NE300 series drive technical specifications:
Rated power/
                                          3-phase 380V ~ 440V; 50Hz/60Hz
        Input          frequency
                      Voltage range       304V ~ 456V; Voltage unbalance degree: d 3% ; Permissable frequency fluctuation: ±5%
                      Voltage range       0~380V/440V
       Output                             Type G: 150% rated current 1min, 180% rated current 20s
                    Overload capacity
                                          Type P: 120% rated current for 1min, 150% rated current for 1s
                      Control mode         Vector control with PG(VC)         Vector control without PG(SVC)                     V/F control
                      Startup torque              0.00Hz 180%                            0.5Hz 150%                              1.5Hz 150%
                   Speed adjust range                 1:1000                                 1:100                                   1:50
       Control      Speed stabilization
                                                      ± 0.02%                               ± 0.2%                                  ± 0.5%
       features         precision
                      Torque control                    Yes                                  Yes                                     N/A
                     Torque precision                  ± 5%                                 ± 10%                                    ----
                   Torque response time               <10ms                                <20ms                                     ----
                                          Torque/speed control switching, Multi-function input/ output terminals, under voltage regulation, AC
                                          operation grounding switching, flying start, torque limit, multi speed operation, autotune, S curve Acc/
                      Key functions
                                          Dec, slip compensation, PID regulation, simple PLC, fix length control, droop control, current control,
                                          manual/ automatic torque increase, current limit, AVR function
                     Frequency setup      Keypad, terminal Up/Down, communication, Analog input AI1/AI2, Terminal pulse input X4,X5
                    Output frequency      0.00~550.0Hz
                    Startup frequency     0.00~60.00Hz
       Product
      functions       Acc/Dec time        0.1~3600s
                                        400V drive: braking unit voltage: 650 ~ 750V;
                     Dynamic braking
                                        200V drive: braking unit voltage: 360 ~ 390V;
                                        DC braking activation: 0.00 ~ 550.0Hz
                   DC injection braking DC braking current: G type 0.0 ~ 100.0%; P type 0.0 ~ 80.0%
                                        DC braking time: 0.0 ~ 30.0s; Quick DC brake activation without lag time
                   Magnetic flux braking Fast deceleration through adding motor magnetic flux
                    Parameter cloning     Parameter upload, download. User can forbid the overwriting of the uploaded parameters.
                         Keypad           LED keypad as standard.
                    Common DC bus         Common DC bus for multiple drives power supply
       Unique
      functions      Independent air
                                          Independent air duct design for whole series product
                          duct
                     Extension card           xtension card, injection molding machine connecting card etc.
                                          IO extension
                   Power-up detection Automatic detection of internal and external circuits when power-up
                   Power undervoltage/overvoltage protection, overcurrent protection, autotune trip, IGBT protection, heatsink overheat
                   protection, drive overload protection, motor overload protection, external device false protection, output to ground short-
      Protection
                   circuit protection, abnormal power failure in running, power supply abnormal, output phase loss, EEPROM trip, relay contact
       function
                   error, temperature sampling abnormal, encoder off-line, analog input trip, communication trip, version compatibility trip,
                                  xtension card connection trip, hardware overload protection
                   cloning trip, extension
      Efficiency                        Operation at rated power: 7.5kW or belowt 93%; 11kW~45kWt 95%; 55kW or abovet 98%
                        Application       Vertical installation in well ventilated cabinet. Horizontal or other installation are forbidden. The cooling
                       environment        medium is air. Free from direct sunlight, dust, corrosive gas, combustible gas, oil mist, steam, and water drop.
                         Ambient          -10°C~+40°C, deration is required from 40 to 50°C, rated output current decreasing 1% per 1 °C temperature
                       temperature        higher
     Environment        Humidity          5~95% without condensation
                         Altitude         0~2000m, deration is required for more than 1000 meters, at rated output current decreasing 1% per 1 00m higher
                        Vibration         3.5mm, 2~9Hz; 10 m/s2, 9~200Hz; 15 m/s2, 200~500Hz
                   Storage temperature -40~+70°C
                     Protection level     IP20
      Structure
                         Cooling          Fan force cooling
     *Please consult our company for vector control drive with PG model selection.
                                                              www.controltechniques.com
10