) for each generating unit shall be
                                                 provided, and gross MW and gross MX or net MX for each generation unit shall be provided if
                                                 designated by the IESO as required using the criteria listed above in part a).
                                          e) For frequency changers:
                                            (i) total MW and MX at either frequency; or
                                            (ii) if so designated by the IESO as required for determination of operating security limits, total
                                                 MW and MX at both frequencies.
                                          f) For synchronous condensers:
                                            (i) total MX.
                                      2. Voltage:
                                          a) For each generation unit, unit terminal voltage, except if generation units are connected to a
                                             common low voltage bus section, then the bus section voltage is adequate for those generation
                                             units.
                                      3. Frequency:
                                          a) For each generation unit or generation facility providing black start capability, frequency of the
                                             applicable generation unit or generation facility.
                                      4. Equipment Status
                                          a) Unit mode (i.e. generator, condenser, pump) for each generation unit capable of different modes
                                             of operation.
                                          b) AGC status for each generation unit providing regulation.
                                          c) AVR and Stabilizer Status for each generating unit with a rated capacity > 100 MVA. Stabilizer
                                             status reporting is only required if it can be switched off by generation facility personnel remotely
                                             or at the facility.
                                          d) AVR and Stabilizer status for each generation unit with a rated capacity < 100 MVA if the status
                                             of this equipment is designated by the IESO as required for determination of operating security
                                             limits or to maintain reliable operation of the IESO-controlled grid. Stabilizer status reporting is
                                             only required if it can be switched on or off by market participant operating personnel remotely
                                             or at the facility.
                                          e) Synchronizing Breaker status for each generation unit. Where a generation facility is designed
                                             such that no low voltage synchronizing breaker is installed for each generation unit, the status of
                                             the appropriate HV breaker(s) and disconnect switch(es) normally used to isolate the generation
                                             unit must be provided. Where this results in access to the majority of breakers on a bus, the
                                             status of the remainder of the breakers shall be provided to complete the bus configuration.
                                            Where a generation facility is designed such that there are disconnect switches in parallel, or
                                            directly in series, with the synchronizing breaker, the status of those switches is also required.
                                          f) Remedial Action Scheme status for each applicable generation unit.
TYPE
              connected to IESO-
              controlled grid
                                                                                     Grid Connection Requirements - Appendices
INFORMATION REQUIREMENTS
                                            a) The standard requirement for active and reactive power is the provision of net MW
                                               and net MX or gross MX. Gross MW and gross MX or net MX are also to be
                                               provided, if designated by the IESO as required for:
                                                                                                                                 4
                                              (i) determination of operating security limits;
                                              (ii) to maintain reliable operation of the IESO-controlled grid;
                                              (iii) for compliance monitoring purposes; or
                                              (iv) if provision of only the standard requirement values as defined above would have a
                                                  negative impact on other market participants through reduced operating security
                                                  limits.
                                            b) For generation facilities that have not been aggregated pursuant to Chapter 7 section
                                               2.3:
                                              (i) for a group of generation units if those generation units are similar in size and
                                                  operating characteristics, the standard requirement as defined in part a) shall be
                                                  provided as a total for these generation units, and total gross MW and gross MX or
                                                  net MX shall be provided if designated by the IESO as required using the criteria
                                                  listed above in part a);
                                              (ii) if designated by the IESO as required for determination of operating security limits
                                                   or to maintain reliable operation of the IESO-controlled grid or for compliance
                                                   monitoring purposes, the standard requirement as defined in part a) for each
                                                   generating unit shall be provided, and gross MW and gross MX or net MX for each
                                                   generation unit shall be provided if designated by the IESO as required using the
                                                   criteria listed above in part a).
                                            c) For generation facilities that have been aggregated pursuant to Chapter 7 section 2.3:
                                              (i) the standard requirement as defined in part a) shall be provided as an aggregated
                                                  total, and an aggregated total gross MW and gross MX or net MX shall be provided
                                                  if designated by the IESO as required using the criteria listed above in part a); or
                                              (ii) if so designated by the IESO as required for determination of operating security
                                                   limits or to maintain reliable operation of the IESO-controlled grid or for dispatch
                                                   compliance monitoring purposes, the standard requirement as defined in part a) for
                                                   each generating unit shall be provided, and gross MW and gross MX or net MX for
                                                   each generation unit shall be provided if designated by the IESO as required using
                                                   the criteria listed above in part a).
                                            d) For frequency changers:
                                              (i) total MW and MX at either frequency; or
                                              (ii) if so designated by the IESO as required for determination of operating security
                                                   limits, total MW and MX at both frequencies.
                                            e) For Synchronous Condensers:
                                              (i) Total MX.
                                        2. Voltage:
                                            a) For generation units that are VAR dispatchable, unit terminal voltage, except if the
                                               generation units are connected to a common low voltage bus section, then the bus
                                               section voltage is adequate for those generation units.
                                        3. Frequency:
                                          a) For each generation unit or generation facility providing black start capability,
                                             frequency of the applicable generation unit or facility.
                                      4. Equipment Status
                                          a) Unit mode (i.e. generator, condenser, pump) for each generation unit capable of
                                             different modes of operation.
                                          b) AVR and Stabilizer Status for each generation unit if the status of this equipment is
                                             designated by the IESO as required for determination of operating security limits or to
                                             maintain reliable operation of the IESO-controlled grid. Stabilizer status reporting is
                                             only required if it can be switched on or off by market participant operating personnel
                                             remotely or at the facility.
                                          c) Synchronizing Breaker Status for each generation unit. Where a generation facility is
                                             designed such that no low voltage synchronizing breaker is installed for each
                                             generation unit, the status of the appropriate HV breaker(s) and disconnect switch(es)
                                             normally used to isolate the generation unit must be provided. Where this results in
                                             access to the majority of breakers on a bus, the status of the remainder of the
                                             breakers shall be provided to complete the bus configuration.
                                             Where a generation facility is designed such that there are disconnect switches in
                                             parallel, or directly in series, with the synchronizing breaker, the status of those
                                             switches is also required.
                                          d) Remedial Action Scheme status for each applicable generation unit.
            Self-scheduling           None
            generation facility
            with a name-plate
            rating of less than
            10 MW
            Intermittent and          • if a major generation facility, as described above for a major generation facility
            transitional
            scheduling                • if a significant generation facility, as described above for a significant generation facility
            generator                 • if a minor generation facility, as described above for a minor generation facility if
                                      designated by the IESO at the time of registration as affecting the reliability of the IESO-
                                      controlled grid
                                      • if a small generation facility, none
            Small generation          None
            facility
            Minor generation          • Total active power (MW) output of the individual generation unit or of the aggregated
            facility that is          resource.
            embedded in a
            distribution system       • Unit status if the facility is comprised of a single generation unit.
            and registered as a       • Aggregated resource status if the facility is comprised of aggregated resources, i.e. if at
            dispatchable              least one unit of the aggregated resource is synchronized, the aggregated resource is
            generator                 synchronized or if no unit in the aggregated resource is synchronized, the aggregated
                                      resource is not synchronized.
                                      • Reactive Power (MX) output, if requested by the IESO for reliable operation of the IESO-
                                      controlled grid, of individual generation units or of the aggregated resource.
TYPE
              Generation facility
                                                                                    Grid Connection Requirements - Appendices
Monitored Quantities
                                                                                             MW and MVAR
                                                                                                                             4
                                                                                             Phase to ground Voltage, for each
                                                                                             winding measured on the high voltage
            Step Down                 50 kV and
                                                                                             side. Where only LV PTs are available:
            Transformers              higher
                                                                                             MW and phase to phase voltages for
                                                                                             each LV winding
                                                                                             ULTC tap positions.
                                                                                             MW and MVAR may be required as
                                                                                             directed by the IESO
                                                    Bypass and isolating switches
            Voltage Regulating        50 kV and
            Transformers              higher                                                 ULTC tap positions for the transformer
                                                                                             The IESO may require the monitoring of
                                                                                             any Off-Load Tap Changers.
            Isolating Devices
                                                    All Circuit breakers, including bus
                                                    tie breakers
                                                    All breakers connecting loads for
                                                    each tertiary winding of
                                                    autotransformer other than that for
                                                    Station Service
Equipment Type
                                     50 kV and
                                                               Monitored Status
Monitored Quantities
Circuits
           Special Protection
           Schemes
                                                       As directed by the IESO on a case-   As directed by the IESO on a case-by-
                                                       by-case basis. Where so directed,    case basis.
           Remedial Action           50 kV and         must include all associated
           Schemes (RAS)             higher            capacitors and reactors breaker
                                                       status.
           Reactive Devices
                                     All levels        Breaker Status                       MVARs where output is variable.
           Capacitors,
                                     designated by
           Synchronous
                                     the IESO as
           Condensors,
                                     affecting the
           Reactors, Static Var
                                     reliability of
           Compensators,
                                     the IESO-
           FACTS
                                     controlled grid
Equipment Type
            Station Buses
                                          Voltage
                                           Level
                                      50 kv and
                                      higher
                                                                              Grid Connection Requirements - Appendices
            Required to restore
            IESO-controlled
            grid from
            generating facilities
            providing black-
            start capability.
            Circuits defining         50 kv and     Positive sequence current phasor magnitude measured at terminals
            Interconnection           higher        Positive sequence current angle magnitude measured at terminals
            Reliability
            Operating Limits                        Positive sequence voltage phasor magnitude measured at terminals
            (IROL) and interties
                                                    Positive sequence voltage phasor angle measured at terminals
                                                    Frequency
            Static Var                Below 50 kv   Positive sequence current phasor magnitude measured at terminals
            Compensators                            Positive sequence current angle magnitude measured at terminals
            (SVCs),
            Synchronous                             Positive sequence voltage phasor magnitude measured at terminals
            condensers, and                         Positive sequence voltage phasor angle measured at terminals
            Static synchronous
            compensators                            Frequency
            (STATCOMs)
            TYPE
            Distributor connected to
            the IESO-controlled grid
            or designated pursuant
            to section 7.5.2
                                            MONITORED QUANTITIES
                                                  •
                                                                                      Grid Connection Requirements - Appendices
           Connected wholesale
           customers
                                          MONITORED QUANTITIES
                                          For:
                                                                                                                          MDP_RUL_0002_04A
                                                                                                                                  4
          Consumers
          The following information, as a minimum, shall be available on a continual basis to the IESO
          from all embedded load consumers designated by the IESO pursuant to section 7.6.1. Needs
          of the state estimation process or other reasons may result in additional requirements. The
          direction of all real and reactive power flows shall be indicated measurements. An embedded
          load consumer that is also a generator shall also comply with the applicable requirements of
          Appendix 4.15.
         Standards
         The following performance standards, as a minimum, shall be achieved on a continual basis
         by all generators referred to in section 7.3.1 of this Chapter when monitored by the IESO.
         Needs of the state estimation process or other reasons may result in additional requirements.
         The direction of all real and reactive power flows shall be indicated measurements.
                                                                               Minor generation
                                                                               facility and
                                                                               intermittent
                                                                               generator or
                                                                               transitional
                                                                                                      Small generation facility
                                                                                                                                   4
                                                                               scheduling
                                                                               generator
                                                                               designated pursuant
                                                                               to section 7.3.2.3
                                                                               (Medium
                                                                               Performance)
              IESO scan period for data           Maximum:* 4                  Minimum:** 4           Not applicable
              measurements                        seconds                      seconds
              IESO scan period for                Maximum:* 4                  Minimum:** 4           Not applicable
              Equipment Status                    seconds                      seconds
              Data Skew                           Maximum: 4                   Not applicable         Not applicable
                                                  seconds
         Standards
         The following performance levels, as a minimum, shall be achieved on a continual basis by
         all transmitters when monitored by the IESO. Needs of the state estimation process or other
         reasons may result in additional requirements. The direction of all real and reactive power
         flows shall be indicated measurements.
                           PERFORMANCE LEVEL                                                 FACILITIES
                                                                       All facilities and assets at 50 kV and above which are
                                                                       monitored for system limits such as transformer or
                                                                       switching stations
                                                                       All transformer and switching stations with
         For transmission facilities or assets designated by the       interconnected ties
         IESO as high performance at the time of registration,
         must meet the high performance levels in Appendix             An RTU which collects information at several locations
         4.21                                                          on the electricity system
                                                                       Step-down transformer facilities that supply a
                                                                       dispatchable load facility that is required to meet high
                                                                       performance monitoring standard
                                                                       All other facilities where medium performance is not
                                                                       specified below
                                                                       Step-down transformer facilities that supply a
                                                                       dispatchable load facility that is required to meet
                                                                       medium performance monitoring standard
         For transmission facilities or assets designated by the       Step-down transformer facilities that supply a non-
         IESO as medium performance at the time of                     dispatchable load facility that includes a non-
         registration, must meet the medium performance levels         dispatchable load rated at 20 MVA or higher or that
         in Appendix 4.21                                              comprises non-dispatchable loads the ratings of which
                                                                       in the aggregate equals or exceeds 20 MVA
                                                                       Facilities and assets at 50 kV and above designated
                                                                       by the IESO as requiring medium performance
                                                                                                                         4
          Standards
          The following performance standards, as a minimum, shall be achieved on a continual basis
          by all transmitters when monitored by the IESO. Needs of the state estimation process or
          other reasons may result in additional requirements. The direction of all real and reactive
          power flows shall be indicated measurements.
           FUNCTION                   Major Dispatchable Load Facility     Minor Dispatchable Load Facility and Non-
                                      and Significant Dispatchable         Dispatchable Load Facility*** that includes a non-
                                      Load Facility                        dispatchable load rated at 20 MVA or higher or is
                                                                           comprised of non-dispatchable loads the ratings of
                                      (High Performance)                   which in the aggregate equals or exceeds 20 MVA
                                                                           (Medium Performance)
           Data measurements          Less than 2 seconds from             Less than 10 seconds from change in field
           available at the IESO      change in field monitored            monitored quantity
           communications             quantity
           interface
           Equipment status           Less than 2 seconds from field       Less than 10 seconds from field status change
           change available at        status change
           the IESO
           communications
           interface
           Data skew                  Maximum:* 4 seconds                  Not applicable
           IESO scan period for       Maximum:* 4 seconds                  Minimum:** 4 seconds
           data measurements
           IESO scan period for       Maximum:* 4 seconds                  Minimum:** 4 seconds
           equipment status
                                                                                                                                 4
          Consumers Performance Standards
          The following performance standards, as a minimum, shall be achieved on a continual basis
          by all embedded load consumers designated pursuant to section 7.6.1 when monitored by the
          IESO. Needs of the state estimation process or other reasons may result in additional
          requirements. The direction of all real and reactive power flows shall be indicated
          measurements. An embedded load consumer that is also a generator shall also comply with
          the requirements of Appendix 4.19.
              FUNCTION                            Major Dispatchable Load          Minor Dispatchable Load Facility and Non-
                                                  Facility and Significant         dispatchable Load Facility*** that includes a
                                                  Dispatchable Load Facility       non-dispatchable load rated at 20 MVA or
                                                                                   higher or is comprised of non-dispatchable
                                                  (High Performance)               loads the ratings of which in the aggregate
                                                                                   equals or exceeds 20 MVA
                                                                                   (Medium Performance)
              Data measurements                   Less than 2 seconds from         1. Less than one minute from change in field
                                                                                      monitored quantity; or
              available at the IESO               change in field monitored        2. Less than 10 seconds from change in field
              communications interface            quantity                            monitored quantity if designated by the IESO as
                                                                                      required to maintain reliable operation of the
                                                                                      IESO-controlled grid.
              Equipment status change             Less than 2 seconds from field   1. Less than one minute from change in field
                                                                                      monitored quantity; or
              available at the IESO               status change                    2. Less than 10 seconds from field status change if
              communications interface                                                designated by the IESO as required to maintain
                                                                                      reliable operation of the IESO-controlled grid.
              Data skew                           Maximum:* 4 seconds              Not applicable
              IESO scan period for data           Maximum:* 4 seconds              Minimum:** 4 seconds
              measurements
              IESO scan period for                Maximum:* 4 seconds              Minimum:** 4 seconds
              equipment status
         Participants
         The following information, as a minimum, shall be available on a continual basis to the IESO
         from:
         (a) any electricity storage participant (i) whose electricity storage facility is connected to the
         IESO-controlled grid, or (ii) that is participating in the IESO-administered markets; and
         (b) any embedded electricity storage participant (i) that is not a market participant or whose
         embedded electricity storage facility is not a registered facility; (ii) whose embedded
         electricity storage facility includes an electricity storage unit with an electricity storage unit
         size rated at greater than 20 MVA or that comprises multiple electricity storage units, the
         aggregated electricity storage unit size ratings of which exceeds 20 MVA; and (iii) that is
         designated by the IESO for the purposes of section 7.3.1 of this Chapter as being required to
         provide such data in order to enable the IESO to maintain the reliability of the IESO-
         controlled grid.
                     TYPE
                                                                                            Grid Connection Requirements - Appendices
                                                                       INFORMATION REQUIREMENTS
                                                                                                                                            4
                                              (ii) if designated by the IESO as required for determination of operating security limits or to
                                                   maintain reliable operation of the IESO-controlled grid or for compliance monitoring purposes,
                                                   the standard requirement as defined in part a) for each electricity storage unit shall be
                                                   provided, and gross MW and gross MX or net MX for each electricity storage unit shall be
                                                   provided if designated by the IESO as required using the criteria listed above in part a).
                                            d) For electricity storage facilities that have been aggregated pursuant to Chapter 7 section 2.3:
                                              (i) the standard requirement as defined in part a) shall be provided as an aggregated total, and
                                                  an aggregated total gross MW and gross MX or net MX shall be provided if designated by the
                                                  IESO as required using the criteria listed above in part a); or
                                              (ii) if so designated by the IESO as required for determination of operating security limits or to
                                                   maintain reliable operation of the IESO-controlled grid or for dispatch compliance monitoring
                                                   purposes, the standard requirement as defined in part a) for each electricity storage unit shall
                                                   be provided, and gross MW and gross MX or net MX for each electricity storage unit shall be
                                                   provided if designated by the IESO as required using the criteria listed above in part a).
                                        3. Base point
                                            a) For each electricity storage unit or electricity storage facility, providing regulation, the basepoint,
                                               if applicable, of the electricity storage unit expressed in MW, according to the applicable market
                                               manual.
                                        5. Voltage:
                                            a) For each electricity storage unit, unit terminal voltage, except if electricity storage units are
                                               connected to a common low voltage bus section, then the bus section voltage is adequate for
                                               those electricity storage units.
                                        6. Equipment Status
                                            a) Voltage Control status and stabilizer status (if applicable) for each electricity storage unit with an
                                               electricity storage unit size > 100 MVA. When applicable, stabilizer status reporting is only
                                               required if it can be switched off by electricity storage participant personnel remotely or at the
                                               facility.
                                            b) AGC status for each electricity storage unit providing regulation.
                                            c) Voltage control status and stabilizer status (if applicable) for each electricity storage unit with an
                                               electricity storage unit size < 100 MVA if the status of this equipment is designated by the IESO
                                               as required for determination of operating security limits or to maintain reliable operation of the
                                               IESO-controlled grid. When applicable, stabilizer status reporting is only required if it can be
                                               switched on or off by market participant operating personnel remotely or at the facility.
                                            d) Synchronizing Breaker status for each electricity storage unit. Where a electricity storage facility
                                               is designed such that no low voltage synchronizing breaker is installed for each electricity
                                               storage unit, the status of the appropriate HV breaker(s) and disconnect switch(es) normally
                                               used to isolate the electricity storage unit must be provided. Where this results in access to the
                                               majority of breakers on a bus, the status of the remainder of the breakers shall be provided to
                                               complete the bus configuration.
                                          e) Where a electricity storage facility is designed such that there are disconnect switches in
                                             parallel, or directly in series, with the synchronizing breaker, the status of those switches is also
                                             required.
                                          f) Remedial Action Scheme status for each applicable electricity storage unit.
                                      2. Voltage:
                                          a) For electricity storage units that are VAR dispatchable, unit terminal voltage, except if the
                                             electricity storage units are connected to a common low voltage bus section, then the bus
                                             section voltage is adequate for those electricity storage units.
                     TYPE
                                                                                              Grid Connection Requirements - Appendices
INFORMATION REQUIREMENTS
                                            a) For each electricity storage unit or electricity storage facility, the economic maximum power
                                               mode and economic minimum power mode, expressed in MW. 5. Base point
                                                                                                                                              4
                                            a) For each electricity storage unit or electricity storage facility, providing regulation, the basepoint,
                                               if applicable, of the storage unit expressed in MW, according to the applicable market manual.
                                        5. Equipment Status
                                            a) Automatic Voltage Control and stabilizer status (if applicable) for each electricity storage unit if
                                               the status of this equipment is designated by the IESO as required for determination of
                                               operating security limits or to maintain reliable operation of the IESO-controlled grid. When
                                               applicable, stablizer status reporting is only required if it can be switched on or off by the market
                                               participant operating personnel remotely or at the facility.
                                            b) Synchronizing Breaker Status for each electricity storage unit. Where an electricity storage
                                               facility is designed such that no low voltage synchronizing breaker is installed for each electricity
                                               storage unit, the status of the appropriate HV breaker(s) and disconnect switch(es) normally
                                               used to isolate the electricity storage unit must be provided. Where this results in access to the
                                               majority of breakers on a bus, the status of the remainder of the breakers shall be provided to
                                               complete the bus configuration.
                                            Where an electricity storage facility is designed such that there are disconnect switches in parallel,
                                              or directly in series, with the synchronizing breaker, the status of those switches is also required.
                                            c) Remedial Action Scheme status for each applicable electricity storage unit.
                                                  purposes, the standard requirement as defined in part a) for each electricity storage unit
                                                  shall be provided, and gross MW and gross MX or net MX for each electricity storage unit
                                                  shall be provided if designated by the IESO as required using the criteria listed above in part
                                                  a).
                                      2. Voltage:
                                          a) For electricity storage units that are VAR dispatchable, unit terminal voltage, except if the
                                             electricity storage units are connected to a common low voltage bus section, then the bus
                                             section voltage is adequate for those electricity storage units.
                                      5. Base point
                                          a) For each electricity storage unit, providing regulation, the basepoint of the applicable electricity
                                             storage unit expressed in MW according to the applicable market manual.
                                      6. Equipment Status
                                          a) Automatic Voltage Control status and Stabilizer status (if applicable) for each electricity storage
                                             unit if the status of this equipment is designated by the IESO as required for determination of
                                             operating security limits or to maintain reliable operation of the IESO-controlled grid. When
                                             applicable, stablizer status reporting is only required if it can be switched on or off by market
                                             participant operating personnel remotely or at the facility.
                                          b) Synchronizing Breaker Status for each electricity storage unit. Where an electricity storage
                                             facility is designed such that no low voltage synchronizing breaker is installed for each electricity
                                             storage unit, the status of the appropriate HV breaker(s) and disconnect switch(es) normally
                                             used to isolate the electricity storage unit must be provided. Where this results in access to the
                                             majority of breakers on a bus, the status of the remainder of the breakers shall be provided to
                                             complete the bus configuration.
                                          Where an electricity storage facility is designed such that there are disconnect switches in parallel,
                                            or directly in series, with the synchronizing breaker, the status of those switches is also required.
                                          c) Remedial Action Scheme status for each applicable electricity storage unit.
TYPE
                                              c)
                                                                                       Grid Connection Requirements - Appendices
                                                                    INFORMATION REQUIREMENTS
                                                                                                                                   4
                                                   Reactive Power (MX) output, if requested by the IESO for reliable operation of the
                                                   IESO-controlled grid, of individual electricity storage units or of the aggregated
                                                   resource.
                                              d)   Unit terminal voltage (kV) if requested by the IESO for reliable operation of the
                                                   IESO controlled grid
         Performance Standards
         The following performance standards, as a minimum, shall be achieved on a continual basis
         by all electricity storage participants referred to in section 7.3.A of this Chapter when
         monitored by the IESO. Needs of the state estimation process or other reasons may result in
         additional requirements. The direction of all real and reactive power flows shall be indicated
         measurements.
                                                                               Minor electricity
                                                                               storage facility and
                                                                               self-scheduling
                                                                               electricity storage
                                                                               facility (electricity
                                                                                                           Small electricity storage
                                                                                                           facility
                                                                                                                                       4
                                                                               storage facility unit
                                                                               size <10MW)
                                                                               (Medium
                                                                               Performance)
              Equipment status change             Less than 2 seconds          1. Less than 10             Not applicable
              available at the IESO               from field status               seconds from field
              communications interface            change                          status change or
                                                                               2. If the minor
                                                                                  electricity storage
                                                                                  facility is
                                                                                  embedded within a
                                                                                  distribution
                                                                                  system, less than
                                                                                  one minute from
                                                                                  change in
                                                                                  equipment status
                                                                                  unless otherwise
                                                                                  designated by the
                                                                                  IESO to maintain
                                                                                  the reliability of the
                                                                                  IESO-controlled
                                                                                  grid.
              IESO scan period for data           Maximum:* 4                  Minimum:** 4                Not applicable
              measurements                        seconds                      seconds
              IESO scan period for                Maximum:* 4                  Minimum:** 4                Not applicable
              Equipment Status                    seconds                      seconds
              Data Skew                           Maximum: 4                   Not applicable              Not applicable
                                                  seconds