Mic 2000
Mic 2000
Form 2844
             Edition 11
             © August 1993
             Updated March 1997
Brand
              SECTION 2 -
              INSTALLATION & WIRING
              2.1   Installation and Wiring                               7
              2.2   Preparation for Wiring                                8
              2.3   Input Connections                                    13
              2.4   Output Connections                                   19
              SECTION 3 -
              CONFIGURATION & OPERATION
              3.1   Configuration and Operation                          22
              3.2   Operation Summary                                    22
              3.3   Configuration Summary                                24
              3.4   Tune Mode Operation                                  34
              SECTION 5 - SERVICE
              5.1   Service                                              44
              5.2   Calibration                                          44
              5.3   Test Mode                                            48
              5.4   Troubleshooting and diagnostics                      52
              APPENDICES
              A - Board Layout - Jumper Positioning
                                 Figure A-1 Power Supply Board            59
                                 Figure A-2 Processor Board               60
                                 Figure A-3 Option Board                  61, 62
              B - Glossary of terms                                       63
              C - Model Number Hardware Matrix Details                    66
              D - Specifications                                          67
              E - Software Record/Reference Sheet                         70
              Warranty                                           Inside back cover
                                                FLOW CHARTS
                                                Flow - Calibration                                       44
                                                Flow - Enable Mode                                       25
                                                Flow - Program Mode                                      26
                                                Flow - Setpoint                                          42
                                                Flow - Standby Mode                                      41
                                                Flow - Test Mode                                         48
                                                Flow - Tune Mode                                         32
              Control functions, alarm settings and other parameters are easily entered through the front
              keypad. All user's data can be protected from unauthorized changes with it’s ENABLE MODE
              security system. Battery back-up protects against data loss during AC power outages.
              The input is user configurable to directly connect to either thermocouple, RTD, mVDC, VDC
              or mADC inputs. Thermocouple and RTD linearization, as well as thermocouple cold junction
              compensation is performed automatically. The sensor input is isolated . The instrument can
              operate on either 115VAC or 230VAC power at 50/60Hz. It is housed in an extruded alumi-
              num enclosure suitable for panel mounting. It may be surface mounted using an optional
              adaptor.
FIGURE 1-1
                                              S.P.                                    °C
                                                                                      °F
                                                                                       U
              1.1.2 DISPLAYS
              Each instrument is provided with a digital display and status indicators as shown in Figure
              1-1. The digital display is programmable to show the process variable only, process variable
              and setpoint, deviation from setpoint only, deviation and setpoint, or setpoint continuously.
              Status indication is as shown (Figure 1-1). Display resolution is programmable for 0 to 3
              decimal places depending upon the input type selected.
                                                1.1.4 ALARM
                                                Alarm indication is standard on all instruments. Alarm type may be set as PROCESS DIRECT
                                                or REVERSE (High or Low), DEVIATION DIRECT or REVERSE (Above or Below setpoint), or
                                                DEVIATION BAND TYPE (Closed or Open within the band). Alarm status is indicated by
                                                LED. An alarm output can be provided by assigning any output(s) SPST relay(s) or SSR
                                                Driver(s) to the alarm.
EA Software Features
                                                Fast Scan                   Provides an optional faster scan rate of 3 scans per second.
                                                                            Normal scan is one scan per second.
                                                Process Rounding            Provides rounding of the process value displayed to reduce display
                                                                            fluctuation. For example, the displayed value can be rounded to
                                                                            the nearest 5 (display -5, 0, 5, 10, etc.). This is for display only and
                                                                            does not affect the control action.
                                                Extended Current            The current outputs available can be extended to include 0-20mA
                                                Output Ranges               and 0-5VDC (with the appropriate shunt resistor), rather than the
                                                                            standard 4-20mA and 1-5VDC outputs.
                                                Process/Setpoint            The process or setpoint value can be scaled over any desired
                                                Value Retransmit            range and retransmitted using one of the current outputs. (This
                                                Capability                  precludes the use of the output for control).
                                                Percent Output              Provides a relay actuation based upon a proportional output being
                                                Relay Actuation             above or below a specified value.
                                                Contact Closure Sensing This feature provides the following action: When a contact closure
                                                for SP=PV               is sensed, the setpoint will be set equal to the current process
                                                                        value. This is only done on the transition from open to closed, and
                                                                        not continuously while the switch is closed.
EB Software Features
                                                Setpoint Ramp      Provides a limitation on how fast the process value will ramp to setpoint by
                                                Rate               limiting the rate of change of an internal setpoint used for control versus
                                                                   the setpoint the operator specifies.
             230 VAC models may be converted to 115 VAC operation by the user, by changing the
             position of jumpers soldered on the Power Supply Board, see Appendix A-1 (page 59) for
             details.
             Electrical code requirements and safety standards should be observed and installation
             performed by qualified personnel.
             The electronic components of the instrument may be removed from the housing during
             installation. To remove the components, loosen the locking screw located in the lower center
             of the instrument’s front panel. Pull the entire instrument straight out of the
             housing. During re-installation, the vertically mounted circuit boards should be properly
             aligned in the housing. Be sure that the instrument is installed in the original housing. This
             can be verified by matching the serial number on the unit to the serial number on the housing.
             (Serial numbers are located on the inside of the housing enclosure and on the label on the
             underside of the front panel). This will insure that each instrument is accurate to its published
             specifications. The ambient compensator on the rear of the housing enclosure is calibrated to
             the electronics of the instrument at the factory.
             Recommended panel opening sizes are illustrated below (Figure 2-1). After the opening is
             properly cut, insert the instrument housing into the panel opening. Insert the two panhead
             screws provided, through the holes in the mounting bracket into the holes in the rear of the
             instrument as shown in Figure 2-1. Firmly tighten the screws. Instruments are shipped
             standard for panel mounting. To surface mount, an adaptor is required and should be
             specified when ordering. For installation in wash-down areas, a watertight cover is available.
146.8 (5.78)
                                                            96.0                                               90.4
                                                           (3.78)                                             (3.560)
Side View
                                      96.0 (3.78)
                                                                                                   Mounting Bracket
                                                                     Panel
                                    92 + or - 0.8
                                 (3.622 + or - .031)
                                                                             Top View
                               All dimensions shown
                               in mm and inches. Inches
                               shown in ( ).                                                         Mounting screw
                                                Before using any instrument near the devices listed, the instructions below should be fol-
                                                lowed:
                                                1. If the instrument is to be mounted in the same panel as any of the listed devices, separate
                                                   them by the largest distance possible. For maximum electrical noise reduction, the noise
                                                   generating devices should be mounted in a separate enclosure.
                                                2. If possible, eliminate mechanical contact relay(s) and replace with solid state relays. If a
                                                   mechanical relay being powered by an instrument output device cannot be replaced, a
                                                   solid state relay can be used to isolate the instrument.
                                                4. If the instrument is being installed on existing equipment, the wiring in the area should be
                                                   checked to insure that good wiring practices have been followed.
                                                The only wires that should be run together are those of the same category. If they need to be
                                                run parallel with any of the other lines, maintain a minimum 6 inch space between the wires.
                                                If wires must cross each other, do so at 90 degrees. This will minimize the contact with each
                                                other and reduces "cross talk" "Cross talk" is due to the EMF (electro Magnetic Flux) emitted
                                                by a wire as current passes through it. This EMF can be picked up by other wires running in
                                                the same bundle or conduit.
             This instrument has been designed to operate in noisy environments, however, in some cases
             even with proper wiring it may be necessary to suppress the noise at its source.
             For those devices that do not have surge suppressors supplied, RC (resistance-capacitance)
             networks and/or MOV (metal oxide varistors) may be added.
             Inductive Coils - MOV's are recommended for transient suppression in inductive coils con-
             nected in parallel and as close a possible to the coil. See Figure 2-2. Additional protection
             may be provided by adding an RC network across the MOV.
FIGURE 2-2
                                                                                             0.5
                                                                                             mfd
                                                                       Inductive             1000V
               A.C.                        MOV                         Load
                                                                                             220
                                                                                             ohms
                                                                                             115V 1/4W
                                                                                             230V 1W
                                                For circuits up to 3 amps, a combination of a 47 ohm resistor and 0.1 microfarad capacitor
                                                (1000 volts) is recommended. For circuits from 3 to 5 amps, connect 2 of these in parallel.
                                                See Figure 2-3.
FIGURE 2-3
MOV
                                                                                                                          Inductive
                                                             A.C.                  R            C                         Load
              To determine the temperature error resulting from the lead length resistance, use the following
              equation:
TABLE 1
TABLE 2
              Example:
              A 1/4 Din unit is to be located in a control room 660 feet away from the process. Using 16
              AWG, type J thermocouple, how much error is induced?
              Terr = TLe * L
                       TLe = 2.47 (°F/1000 ft) from Table 2
Terr = 1.6 °F
                                                To determine the temperature error resulting from the lead length resistance, use the following
                                                equation:
                                                Terr = TLe * L     where;     TLe = value from Table 3 if 3 wire RTD or Table 4 is 2 wire RTD
                                                                              L = length of lead wire in thousands of feet
                                                Example:
                                                An application uses 2000 feet of 18 AWG copper lead wire for a 3 wire RTD sensor. What is
                                                the worst case error due to this leadwire length?
                                                Terr = TLe * L
                                                         TLe = ± .46 (°F/1000 ft) from Table 3
Terr = ± 0.92°F
                                                                                                OUT1
                                                  F                                         6          +
                                                                                                4-20mA
                                    RELAY B
E 5 RETURN
                                                        INPUT RATINGS:
                                                        115/230 VAC 50/60 HZ 15VA MAX
                                                 D                                          4
                                                        RELAY OUTPUT RATINGS:
                                    RELAY A              115VAC 5.0A RESISTIVE
                                                         230VAC 2.5A RESISTIVE
                                                 C       230VAC 1/8 HP                      3 SIGNAL +
                                                         115/230VAC 250VA
             FIGURE 2-5
             AC Power
             Connect 115 VAC hot and neutral to terminals B and A respectively as illustrated below.
             Connect 230 VAC as described below. Connect Earth ground to the ground screw as shown.
                  .5 AMP*
                                                                                         .25 AMP*
                  FUSE
                                                                                         FUSE
             L1                B                                                    L1                     B
             L2                A                                                    L2                     A
                                               GROUND
                                                                                                                           GROUND
                                                                                THERMOCOUPLE INPUT
                                                                                   Rear view
                                                                                               4
                                                                                                   +
                                                                                               3
                                                                                               1
                                                                                                   -   300 OHMS
                                                                                                       MAXIMUM
                                                                                                       LEAD
                                                FIGURE 2-7
                                                RTD Input
                                                Make RTD connections as illustrated below. For a three wire RTD, connect the resistive leg
                                                of the RTD to terminal 3, and the common legs to terminal 1 and 5. For a two wire RTD,
                                                connect one wire to terminal 1 and the other wire to terminal 3 as shown below. A jumper
                                                wire supplied by the customer must be installed between terminals 1 and 5. Be sure that the
                                                input conditioning jumpers are properly positioned for an RTD input. See Appendix A-2 (page
                                                60) and A-3 (page 61, 62).
8 8
7 7
6 6
5 5
                                                                  4
                                                                      JUMPER*
                                                                                                                        4
3 3
                                                                  2
                                                                                                                        2
                                                                  1
                                                                                                                        1
                                                                         100 OHM*
                                                                         PLATINUM                                                100 OHM*
                                                                                                                                 PLATINUM
*Supplied by customer
8 8
                                                                                    7
                                7
                                                                                    6
                                6
                                                                                    5
                                5        Shielded Twisted
                                         Pair                                                 Shielded Twisted
                                4
                                                                                    4
                                                                                         +    Pair
                                3
                                    +                                               3
                                                                                    2
                                2
                                                                                    1
                                1
                                    -                                                    -
                                                                                             MILLIAMP DC
                                        MILLIAMP DC                                          SOURCE
                                        SOURCE                                               2.5 OHM SHUNT
                                        250 OHM SHUNT                                        RESISTER
                                        RESISTER                                             REQUIRED
                                        REQUIRED
8 8
7 7
6 6
                                5                                                   5
                                          Shielded Twisted                                    Shielded Twisted
                                                                                    4
                                          Pair                                                Pair
                                4
                                    +                                               3
                                                                                        +
                                3
                                                                                    2
                                2
                                1
                                    -
                                                                                    1
                                                                                        -
                                          MILLIVOLT DC                                       VOLT DC
                                          SOURCE                                             SOURCE
                                          50 MILLIVOLT DC                                    5 VOLT DC
                                          MAXIMUM                                            MAXIMUM
+3 +
                                                                                                                 Two Wire
                                                                  2                                              Transmitter
-1 -
                                                FIGURE 2-9B
                                                24 Volt Power Supply (XA Option)
                                                Make connections as shown below. Terminal G is positive (+) and terminal H is negative (-).
                                                Be sure the input conditioning jumpers are properly positioned. See Figure A-2 Processor
                                                Board, page 60 and Figure A-3 Option Board, page 61 or 62.
                                                                                                          H-
                                                                 24VDC
                                                                                                          G+
                                                                                               Shielded Twisted
                                        Shielded Twisted Pair              Rear View           Pair
                       Rear View
                                    +                                                  8
                                                                                           +
                              8
7 7
6 6
                              5
                                    -                                                  5
                                                                                           -
                              4                                                        4
3 3
                              2                                                        2        VOLT DC
                                                                                                SETPOINT
                              1                                                        1        SIGNAL
                                          MILLIAMP                                              5VDC
                                          SETPOINT                                              MAXIMUM
                                          SIGNAL
                                          250 OHM
                                          SHUNT
                                          RESISTER
                                          NEEDED
POTENTIOMETER
Rear View
                                                                  5
                                                                         150 ohm to
                                                                  4      10 K ohm
                                                                  3
                                                                                          DIGITAL COMMUNICATIONS
                                                                                          CONNECTIONS - TERMINALS 7 & 8
                                                                                                                          FROM HOST
                                                                                          Output 2 cannot be DC Current   COMPUTER
                                                                                                                  8
                                                                                                                  5       TO OTHER
                                                                                                                          INSTRUMENTS
                                                                                                                  4
                               RELAY A                                                          RELAY B
                                           Rear View                                                      Rear View
LOAD G
L2 F
                        LOAD                                               L1                        E
                   L2                  D
                                                                                                     D
                   L1                 C
                                                                                                     C
              INPUT
              POWER                    B                              INPUT
                                                                      POWER                          B
                                       A
                                                                                                     A
                                                       GROUND
                                                                                                                      GROUND
RELAY C
                                                                          Rear View
                                                       LOAD
                                                 L2                  H
L1 G
                                           INPUT                     B
                                           POWER
                                                                     A
GROUND
                                                                     H
                                                                                                                                   H
                                                                     G                                              SOLID STATE
                                                                                                                                  G
                                                                                                                      RELAY
                                                                     F
                                                                                                                             +     F
                                                     SOLID STATE
                                                       RELAY         E                                                       -
                                                              +      D
                                                                                                                                   E
                                                              -      C                                                             C
                                                INPUT                                                        INPUT
                                                                     B
                                                POWER                                                        POWER                 B
                                                                     A                                                             A
                                                                                      GROUND                                                       GROUND
- G
                                                                                                    C
                                                                         INPUT
                                                                         POWER                      B
GROUND
                                   8
                                                 Shielded
                                                 Twisted
                                                                                                 8
                                                                                                     +   Shielded
                                                                                                         Twisted
                                   7             Pair                                            7
                                                                                                         Pair
                                   6
                                       +                                                         6
                                   5
                                        -                   LOAD
                                                                                                 5
                                                                                                     -          LOAD
                                   4                                                             4
                                                            650 OHMS                                            650 OHMS
                                                            MAXIMUM                                             MAXIMUM
                                   3                                                             3
2 2
1 1
             FIGURE 2-15
             Position Proportioning Output
             The relay and slidewire feedback connections are made as illustrated below. The relay
             assigned to Output 1 will be used to drive the motor in the open direction and the relay
             assigned to Output 2 will be used to drive the motor in the closed direction. The minimum
             slidewire feedback resistance is 135 ohms, the maximum resistance is 10K ohms.
L2
OPEN
CLOSE
Modulating Motor
                                                                                   POS.PROP.
                                                                              8     WIPER
                                                                                   POS.PROP.
                                                                              7      HIGH +
                                                  F
                                       RELAY B                  Rear View
                                                                                   RETURN
                                                  E                           5
RELAY A
L1 C
                                                If the instrument is being configured (set up) for the first time, it may be desirable to discon-
                                                nect the controller output connections. The instrument will go into the Control mode following
                                                the power up sequence and the output(s) may turn on. During power up, the seven digit
                                                model number will be displayed. Next, the software revision level will be displayed, followed
                                                by the EPROM tab number. Instrument self test 1 through 3 will take place as they are
                                                displayed. After completion of the tests Ctrl will be displayed for 3 seconds. At this time
                                                another mode of operation may be selected by pressing the SCROLL key.
                                                SCROLL KEY
                                                This key is used to:
                                                1. Display enabled modes of operation
                                                2. Display a mode parameter value
                                                3. Advance display from a parameter value to the next parameter code
                                                4. Exit some calibration/test functions
                                                5. Used with other keys:
                                                         A. With UP key to view output percentages of proportional output(s)
                                                         B. With DOWN key
                                                                  1. On power up to alter model number
                                                                  2. Enter calibration /test functions
              DOWN KEY
              This key is used to:
              1. Decrease displayed parameter value
              2. View setpoint (press and release)
              3. Decrease setpoint (press and hold)
              4. Enter modes
              5. While in a mode, will sequence the parameter codes
              6. Used with other keys
                       A. With SCROLL key
                                1. On power up to alter model number
                                2. Enter calibration/test functions
                       B. With UP key
                                1. On power up resets instrument
                                2. Lamp test (press and release)
                                3. Enter enable mode (press and hold)
                                                The instrument is provided with a “time-out” feature. If the instrument is in any mode, other
                                                than the Control mode, and no keypad activity takes place for 30 seconds, the mode will be
                                                exited automatically. The instrument will then display the code for the respective mode. If a
                                                mode code is displayed for five seconds with no key stroke activity the “time-out” will cause
                                                the instrument to return to the Control mode of operation.
EnAb
                                                           ON
                                                  EtSt
                                                           OFF
                                                  ECAL     ON
                                                           OFF
                                                  EPro     ON
                                                           OFF
                                                  Etun     ON
                                                           OFF
                                                  ESbY     ON
                                                           OFF
                                                  ESPS     ON
                                                           OFF
                                                  ESPC     ON
                                                           OFF
                                                                       Key
                                                                        Actual Display
                                                                 ON     On/Off Display -
                                                                 OFF    Use arrow keys
                                                                        to turn on or off
Scroll Key
                                                                        Numeric Display -
                                                                        Use arrow keys
                                                                        to change value
Up Arrow Key
Down Arrow
Prog
inPS rLyC
iCor diSP
out1 dPoS
o1PL Euu
out2 EuL
o2PL HySt
out3 rSP
                           Key
                                                           rLyA       rSPu
                            Actual Display
                     ON     On/Off Display -
                     OFF    Use arrow keys
                            to turn on or off              rLyb       rSPL
Scroll Key
                            Numeric Display -                A          B
                            Use arrow keys
                            to change value
Up Arrow Key
Down Arrow
B C
                      SPL                                      Pout
                               (SPuL -
                               EA Option)
                     SPLL
                     (EA                                       Pou
                     Option)
AtFr PoL
PFF PorA
EA Option
dFF PoAP
EB Option
FSCn SPrr
Com Option
Prnd CCon
Co1r CbS
Co2r CAd
                                                Note that parameter values are referred to in Degrees (°) and Engineering Units in the
                                                following tables. The input selection determines what the parameter values will be.
* Whenever inPS is changed, the parameter is set to the upper limit of advertised span.
36 Communications CAd 0 to 99 0
tunE
SPrd Ct1
PAL Ct2
dAL SEnS
dbAL FoP
Pb1
Pb2
rSEt
                                                           ArSt
                           Key
                            Actual Display
rAtE
                     ON     On/Off Display -
                     OFF    Use arrow keys
                            to turn on or off
                                                            A
                            Scroll Key
                            Numeric Display -
                            Use arrow keys
                            to change value
Up Arrow Key
Down Arrow
             Note: The Program, Tune and Enable Mode selections can be conveniently recorded on
             the Software Reference Sheet located in Appendix E (page 70).
                                                2. After making any changes in tuning parameters, a disturbance should be introduced into
                                                   the process so that the process reaction may be observed. This process reaction, or
                                                   recovery, will tell whether the tuning parameters provide the desired control. It is usually
                                                   easiest to make a step change in setpoint to introduce this disturbance.
                                                3. The change in setpoint, or disturbance, referenced above should be large enough to cause
                                                   an observable deviation of process from setpoint. However, this change should not be so
                                                   large that it will cause the controller output to proceed to either extreme limit.
                                                4. Controller tuning for optimal control is not hard and fast, BE PATIENT. The process will
                                                   take a certian amount of time to react to the setpoint changes during tuning. The amount
                                                   of time depends upon the specific process, however, a period of 8 to 12 minutes should be
                                                   allowed between changes. The important point to remember is to allow the process to
                                                   react completely, do not rush through tuning of the controller. If the complete process
                                                   reaction is not observed, optimum control may never be achieved.
                                                5. Time Proportioning control output(s) require(s) the cycle time to be adjusted for the
                                                   application. Short cycle times typically result in the most accurate process control, but will
                                                   cause the quickest wear out of any mechanical components.
                                                6. Leave all other tuning parameters (except for the alarm settings, if used) at the factory
                                                   default settings. Obtain the best possible process reaction by adjusting the Proportional
                                                   Bandwidth parameter. The setting that achieves the best response for the process should
                                                   be left in the controller programming, and should be noted on the Software Reference
                                                   Sheet in Appendix E (page 70).
                                                7. If there are to be no setpoint or load changes in the process, the Proportional Band
                                                   adjustment may be all that is necessary for proper control. If an offset still exists (the
                                                   process does not settle out at setpoint with the best possible proportional band adjustment)
                                                   Manual Reset may be added to eliminate this offset.
                                                8. Auto Reset may be added to eliminate offsets and improve response to setpoint and load
                                                   changes. Increase Auto Reset from 0 to 0.2 increments. Start with a small amount.
                                                   Increase this increment if there is no apparent reaction. Remember to allow the process 8
                                                   to 12 minutes to react.
                                                9. If necessary, Rate may be added. Rate is a dynamic tuning parameter. Rate may be
                                                   required to compensate for process lags or to help inhibit reset windup when a large
                                                   amount of Auto Reset (4 or 5 repeats per minute) is being used.
                                                10. Controller tuning is not hard and fast. It may be necessary to adjust the tuning
                                                    parameters over a period of time to obtain optimal control of the process.
1. Set Manual Reset rSet to 0.0, set ArSt to 0.0 and set rAtE to 0.0
                      3. Set the Proportional Band (PB) at 100 and upset the process and observe the
                 response. One easy method for imposing the upset is to move the setpoint for a
                 few seconds and then return it to its original value.
                       4. Achieve a response curve similair to the sustained oscilaltion (curve C), this is the
                          Ultimate Proportional Band (UPB) and Ultimate Time Period (UTP).
                                 a) If the response curve from step 3 does not damp out, as in Curve A from
                                    the drawing, the PB is too low. The PB should be increased and step 3
                                    repeated.
                                 b) If the response in step 3 damps out, the PB is too high. The PB should
                                    be decreased and step 3 repeated.
             These values obtained for Ultimate Proportional Band (UPB) and Ultimate Time Period (UTP)
             are used to calculate ideal P, PI, PD, PID tuning parameters using the following Ziegler-
             Nichols equations:
Period
                                                     A
                                                                    B
                                                             Curve A : unstable
                                                             Curve B : stable
                                                             Curve C : continuously cycling,
                                                                        ultimate PB and
                                                                                      period
             The capabilities available in a specific unit are dependent upon the hardware options specified
             when the instrument is ordered. Refer to Appendix C (page 61) for the decoding of the
             instrument model number. Current proportioning control cannot be implemented if a current
             output was not ordered. Position proportioning cannot be implemented if two relays (Outputs
             1 and 2) and the option have not been ordered. The available output types and quantity of
             each are as follows:
             The maximum number of SPST relay and/or SSR driver outputs available on a single instru-
             ment is three. Relay and SSR drivers may be assigned as either control or alarm outputs.
             The mADC current output(s) may be assigned control or process value retransmission
             output functions.
             Manual Reset is provided for use in lieu of, or in conjunction with automatic reset. A cycle
             time adjustment parameter is provided for use with each time proportioning control output.
             Direct/Reverse
             Operation of Outputs 4.3
             Direct operation is typically used with cooling applications. On-Off direct output(s) will turn on
             when the process variable exceeds setpoint. Proportional direct output(s) will increase the
             percentage of output as the process value increases within the proportional band.
             Reverse operation is typically used with heating applications. On-Off reverse output(s) will
             turn off when the process variable exceeds setpoint. Proportional reverse output(s) will
             decrease the percentage of output as the process value increases within the proportional
             band.
                                                When the unit is operating in the Control mode, the control algorithm determines the output %
                                                required to correct for any difference between the process value and the
                                                setpoint. The output calculation is affected by Tune mode parameter adjustments.
See Figure 4-1 (page 39) for proportional bandwidth effect on the output.
See Figure 4-1 (page 39) for proportional bandwidth effect on the output.
                                                Position Proportioning control permits the use of PID control when the final control element is
                                                a modulating device such as a motorized valve. Two outputs are required to control the
                                                valve. One output opens the valve, the second output closes the valve. The slidewire
                                                feedback is used to indicate the valve position to the instrument. The valve position will be
                                                dependant upon the process value, the setpoint and Tune mode
                                                parameters.
FIGURE 4-1
                        100%
                                                             PB=100
                      Output
                      Action
                           0%
                                     100                         150                         200
                                                                                                     Process
                                                             Setpoint                                Variable
                        100%
                                                             PB=50
                        Output
                        Action
                           0%
                                                 125            150            175
                                                             Setpoint
                             The Proportional Bandwidth is the area where the output is a percentage of the full output. The
                             size of the proportional band determines what change in the output will result from a change in the
                             process variable. In the upper figure when the process variable is at 125 the output will be at 75%
                             of full output. In the lower figure the proportional bandwidth is smaller. When the process variable
                             is at 125 the output is now at 100%. The larger the proportional band the smaller the "gain" and
                             vice versa.
                                                The output action is dependent upon the setpoint, the process value, and Tune mode parame-
                                                ters. If two proportional outputs are selected, both output proportional bands will be biased so
                                                that 0 % of output is seen when the process value equals setpoint. The output(s) can be
                                                biased by the use of the Tune mode parameters FOP and SPrd as shown below.
FIGURE 4-2
                                                 100%                                                                100%
                                                 Proportional           Reverse                                      Proportional
                                                 Output 1                                        Direct              Output 2
                                                                        Acting Output            Acting Output
                                                                                      Control
                                                                                      Setpoint
                                                                                                                                      Process
                                                                                                                                      Value
                                                                First
                                                                Output                                  Spread = Y
                                                                                              +Y
                                                                Position = X          -X
                                                The first output is programmed as a proportional reverse output and the second as a propor-
                                                tional direct output. (See Glossary, page 63, for definitions of these terms). Dual propor-
                                                tioning outputs are provided with separate proportional band and cycle time adjustments for
                                                each output.
             Switching between the automatic and manual control modes is accomplished by scrolling to
             the Standby mode and pressing the DOWN key to enter the mode. Switching from automatic
             to manual is always bumpless.
             CAUTION: If the unit is in the Manual mode, be careful not to leave the process unwatched. Since the
             unit is intentionally ignoring the setpoint, it is possible to unintentionally let the process exceed safe
             limits. Limit devices must be used to guarantee the process does not get out of control.
             The proportional output values initially displayed upon entry into the Standby mode will be the
             last output values calculated by the control algorithm. Changes made to output values are
             made "on-line".
             When the unit is placed in manual, Po1 and/or Po2, as approporiate, will appear in the
             display. If the keys are depressed within 5 second intervals, the units will respond as follows:
             If a code is displayed:
             SCROLL - The corresponding value will be displayed
             DOWN - The next code will be displayed
             If a value is displayed:
             SCROLL - The next code will be displayed
             UP - The value will increment
             DOWN - The value will decrement
             To exit from the Standby mode (manual operation), depress the UP key twice. (Pressing the
             UP key once stops the cyclic display and leaves the controller in Standby) The controller will
             be in automatic control with Stby displayed. After a time-out period, the unit will display Crtl.
             To get directly to the Ctrl display, press the UP key three times instead of twice. Shifting to
             the Control mode is balanceless.                                                                                   Key
             STANDBY MODE FLOW CHART                                                                                             Actual Display
                                                                                                                                 Scroll Key
                                                     Po1
                                                                                                                                 Numeric Display -
                                                                                                                                 Use arrow keys
                                                                                                                                 to change value
                                                     Po2
                                                                                                                                 Up Arrow Key
Down Arrow
             NOTE: If an error condition occurs while in the Manual mode and Automatic Transfer
             Function is selected, the output will go to a Failsafe condition.
                                                Sudden changes in the setpoint value entered via the keypad can be inhibited from
                                                effecting the control outputs by use of this feature. The internal setpoint used to control
                                                the process will ramp to the setpoint value entered at the rate of change selected.
FIGURE 4-3
                                                                                                Setpoint Ramp
                                                                          205
                                                                          204
                                                               Setpoint   203
                                                               in         202
                                                               Degrees
                                                                          201
                                                                          200
                                                                                       0             5          10
                                                                                            Time in Minutes
                                                Remote Setpoint
                                                Remote Setpoint adjustment is an optional feature. The instrument setpoint can be
                                                adjusted by supplying a signal to the remote setpoint terminals as indicated in the
                                                installation section. Local or Remote setpoint operation is selected by pressing and
                           Key                  releasing the SCROLL key until the display reads setpoint select SPS. Press the DOWN
                                                key to enter the Setpoint Select mode. The display will change to show the current
                            Actual Display      setpoint mode, either local loc or remote rSP. To change the setpoint mode press the
                                                SCROLL key. To exit the setpoint mode press the UP key. To prevent unwanted setpoint
                                                mode changes, the Setpoint Select mode can be disabled in the Enable mode. The
                     ON     On/Off Display -
                     OFF    Use arrow keys      setpoint value can be adjusted by using the Digital Communcations Option. Refer to the
                            to turn on or off   Protocol Manual (Form 2878) for more details about this option.
                            Up Arrow Key
                                                                                      LOC
Down Arrow
rSP
             The example illustrated in Figure 4-4 (below) shows a process re-transmission application for
             0 to 200 degrees F.
FIGURE 4-4
100 %
OUTPUT
                                       0%
                                             0° F          INPUT                200° F
             The example illustrated in Figure 4-5 (below) shows a setpoint re-transmission application for
             0 to 400 degrees F.
FIGURE 4-5
OUTPUT
                                    0%
                                          0° F             SETPOINT             400° F
                                                 Calibration 5.2
                                                 Caution: Do not attempt any of these calibrations without the proper test equipment with specifications
                                                 equal to or better than those listed.
                                                 Press and release the SCROLL key to sequence the display until CAL appears. If CAL does
                                                 not appear, refer to Section 3 for instructions on how to enable the Calibration mode. When
                                                 CAL appears on the display, press the DOWN key. The display will read CAL 1. CAL 1 can
                                                 be initiated at this time or press the SCROLL key to advance the display to the other calibra-
                                                 tions available.
CAL Prog
CAL1
CAL2
CAL3
                           Key
                                                                                      CAL4
                             Actual Display
                     ON      On/Off Display -
                     OFF     Use arrow keys
                                                                                      CAL5
                             to turn on or off
Scroll Key
Up Arrow Key
                                                                                      CAL7
                             Down Arrow
             Calibration
             Procedure           Description
             CAL 2               Main Calibration used by all inputs. This is the only calibration required
                                 for voltage and millivolt inputs.
             CAL 4               Cold Junction utility. The temperature of the cold junction is displayed.
                                 No adjustment is made with this procedure.
             CAL 5               RTD input calibration used to correct for component differences in the
                                 RTD input circuit.
             With CAL1 displayed, depress and hold the DOWN key, then press the SCROLL key. The
             display will momentarily go blank. Release the keys. CAL1 will reappear on the display. This
             calibration can be done again or another may be selected.
             A 50.00 ± .01mVDC source is required for calibrating. In addition make sure that JU1 on the
             Processor board is in the “non volt” position. See Appendix A-2 (page 60).
             Make sure all input wiring is disconnected. Short the input terminals 1 and 3 or apply 0.00
             mV to the input. With CAL2 displayed, press and hold the DOWN key, then press the
             SCROLL key. Release both keys and the instrument will display hLd1. Depress the DOWN
             key; dELy will appear for up to ten seconds, then SCAn will appear for up to ten seconds. If
             the calibration reference number which appears is not between -50 and +50, proceed per
             note below. Otherwise, connect a 50.00 ± .01mV source to the input terminals. Press the
             DOWN key and deLy will be displayed for ten seconds and then SCAn for ten seconds. Then
             CAL2 will reappear. If there is a problem, the appropriate error code will be displayed.
             Restore JU1 to the position necessary for the input type.
             NOTE: If the calibration reference number falls outside the -50 to +50 range, depress
             the SCROLL key and CAL2 will be displayed. Depress the DOWN key and perform the
             calibration once more. Repeat the calibration until the number falls within the toler-
             ance limits. If the calibration number remains outside these limits, check the connec-
             tions to the test equipment and try the calibration again. If the number still does not
             approach the tolerance limits contact an Applications Service Engineer at the factory
             or a local representative.
                                                With CAL2 displayed, press and hold the DOWN ARROW key, then press the SCROLL key.
                                                Release both keys and the instrument will display hLd1. Press and hold the UP ARROW key,
                                                then press the SCROLL key. The display will momentarily blank and then CAL1 will be
                                                displayed. Release both keys and depress the UP ARROW key. CAL will be displayed.
                                                Test equipment: one type J thermocouple and one mercury thermometer, accurate to ± .25
                                                degrees C or equivalent are required.
                                                Make sure all input wiring is disconnected and connect the J thermocouple to the input. Place
                                                the thermometer next to the thermocouple and allow the controller to warm up for 30 minutes,
                                                before proceeding with the calibration.
                                                With CAL3 displayed, depress and hold the DOWN key. Then press the SCROLL key and
                                                the unit will display hoLd. Release both keys. Press the DOWN key and deLy will be
                                                displayed for ten seconds, then SCAn for ten seconds. If SCAn remains in the display for
                                                much longer than ten seconds, refer to the note below. The instrument will compute and
                                                display the cold junction temperature to the nearest tenth of a degree C. Compare reading
                                                with thermometer and use the UP and DOWN keys to correct the reading, if necessary. To
                                                end the procedure press the SCROLL key and CAL3 will be displayed again.
                                                NOTE: If the instrument continues to display in SCAn, proceed as follows. With SCAn
                                                displayed, press the SCROLL key. CAL3 should be displayed. With CAL3 displayed, while
                                                pressing the DOWN key, press and release the SCROLL key. The instrument will display
                                                hoLd. Press the UP key. The instrument will begin the calibration procedure with a default
                                                value and proceed to deLy. Complete calibration as described above.
                                                Error Recovery - see 5.4 ( page 52) for details on specific errors. The calibration can be
                                                exited at any time hoLd is displayed by pressing the SCROLL key.
                                                With CAL4 displayed, press and hold the DOWN key then press the SCROLL key and
                                                release both keys. SCAn will be displayed for ten seconds while the instrument
                                                computes the CJC temperature. The result will then be displayed to a tenth of a degree C.
                                                The input terminals must be shorted with a jumper wire. Remember, the temperature
                                                displayed is that of the CJC terminals not the ambient temperature. To exit, press the
                                                SCROLL key and CAL4 will be displayed.
             Test equipment needed will include a Decade Box (Resistance Substitution ) with .01%
             resolution or equivalent. Make sure the jumpers JU1 (Processor Board), JU2 and JU3
             (Options boards) are in the proper positions for RTD input. See Appendix A-2 (page 60) and
             A-3 (page 61, 62).
             With CAL5 displayed press and hold the DOWN key, then press the SCROLL key and
             release both keys. hLd1 will then be displayed. Connect the Decade Box at 100 ohm setting
             across the input terminals 1 and 3 and Jumper terminals 1 and 5. Press the DOWN key and
             dELy will be displayed for up to ten seconds, then SCAn for ten seconds. When hLd2 is
             displayed, connect 277 ohms to the input and press the DOWN key. Again dELy will display
             for up to ten seconds, followed by SCAn for ten more seconds. CAL5 will be displayed after
             the calibration is completed.
Error Recovery - See section 5.4 (page 51) for details about specific errors.
             The Calibration mode can be exited any time the unit displays hLd1 or hLd2 by pressing the
             SCROLL key.
                                                 All available test procedures are listed in TABLE 5-2 (page 49). Test 1, 2, and 3 are per-
                                                 formed on start up, periodically during Control, and on entry into the Test mode. Test 4 is
                                                 executed on entry into and periodically during the Control mode. These tests can be used as
                                                 trouble-shooting aids.
tESt
tSt1
tSt4
tSt5
tSt6
Key tSt7
Actual Display
Scroll Key
                                                                                                tSt9
                             Numeric Display -
                             Use arrow keys
                             to change value
                             Up Arrow Key
                                                                                                tStA
                             Down Arrow
TEST DESCRIPTION
             Test 1    Microprocessor internal RAM test.; used to verify that the processor RAM is
                       functioning correctly.
             Test 2    External RAM test; used to test the instrument’s RAM for proper
                       function.
Test 3 EPROM checksum test; used to check program for correct data.
             Test 4    External RAM checksum test; displays the number of times Error 16
                       and 17 have occurred.
Test 5 Verifies that all keys are functional and all LED displays are working.
Test 6 Used to verify that all relays and/or solid state relay driver outputs are working.
Test A Communications hardware test; tests the send and receive functions.
                                                           KEY                       DISPLAY
                                                           SCROLL                    SCRL
                                                           UP KEY                    uAro
                                                           DOWN KEY                  dAro
                                                           UP AND DOWN KEYS          ALL LED’s AND SEGMENTS LIGHTED
To exit Test 5, press the SCROLL and UP key simultaneously. tSt5 will be displayed.
                                                           DISPLAY          RELAY ON
                                                           rLYA             A Only
                                                           rLYb             B Only
                                                           rLYC             C Only
                                                           oFF              None
                                                The relays should be checked for continuity when on and high impedance when off. SSR
                                                drivers will output 5 VDC when on and 0 VDC when off. This sequence may be repeated by
                                                using the DOWN key. To exit press the SCROLL key and tSt6 will be displayed. The
                                                existence of relay SSR outputs is dependent upon the hardware configuration.
             The existence of the auxiliary input tested in Test 9 depends upon the hardware
             configuration as indicated by the model number.
             In the SEnd (send or transmit) mode, the instrument will repeat the following sequence.
             First, the transmitter will go logic 1 for one second. Next, the transmitter will change the
             logic level to 0 for one second. Then, the transmitter will be disabled for one second. In the
             rEC mode, the transmitter will be disabled. In either mode, the instrument will monitor the
             line logic level. The display will be rEC0 when a logic 0 is on the line . The display will be
             rEC1 when logic 1 is on the line. In the SEnd mode, the unit will display rEC when the
             transmitter is disabled.
             To perform an internal test to verify the operation of the hardware, place the instrument in
             the Send mode. Verify that the display cycles through rEC1, rEC0, and rEC. To verify that
             the transmitter functions properly, two LED’s, each with a current limiting resistor, can be
             connected to the communications terminals, with their polarities connected opposite of each
             other. The following three states will be produced: one LED on, then the other LED on, then
             both off. Alternately, a load resistor can be placed on the terminals, the voltage generated
             across the load resistor is as follows: > +3 VDC then > -3VDC and then 0 VDC. The terminals
             used are 7 & 8.
             Another test method, would be to connect one or more instruments in the Receive mode to an
             instrument in the Send mode. The instruments in the Receive mode should have their display
             alternating in sync with the instrument that is in the Send mode. When the sending unit
             displays rEC, the receiving units should display rE1.
             To terminate the test, press the SCROLL key for one second. Upon exit, tStA will be dis-
             played.
                                                Trouble-shooting should be performed by qualified personnel using the proper equipment and
                                                following all safety precautions. Whenever possible, the trouble-shooting should be accom-
                                                plished with the electrical power disconnected. The instrument contains static sensitive
                                                components so care should be taken to observe anti-static procedures.
                                                Model Number Displayed              1. Turn off the instrument power, wait 5 seconds then
                                                is incorrect                           reapply the power. Verify that the number dis-
                                                                                       played during the power up sequence is the same
                                                                                       as indicated on the label affixed to the lower front
                                                                                       of the display bezel.
             Relay/SSR Driver Output(s)             1. Verify that the Program and Tune mode
             Malfunction                                parameters are correctly set (pages 28 & 33 or the
                                                        Software Ref. Sheet, page 70, if already filled out).
                                                    2. Turn off the power to the instrument. Wait about 5
                                                        seconds and turn the power on again. Confirm
                                                        that the model number displayed during the power
                                                        up sequence indicates that the output(s) is/are
                                                        present in the instrument. This number should
                                                        match the number on the label affixed to the lower
                                                        front of the display bezel. If model # is incorrect,
                                                        follow steps for "Model # displayed is incorrect".
                                                    3. Turn off the power to the instrument. Loosen the
                                                        front panel screw and remove the unit from the
                                                        housing. Inspect the Power Supply board
                                                        (Appendix A-1, page 59) for the presence of the
                                                        output device(s). Relay A is located at K1, Relay
                                                        B at K2, and Relay C at K3. A relay output will
                                                        appear to be a cube. The SSR Driver will appear
                                                        as a resistor and a jumper wire. The output will
                                                        not work if the hardware is not present.
                                                    4. Check the output operation by performing Test 6
                                                        as described in the Test section (page 48). If the
                                                        output(s) function(s) in the Test Mode re-examine
                                                        the Program and Tune Mode Parameters settings
                                                        (page 28 & 33, or the Software Ref. Sheet, page
                                                        68, if already filled out).
                                                    5. If the output appears not to turn off, remove the
                                                        power to the instrument. Loosen the front panel
                                                        screw and take the unit out of the housing. Clip
                                                        the resistor located on the Power Supply
                                                        (Appendix A-1, page 59) for the output(s) that
                                                        seem to stay on. A .01 microfarrad, 1 KV capacitor
                                                        should be connected from the terminal listed below, to
                                                        the AC ground for the output where the resistor
                                                        indicated was removed.
                                                               Relay A             R12       Terminal C
                                                               Relay B             R13       Terminal E
                                                               Relay C             R14       Terminal G
                                                       (Continued on next page)
             Hi - Input more than 10%               1. Perform the steps listed for the SnSr error
             Over Span                                 condition (page 54).
             Lo - Input more than 10%               1. Perform the steps listed for the SnSr error
             Under Span                                condition (page 54).
             Er 2 - External RAM Failure            1. Turn off the power to the instrument. Wait 5
                                                       seconds, and turn the power on.
             Er 3 - EPROM Checksum                  1. Perform the steps listed for Er 1 except that the
             Failure                                   EPROM (U2) on the Processor board should be
                                                       inspected.
                                                Er 8 - Cal 2 Volt Input Error   1. Check that 50 mVDC is properly connected to the
                                                                                    instrument and is within the tolerance limits as
                                                                                    indicated in the CAL 2 procedure of the Calibration
                                                                                    section (page 45).
                                                                                2. Loosen the front panel screw and remove the
                                                                                    instrument from the housing. Inspect the
                                                                                    Processor board (Appendix A-2, page 60) to
                                                                                    insure that the input conditioning jumper JU 1 is in
                                                                                    the non-volt position.
                                                                                3. Perform the CAL 2 procedure as described in the
                                                                                    Calibration section (page 45).
             Er 13 - RTD CAL 5 Input Error          1. Check that the resistance device is of the correct
                                                        value and properly connected to the instrument
                                                        and is within the tolerance limits as indicated in the
                                                        CAL 5 procedure of the Calibration section (page
                                                        47).
                                                    2. Loosen the front panel screw and remove the
                                                        instrument from the housing. Inspect the
                                                        Processor board (Appendix A-2, page 60) to
                                                        insure that the input conditioning jumper JU1 is in
                                                        the non-volt position and that the Option board
                                                        jumpers JU2 and JU3 are in the RTD position.
                                                    3. Perform the CAL 5 procedure as described in the
                                                        Calibration section (page 47).
                                                Er 37 - Incorrect Micro.       1. Turn off the power to the instrument, wait 5 seconds,
                                                For Digital Comm.                 then turn the power on.
                                                                               2. Check to see if U1 is marked "8032" (see Appendix
                                                                                  A-2, Page 60).
TOP
                       R14
                               RELAY C
                                                                                        FRONT
                                                                                        OF UNIT
                       R13
                                                       115 VAC JUMPER POSITION
                                RELAY B
                                                 JU6
                                                 JU5
                       R12
                                RELAY A          JU4
COMPONENT SIDE
Revision L, M and M2
                                                                                                                                              J12
                                                                                                                JU2
MICRO U1 Y1
                                                           FRONT                                                      REV
                                                           OF UNIT
                                                                                          EPROM        U2
                                                                                                                                        JU1
                                                                           BATTERY        RAM         U3
COMPONENT SIDE
                                                                                                                                                 J12
                                                                                                                  JU2
                                                                                         MICRO     U1                   Y1
                                                                                                                                              Rev. M2 and
                                                                                                                                              above only
                                                            FRONT                                                       REV
                                                            OF UNIT
                                                                                           EPROM           U2
                                                                                                                                           JU1
                                                                               BATTERY      RAM         U3
COMPONENT SIDE
FIGURE A-3 - Option Board, Revision E and above (For Rev. D and below, see next page)
                                                                                                                     REV
                                                                                                        JU1
                                                                                      JU2                       JU14
                                                                                JU3
                                                                                                       J16
JU13
J15
                                                                                                      JU3
                                                JU1
                                                                              JU2
                                Com                                                                          RTD
                               RS-485                                         RTD
                              Com &
                             2nd 4-20
                                                                              XPS
                         *Pos. Prop. &                                                                       XPS
                           Alt. Com
                               RSP &
                                Com
                                 Alt.
                                 Com
TOP
REV
                                                 FRONT
                                                 OF UNIT
                                                                            For 2nd 4-20mA,
                                                                                                   JU1
                                                                            U5 is populated
                                                                                     U5
                                                                                                                    JU2
                                                                       U1
                                                                             For 1st 4-20mA,                  JU3
                                                                             U1 is populated
COMPONENT SIDE
                                                                                                             JU2
                                                            JU1
                                                                                                                   RTD
                                                                     2ND 4-20 mADC
                                                                     DIGITAL
                                                                     COMMUNICATIONS                           T/C , mV , VOLT
                                                                     422/485                                  (NON-RTD)
             Automatic Transfer
             Automatic transfer is a Program mode parameter that will allow the instrument to switch from
             the Manual to the Control mode of operation automatically when the process value reaches
             setpoint.
             Balanceless Transfer
             This feature prevents changes in proportional output when changing from the Manual to
             Control mode of operation. When transferring from the manual mode to the control mode, the
             proportional outputs will be "balanceless" regardless of whether the unit is inside or outside
             the proportional band. This only holds true if the Auto Reset (ArSt) value is greater than 0.
             Bumpless Transfer
             This feature prevents changes in proportional outputs when changing from the Control to the
             Manual mode of operation only.
             Control Algorithm
             A pre-programmed series of instructions that are used by the instrument when
             determining the status of the output(s).
             Cycle Time
             This Tune mode parameter is used to select the on/off cycle time for time proportioning
             outputs (Ct1 for Output 1 and/or Ct2 for Output 2). (See page 29, section 4.5)
             When using the Position Proportioning option, Ct1 must be selected for the stroke time of the
             motor.
                                                Input Correction
                                                This parameter is used to adjust the process variable value to compensate for sensor errors.
                                                This Program mode parameter is selectable from -300 to + 300 degrees/units. The factory
                                                default is 0.
                                                Manual Reset
                                                This parameter is adjustable from -1500 to 1500 units representing a manual shift of propor-
                                                tional band(s) relative to the normal position. Manual reset is intended to be used when
                                                automatic reset is not used to allow compensation for deviations from setpoint which remain
                                                after the process has stabilized. Factory default is 0. Increasing the value increases the
                                                process variable, i.e. if the process variable stabilized too low, increase the manual set.
                                                Integral action, and conversely reset-windup inhibit apply over the same process value range
                                                regardless of the manuals reset value. Display code rSEt.
                                                Process Output Upper and Lower Values (Used in conjunction with process or setpoint
                                                retransmission output)
                                                These parameters specify the process or setpoint value range over which the assigned
                                                current output will vary in a linear manner from 100% to 0%. If the process or setpoint value
                                                is greater than Pou, the output will be 100%. If the process or setpoint value is less than PoL,
                                                the output will be 0%. Factory default values are 2000 for the upper value and 0 for the lower
                                                value. Display codes Pou (upper) and PoL (lower).
                                                Process Rounding
                                                This Program mode parameter is used to determine the step size of the process value that
                                                will be seen on the display. This feature can be used to reduce display fluctuation. This
                                                parameter is adjusted from 1 to 100 degrees/units. The factory default is 1, no rounding (e.g.
                                                Process rounding = 2, Process Value Display - 4, -2, 0, 2, 4, etc.).
                                                Process Variable
                                                The process variable refers to the condition of the process being measured (sensed). The
                                                instrument will accept process inputs other than temperature (pressure, level, flow, etc.).
                                                Proportional Band
                                                This Tune mode parameter selects the span of the proportional output range. This parameter
                                                is adjustable from 1 to 3000 degrees/units. Factory default is 100. If Output 1 is selected as a
                                                proportional output, a display code of Pb1 will be seen. If Output 2 is selected as a propor-
                                                tional output, the display code will be Pb2.
                                                 Input
                                                 1 T/C or MV
                                                 2 Volts/MA
                                                 3 RTD
                                                 4 All Inputs
                                                 Output 1
                                                 1 Relay
                                                 2 SSR Driver
                                                 3 4-20mA
                                                 Output 2
                                                 0 None
                                                 1 Relay
                                                 2 SSR Driver
                                                 3 4-20mA
                                                 Alarm
                                                 0 None
                                                 1 Relay
                                                 2 SSR Driver
                                                 Remote
                                                 0 None
                                                 1 Position Prop. *
                                                 2 Remote Setpoint
                                                 3 RS-485 Standard Com. **
                                                 5 RS-485 Total Access Com. **
                                                 Voltage
                                                 1 115VAC Input & Relays
                                                 2 230VAC Input & Relays
                                                 3 115VAC Input, 230VAC Relays
                                                 Option Suffix
                                                 None    (blank)
                                                 EA      Extended Features Software
                                                 EB      Extended Features Software***
                                                 XP      24VDC Transmitter Power Supply
                                                 XA      24VDC Power Supply
                                                 BA      Remote Keypad
             Input Specifications
             THERMOCOUPLE
             TYPE    RANGE                          TYPE    RANGE
                S        200 TO 1650C
                         400 TO 3000F
                                                ALARM OUTPUT
                                                Relay Output       SPST
                                                                   115 VAC: 5.0 A Resistive; 1/8HP or 250 VA
                                                                   230 VAC: 2.5 A Resistive; 1/8HP or 250 VA
                                                Display Specifications
                                                Digital Display    Four (4) 7 segment LED’s each; .56 inches high
                                                Status Indicators Individual LED indicators for Setpoint, Out 1, Out 2, Manual,
                                                Alarm, Degrees F, Degrees C, or Engineering Units, minus sign for negative values
             Auto Reset Windup Inhibit Auto reset is disabled when the process is outside of
                                       the proportional band
Dimensions 1/4 DIN front panel (96mm X 96mm) 5.8 inches deep
                                                                          EB
                                                     ICor                        SPrr               EtSt
                                                     out1                        CCon               ECAL
                                                                          Comm
                                                     o1PL                        CbS                EPro
                                                     out2                        CAd                Etun
                                                     o2PL                                           ESby
                                                     out3                                           ESPS
                                                     rLyA                                           ESPC
                                                     rLyb
                                                     rLyC                               Tune Mode
                                                     diSP                        SPrd
                                                     dPoS                        PAL
                                                     Euu                         dAL
                                                     EuL                         dbAL
                                                     HySt                        Pb1
                                                     rSP                         Pb2
                                                     rSPu                        rSEt
                                                     rSPL                        ArSt
                                                     SPL                         rAtE
                                                     SPuL                        Ct1
                                               EA
                                                     SPLL                        Ct2
                                                     AtFr                        SEnS
                                                     PFF                         FoP
                                                     dFF
                                                     FScn
                                                     Prnd
                                                     Co1r
                                                     Co2r
                                               EA
                                                     Pout
                                                     Pou
                                                     PoL
                                                     PorA
                                                     POAP
             Warranty
             These products are warranted to be free from functional defects in materials and workman-
             ship at the time the products leave the factory and to conform at that time to the specifications
             set forth in the relevant instruction manual or manuals, sheet or sheets, for such products for
             a period of three years.
             Limitations
             The factory shall not be liable for any incidental damages, consequential damages, special
             damages, or any other damages, costs or expenses excepting only the cost or expense of
             repair or replacement as described above.
             Products must be installed and maintained in accordance with factory instructions. Users are
             responsible for the suitability of the products to their application. There is no warranty against
             damage resulting from corrosion, misapplication, improper specifications or other operating
             condition beyond our control. Claims against carriers for damage in transit must be filed by
             the buyer.
             This warranty is void if the purchaser uses non-factory approved replacement parts and
             supplies or if the purchaser attempts to repair the product themselves or through a third party
             without factory authorization.
             Returns
             The factory’s sole and exclusive obligation and buyer’s sole and exclusive remedy under the
             above warranty is limited to repairing or replacing (at factory’s option), free of charge, the
             products which are reported in writing to the factory at its main office indicated below.
             The factory is to be advised of return requests during normal business hours and such returns
             are to include a statement of the observed deficiency. The buyer shall pre-pay shipping
             charges for products returned and the factory or its representative shall pay for the return of
             the products to the buyer.