TAX Series
Molded Case Circuit Breakers
Reliable
             From 16A to 800A
The TAX range MCCBs provides safe
and easy solution for low voltage
electrical circuit protection.
Selection guide                    1
Application,                        2
Operating and Installation conditions
Technical Specifications           3
Accessories                        6
Installations Dimensions           9
TECO MCCB's Selection Guide
TAX-□□□□                □                           □                  □□□                     □□□□
Basic nominal    Constitutional   Number of Poles                    Rated      Internal accessories
specifications   functions                                           current
125L             Blank: for       3=3P                               016=16A    First:
125M             distribution;    A: 4 poles, no overcurrent         020=20A    2:Electromagnetic trip
125H             M: for Motor     tripping components are            025=25A    3:Reset trip
250L             protection       installed on the N pole, which     032=32A    Last 3(bland=no accessories)
250M                              is always connect_x005f ed,        040=40A    080=L
250H                              not switched on or off along       050=50A    101=S (AC230V)
400L                              with the other three poles;        063=63A    102=S (AC400V)
400M                              B: 4 poles, no overcurrent         080=80A    103=S ( AC110V)
400H                              tripping compo nents are           100=100A   104=S ( AC24V )
630L                              installed on the N pole, which     125=125A   105=S ( DC24V)
630M                              switched on or off along with      140=140A   301=U ( AC230V)
630H                              with the other three poles;        160=160A   302=U ( AC400V)
800L                              the N pole is switched on first    180=180A   200=X
800M                              then off;                          200=200A   181=L+S ( AC230V )
800H                              C: 4 poles, the N pole is          225=225A   182=L+S ( AC400V )
                                  equipped with an                   250=250A   183=L+S ( AC110V )
                                  tripping component, and            315=315A   184=L+S ( AC24V )
                                  the N pole is switched on or       400=400A   185=L+S ( DC24V )
                                  along with the other three         500=500A   280=L+X
                                  poles, the N pole is switched      630=630A   381=L+U ( AC230V )
                                  first then off;                    700=700A   382=L+U ( AC400V)
                                  D: 4 poles, the N pole is          800=800A   401 =S ( AC230V ) +X
                                  equipped with an                              402=S ( AC400V ) +X
                                  tripping component, and the                   403=S ( AC110V ) +X
                                  pole is always on, and it is not              404=S ( AC24V ) +X
                                  switched on or off along with                 405=S ( DC24V ) +X
                                  the other three poles.                        701=U ( AC230V ) +X
                                                                                702=U ( AC400V ) +X
                                                                                481=A+S ( AC230V )
                                                                                482=A+S ( AC400V )
                                                                                483=A+S ( AC110V)
                                                                                484=A+S ( AC24V )
                                                                                485=A+S ( DC24V )
                                                                                780=U ( AC230V ) +A
                                                                                781=U ( AC400V ) +A
                                                                                600=X (左)+X (右)
                                                                                680=X+A
                                                                                800=A
                                                                                880=A+A
                                                                                Note:X-XAUX: Auxiliaries
                                                                                L-ALT: Alert
                                                                                A-AUX+ALT:Auxiliary alert
                                                                                S-SHT: Shunt
                                                                                U-UVT: Undervoltage
                                                        1
Scope of Application
TAX Range MCCBs is a new type of circuit breaker developed with
internationally
advanced  design and manufacture technologies. Its rated insulation voltage
is
1000V, suitable for infrequent conversion and infrequent starting of motor in
circuits of AC 50Hz, rated operating voltage 690V and below, rated operating
current up to 800A. The MCCBs has overload, short-circuit and undervoltage
protection functions to protect the circuits and power supply from damage.
TAX Series MCCBs are featured with compact structure, small size, high
breaking,
short arcing, complete internal and external accessories.
Compliance with standards:
IEC60947-1, GB//T14048.1 General Provisions
IEC60947-2, GB//T 14048.2 Low-voltage Circuit Breakers
IEC60947-4, GB//T 14048.4 Electromechanical circuit breakers and motor
IEC60947-5-1,GB//T 14048.5 Electromechanical control circuit devices
Operating and installation conditions
◆The altitude of the installation location shall not exceed 2000m;
◆The ambient air temperature shall be -5℃ ~ +40℃, and the average temperature of 24 hours shall not exceed +35
℃;
◆The relative air humidity at the installation location shall not exceed 50% at the maximum temperature of +40℃.
At a lower temperature, the higher relative humidity may be higher, and the monthly mean minimum temperature of
the
wettest month shall not exceed +25℃; the mean maximum relative humidity of the month shall not exceed 90%, and
the
condensation occurs on the surface of the product due to temperature changes shall be considered.
◆Pollution level: 3
◆The installation category of the main circuit and undervoltage trip unit of the MCCB is III, and that of the other
auxiliaryand control circuits is II.
circuits
◆Applicable electromagnetic environment: A
◆Capable of withstanding the effects of humid air, salt spray, oil, mold, and nuclear industrial environment
◆Maximum installation inclination: ± 22.5
◆MCCB can work reliably when it is subjected to normal vibration of the ship.
◆MCCB can work reliably under earthquake conditions (4g)
◆MCCB shall be installed in a place where there is no danger of explosion and no conductive dust, no factors that
would metal or destory the insulation.
corrode
◆The installation site is free from rain and snow.
◆The circuit breaker has isolation function with the symbol
The cross-sectional area of the wire and the corresponding rated current
                                                            2
Technical Specifications
★ Optional
Note: The N poles of 4-pole products are on the right
                                                        3
MCCBs Protection Characteristics
The thermal type trip unit of the circuit breaker has the inverse time limit specificity;
the electromagnetic trip unit is instantaneous, and the characteristics are shown in the following table.
◆For Power Distribution
◆For Motor Protection
◆Power consumption sheet
◆Derating factors of rated operating current of thermal trip unit varying with ambient temperatures
◆Altitude capacity reduction
If the altitude exceeds 2000m of the applicable operating environment, the electrical performance of the
circuit breaker may refer to the following table.
                                                       4
Characteristic curve
Note: The following characteristic curves are measured under cold state and three-phase load.
   TAX-125(16A-32A) action curve       TAX-125(16A-32A) temp. compensation curve     TAX-125(40A-125A) action curve
  TAX-125(40A-125A) temp. compensation curve           TAX-250 action curve         TAX-250 temp. compensation curve
        TAX-400 action curve                     TAX-400 temp. compensation curve       TAX-630/800 action curve
TAX-630/800 temp. compensation curve
                                                          5
Internal Accessories
Internal electrical accessories for MCCBs
According to the needs of users, the accessoris can be directly connected to the wire (wire length is
50cm,the length can be specified) or connected to the end of the sub-row.
                                                                            L-- Alarm switch
                                                                            X-- Auxiliary switch
                                                                            A-- Auxiliary alarm switch
                                                                            S-- Shunt release
                                                                            U-- Undervoltage release
   Code           Accessories           TAX-125        TAX-250          TAX-400      TAX-630       TAX-800
 208/308           Alarm switch         L              L                L            L             L
 210/310           Shunt release        S              S                S            S             S
 230/330       Undervoltage release     U              U                U            U             U
 220/320          Auxiliary switch      X              X                X            X             X
                  Alarm switch+
 218/318                                L      S       L       S        L    S       L      S      L     S
                  Shunt release
                 Auxiliary switch+
 228/328                                X      L       X       L        L    X       L      X      L     X
                  Alarm switch
                 Alarm switch+
 238/338                                U      A       U      A
               Undervoltage release
                  Shunt release+
 240/340                                S      X       S       X        S    X       S      X      S     X
                  Auxiliary switch
              Undervoltage release+
 270/370                                U      X       U       X        U    X       U      X      U     X
                 Auxiliary switch
              Auxiliary alarm switch+
 248/348                                A      S       A       S        A    S       A      S      A     S
                   Shunt release
              Auxiliary alarm switch+
 278/378                                U      A       U      A
               Undervoltage release
               Left auxiliary switch+
 260/360                                X      X       X       X        X    X       X      X      X     X
               right auxiliary switch
              Auxiliary alarm switch+
 268/368                                A      X       A       X        A    X       A      X      A     X
                 Auxiliary switch
 280/380       Auxiliary alarm switch   A              A                A            A             A
              Auxiliary alarm switch+
 288/388                                A              A
               Auxiliary alarm switch
1 The first part of the code, 2 electromagnetic trip, 3multiple trip.
The last two are the internal accessory code, blank means no accessories
                                                       6
Internal Accessories & Functions
                 Shunt trip unit
                 ◆Can be used for long distance trip of MCCB.
                 Note: When a DC24V shunt trip unit is selected, the power supply of the shunt
                 trip terminal must be ≥50W.
                 Undervoltage trip unit
                 ◆When the power supply voltage drops to 35~70% of the rated voltage, the
                 circuit breaker is instantaneously tripped;
                 ◆When the voltage is <35% Ue, it shall prevent the MCCB from closing; when
                 the voltage is ≥85% Ue, it shall ensure the close of the MCCB;
                 ◆When applied, the power supply must be turned on before the MCCB can be
                 switched-on or off.
                 Auxiliary contacts
                 ◆Used for indicating the on or off status of the MCCB;
                 ◆One set of NO/NC is used for Inm 125, 250;
                 ◆One set of 2NO/2NC is used for Inm 400, 630, 800.
                 Alarm contacts
                 ◆Used to indicate the fault tripping state of the MCCB;
                 The alarm contacts do not operate when the MCCB is normally on or off, and
                 only operate under the situation of free trip or the fault trip. When the MCCB is
                 reclosed, the IT return to their original state.
                 Note: For all internal accessories except undervoltage release, if the installation
                 size is affected by external wiring terminals, lead-type accessories can be selected
                                       7
CD2 type motor type electric operation mechanism
Used for electric ON/OFF operation of MCCB
                                                      Description:
                                                      P1-P2: external power inputs;
                                                      SB1, SB2: operation button (user-supplied)
                                                      Voltage specification: AC50Hz/60Hz 110V, 230V
                                                                             DC24V, 110V, 220V
                                                      Symbol Description:
CD2 motor type wiring schematic                       SB1, SB2 are operation buttons (user-supplied)
Note: The dotted line frame is the wiring diagram     X is the terminal block, P1 and P2 are external power inputs
of the internal accessories of the circuit breaker.
1. The square shafts of handles have three kinds of lengths: 50mm, 100mm, and 150mm (special
specifications shall be stated when ordering);
2. The 3-pole and 4-pole circuit breakers have the same parameters for turning handles.
                                                           8
Installation dimensions
■TAX-125 front-panel wiring installation dimensions (3P,4P)
■TAX-125 back-panel wiring installation dimensions (3P,4P)
■TAX-125 plug-in back-panel wiring installation dimensions (3P,4P)
■TAX-125 plug-in front-panel wiring installation dimensions (3P)
                                                    9
■TAX-250 front-panel wiring installation dimensions (3P,4P)
■TAX-250 back-panel wiring installation dimensions (3P,4P)
■TAX-250 plug-in back-panel wiring installation dimensions (3P,4P)
■TAX-250 plug-in front-panel wiring installation dimensions (3P)
                                                   10
■TAX-400 front-panel wiring installation dimensions (3P,4P)
■TAX-400 back-panel wiring installation dimensions (3P,4P)
■TAX-400 plug-in back-panel wiring installation dimensions (3P,4P)
■TAX-400 plug-in front-panel wiring installation dimensions (3P)
                                                   11
■TAX-630 front-panel wiring installation dimensions (3P,4P)
■TAX-630 back-panel wiring installation dimensions (3P,4P)
■TAX-630 plug-in back-panel wiring installation dimensions (3P,4P)
■TAX-630 plug-in front-panel wiring installation dimensions (3P)
                                                   12
■TAX-800 front-panel wiring installation dimensions (3P,4P)
■TAX-800 back-panel wiring installation dimensions (3P,4P)
■TAX-800 plug-in back-panel wiring installation dimensions (3P,4P)
■TAX-800 plug-in front-panel wiring installation dimensions (3P)
                                                   13
Taian Technology (Wuxi) Co., Ltd.
No. 29, Gao Lang East Road, New District,China
Wuxi0510-85227555
Tel: City,
www.taian-tech.com
DISCLAIMER: Whilst every effort has been made to ensure the reliability of
the information is correct at time of publication, TECO cannot guarantee the
accuracy of all of the information contained herein. Changes/updates brought to
the attention of TECO, once verified, will be corrected in future editions.