Model:
Powered By Perkins
AP60S
Generator Specification
Service PRP(1) ESP(2) Perfomance Data
Power (KVA) 68 75 Model AP60S
Power (KW) 54.4 60 Engine Brand Perkins
Rated Speed (RPM) 1800 Engine Model 1103A-33TG2
Standard Voltage (V) 400/230V Speed Control Mechanical
Rated at Power Factor (cos phi) 0.8 Phase 3
Control Sytem DIGITAL
Starter motor voltage 12V
Frequency 60HZ
Engine speed (RPM) 1800
100% Standby 18.2
Fuel
100% Prime 16.6
Cosumption
(L/H) 75% Prime 12.5
50% Prime 8.8
(1) PRP (Prime Power): Standard reference Conditions
According to ISO8528-1, prime power is the maximum power available during a variable power Note: Standard reference condition 25℃ (77℉) air inlet temp, 100m(328ft) A.S.L 30% relative humidity.
sequence, which may be run for an unlimited number of hours per year, between stated maintenance Fuel consumption dat with diesel fuel with specific gravity of 0.85 and conforming to BS 2869: 1998 Class
intervals. The permissible average power output during at 24 hours period shall not exceed 80% of the A2
prime power. 10% overload available for overning purposes only.
(2) ESP (Standby Power):
According to ISO 8528-1, It is defined as the maximum power available, under the agreed operating
conditions, for which the generating set is capable of delivering for up to 500 hours of operation per
year (of which no more than 300 hours for continuative use) with the maintenance intervals and
procedures being carried out as prescribed by the manufacturers. No overload capability is available.
Powers ESP PRP Standby Dimension and Weight
Voltage KVA KW KVA KW Amps Open Silent
480/277 75 60 78 54.4 90.2 Lenght (L) 1920mm 2700mm
440/254 75 60 78 54.4 98.4 Width (W) 750mm 1100mm
400/230 75 60 78 54.4 108.3 Height (H) 1410mm 1632mm
380/220 75 60 78 54.4 114.0 Net Weight REQ REQ
220/127 75 60 78 54.4 196.8 Fuel Tank (L) Option Option
ELECTROMECANICOS P&S SAS
Cl 23a 1F - 50 - Tel. 8716947 - Neiva - Huila / orpasper@hotmail.com
Celular 3167414042
Engine Specification
Basic Technical Data Induction System
No. Of Cylinders 3 Clean filter 5kpa
Cylinder Arrangement In - line Dir ty filter 8kpa
Cycle 4 stroke Air filter type Dry
Injection timing Turbocharged
Compression Ratio 17.25:1 Lubrication System
Bore 105mm Total lub capacity 8.3L
Stroke 127mm Sump minimum 6.2L
Displacement 3.31L Sump maximum 7.8L
Fly wheel housing TBD Maximum engine operating angles
Number of teeth on flywheel ±0. 75% front up, front down, right side
or left side 25°C
Lubricating oil pressure
Cooling System Relief valve opens 415-470 kPa
Total coolant capacity at maximum no-load speed 276-414 kPa
with radiator 10.2l Oil consumption at full load
without radiator 4.4L as a % of fuel consumption 0.15%
Presuure cap Max. 49 kPa
Maximum top tank temp 110℃
Thermostat operation range 82-93℃ Electrical System
Radiator face area 0.276 m² Type Negative ground
Rows and material Single rows aluminium Alternator voltage 12 volts
Pressure cap setting 107 kPa Alternator output 65 amps
Fan diameter 457 mm Star ter motor voltage 12 volts
Drive ratio 1.25 : 1 Star ter motor power 3 KW
Number of blades 7
Fuel System
Injection System Direct General Installation
Fuel injection pump Rotary Combustion air flow 4.7 m³/min
Fuel atomiser Multi-hole Exhaust gas temp 534°C
Nozzel opening pressure 29.0 Mpa Exhaust gas flow, wet 11.8 m³/min
Fuel lift pump type Mechanical Engine coolant flow 151 l/min
flow/hour 120-150 l/h Cooling fan air flowpressure 111.0 m³/min
pressure 30-75 kPa
Maximun fuel inlet restriction 10 kPa
Maximum suction head:
1500 rev/min 20kPa
ELECTROMECANICOS P&S SAS
Cl 23a 1F - 50 - Tel. 8716947 - Neiva - Huila / orpasper@hotmail.com
Celular 3167414042
Alternator Specification
Alternator
Number of Phase 3
Power Factor (Cos Phi) 0.8
Poles 4
Winding Connections (standard) star-serie
Terminals 12
Insulation type H class
Winding Pitch 2/3
IP rating IP23
Excitation system Self- excited
Bearing Single bearing
Coating Vaccum impregnation
Voltage Regulator A.V.R
Couping Flexible disc
Options
Engine Alternator Generator Sets Fuel System
Water Jacket Winding Tem measuring Tools with the machine Low Fuel level alarm
Pre-heater instrument Extended range fuel Tank Automatic fuel
Fuel heater Alternator pre heater Bunded fuel tank Feeding system
PMG Fuel T-valves
Anti-damp and acnti- corrosion
treatment
Anti- Condensation heater
Winding and bearing RTD
Canopy Lub oil system Cooling System Control Panel
Rental type Oil Pre- Heater Front heat protection Remote control Panel
Canopy Oil temp sensor ATS
Trailer Synchronizing Controller
Adjustable earth leakage
relay
ELECTROMECANICOS P&S SAS
Cl 23a 1F - 50 - Tel. 8716947 - Neiva - Huila / orpasper@hotmail.com
Celular 3167414042
Control Panel
Configuration Benefits
Emergency stop button Less wiring and components
Protection MCB Integrated solution
Battery charger Less engineering and programming
Integrated aviation plug User friendly set-up and button layout
ATS connection Module can be configured to suit individual applications
Digital control module PC software for simplified configuration
Wide range of communication capabilities
Configuration Operation conditions
3 phase generator set monitoring Operation temp: 20 °C to + 70 °C
Support of engines equipped with electronic control Storage temp: -30 °C to + 80 °C
unit Operating humidity: 95% w / o condensation
Comprehensive diagnostics message Vibration: 5-25 Hz, +/- 1.6 mm
Automatic or manual start/stop of the gensets 5-100 Hz, a=4g
Push buttons for simple control, lamp test Shocks: a=500 m/s2
Graphic back-lit LCD display
Parameters adjustable via keyboard or PC
Mains measurements (50HZ / 60HZ) Options
Generator measurements (50HZ / 60HZ) Ethernet interface (Remote monitoring and control)
Comprehensive shutdown or warning on fault condition GSM modem / wireless internet (Remote monitoring and control)
3 phase generator protections RS232 - RS485 Dual port interface
Over- / under voltage Synchronizing contro panel
Over- / under frequency Distribution board with sockets kit and power busbar
Current/ voltage asymmetry Battery trickle charge ammeter
Over current/ overload Ear th leakage protection
3 phase AMF function Ear th fault protection
Over-/under frequency Low fuel level alarm
Over-/under voltage Low fuel level shutdown
Voltage asymmetry High fuel level alarm
Configurable analog inputs Fuel transfer system control
Battery voltage, engine speed (pick-up) measurement Low coolant level shutdown
Configurable programmable binary inputs and outputs High lube oil temp shutdown
Warm-up and cooling functions Overload via alarm switch on breaker
Generator C.B. and Mains C.B. control with feedback Engine coolant heater controls
and return timer Control panel heater
RS232 interface Speed adjust switch
Modem communication suppor t Oil temp displayed on LCD screen
Hours counter Additional 8 inputs and outputs
Sealed to Ip65
Event log
Distributed by:
All information in the document is substantially correct a the time of
printing but may be subsequently altered by the company.
ELECTROMECANICOS P&S SAS
Cl 23a 1F - 50 - Tel. 8716947 - Neiva - Huila / orpasper@hotmail.com
Celular 3167414042