Jubail Civil Design Basis
Jubail Civil Design Basis
NATIONAL GRID SA
M.H
Engineering & Design Department
APPR'D
Engineering Division-South
H.A
CHK'D
SH.S
THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ELECTRICITY CO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
ISSUED FOR APPROVAL
DESCRIPTION
JUBAIL PROJECT
CIVIL DESIGN BASIS
M.A.M
BY
27-Dec-23
DATE
NO.
REVISIONS
DESIGNED
BY M.A.M
DATE 27/12/23
CHECKED
BY SH.S
DATE 27/12/23
OPRG. DEPT
BY
DATE
ENG'G. DEPT.
BY
DATE
CERTIFIED.
BY
Engineering Division-South
H.A
CHK'D
SH.S
Contents Page #
1. General
1.1 Introduction » 2
1.2 Scope of work » 2
1.3 Project description » 3
1.4 Additional notes » 6
1.5 Units of measurement » 6
THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ELECTRICITY CO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
1.6 Reference documents » 7
2. Design standards, codes of practices and specifications
ISSUED FOR APPROVAL
2.2 Specifications » 7
3. Loads
3.1 Dead load » 8
3.2 Live load » 9
3.3 Wind load » 9
3.4 Seismic load » 10
3.5 Surcharge load » 10
3.6 Earth pressure load » 11
3.7 Crane load » 11
3.8 Blast Load » 11
3.9 Thermal load / temperature load (T) » 11
4. Method of analysis
M.A.M
BY
4.3 Results » 12
5. Concrete (works / design)
Material properties & design strength »
NO.
5.1. 12
0
Engineering Division-South
H.A
CHK'D
SH.S
1. General
1.1 Introduction
• This document describes the design criteria for civil and structural work to be used in this project.
This design criteria report complies with all relevant (*NG codes and standards) for engineering, materials, codes, standards
•
and Saudi Arabian government codes.
This document outlines the design criteria and considerations made for the design of Civil, Structural and architectural works
THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ELECTRICITY CO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
•
related to the mentioned project.
Civil Design Criteria complies with all relevant Codes, Specification & Standards for Engineering, Materials and Construction,
•
which serve as the basis for the preparation of structural analysis and design of steel and concrete structure.
ISSUED FOR APPROVAL
DESCRIPTION
The main work of proposed Jubail Airport Substation involves construction of 34.5/13.8 kV substation with (2) transformers
• and will consist of 34.5 kV and 13.8 kV switchgears, 20/25 MVA power transformers and all associated facilities. The substation
is proposed to be served by 34.5 kV incoming cables from the source substation 230/115/34.5 kV Substation-1 Jubail-2.
M.A.M
BY
REVISIONS 1.3 Asphalt Road with 5.0 meter minimum width. 1 TCS-Q-113.01/Rev.0l
DESIGNED Drive/Entrance gates
BY M.A.M
Main gate with 6.0 meter minimum width
DATE 27/12/23 2.1 *(2 typical gates/substation). 1
*(2-leaf swing door 3.0 m each).
CHECKED 2.
BY SH.S
Personnel/pedestrian gate with 1.2 meter width to
DATE 27/12/23 2.2 be provided beside the main gate 1
*(2 typical doors/substation).
OPRG. DEPT
DATE
CERTIFIED. *NG code = NGSA = "The National Grid Saudi Arabia" technical codes and standards for electrical infrastructure projects.
BY Back to top ↑
DATE AS BUILT BY HAIF CO. DATE DWG. CONTROL SHT. SE-235870
THIS DRAWING IS NOT DRAWING TITLE INDEX PLANT NO. DRAWING NO. SHEET NO. REV.
TO BE USED FOR
CONSTRUCTION OF CIVIL DESIGN CRITERIA
FOR ORDERING A ASR434 SE-235902 0
MATERIALS UNTIL CONSTRUCTION OF JUBAIL 132/13.8 kV SUBSTATION
CERTIFIED AND
DATED JUBAIL SAUDI ARABIA CONTRACT NO: 4400018951
CERT'D NATIONAL GRID SA
M.H Engineering & Design Department
APPR'D
Engineering Division-South
H.A
CHK'D
SH.S
THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ELECTRICITY CO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
4. TES-P-119.19/Rev.01
4.1 Galvanized steel caged ladder for roof & ET-800714
4.1.2 access in the substation building (2/main 1
building).
ISSUED FOR APPROVAL
5.
Septic tank (type 2), soak pit, sewer manhole, TA-800134
1
distribution box and acid neutralizing dry pit.
5.2
Power/Service transformers
M.A.M
BY
BY
DATE
ENG'G. DEPT.
BY
DATE
CERTIFIED.
BY Back to top ↑
DATE AS BUILT BY HAIF CO. DATE DWG. CONTROL SHT. SE-235870
THIS DRAWING IS NOT DRAWING TITLE INDEX PLANT NO. DRAWING NO. SHEET NO. REV.
TO BE USED FOR
CONSTRUCTION OF CIVIL DESIGN CRITERIA
FOR ORDERING A ASR434 SE-235902 0
MATERIALS UNTIL CONSTRUCTION OF JUBAIL 132/13.8 kV SUBSTATION
CERTIFIED AND
DATED JUBAIL SAUDI ARABIA CONTRACT NO: 4400018951
CERT'D NATIONAL GRID SA
M.H Engineering & Design Department
APPR'D
Engineering Division-South
H.A
CHK'D
SH.S
THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ELECTRICITY CO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
Reinforced concrete communication duct banks.
7. 7.2 1
*(2*2)
ISSUED FOR APPROVAL
DESCRIPTION
8.
Reinforced concrete communication manholes.
8.2 *CMH-01, CMH-02, CMH-03. 1
*(3 typical manholes / substation).
M.A.M
BY
8.3 Handholes 1
Miscellaneous
27-Dec-23
DATE
9.1
REVISIONS
Pre-engineered steel structure and
DESIGNED 9.1.2 1
sunshade for the capacitor bank.
BY M.A.M
DATE 27/12/23 Enclosed chain link fence (Type V) for the capacitor
9.3 banks yard including gates conforming to SAG SSD/2 1
OPRG. DEPT
with steel tube post.
BY
BY Back to top ↑
DATE AS BUILT BY HAIF CO. DATE DWG. CONTROL SHT. SE-235870
THIS DRAWING IS NOT DRAWING TITLE INDEX PLANT NO. DRAWING NO. SHEET NO. REV.
TO BE USED FOR
CONSTRUCTION OF CIVIL DESIGN CRITERIA
FOR ORDERING A ASR434 SE-235902 0
MATERIALS UNTIL CONSTRUCTION OF JUBAIL 132/13.8 kV SUBSTATION
CERTIFIED AND
DATED JUBAIL SAUDI ARABIA CONTRACT NO: 4400018951
CERT'D
NATIONAL GRID SA
M.H
Engineering & Design Department
APPR'D
Engineering Division-South
H.A
CHK'D
SH.S
Control room panels minimum clearance to wall shall be 1800 mm as required by SEC (ISD)
a. TES-P-119.19
Industrial Security department.
TES-P-119.19/Rev.03
b. Cable basement is required under entire floor of GIS room and SWGR room.
P.25
THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ELECTRICITY CO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
c. Staircase and enclosure lobby design shall be isolated from the cable basement.
Enclosure lobby and door at basement shall be elevated by 1 step from main floor of cable
ISSUED FOR APPROVAL
d.
basement.
DESCRIPTION
Substation building shall have a minimum clear height of 3000 mm from top of basement floor
e.
to bottom of ground floor beam.
TES-P-119.19/Rev.03
The design of slab on grade shall be as per ASCE/SEI-7 floor of the slab on grade portion of P.25
f. substation building shall be of concrete with a minimum of 150 mm thickness, reinforced with
welded wire fabric , deformed steel bars or a combination of both. P.25 TES-P-119.19 R.03
Clear height of GIS room shall be determined from the clearance of top most part of GIS TES-P-119.19/Rev.03
g. equipment, crane hook and the clearance from top of platform to bottom of roof beam shall be CL. 7.2.3
as per NG requirement considering space for (Mechanical Electrical) facilities and maintenance. P.25
h. The roof shall be precast pre-stressed slab with 2% slope provided for drainage.
M.A.M
BY
TCS-Q-113.03/Rev.01
a. All concrete works shall conform to COMPANY/SEC standards.
TCS-Q-113.04/Rev.00
NO.
b. Pozzolanic material shall be added to concrete mix for foundation structures. 70-TMSS-03/Rev.01
REVISIONS
DESIGNED
BY
Engineering Division-South
H.A
CHK'D
SH.S
THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ELECTRICITY CO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
Report : 2017/60/REV.02/Dated:28 August 2017
• The latest editions of the following codes and standards shall constitute minimum requirements, where applicable.
3 ACI-318M American Concrete Institute, Building Code Requirements for Structural Concrete.
M.A.M
Construction Assemblies.
Engineering Division-South
H.A
CHK'D
SH.S
3. Loads
3.1 Dead load (D)
Dead Loads shall comprise of the weight of the structure including weights of walls, floors, roof, finishes, and services such as
•
ducts, pipe work etc., and any other permanent construction. For design, the following weights of materials will be considered.
THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ELECTRICITY CO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
# Building Materials Unit Weight Units Reference
1 Reinforced Concrete 23.35 kN/m³
2 Steel 77.08 kN/m³ TES-P-119.19
ISSUED FOR APPROVAL
9 Others. 0.10
Total 3.915
NO.
DATE Note:
ENG'G. DEPT. Self-weight of concreter/steel members/elements to be calculated by the software/STAAD itself.
BY
DATE
CERTIFIED.
BY Back to top ↑
DATE AS BUILT BY HAIF CO. DATE DWG. CONTROL SHT. SE-235870
THIS DRAWING IS NOT DRAWING TITLE INDEX PLANT NO. DRAWING NO. SHEET NO. REV.
TO BE USED FOR
CONSTRUCTION OF CIVIL DESIGN CRITERIA
FOR ORDERING A ASR434 SE-235902 0
MATERIALS UNTIL CONSTRUCTION OF JUBAIL 132/13.8 kV SUBSTATION
CERTIFIED AND
DATED JUBAIL SAUDI ARABIA CONTRACT NO: 4400018951
CERT'D NATIONAL GRID SA
M.H Engineering & Design Department
APPR'D
Engineering Division-South
H.A
CHK'D
SH.S
Live loads shall be considered as per ASCE7-16 and or manufacturer’s specification. Unless otherwise specified the following
•
loads are considered for the civil design of all the related structures.
THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ELECTRICITY CO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
3.2.1 With access 1.5 kN/m² TES-P-119.19/Rev.03
Without access 1 kN/m² CL. 7.1.2 (a)
3.2.3 TES-P-119.18/Rev.01
Equipment load in operating condition
CL. 4.2.2 (c)
NO.
Data to be provided by
REVISIONS supplier/vendor/ equipment
Crane load manufacturer TES-P-119.18/Rev.01
DESIGNED
(refer to point 3.7. of this document for details) CL. 4.2.2 (f)
BY M.A.M
DATE 27/12/23
Engineering Division-South
H.A
CHK'D
SH.S
THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ELECTRICITY CO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
01 Risk category Occupancy category /Risk category = III
Table 1.5-1, ASCE 7-16
02 Ie Seismic importance factors by risk category of buildings = 1.25 Table 1.5-2, ASCE 7-16
ISSUED FOR APPROVAL
According to
04 SS The mapped spectral response accelerations for short periods = 0.6 soil report and with
reference to
The mapped spectral response accelerations for a 1 second Section 1613.3, IBC 2012
05 S1 = 0.18 Section 11.4.2, ASCE 7-16
period
(as per the municipality
Long period Transition Period 8.0 provided maps for KSA)
06 TL =
(obtained from local hazard maps) Sec.
07 Fa Short period Site coefficient = 1.26 Tables 1613.3.3 (1) & (2),
IBC 2012
Tables 11.4-1 & 11.4-2,
08 Fv Long period Site coefficient = 1.5 ASCE 7-16
SMS=
09 Adjusted spectral acceleration for short periods (0.2 seconds) = 0.756
Fa * Ss
M.A.M
SM1= 1613.3.4,
10 Adjusted spectral acceleration for short periods (0.2 seconds) = 0.27
Fv * S1 IBC 2012
27-Dec-23
12 = 0.18
REVISIONS 2/3 * SM1 1-second periods
ENG'G. DEPT. In the design of substation basement wall and vertical structures below grade, provision shall be made for the lateral pressure
of adjacent soil. In addition, minimum of 10 kN/m2 or HS 20 wheel load, whichever is higher, shall be made for surcharge from
BY •
fixed or moving loads. When a portion or whole of the adjacent soil is below a free water surface, computations shall be based
DATE on weight of soil diminished by buoyancy, plus hydrostatic pressure. Surcharge loads are considered as live loads.
CERTIFIED.
BY Back to top ↑
DATE AS BUILT BY HAIF CO. DATE DWG. CONTROL SHT. SE-235870
THIS DRAWING IS NOT DRAWING TITLE INDEX PLANT NO. DRAWING NO. SHEET NO. REV.
TO BE USED FOR
CONSTRUCTION OF CIVIL DESIGN CRITERIA
FOR ORDERING A ASR434 SE-235902 0
MATERIALS UNTIL CONSTRUCTION OF JUBAIL 132/13.8 kV SUBSTATION
CERTIFIED AND
DATED JUBAIL SAUDI ARABIA CONTRACT NO: 4400018951
CERT'D NATIONAL GRID SA
M.H Engineering & Design Department
APPR'D
Engineering Division-South
H.A
CHK'D
SH.S
• Earth pressure for cantilever walls of cable trenches & boundary wall will be calculated based on active earth pressure.
• Other soil parameters shall be considered as per the approved soil investigation report.
THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ELECTRICITY CO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
Unit weight of soil and water shall be considered shown below (Soil Parameters are considered conservatively as the soil report
•
recommendations are shown below the foundation levels).
3.7 Crane load (CL) CL 4.9, ASCE 7-16 & TES-P-119.18/Rev.01 CL. 4.2.2 (f)
All crane ways shall have their design load increased for the impact as follows:
• A vertical force equal to 25% of the maximum wheel load.
• The lateral force 20% of the weight of the trolley and lifted load only, applied one-half at the top of each rail.
Unit weight of soil and water shall be considered shown below (Soil Parameters are considered conservatively as the soil report
•
recommendations are shown below the foundation levels).
Thermal load shall be considered in case of RC building length exceeds 36 m without expansion joints provision and for steel
•
structures in all cases considering the following thermal conditions:
27-Dec-23
DATE
REVISIONS • Thermal loads shall be applied on exposed surfaces including framing members / slabs and walls.
DESIGNED
DATE
ENG'G. DEPT.
BY
DATE
CERTIFIED.
BY Back to top ↑
DATE AS BUILT BY HAIF CO. DATE DWG. CONTROL SHT. SE-235870
THIS DRAWING IS NOT DRAWING TITLE INDEX PLANT NO. DRAWING NO. SHEET NO. REV.
TO BE USED FOR
CONSTRUCTION OF CIVIL DESIGN CRITERIA
FOR ORDERING A ASR434 SE-235902 0
MATERIALS UNTIL CONSTRUCTION OF JUBAIL 132/13.8 kV SUBSTATION
CERTIFIED AND
DATED JUBAIL SAUDI ARABIA CONTRACT NO: 4400018951
CERT'D NATIONAL GRID SA
M.H Engineering & Design Department
APPR'D
Engineering Division-South
H.A
CHK'D
SH.S
A three-dimensional model which contains the columns and beams as members and walls and Raft as finite element plates by
providing space co-ordinates are generated. These members are assigned with properties as per their sizes. Slab is modeled as
a shell member (and as Membrane in case of precast slab (if any)) to transfer the load to vertical supports and wall is modeled
• as shell element. Foundations is modeled as a shell element and spring support is given in software. Material constants,
supports, end condition of members, primary loads & load combinations are directly fed into the software. Relevant basic
cases of Dead, Live, Wind and Seismic forces are created and they are algebraically combined as per American standards.
THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ELECTRICITY CO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
Analysis is done subsequently.
ISSUED FOR APPROVAL
Table 6.6.3.1.1(a),
• Property modifiers to be considered in STAAD model as per ACI 318-14 requirements.
DESCRIPTION
ACI 318-14
4.3 Results
All computer-generated results such as member forces, support reactions, displacements will be provided. Graphical output of
• analysis results such as bending moment diagrams, shear force diagram, displacement diagrams, etc. will be provided to
substantiate the numerical output.
M.A.M
BY
The structure will be designed for Ultimate limit state & Serviceability limit state for the worst combination
of Dead loads, Live loads, Crane loads, Wind loads and Seismic loads as applicable. Design of structural
• elements (i.e., Slabs, Walls, Columns, Beams, RC Staircase, and outdoor foundations etc.) will be performed using STAAD and
NO.
Excel spread sheets. STAAD will be used to design Isolated/combined footings, Strip footing and Raft. Excel spread sheets;
REVISIONS
Manuals & Checklist can also be used for inspection / checking.
DESIGNED
BY M.A.M
ENG'G. DEPT.
BY
DATE
CERTIFIED.
BY Back to top ↑
DATE AS BUILT BY HAIF CO. DATE DWG. CONTROL SHT. SE-235870
THIS DRAWING IS NOT DRAWING TITLE INDEX PLANT NO. DRAWING NO. SHEET NO. REV.
TO BE USED FOR
CONSTRUCTION OF CIVIL DESIGN CRITERIA
FOR ORDERING A ASR434 SE-235902 0
MATERIALS UNTIL CONSTRUCTION OF JUBAIL 132/13.8 kV SUBSTATION
CERTIFIED AND
DATED JUBAIL SAUDI ARABIA CONTRACT NO: 4400018951
CERT'D NATIONAL GRID SA
M.H Engineering & Design Department
APPR'D
Engineering Division-South
H.A
CHK'D
SH.S
b. Concrete
The concrete grade / properties used in the various works shall be as follows:
THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ELECTRICITY CO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
Precast F’cu (Cylindrical
45.0 450.0 4.50 / /
TES-Q-113-01 compressive strength)
* Additional notes
M.A.M
BY
Sec. 19.2.2.1,
NO.
REVISIONS ACI318-14
DESIGNED W/C Water / Cement Ratio for R.C & P.C ≤ 0.4
BY M.A.M Poisson’s ratio = 0.2
DATE 27/12/23 CL:7.1 & 7.3.4.4,
Coefficient of Thermal Expansion = 1x10-5 per deg. C
CHECKED ACI 22R-01
BY SH.S
Engineering Division-South
H.A
CHK'D
SH.S
THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ELECTRICITY CO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
Where
bw = Web width or diameter for circular sections in mm.
d = Effective depth.
Table 22.5.5.1,
ISSUED FOR APPROVAL
Shear stress
ACI 318-14
DESCRIPTION
Values at midspan for simple and continuous spans, and at support for
ρ' =
BY
cantilevers.
Table 9.5b,
27-Dec-23
ACI 318M-14
b.4. Story drift / Maximum deflection (for the structure / building) Eq. 12.8.15, ASCE 7-10
NO.
DATE 27/12/23
L/600 to L/400 Chapter C, Appendix C, CL.
Permissible story drift for wind load
OPRG. DEPT = Considered value in design CC 1.2,
combination
BY
= L/500 ASCE 7- 16
DATE
ENG'G. DEPT. Permissible story drift for seismic load 0.015*hsx Table 12.12.1,
=
BY combinations to be revised according to ASCE 7- 16
DATE Figure 12.8-2,
The inter-story drift shall be calculated as per
CERTIFIED. ASCE 7 – 16
BY Back to top ↑
DATE AS BUILT BY HAIF CO. DATE DWG. CONTROL SHT. SE-235870
THIS DRAWING IS NOT DRAWING TITLE INDEX PLANT NO. DRAWING NO. SHEET NO. REV.
TO BE USED FOR
CONSTRUCTION OF CIVIL DESIGN CRITERIA
FOR ORDERING A ASR434 SE-235902 0
MATERIALS UNTIL CONSTRUCTION OF JUBAIL 132/13.8 kV SUBSTATION
CERTIFIED AND
DATED JUBAIL SAUDI ARABIA CONTRACT NO: 4400018951
CERT'D NATIONAL GRID SA
M.H Engineering & Design Department
APPR'D
Engineering Division-South
H.A
CHK'D
SH.S
THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ELECTRICITY CO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
• Horizontal reinforcement shall be prefabricated truss/ladder type and shall be installed in alternate layer of CMU wall.
• All cells of the CMU for exterior and interior wall shall be fully grouted.
ISSUED FOR APPROVAL
• Steel reinforcement shall be deformed, type 2, complying with CL. 20.2.1.3, ACI318-14
• For design, the specified characteristic strength considered will be as follows:
REVISIONS
DESIGNED Min. reinforcement in slabs Min. reinforcement in beams
BY M.A.M
DATE 27/12/23
CHECKED
BY SH.S
DATE 27/12/23
OPRG. DEPT
BY
DATE
ENG'G. DEPT. • Diameter of reinforcement bars used shall be: 8,10, 12, 16, 20, 25 & 32. (Max. bar length 12m).
BY • Welded deformed bar mats shall confirm to ASTM A184M, ASTM A 615M or A706M
DATE • Note: Steel conforming to BS 4449
CERTIFIED.
BY Back to top ↑
DATE AS BUILT BY HAIF CO. DATE DWG. CONTROL SHT. SE-235870
THIS DRAWING IS NOT DRAWING TITLE INDEX PLANT NO. DRAWING NO. SHEET NO. REV.
TO BE USED FOR
CONSTRUCTION OF CIVIL DESIGN CRITERIA
FOR ORDERING A ASR434 SE-235902 0
MATERIALS UNTIL CONSTRUCTION OF JUBAIL 132/13.8 kV SUBSTATION
CERTIFIED AND
DATED JUBAIL SAUDI ARABIA CONTRACT NO: 4400018951
CERT'D NATIONAL GRID SA
M.H Engineering & Design Department
APPR'D
Engineering Division-South
H.A
CHK'D
SH.S
• The following loading combinations shall be considered to determine the maximum stress condition on the structural member.
Seismic load (the mass on which the seismic acceleration is acting) shall be calculated using the complete weight of all
•
THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ELECTRICITY CO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
structural and permanent elements of the structure, along with all equipment weights (Live load).
• The load combination, which causes the most unfavorable effect, shall govern.
ISSUED FOR APPROVAL
1.4D
1.2D + 1.2F + 1.6H + 1.6L + 0.5Lr
1.2D + 1.2F + 1.6H + 1.6Lr + L
1.2D + 1.2F + 1.6H + 1.6Lr + 0.5W
1.2D + L + 0.5Lr + 1.2F + 1.6H + W
0.9D + 1.6H + W
1.2D + L + 1.2F + 1.6H + E
0.9D + 0.9F + 1.6H + E
Where fluid loads F are present, they shall be included in combinations with the same factor as that used for dead load D.
Where the effect of H adds to the primary variable load effect, include with a load factor of 1.6.
5.2.2 Load combinations for the Service Limit State (SLS - Serviceability):
M.A.M
BY
D
D+L
27-Dec-23
DATE
D+H+F+L
D + H + F + Lr
D + H + F + 0.75L + 0.75Lr
NO.
REVISIONS D + H + F + (0.6W)
DESIGNED D + H + F + 0.75L + 0.75Lr + 0.75(0.6W)
BY M.A.M 0.6D + H + 0.6W
DATE 27/12/23 D + H + F + 0.7E
CHECKED D + H + F + 0.75L + 0.75Lr + 0.525E
BY SH.S 0.6D + H + F + 0.7E
DATE 27/12/23 Where fluid loads F are present, they shall be included in combinations with the same factor as that used for
OPRG. DEPT dead load D
BY Where the effect of H adds to the primary variable load effect, include with a load factor of 1.0
DATE
Engineering Division-South
H.A
CHK'D
SH.S
5.3 Allowable deflections in concrete slabs & beams (Table 24.2.2, ACI 318M-14)
# Condition Deflection limitation
Flat roofs or Floors (Not Supporting non-structural elements not likely to be damaged by large
1 deflections) Span/250
Immediate deflection due to maximum of Lr
Flat roofs or Floors (Not Supporting non-structural elements not likely to be damaged by large
THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ELECTRICITY CO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
deflections) minimum of
2
Span/360 or 20 mm
Immediate deflection due to L
minimum of
3 Roofs or floors (supporting non-structural elements likely to be damaged by large deflections)
ISSUED FOR APPROVAL
Span/480 or 20mm
DESCRIPTION
27-Dec-23
DATE
atmosphere
CHECKED 2 75 50 50
up to 3 m height from
BY SH.S grade level.
DATE 27/12/23
Columns and walls above
OPRG. DEPT 3 3 m height from grade 50 50 40
BY
level and beams.
DATE
Slabs and joist exposed to 40 for > 35mm bars 40 for > 35mm bars
ENG'G. DEPT. 4 40
atmosphere. 30 for < 35mm bars 20 for < 35mm bars
BY
DATE Ensurance of the required minimum clear cover shall not result in the reduction at site, of the design effective depth of the member. The
CERTIFIED. tolerances in concrete cover for slabs shall be as per ACI 302.1R.
BY Back to top ↑
DATE S BUILT BY HAIF CO. DATE DWG. CONTROL SHT. SE-235870
THIS DRAWING IS NOT DRAWING TITLE INDEX PLANT NO. DRAWING NO. SHEET NO. REV.
TO BE USED FOR
CONSTRUCTION OF CIVIL DESIGN CRITERIA
FOR ORDERING A ASR434 SE-235902 0
MATERIALS UNTIL CONSTRUCTION OF JUBAIL 132/13.8 kV SUBSTATION
CERTIFIED AND
DATED JUBAIL SAUDI ARABIA CONTRACT NO: 4400018951
CERT'D NATIONAL GRID SA
M.H Engineering & Design Department
APPR'D
Engineering Division-South
H.A
CHK'D
SH.S
• The foundation design shall be carried out for each loading combination and the critical case shall be adopted.
THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ELECTRICITY CO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
5.5.1 Ground Water Table (GWT) & Factor of Safety (F.O.S)
# Parameters Value Reference
ISSUED FOR APPROVAL
Minimum number of coats shall be two (2) or the dry film thickness shall not be less than 600 78-TMS-11/Rev.00
•
microns, whichever produces higher thickness. CL. 4.4.4 pg. 8
M.A.M
BY
After a minimum of thirty-five (35) days of concrete placement for severe exposure concrete, all
78-TMS-11/Rev.00
DATE
• exposed concrete surfaces (above grade) shall be coated with an elastomeric polyurethane
CL. 8.2 pg. 17
waterproofing material.
The coating application shall extend continuously 300 mm below grade after curing of first coat 78-TMS-11/Rev.00
NO.
•
0
CHECKED 78-TMS-11/Rev.00
• The primer shall be suitably selected for concrete and steel surfaces.
BY SH.S CL. 4.4.11 pg. 10
DATE 27/12/23 c. Concrete interior surfaces:
OPRG. DEPT
BY
All interior surfaces (wall and base slab) of concrete (manholes, hand holes, trenches and cable
78-TMS-11/Rev.00
• basement/cable entry room) shall be coated with two (2) coats of elastomeric cementitious
DATE CL. 9.0 pg. 19
impermeable membrane after thirty-five (35) days of concrete placement.
ENG'G. DEPT.
BY 78-TMS-11/Rev.00
• The total wet film thickness shall not be less than 1mm (minimum).
DATE CL. 9.0 pg. 19
CERTIFIED.
BY Back to top ↑
DATE AS BUILT BY HAIF CO. DATE DWG. CONTROL SHT. SE-235870
THIS DRAWING IS NOT DRAWING TITLE INDEX PLANT NO. DRAWING NO. SHEET NO. REV.
TO BE USED FOR
CONSTRUCTION OF CIVIL DESIGN CRITERIA
FOR ORDERING A ASR434 SE-235902 0
MATERIALS UNTIL CONSTRUCTION OF JUBAIL 132/13.8 kV SUBSTATION
CERTIFIED AND
DATED JUBAIL SAUDI ARABIA CONTRACT NO: 4400018951
CERT'D
NATIONAL GRID SA
M.H
Engineering & Design Department
APPR'D
Engineering Division-South
H.A
CHK'D
SH.S
PTS/APPENDIX IX CIVIL
d. RCC walls / Concrete Masonry Unit (CMU) walls and finishing
CL. 3.06 pg. 50 & 51 /92
• Non-load bearing concrete Masonry units and shall conform to ASTM C129, Type II
78-TMS-11/Rev.00
• The surface of CMU shall fair-faced, strain-free ready to receive paint.
CL. 4.4.4 pg. 8
• The CMU shall be true to shape and size, free from flaws, cracks and other defects.
THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ELECTRICITY CO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
• CMU with broken edges or damaged shall not be used.
• The CMU wall shall be cured continuously for at least seven (7) days.
Where wall heights are not an exact number of courses, the extra height shall be make up with cast-in-place concrete of
ISSUED FOR APPROVAL
•
minimum compressive strength 38 MPa.
DESCRIPTION
Horizontal reinforcement shall be ladder or truss type, pre-fabricated from steel conforming to ASTM A116, Class 1 or
• ASTM A82 and galvanized in accordance with ASTM A116, Class 1 or Class 3, or ASTM A153, CB- Class 3, or ASTM A153, CB-
2. 2.
• At the interface of concrete elements (beams, columns) and CMU wall expanded metal lath, dovetail anchor shall be provided.
All the plastering accessories such as expanded metal lath, angle bead, control joint bead, strip mesh, corner mesh, block work
•
reinforcement, plaster stop bead etc., shall be galvanized steel.
M.A.M
BY
Mortar shall conform to ASTM C270, Type M and shall have a minimum compressive
27-Dec-23
DATE
CHECKED Masonry grout shall conform to ASTM C476 and shall have a minimum compressive strength
BY SH.S of 21 MPa at twenty-eight (28) days. ASTM C476
DATE 27/12/23 Portland Cement: ASTM C150, Type V ASTM C150, Type V
• ASTM C207, Type S
OPRG. DEPT Lime: ASTM C207, Type S ASTM C144
BY ASTM C404, maximum coarse aggregate size shall ASTM C404
Aggregate:
DATE be 9.5mm.
ENG'G. DEPT.
BY Note:
DATE *SASO: is the Saudi Standards, Metrology and Quality Organization.
CERTIFIED.
BY Back to top ↑
DATE AS BUILT BY HAIF CO. DATE DWG. CONTROL SHT. SE-235870
THIS DRAWING IS NOT DRAWING TITLE INDEX PLANT NO. DRAWING NO. SHEET NO. REV.
TO BE USED FOR
CONSTRUCTION OF CIVIL DESIGN CRITERIA
FOR ORDERING A ASR434 SE-235902 0
MATERIALS UNTIL CONSTRUCTION OF JUBAIL 132/13.8 kV SUBSTATION
CERTIFIED AND
DATED JUBAIL SAUDI ARABIA CONTRACT NO: 4400018951
CERT'D NATIONAL GRID SA
M.H Engineering & Design Department
APPR'D
Engineering Division-South
H.A
CHK'D
SH.S
Manufacturer's recommendations shall be strictly followed in all aspects of surface preparation, priming, coating application
•
(first and succeeding coats and intervals therein, etc.), and curing time and safety practices.
The coating on the exterior concrete surfaces shall be carried out after a minimum of fourteen (14) days following the curing
•
period.
THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ELECTRICITY CO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
• The coating shall form and maintain a continuous film over the concrete.
The coating material shall penetrate into the concrete and adhere to it effectively so as to afford
ISSUED FOR APPROVAL
•
protection to the concrete against the entry of oxygen, moisture and aggressive ions.
DESCRIPTION
a. Building roof
Shall be provided with one (1) layers bituminous waterproofing membrane or one (1) PTS/APPENDIX IX CIVIL
•
layer PVC waterproofing membranes. CL. 2.35 pg.42&43 /92 (A&B)
b. Door canopy
Shall be provided with waterproofing shall be with one (1) “PVC” Or one (1) “4 mm thick PTS/APPENDIX IX CIVIL
•
Bituminous” membrane. CL. 2.35 pg.44 /92 (C)
PTS/APPENDIX IX CIVIL
• Waterproofing shall be carried out as per the requirements of
CL. 2.36 pg.45/92
M.A.M
BY
The waterproofing membrane shall be extended up to the finished floor level and shall be fixed to finished grade slab with
d.
aluminum flashing and sealant.
27-Dec-23
DATE
REVISIONS
DESIGNED
BY M.A.M
DATE 27/12/23
CHECKED
BY SH.S
DATE 27/12/23
OPRG. DEPT
BY
DATE
ENG'G. DEPT.
BY
DATE
CERTIFIED.
BY Back to top ↑
DATE AS BUILT BY HAIF CO. DATE DWG. CONTROL SHT. SE-235870
THIS DRAWING IS NOT DRAWING TITLE INDEX PLANT NO. DRAWING NO. SHEET NO. REV.
TO BE USED FOR
CONSTRUCTION OF CIVIL DESIGN CRITERIA
FOR ORDERING A ASR434 SE-235902 0
MATERIALS UNTIL CONSTRUCTION OF JUBAIL 132/13.8 kV SUBSTATION
CERTIFIED AND
DATED JUBAIL SAUDI ARABIA CONTRACT NO: 4400018951
CERT'D NATIONAL GRID SA
M.H Engineering & Design Department
APPR'D
Engineering Division-South
H.A
CHK'D
SH.S
PTS/APPENDIX IX CIVIL
Asphalt access road to substation & CL. 2.22 pg. 36 & 37 / 92
5.7 CL. 3.12, 3.13 & 3.14
Asphalt concrete paving
pg. 64 & 65 / 92
• Haif shall construct proposed asphalt access road to the proposed substation drive gate from the existing asphalt road.
THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ELECTRICITY CO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
TES-P-122.11/Rev.01
• Design and construction of access road shall conform to
TES-P-119.19/Rev.03
ISSUED FOR APPROVAL
Haif shall provide all necessary road traffic warning signs such as stop, speed limit, cautions, slow down, direction etc., speed
DESCRIPTION
• humps and substation informative signs at the intersection of proposed asphalt access road and the existing asphalt road.
Speed humps shall be provided at 100 meters from substation and existing asphalt road.
• The access road shall be 6.0 m wide with 2.0 m wide shoulder on each side.
• The slope of embankment shall be protected with riprap or 50 mm thick. asphalt.
• Asphalt Concrete paving works shall be as per the requirements of TCS-Q-113.01/Rev.01
Minimum thickness of combined binder and wearing course shall be 102 mm (64 mm thick. class “A” asphalt binder course and
•
38 mm thick class “C” asphalt wearing course).
TCS-Q-113.01/Rev.01
• Base and sub-base materials shall satisfy the requirement of
TCS-Q-113.02/Rev.01
M.A.M
Minimum thickness of base course shall be 300 mm thick Class “C”, with liquid limit =35% and
• TCS-Q-113.02/Rev.01
BY
Plasticity Index of 4.
27-Dec-23
Axle loads shall be based on or a load meter survey , truck and equipment manufacturer's technical data of the maximum axle
•
NO.
loads allowed by the MOT. See Table below for maximum legal Saudi Arabia truck loads.
0
REVISIONS
DESIGNED
BY SH.S Connections/lap splices transferring stress may be lapped, welded or joined with mechanical Sec. 25.4 & Sec. 25.5,
•
DATE 27/12/23 devices. ACI 318-14.
OPRG. DEPT Connections/lap splices should be placed, if possible, away from points of high stress and
•
BY should preferably to be staggered.
DATE
ENG'G. DEPT.
BY
DATE
CERTIFIED.
BY Back to top ↑
DATE AS BUILT BY HAIF CO. DATE DWG. CONTROL SHT. SE-235870
THIS DRAWING IS NOT DRAWING TITLE INDEX PLANT NO. DRAWING NO. SHEET NO. REV.
TO BE USED FOR
CONSTRUCTION OF CIVIL DESIGN CRITERIA
FOR ORDERING A ASR434 SE-235902 0
MATERIALS UNTIL CONSTRUCTION OF JUBAIL 132/13.8 kV SUBSTATION
CERTIFIED AND
DATED JUBAIL SAUDI ARABIA CONTRACT NO: 4400018951
CERT'D NATIONAL GRID SA
M.H Engineering & Design Department
APPR'D
Engineering Division-South
H.A
CHK'D
SH.S
Bolts, washers, Nuts and Anchor rods, threaded bolts materials confirming to relevant ASTM specifications
•
mentioned in clause A3.3 and A3.4 of AISC360, respectively.
THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ELECTRICITY CO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
• Minimum design strength of Steel members shall be = 275 N/mm2
• The Modulus of elasticity of structural steel "E" = 200000 N/mm2
• The Shear Modulus of elasticity of structural steel "G" = 76923 N/mm2
ISSUED FOR APPROVAL
DESCRIPTION
For any member normally acting as tie but subject to reversal of stress
c. = 300
The slenderness limit for main beams &Resulting from the action of wind
6.4 Deflections
M.A.M
BY
The maximum permissible deflections shall be as specified in AISC 360, Table 24.2.2, ACI 318-14 and as given by manufacturer,
•
27-Dec-23
whichever is critical. Clause 6.1.4 of this clause also shall be referred for various limits of deflections.
DATE
BY
DATE
CERTIFIED.
BY Back to top ↑
DATE AS BUILT BY HAIF CO. DATE DWG. CONTROL SHT. SE-235870
THIS DRAWING IS NOT DRAWING TITLE INDEX PLANT NO. DRAWING NO. SHEET NO. REV.
TO BE USED FOR
CONSTRUCTION OF CIVIL DESIGN CRITERIA
FOR ORDERING A ASR434 SE-235902 0
MATERIALS UNTIL CONSTRUCTION OF JUBAIL 132/13.8 kV SUBSTATION
CERTIFIED AND
DATED JUBAIL SAUDI ARABIA CONTRACT NO: 4400018951
CERT'D NATIONAL GRID SA
M.H Engineering & Design Department
APPR'D
Engineering Division-South
H.A
CHK'D
SH.S
6.6 Connections
All the Braced, Splice, shear and moment connection for the structural elements shall be designed for the allpossible load
•
combinations as per AISC 360.
Connection Bolts
Secondary bolted connections shall be made using at least two machine bolt conforming to
a. ASTM A307
ASTM A307 and shall be electro-galvanized finish.
THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ELECTRICITY CO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
b. Nuts and washers shall have the same finish as the bolts.
Bolts shall conform to ASTM A325 M
c. Nuts shall conform to ASTM A563 M
ISSUED FOR APPROVAL
a. Shear capacity
Shear capacity (Ps) = 0.75 * Ps * As CL J6, AISC 360
• Ps = Nominal Shear strength
Where
As = Shear area of bolt
b. Tension capacity
M.A.M
BY
Where
DATE
DATE
CERTIFIED.
BY Back to top ↑
DATE AS BUILT BY HAIF CO. DATE DWG. CONTROL SHT. SE-235870
THIS DRAWING IS NOT DRAWING TITLE INDEX PLANT NO. DRAWING NO. SHEET NO. REV.
TO BE USED FOR
CONSTRUCTION OF CIVIL DESIGN CRITERIA
FOR ORDERING A ASR434 SE-235902 0
MATERIALS UNTIL CONSTRUCTION OF JUBAIL 132/13.8 kV SUBSTATION
CERTIFIED AND
DATED JUBAIL SAUDI ARABIA CONTRACT NO: 4400018951
CERT'D NATIONAL GRID SA
M.H Engineering & Design Department
APPR'D
Engineering Division-South
H.A
CHK'D
SH.S
6.7.3 Welding
THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ELECTRICITY CO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
• Welding shall conforming to TES-W-109.01
• Minimum size of weld shall be 6mm
The vector sum of the design stress due to all forces and moments transmitted by the weld should not exceed the design
ISSUED FOR APPROVAL
•
strength.
DESCRIPTION
• The design stress in a fillet weld should be calculated on a thickness equal to the effective throat size.
• Along edges of material less than 1/4 in = (6 mm) thick; welding shall be not greater than the thickness of the material.
Along edges of material 6 mm or more in thickness; welding shall be not greater than the thickness of the material minus 2
•
mm, unless the weld is especially designated on the drawings to be built out to obtain full-throat thickness.
In the as welded condition, the distance between the edge of the base metal and the toe of the weld is permitted to be less
•
than 2 mm, provided the weld size is clearly verifiable.
Fillet welds and design rules for fillet welds shall conform to AWSD1.1/D1.1M Structural
•
welding code of American Welding Society. AWSD1.1/D1.1M &
Design strength for fillet welds and butt welds (Refer to AWSD1.1/D1.1M Structural welding Chapter 2 of AISC 360
•
code).
M.A.M
BY
The design strength of full or partial penetration butt weld should be taken as equal to
•
that of the parent metal.
27-Dec-23
DATE
NO.
REVISIONS
DESIGNED
BY M.A.M
DATE 27/12/23
CHECKED
BY SH.S
DATE 27/12/23
OPRG. DEPT
BY
DATE
ENG'G. DEPT.
BY
DATE
CERTIFIED.
BY Back to top ↑
DATE AS BUILT BY HAIF CO. DATE DWG. CONTROL SHT. SE-235870
THIS DRAWING IS NOT DRAWING TITLE INDEX PLANT NO. DRAWING NO. SHEET NO. REV.
TO BE USED FOR
CONSTRUCTION OF CIVIL DESIGN CRITERIA
FOR ORDERING A ASR434 SE-235902 0
MATERIALS UNTIL CONSTRUCTION OF JUBAIL 132/13.8 kV SUBSTATION
CERTIFIED AND
DATED JUBAIL SAUDI ARABIA CONTRACT NO: 4400018951
CERT'D NATIONAL GRID SA
M.H Engineering & Design Department
APPR'D
Engineering Division-South
H.A
CHK'D
SH.S
Foundation design shall be based on the allowable bearing capacity of the soil if working loads (unfactored) are to be
•
considered.
THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ELECTRICITY CO. NO REPRODUCTION IN FULL OR IN PART SHALL BE OBTAINED FROM THIS DOCUMENT WITHOUT THE WRITTEN CONSENT OF ITS OWNER.
1 Density of Soil (For Fill Material) 18 kN/m³
2 Effective Density of Soil (For Fill Material) 8 kN/m³
7.2 Recommendations
Type of Type of Footing Depth Ultimate Bearing
# Units
Structure foundation from FGL (m) Capacity
1 150
1 Power TR. Raft 2 150
M.A.M
BY
3 200
27-Dec-23
kN/m²
3 132 kv GIS Room Raft 3&4 200
NO.
REVISIONS
4 Control & Relay Room Isolated footing 1&2 150
DESIGNED
BY M.A.M
5 Future Capacitor Bank Isolated footing 1&2 150
DATE 27/12/23
CHECKED
CERTIFIED.
BY Back to top ↑
DATE AS BUILT BY HAIF CO. DATE DWG. CONTROL SHT. SE-235870
THIS DRAWING IS NOT DRAWING TITLE INDEX PLANT NO. DRAWING NO. SHEET NO. REV.
TO BE USED FOR
CONSTRUCTION OF CIVIL DESIGN CRITERIA
FOR ORDERING A ASR434 SE-235902 0
MATERIALS UNTIL CONSTRUCTION OF JUBAIL 132/13.8 kV SUBSTATION
CERTIFIED AND
DATED JUBAIL SAUDI ARABIA CONTRACT NO: 4400018951