PFC3
PFC3
NP7 - 035
ISSUE 8
August 1997
Installation
and Adjustments Manual.
SAFETY PRECAUTIONS
Before operating the generating set, read the generating set
operation manual and this generator manual and become familiar
with it and the equipment.
Due to our policy of continuous improvement, details in this manual which were
correct at time of printing, may now be due for amendment. Information included
must therefore not be regarded as binding.
CONTENTS
SAFETY PRECAUTIONS IFC
SECTION 1 GENERAL DESCRIPTION 3
SECTION 3 INSTALLATION 8
3.1 General 8
3.2 Generating Set Protection; General 8
3.3 Basic Operation - Power Factor
Control of Individual Generator(s) - Fig 6 8
3.3.1 Voltage Input ( E2 , E1 ) 8
3.3.2 Current Input ( S1 , S2 ) 8
3.3.3 AVR Control Output ( A1 , A2 ) 11
3.3.4 Circuit Breaker Input (CB1 , CB2 ) 11
3.4 Installing Options - Fig 8 11
3.4.1 Remote Power Factor (VAr) Adjustment - <1> 11
3.4.2 Remote Switching of Power Factor/VAr Mode - <2> 11
3.4.3 Generator Current Limiting - <3> 11
3.4.4 Excitation Voltage Limiting - <4> 11
3.4.5 Voltage Matching - <5> 11
3.5 PFC3 used for Power Factor Correction - Fig 9 11
4.1 Installations 15
4.2 Commissioning Basic System 15
4.2.1 Preliminary Adjustments 15
4.2.2 Droop Setting 16
4.2.3 PFC3 Setting 17
4.3 Commissioning Options 17
4.3.1 Voltage Matching Option 17
4.3.2 Current Limiting Option 18
4.3.3 Low Excitation Limiting Option 18
4.3.4 Dead-Band and Dynamic Control Options 19
4.4 Power Factor Correction 19
SECTION 6 OPERATION 22
6.1 General 22
6.2 Combined Heat And Power Installations 22
6.3 Peak Lopping Installations 22
6.4 Power Factor Correction 22
6.5 Synchronous Motors 22
6.6 Overvoltage 22
1
Newage International STRONGLY recommend that when a PFC3 is used
then "Loss of Excitation" tripping should also be used.
2
SECTION 1
GENERAL DESCRIPTION
The control loop within the PFC3 has two modes of operation to
allow for the best response matching of the prime-mover governor
and the generator voltage regulator. 'Dynamic Control' is the
preferred method providing continuous correction and high
accuracy. 'Deadband Control' provides an alternative means
which allows the power factor (or VAr) to drift between presettable
Fig. 1b Basic Power Factor Control
limits before any correction signal is given. This method is
employed where system stability may be a problem.
6
Fig 4 (Dead-band vs Dynamic) shows diagramatically the difference between dead-band and dynamic control modes and the effect
of the [ BAND ] control as seen on a typical power factor meter.
7
SECTION 3
INSTALLATION
3.2 Generating Set Protection; General
DO NOT defeat or otherwise disable
any system interlocks whilst installing Unless adequate protection is installed, engine control system
this equipment. malfunction or poor set-up can cause engine over-load or reverse
Warning ! power conditions resulting in damage to the engine.
Generator control system malfunction or poor set-up can cause
generator over-current or loss of synchronism (pole-slipping)
resulting in severe damage to the generator.
To prevent personal injury or damage
to equipment, only qualified personnel Generator Over-current Protection
should install or operate this unit.
Warning ! It is the responsibility of the Generating Set Assembler to ensure
that adequate protection systems are installed to trip the
Important ! The use of Megger or High Potential generator circuit breaker in the event of generator over-current.
test equipment may result in damage
Excitation Loss Protection
to this unit. Disconnect all leads
before using such equipment. It is the responsibility of the Generating Set Assembler to ensure
that adequate protection systems are installed to trip the
3.1 General generator circuit breaker in the event of loss of synchronism.
Newage International Ltd. can supply a suitable unit for linking
The Power Factor Controller PFC3 incorporates as standard with the generator circuit breaker and control gear. Please refer
many features which enable it to be used in a wide range of to factory for details.
applications. These features may be used in any combination
Automatic Synchronisers
depending upon the requirements of the end user.
It is the responsibility of the Generating Set Assembler to ensure
It is assumed that the AVR is ready wired to the generator as that adequate protection systems are installed for Automatic
specified in the appropriate machine wiring diagram. Synchronising of AC Generators.
The following Automatic Synchroniser settings are recommended
In ALL applications of the PFC3, the AVR and generator MUST when using PFC3:-
be equipped with a standard Quadrature Droop Paralleling kit. Generator frequency mismatch 0.1 Hz
This is shown in all figures fitted in 'W' phase (the more normal Voltage mismatch +/-3%
position). For exact details refer to the wiring diagrams supplied CB closing angle +/-10 degrees
with your generator.
Over/Under Voltage Protection
The PFC3 should be located in a clean, vibration free
environment, typically on the back panel of a control cubicle. If It is the responsibility of the Generating Set Assembler to ensure
the unit is for machine mounting it will have been supplied without that adequate protection systems are installed to prevent damage
metalwork and MUST be fitted on anti-vibration mounts equal to to the generator or connected equipment in the event of over or
those of the AVR. under voltage caused by malfunction/poor set-up of the control
system.
All wiring should be carried out using cables rated at 6A/600V
3.3 Basic Operation - Power Factor Control of
(minimum 0.75mm sq : 20AWG). For details of the AVR wiring,
reference should be made to the wiring diagrams supplied with Individual Generator(s) - Fig 6
your generator.
This is the simplest configuration involving one or more
generators coupled to the mains bus.
Different applications may demand the installation of one or more
of the optional features offered in the PFC3. Four typical 3.3.1 Voltage Input ( E2 , E1 )
configurations are described in this manual.
These are connected to the generator output terminals (normally
Fig 6 - Basic Operation - Power Factor Control of Individual 'U' phase and Neutral) and act as the power supply to the unit as
Generators well as its sensing input. The maximum voltage allowed at these
terminals is 277Vac/60Hz. If local regulations demand supply
fuses, then these should be rated at 5A.
Fig 7 - Replacing earlier VAr2 with the PFC3
3.3.2 Current Input ( S1 , S2 )
Fig 8 - Maximum configuration - All Options Fitted
These are connected to the generator current sensing C/T having
Fig 9 - PFC3 used for Power Factor Correction a secondary rating of 5A. This MUST be positioned in the correct
phase and with the correct polarity for successful operation of
the PFC3. See wiring diagrams for details of your particular
IF IN DOUBT - REFER TO FACTORY machine. If local regulations demand, then either lead S1 or S2
may be grounded.
8
3.3.3 AVR Control Output ( A1 , A2 ) Important ! Do NOT ground the screen at the
switch end. Simply leave the screen
These are connected directly to the corresponding terminals on unconnected and insulated.
the AVR. Should the cable length between the PFC3 and the
AVR exceed 5m (16ft) then it is advisable to use screened leads 3.4.3 Generator Current Limiting - <3>
with the cable screen connected to terminal A1.
Under certain operating conditions it is desirable to be able to
Important ! Do NOT ground the screen at either end.
limit the maximum current delivered by the generator. Connect
the current transformer to the terminals 0V and ILIM as shown.
3.3.4 Circuit Breaker Input ( CB1 , CB2 ) The current transformer should have a secondary current output
of 0.32A (class index 3.0) at 100% generator output and must
Contact closure of these terminals switches the PFC3 into power be positioned in the correct phase and with the correct polarity
factor (or VAr) control operation. These two terminals would for the successful operation of the PFC3. See loose leaf wiring
normally be connected to a normally open auxiliary contact on diagrams for details of your particular machine. Bar mounted
the generator circuit breaker. current transformers with the correct secondary rating and
mechanical fixings are available from Newage International.
In the case of multi-generator installations, where the generator
can run off-grid in parallel (island system), then a normally open Important ! Do NOT ground either lead S1 or S2 of
auxiliary contact from the incoming mains circuit breaker/ the current limiting C/T circuit.
contactor MUST be connected in series with the 'E2' supply to
the PFC. The voltage matching facility will then NOT operate in 3.4.4 Excitation Voltage Limiting - <4>
island operation. (See Fig 9).
Under certain operating conditions it is desirable to be able to
Where the PFC3 is used to replace an earlier VAr-2 then the limit the minimum excitation voltage (and therefore excitation
alternative wiring as shown in Fig 7 can be used. This will current) to prevent generator pole slipping. All that is required to
eliminate the need for any wiring changes when fitting the new enable this facility is to install two wires from X and XX (exciter
PFC3. 'Voltage matching' will NOT operate with this wiring field + and -) on the generator to the terminals X and XX on the
configuration. PFC3. See loose leaf wiring diagrams for any additional details
of your particular machine.
3.4 Installing Options - Fig 8
Important ! Do NOT ground either lead X or XX.
If it is required to expand on the basic use of the PFC3 and to
use one or more of the built-in options then the following notes 3.4.5 Voltage Matching - <5>
apply.
Under certain operating conditions it is desirable to use the
Note: The numbers in the <brackets> refer to the relevant feature voltage matching facility built into the PFC3. The inputs L1 and
shown in Fig 8. L2 have been designed to accept a standardised 110-120Vac
supply from the customers low, medium or high voltage bus. In
3.4.1 Remote Power Factor (VAr) Adjustment - <1> ALL cases the supply to the PFC3 MUST be isolated using a
suitable transformer but unlike the other unit inputs, the phasing
is unimportant. The input burden is typically 5VA.
Should front panel/remote adjustment of power factor or VAr be
required then a 10k ohm / 1W potentiometer may be connected Important ! Do NOT ground either lead L1 or L2.
to terminals RX, RY and RZ as shown. The use of screened
leads is essential with the screen connected to the adjacent
'0V' terminal.
3.5 PFC3 used for Power Factor Correction - Fig 9
Important ! Do NOT ground the screen at the It may be a requirement of certain applications to use the installed
potentiometer end. Simply leave the generating capacity in conjunction with the PFC3 to 'correct the
screen unconnected and insulated. power factor' of the incoming mains supply (at the consumers
incoming tie with the mains). In all cases it is necessary to protect
When fitted, the external potentiometer has complete control the generator against excessive current demand by fitting the
over the PFC3 set-point and the on-board adjustment is no longer current limiting option.
effective.
The current limiting transformer(0.32A sec) MUST be fitted in
3.4.2 Remote Switching of Power Factor/VAr the generator output (as shown in Fig 9) and must be correctly
phased.
Mode - <2>
The power factor control current transformer (5A sec) MUST be
Should front panel/remote selection of power factor or VAr fitted in the incoming mains tie with the correct position and
operating modes be required then a single pole changeover phasing. This is usually 'U' phase but local variations may be 'A'
switch (rated at 1A/240V) may be connected to the terminals PF phase, L1 or cables 'red' in colour.
, C and VAR as shown. This will replace the link which is normally
fitted. The use of screened leads is essential with the screen
IF IN DOUBT - REFER TO FACTORY
connected to the adjacent '0V' terminal.
11
9
To prevent personal injury or damage to Before running the generator, the installing/ commissioning
equipment, only qualified personnel engineer should ensure that all equipment is correctly installed
should install or operate this unit. During and that the generator set is safe to start. They should also have
commissioning the engineer will have studied the section on user adjustable controls and selection
Warning ! access to live components and terminals. links and should have become familiar with their function.
Maximum care should be taken when
making adjustments not to contact live If the generator set controls are normally set to apply load
parts. Refer to the generator and automatically then this feature should be inhibited or switched
switch-gear manufacturers handbooks for to 'manual'.
other safety notices.
Important ! All paralleling operations must be
carried out in compliance with the
The following commissioning procedures generator set designers/ installers
cover ONLY the features of the PFC3. instructions. Newage International
They DO NOT cover such matters as take no responsibility for equipment
electrical installation, phase sequence, damage caused by incorrect
Warning ! switchgear or engine controls. paralleling operations.
Installations making use of one or more of the optional Before starting the generator set the commissioning engineer
features: should first make sure that the user adjustable controls and
selection links on the PFC3 and certain AVR controls are set as
Follow sections titled: follows.
4.2 Commissioning Basic System and:
4.3 Commissioning Options Note: CW = Clockwise Adjustment
CCW = Counter-Clockwise Adjustment
Installations configured for power factor correction:
n The droop circuit polarity has now been verified and must
The Input Voltage Selection should be made appropriate for the now be set to a level for the best operation of the PFC3.
application (normally line-neutral voltage). Refer to wiring
diagrams supplied with your machine for further details. n Open the generator circuit breaker and stop the set
before proceeding.
Potentiometer d
Position ( % ) = X 100%
AVR S1 S2 voltage
Potentiometer 0.25
Position ( % ) = X 100% = 50%
0.5
16
4.2.3 PFC3 Setting 4.3 Commissioning Options
Having set the AVR droop equipment the PFC3 can now be Before the generator and its PFC3 is put into full operation it will
commissioned as follows. also be necessary to set-up any of the optional features being
installed. The operation of the PFC3 and AVR will have already
Important ! Make sure that the AVR Trim control is been checked during the Commissioning of the basic system.
in the fully counter-clockwise ( 0% )
position. 4.3.1 Voltage Matching Option
n Start the generator, synchronise it with the mains supply
The Voltage Matching Transformer /Isolating Transformer (user
and apply load as described in the section on droop setting.
At this point the power factor should still be near unity. supplied) should be connected as shown in Fig 9. With the system
voltage and frequency at its nominal value, the secondary voltage
(applied to PFC3 terminals L1 and L2) should be nominally
n The 'CB' LED on the PFC3 will indicate that the generator
100Vac to 120Vac. The phasing of this signal is unimportant.
circuit breaker is closed. Check that this is illuminated.
Note: Certain 'third-party' current transformers do not n The PFC3 will now gradually adjust the generator voltage
comply with standard marking conventions. to a new value which could be higher or lower than the bus
voltage. Return the generator voltage to the 'matched'
n Re-start and parallel the generators, apply load and condition by slowly adjusting the BUSV control on the
confirm that the voltage across AVR terminals A2 and PFC3. If the generator volts are 'High' (compared to the
A1 is now of the correct polarity. bus) then the BUSV control should be adjusted slowly anti-
clockwise to equalize the bus and the generator voltages.
n Slowly adjust the PF/VAR control on the PFC3 to its If the generator volts are low then BUSV control should be
fully clockwise position (maximum lead) and measure adjusted clockwise.
the voltage appearing across AVR terminals A2 and
A1. This should be between -2Vdc and -5Vdc (meter Note: The circuit may take several seconds to return the
leads: positive on A2, negative on A1). generator voltage to the 'matched' condition. Due
allowance must be made for this delay whilst making
Stop the generator and turn the PF/VAR control on the PFC3 to adjustments. For best results it is advisable to adjust
the midway position. Turn the Trim control on the AVR to the in small steps and wait for the response.
fully clockwise position.
Stop the generator and turn the AVR Trim control to the fully
The PFC3 is now ready for operation. clockwise position.
17
4.3.2 Current Limiting Option 10. Turn ILIM slowly clockwise. TP2 voltage should reduce in
value. If it rises then stop generator and reverse the S1 S2
Current limiting should only be used when the PFC3 is connected connections to the PFC3 0V and ILIM terminals. Re-
for Power Factor correction of the incoming main feeder. test from line 5.
If the generator has the MX321 AVR and separate current limiting 11. Adjust ILIM until TP2 = Required voltage as calculated
equipment fitted, this should be disabled by turning the ILIM in line 9.
control on the AVR fully CLOCKWISE. 12. Stop the generator and remove the generator CT
The Current Limiting Transformer should be connected as shown connections S1 S2 on the PFC3 and terminate the
generator CT wires with a suitable shorting link.
in Fig 8 (feature 3). The phasing of this C/T is important.
13. Connect the mains feeder CT S1 / S2 cables to the
For power factor correction applications it is usual to have two PFC3 (observing polarity) and remove the mains
current transformers (C/T's) fitted in the generator terminal box, feeder CT shorting link.
one with a 5 Amp secondary and one with a 330 mA secondary.
There will also be a 5 Amp secondary CT fitted to the Mains 14. Turn the PFC3 PF / VAR setting potentiometer to the
Utility incoming feeder. centre position.
The 5 Amp Generator mounted CT is used for normal 15. Start the generator and parallel to the mains network.
Commissioning and Generator Power Factor Control. This will 16. Set the generator to the required operating kW.
be unused in Power Factor Correction operation and provision
should be made for connection of a shorting link to prevent an 17. Adjust the desired mains power factor using the PF /
open CT secondary. VAR setting potentiometer on the PFC3.
The 330mA Generator mounted CT is used for measuring 18. Set-up is now complete.
generator reactive current for the I Limit feature. 4.3.3 Low Excitation Limiting Option
Low Excitation Limiting should only be used when the generator
The 5 Amp CT connected to the Mains Utility incoming feeder is is to be operated at leading power factor.
the one used in service for Power Factor correction. This CT
could be carrying site current and provision should be made for The Excitation Limiting input ( X and XX ) should be connected
the connection of a shorting link to prevent an open CT secondary. in parallel with the generator exciter field winding as shown, in
Fig 8 (feature 4). The two exciter field connections ( X and XX )
1. With the generator stationary connect the generator will normally be found at the auxiliary terminal block within the
mounted 5 Amp CT to the PFC3 S1 S2 terminals, generator. If these terminals do not exist, a suitable connection
observing polarity. Generator wiring diagrams will show block can be obtained from Newage International.
the full details.
Connect a digital multimeter as follows:
2. Connect the Generator mounted 330mA I Limit CT Negative Input to 0V (any of four) on the PFC3
to the PFC3 connections 0V / ILIM, S1 to ILIM, S2 Positive Input to Test Point TP4 on the PFC3
to 0V. Generator wiring diagrams will show the full Set to measure on the 20Vdc scale
details.
n Set the voltage matching selection link to NORM.
3. Turn the PFC ILIM potentiometer fully anti-clockwise.
n Start the generator and run-up to rated voltage and
4. Set PF / VAR selector to PF. frequency. DO NOT PARALLEL.
5. Parallel generator to mains network and run at maximum n Using the graph shown in Fig 11, adjust the low excitation
kW set-point rating. limit control XLIM to set the voltage on the test point as
indicated.
6. Adjust the PFC3 to give a generator PF of 0.9 lagging.
n Stop the generator and set the voltage matching selection
7. Calculate the operating Per Unit Reactive Current (PURC) link to its original position.
against generator rating :-
The low excitation limiting option is now set.
Fig. 10
8. Measure TP2 voltage between 0V and TP2, meter neg (-)
on OV. This should be between +2 and +4V dc. For the
location of TP2, see the label drawing on the PFC3 access
cover plate or PFC3 manual.
18
4.3.4 Dead-Band and Dynamic Control Options leading power factor must be treated with care. Operating the
generator at leading power factor will cause the excitation to be
reduced to a level where loss of synchronisation may occur. This
For the majority of applications, dynamic control is recommended
may cause protective equipment to operate and the loss of the
as this is the more accurate and has the fastest response time of
correcting influence of the generator or, in extreme cases,
the two operating modes. However, if instability is encountered,
equipment damage.
then dead-band control may provide the necessary flexibility
within the generator control loop to overcome this undesirable
effect. Where these conditions are likely to exist it is recommended that
the Low Excitation Limiting option be used (see section 4.3.3).
In dynamic mode, correction signals are continually fed to the
AVR in order to maintain the set power factor. In dead-band Use of Excitation Loss equipment is also strongly recommended
control, the power factor is allowed to 'drift' within preset limits for all installations where industrial ac generators run in parallel
before any corrective action is taken. Allowing the loop to 'open' with the mains supply (see section 3.2).
in this way provides for a less accurate control but much improved
stability.
Before the generator is put into operation in this mode the Current
Limiting option MUST be installed and commissioned (see section
4.3.2).
CW = Narrow Band
5.2 Selection Links & Switches
CCW = Wide Band
{ PF - C - VAR } Power Factor or VAr modes
[ CLK ] Sets the rate at which AVR adjustments are made
(in dead-band mode only).
{ NORM - C - VMAT } Normal or Voltage Matching modes
E000 - 21030 (BLACK)
CW = Faster Rate
CCW = Slower Rate
{ 1 = DYN 2 = DBD } Dead-Band or Dynamic modes
E000 - 22090 (GREEN)
[ GAIN ] Makes the controller more or less sensitive to
deviation from the set-point (in dead-band mode
only) by altering the size of each adjustment. { DBD - C - DYN } Dead-Band or Dynamic modes
E000 - 21030 (BLACK)
CW = Large Adjustments made
CCW = Small Adjustments made { C - 220 - 240 - 277 } Input Voltage Selection
E000 - 21030 (BLACK)
[ ILIM ] When this option is wired/enabled, adjusts the level
at which generator current limiting takes place. { 115 - C - 220 -
240 - C -277 } Input Voltage Selection
CW = Decreases the current level E000 - 22090 (GREEN)
CCW = Increases the current level
20
Fig. 12 PFC3 User Adjustable Controls and Selection Links
Part number E000 - 21030 (BLACK)
21
SECTION 6
OPERATION
6.1 General 6.6 Overvoltage
Important ! Before putting the generator into full If at any time during generator operation, the terminal voltage
operation the Trim control on the AVR exceeds the rated generator voltage stated on the nameplate,
MUST be set to the fully clockwise position. then stop the generator and consult the factory.
Under normal circumstances the operation of the PFC3 is fully n The reactive power output (kVAr) of the set is controlled
automatic and once commissioned the unit should continue to entirely by the excitation system of the generator (i.e
operate without further attention. Should the system fail in service, the AVR). Problems concerning reactive current
the trouble shooting chart shown in Fig 14 will be helpful in (circulation/ fluctuation etc.) are almost certainly to do with
identifying the cause. the generator AVR and its associated equipment.
23
SECTION 8
TECHNICAL SPECIFICATION
Input voltage (50-60Hz) 115 range 110-125v ac Applies to PFC E000 - 22090 (GREEN)
220 range 200-230v ac 5VA
240 range 231-250v ac
277 range 251-290v ac (60 Hz only)
Power Factor setting range (PF) 0.7 lag to 0.7 lead (see note 1)
Reactive current setting range (VAR) generate/absorb 0-100% gen. current (see note 1)
Note 2: Control accuracy may drift if the CT secondary current falls below 0.5 Amps.
24
NEWAGE INTERNATIONAL LIMITED
REGISTERED OFFICE AND ADDRESS:
PO BOX 17
BARNACK ROAD
STAMFORD
LINCOLNSHIRE
PE9 2NB ENGLAND
SUBSIDIARY COMPANIES
9 6
10
4 2
2 CHINA: WUXI NEWAGE ALTERNATORS LIMITED 8 SINGAPORE: NEWAGE ASIA PACIFIC PTE LIMITED
Plot 49-A, Xiang Jiang Road 10 Toh Guan Road #05-03
Wuxi High - Technical Industrial Dev. Zone TT International Tradepark
Wuxi, Jiangsu 214028 Singapore 608838
PR of China Telephone: Singapore (65) 794 3730
Tel: (86) 51 027 63313 Fax: (65) 898 9065
Fax: (86) 51 052 17673 Telex: RS 33404 NEWAGE