                                                               SUMBAWA LNG TERMINAL &
                                                                   REGAS FACILITY
                                                                                        CLASS 1
                                   17 Feb 2024
                                                                            XLW
                                 FOR CONSTRUCTION
REV.    DATE       PAGE        DESCRIPTION
 3E    05-Feb-24    All   Re-Approved for Construction    S. Juliana        M. Suwita   R. Hardian
 3D    21-Dec-23    All   Re-Approved for Construction    S. Juliana        M. Suwita   R. Hardian
 3C    08-Nov-23    All   Re-Approved for Construction    S. Juliana        M. Suwita   R. Hardian
 3B    15-Sep-23    All   Re-Approved for Construction    S. Juliana        M. Suwita   R. Hardian
 3A    30-Jun-23    All    Approved for Construction      S. Juliana        M. Suwita   R. Hardian
1.
     PT. Amman Mineral Nusa Tenggara (AMNT) plans to build additional combine cycle power generation
     plant for their expansion projects including smelter and other new facilities. To provide gas for those
     facilities AMNT engaged PT. Amman Nusantara Gas (ANG) to develop and operate a new LNG Terminal
     and Regas Facility within AMNT operation area in Benete Bay of Sumbawa Island, West Nusa Tenggara,
     Indonesia.
     The project includes facilities of onshore LNG storage tank with capacity of 50,000 m3 and 135,000 m3,
     regasification unit to produces up to 77 mmscfd gas, an LNG-Carrier jetty with trestle, utilities, buildings
     and gas sendout pipelines to the power plant and smelter.
2.
     This document comprises the basic requirements of the design features, capacities, inspection and testing
     of safety equipment to be provided for EPCC Sumbawa LNG Terminal and Regasification Facility Project.
3.
     COMPANY                 : PT. Amman Nusantara Gas
     CONTRACTOR              : PT. JGC Indonesia
     AMNT                    : PT. Amman Mineral Nusa Tenggara
     AMIN                    : PT. Amman Mineral Industri
     VENDOR                  : Vendor of Safety Equipment
                   Abbreviations                                               Description
              ANSI                            American National Standards Institute
              ASME                            American Society of Mechanical Engineers
              BS                              British Standard
              EPDM                            Ethylene Propylene Diene Monomer
              FAA                             Federal Aviation Administration
              IP                              Ingress Protection
              LNG                             Liquified Natural Gas
              NFPA                            National Fire Protection Association
              SCBA                            Self-Contained Breathing Apparatus
              SOLAS                           Safety of Life at Sea
              VTA                             Vendor to Advise
              VTC                             Vendor to Confirm
THIS DOCUMENT / DRAWING INCLUDING ATTACHEMENT EMBODIES PROPRIEATRY INFORMATION OF PT. AMMAN NUSANTARA GAS IN ANY FORM OR MEDIUM TO
THIRD PARTIES OR USED FOR OTHER THAN THE PURPOSE FOR WHICH IT HAS BEEN PROVIDED IN WHOLE OR IN PARTY IN ANY MANNER EXCEPT AS EXPRESSLY
                                               PERMITTED BY PT. AMMAN NUSANTARA GAS.
4.
     The following Codes and Standards apply to this philosophy.
     4.1. CONTRACTOR Document
              No.     Document Number                                                  Title
               1.     S-000-1241-001                Design Basis for Fire Protection and Fire and Gas Detection
                                                    System
               2.     D-000-1241-009                Safety Equipment Layout LNG Terminal & Regas Facility
               3.     D-000-1241-010                Safety Equipment Layout LNG Trestle & Jetty Area
               4.     D-000-1241-011                Safety Equipment Layout LNG Utility & Building Area
     4.2. Codes and Standards
                  Standard Number                                                     Title
                 NFPA 10, Ed. 2022              Standard for Portable Fire Extinguisher
                 NFPA 17, Ed. 2021              Standard for Dry Chemical Extinguishing System
                NFPA 170, Ed. 2021              Standard for Fire Safety and Emergency Symbols
               ANSI Z358.1, Ed. 2014            Standard for Emergency Eyewash and Shower Equipment
                ANSI Z535, Ed. 2022             Standard for Safety Sign and Colours
                 EN 137, Ed. 2006               Respiratory Protective Devices. Self-contained open-circuit
                                                compressed air breathing apparatus with full face mask.
                                                Requirements, testing, marking
                  BS 5499, Ed. 2013             Fire Safety Signs, Notices and Graphic Symbols
                   SOLAS, 1974                  Safety of Life at Sea
                 ISO 7010, Ed. 2019             Graphical Symbols Safety Colours and Safety Signs
                Permenakertrans No.             First Aid in Workplace
                PER15/MEN/VIII/2008
5.
     The following environment conditions prevailing at sites:
              Ambient Temperature
              Maximum           : 40.2 °C
              Minimum           : 18.8 °C
              Average           : 27.6 °C
              Relative Humidity
              Maximum           : 100%
              Minimum           : 24%
              Average           : 80.8%
THIS DOCUMENT / DRAWING INCLUDING ATTACHEMENT EMBODIES PROPRIEATRY INFORMATION OF PT. AMMAN NUSANTARA GAS IN ANY FORM OR MEDIUM TO
THIRD PARTIES OR USED FOR OTHER THAN THE PURPOSE FOR WHICH IT HAS BEEN PROVIDED IN WHOLE OR IN PARTY IN ANY MANNER EXCEPT AS EXPRESSLY
                                               PERMITTED BY PT. AMMAN NUSANTARA GAS.
6.
     Vendor shall supply complete recharging unit for dry chemical fire extinguisher including dry chemical and
     cartridge.
7.
     All safety signs shall be outdoor signs, with the following details:
          1. The base shall be galvanized plate or equivalent with 2 mm thickness.
          2. Constructed of self-adhesive vinyl or plastic and weather proof material for the sign color and
              pictogram/symbol or text.
          3. The text should be contrast color with the background for better visibility.
          4. The color, pictograms/symbol and text prints shall be laminated for protection.
          5. All safety signs shall be printed with photoluminescent.
          6. All safety signs should be easily viewed.
          7. Vendor shall confirm and inform Purchaser the adequate size for 2 languages, Bahasa Indonesia
              and English required on the safety sign with the font size of minimum 30 mm.
          8. All safety sign shall be mounted typed and equipped with fixing holes. Each fixing hole shall be a
              minimum of 4 mm diameter on the smaller sign types, and 8 mm diameter on larger signs, where
              required.
          9. Required bolt and nuts for fixing shall be provided by VENDOR.
8.
     Testing of fire protection equipment shall be described below:
         1. All safety equipment shall be inspected / tested at shop before shipment in accordance with
             VENDOR
         2. VENDOR shall also make a scope of inspection table, which shows the kind of test, and inspection
             to be carried out at shop. Purchaser shall decide the necessity of witness by the parties after
             reviewing the procedure and kind of test of inspection.
         3. Before delivery, all the safety equipment / system shall be adequately tested and inspected in
             terms of performance, operability, conformance with the general design specification including
             dimension check and visual examination.
THIS DOCUMENT / DRAWING INCLUDING ATTACHEMENT EMBODIES PROPRIEATRY INFORMATION OF PT. AMMAN NUSANTARA GAS IN ANY FORM OR MEDIUM TO
THIRD PARTIES OR USED FOR OTHER THAN THE PURPOSE FOR WHICH IT HAS BEEN PROVIDED IN WHOLE OR IN PARTY IN ANY MANNER EXCEPT AS EXPRESSLY
                                               PERMITTED BY PT. AMMAN NUSANTARA GAS.
    9.2. BC Dry Chemical Portable Fire Extinguisher
           All technical requirements of BC Dry Chemical Portable Fire Extinguisher are specified as follows:
                               BC DRY CHEMICAL PORTABLE FIRE EXTINGUISHER
     Quantity                                            32 ea (outdoor), 5 ea (indoor)
     Design Requirements
         Type                                            BC type dry chemical with gas cartridge
         Standard                                        Comply with NFPA 10 or equivalent
         Fire Class                                      B:C
         Fire Rating (NFPA 10)                           80-B:C
         Agent Capacity                                  9 kg (20 lb)
         Agent Type                                      Potassium bicarbonate (Purple-K or equivalent)
         Propellant Type                                 N2 gas cartridge
         Nozzle type                                     Squeeze Nozzle
         Effective Range                                 15 ft minimum
         Discharge Time                                  Min. 15 seconds
         Shell Material (Note 3)                         Steel with corrosion resistant coating
         Gas Cartridge & Tube Material                   Steel
         (Note 3)
         Discharge Hose Material (Note 3)                Neoprene or EPDM
         Nozzle Material (Note 3)                        Stainless Steel (ANSI 316 L)
         Bottom Skirt                                    Be provided with a detachable neoprene lining, grooved
                                                         to fit the base rim
         Handle                                          Non-slip handle made of steel
         Cartridge guard                                 Yes
         Cap Indicator                                   Yes
         Hose Retainer                                   Yes
         Mounting                                              Wall hanger (Note 1)
                                                               Dyna bolt shall be provided
                                                               Vehicle type mounting bracket (Note 2)
                                                            Bolts and Nuts shall be provided
         Colour of extinguisher body                     Red
         Marking
                                                              Agent Capacity in lbs
                                                              Class of fire (pictogram)
                                                              Fire rating
                                                              Approval standard
                                                              Operating instruction in Bahasa Indonesia and
                                                              English with pictogram
                                                              A warning shall also state whether or not the
                                                              extinguisher is suitable for use on live electrical
                                                              installations
THIS DOCUMENT / DRAWING INCLUDING ATTACHEMENT EMBODIES PROPRIEATRY INFORMATION OF PT. AMMAN NUSANTARA GAS IN ANY FORM OR MEDIUM TO
THIRD PARTIES OR USED FOR OTHER THAN THE PURPOSE FOR WHICH IT HAS BEEN PROVIDED IN WHOLE OR IN PARTY IN ANY MANNER EXCEPT AS EXPRESSLY
                                               PERMITTED BY PT. AMMAN NUSANTARA GAS.
                               BC DRY CHEMICAL PORTABLE FIRE EXTINGUISHER
                                                              The name of manufacturer(s)
                                                              Instruction to check regularly the extinguisher for
                                                              operational serviceability
                                                              The year of manufacture
                                                              The test pressure and work pressure
         Parts/Accessories (Note 3)                           Robust wall brackets for outdoor service with
                                                              expansion bolts and nuts. Vendor shall submit the
                                                              drawing of expansion bolts
                                                              The heavy red vinyl cover for extinguisher protection
                                                              from weather condition shall be provided and
                                                              located outdoor
                                                              Instruction for refilling and special tools for that work
                                                              shall be provided for each unit.
                                                              Portable dry chemical extinguisher standard
                                                              accessories, if any, Vendor to propose.
                                                              Inspection record tag shall be provided for each
                                                              portable extinguisher
                                                            Stainless steel tag plate
         Test and Inspection                             As per applicable NFPA standard
         Approval                                        UL Listed / FM Approved
     Notes:
       1. For fire extinguisher being placed inside building.
       2. For fire extinguisher being placed outside building.
       3. Material shall be suitable for outdoor, salty, and marine environment.
         Reference Drawing:
                Figure 9-2: Example Drawing for BC Dry Chemical Portable Fire Extinguisher
                                                      (for illustration only)