Schedule B
Schedule B
CONSTRUCTION DIVISION
ESTD.
1949
Percentage Unit RateTender for the work :- Supply, Installation, Testing and Commissioning of Fire Fighting System including Fire
Hydrant Network , Fire Alarm and Sprinkler System , Allied accessories etc. in different Buildings of University Campus
ITEM
ITEM DESCRIPTION QTY UNIT RATE AMOUNT
NO
Supplying, Installation, Testing and commissioning of G.I. "B" Class
Heavy duty pipes as per IS: 1239/ IS: 3589 including cutting, screwing,
1 welding etc. and providing all fittings like flanges, bends, tees, elbows, 1 RMT 2000.00 2000.00
reducers, clamps etc. (A) 200mm (Rates are including for job work of
making connection to exsiting water tank)
2 Do…do….(B) 150mm 1 RMT 1519.00 1519.00
3 Do….do….(C) 100mm 1 RMT 1007.14 1007.14
4 Do…..do…..(D) 80mm 1 RMT 953.51 953.51
5 Do……do….(E) 50mm 1 RMT 725.00 725.00
6 Do…. do….. .(F) 40mm 1 RMT 556.78 556.78
7 Do…..do…... (G) 32mm 1 RMT 455.55 455.55
8 Do…….do…...(H) 25mm 1 RMT 362.00 362.00
9 Do…….do…...(I) 20mm 1 RMT 264.00 264.00
10 Do…….do…...(J) 15mm 1 RMT 210.00 210.00
Supplying, Installation, Testing and commissioning of G.I. "C" Class
Heavy duty pipes as per IS: 1239/ IS: 3589 including cutting, screwing,
11 welding etc. and providing all fittings like flanges, bends, tees, elbows, 1 RMT 3350.00 3350.00
reducers, clamps etc. (A) 200mm (Rates are including for job work of
making connection to exsiting water tank)
12 Do…do….(B) 150mm 1 RMT 2450.00 2450.00
13 Do….do….(C) 100mm 1 RMT 1590.00 1590.00
14 Do…..do…..(D) 80mm 1 RMT 1250.00 1250.00
15 Do……do….(E) 50mm 1 RMT 750.00 750.00
16 Do…. do….. .(F) 40mm 1 RMT 690.00 690.00
17 Do…..do…... (G) 32mm 1 RMT 550.00 550.00
18 Do…….do…...(H) 25mm 1 RMT 490.00 490.00
Applying priming coat over steel and other metel surface after and
including preparing the surface by throughly cleaning, oil,grease, dirt and
other foreign matter and scoured with brushes fine steel wood, scrapers
19 and sand paper with ready mixed priming paint brushing red lead 1 SQM 41.06 41.06
complete for all heights with necessary scaffolding as per the instruction.
Painting two coats (excluding priming coat) on steel and other metal
surface with premium enamel paint, brushing, interior to give an even
shade including cleaning the surface an even shade including cleanicn the
20 1 SQM 103.46 103.46
surface of all dirt, dust and other foreign matter complete for all heights
with necessary scaffolding as per the instructions.
Hydrant valves (also called Landing valves) provide the means to draw
water for firefighting from the Fire water piping network.They are
normally mounted onto stand posts , fitted on the fire water network. Brief
Description :Hydrant Valve (Double headed), as per IS: 5290, made of
23 Stainless Steel (SS304), having 100 mm flanged inlet, and 2 Nos. 63 mm 1 Nos. 11200.00 11200.00
Female Instantenous outlets, C.I. handwheels for hydrant operation,and
PVC blank caps with chain. Body duly painted with 2 coats of superior
quality paint. H.P. tested to 21kgf/cm2 (body) and 14 kgf/cm2 (seat). Flow
1800 lpm (min) at 7 kgf/cm2.
Short Branch Pipe with Nozzle is the most common fire fighting nozzle
in use in the country. The nozzle gives a solid jet and different sizes (bore)
of nozzles can be fitted to the branch body depending upon operational
requirement. Brief Description Short Branch Pipe with Nozzle,
24 conforming to IS: 903,madeof Stainless Steel (SS304) fitted with 15/ 20 1 Nos. 1780.00 1780.00
mm bore nozzle, for projecting for projecting water in form of solid jet.
The Branch shall have 63mm MaleInstantaneous Inlet, suitable for use
with 63 mm size Fire fighting hoses. H.P. tested to 21 kgf/cm2 for 2.5
minutes.
Hose Reels Drum are first aid firefighting equipment, meant for use by
untrained/semi-trained personnel at the incipient stages of the fire. Hose
Reels are strategically located at various locations, and fed by pressurized
supply of water. A rubber/ PVC hose of 1”dia. (of 30/ 36 mtrs length) is
wound on the revolving drum, and connected to a discharge nozzle.Brief
25 Description Hose Reel (Swing type), As per IS:884, made of M.S. 1 Nos. 7800.00 7800.00
construction, having Rubber/PVC hose of 1”/ 3Ú4“ dia. of 30/36 mtrs.
length, and fitted with Gunmetal/Stainless Steel Shut off nozzle. The Hose
Reel shall provide a good range jet at the specified pressure for effective
firefighting.
Hose boxes Double Door provide the means to store Delivery Hoses and
branches in indoor and outdoor locations. They protect the
Hoses/Branches from the effects of weather, dust, etc, and allow quick
deployment of the same in the event of emergency. Hose Boxes can be
mounted on the wall, or if outdoors, on specially fabricated stands. Brief
26 Description Box, made of Carbon (Mild) Steel sheet, 18 gauge thickness, 1 Nos. 3850.00 3850.00
approx. dimensions 750 x 600 x 250, suitable for storage of 2 No. 15 Mtrs.
63 mm Delivery hose, and short branch. Box shall have glass front, and
locking arrangement (& small glass window for storing key opener) as per
IS : 636 .
ITEM
ITEM DESCRIPTION QTY UNIT RATE AMOUNT
NO
Hose boxes Single door provide the means to store Delivery Hoses and
branches in indoor and outdoor locations. They protect the
Hoses/Branches from the effects of weather, dust, etc, and allow quick
deployment of the same in the event of emergency. Hose Boxes can be
mounted on the wall, or if outdoors, on specially fabricated stands. Brief
27 1 Nos. 2100.00 2100.00
Description Hose Box, made of Carbon (Mild) Steel sheet, 18 gauge
thickness, approx. dimensions 450 x 600 x 250, suitable for storage of 1
No. 15 Mtrs. 63 mm Delivery hose, and short branch. Box shall have glass
front, and locking arrangement (& small glass window for storing key
opener) as per IS : 636 .
RRL Hose Pipe With SS 304 Coupling Delivery Hose Couplings provide
the means to connect Fire Hoses to one another and to hydrant valves,
branches, fittings and adaptors. Instantaneous couplings consist of Male
and Female parts, and have a serrated tail portion, on which the hose is
28 1 Nos. 4255.00 4255.00
mounted and bound with Copper/ G.I. wire. Brief Description type
Male/Female Hose couplings, 63mm size, Conventional design, made of
Gunmetal, suitable for use with 63 mm Fire fighting delivery Hose.
Fire Brigade Inlet (also called Pumping In Breech) allows Fire Tenders
(Pumpers) to pump in water into the DryRiser/ Wet Riser/ Sprinkler
system piping using external water sources such as hydrants. Fire Brigade
Inlet isfitted with required number of standard Male Instantenous inlets to
feed the Riser pipe depending upon size.Brief Description (Pumping in
29 Breech), having Cast Iron body with 4 Nos. 63 mmsize SS Male 1 Nos. 9800.00 9800.00
Instantaneous inlets (with NRV), and 80 mm size flanged outlet, suitable
for connection to DryRiser piping. Fire Brigade inlet body shall be
provided with drain valve for draining water after operation.
Fire Brigade Inlet (also called Pumping In Breech) allows Fire Tenders
(Pumpers) to pump in water into the Dry Riser/ Wet Riser/ Sprinkler
system piping using external water sources such as hydrants. Fire Brigade
Inlet is fitted with required number of standard Male Instantenous inlets to
feed the Riser pipe depending upon size.Brief Description (Pumping in
30 Breech), having Cast Iron body with 2 Nos. 63 mm size SS Male 1 Nos. 7255.00 7255.00
Instantaneous inlets (with NRV), and 80 mm size flanged outlet, suitable
for connection to Dry Riser piping. Fire Brigade inlet body shall be
provided with drain valve for draining water after operation.
Fire pump panel for Booster Pump - Starter panel with star delta or as per
77 CFO approved starters rated sto suit pump HP with necessary protection 1 Nos. 34500.00 34500.00
features.
ITEM
ITEM DESCRIPTION QTY UNIT RATE AMOUNT
NO
Supplying, installation, testing & commissioning of electric driven
pressurisation JOCKEY ELECTRIC PUMP (fire hydrant & sprinkler
system) suitable for automatic operation & consisting of following etc.
complete in all respect as required. Vertical Inline type, multistage,
centrifugal pump of cast iron body and bronze impeller with stainless steel
shaft, mechanical seal conforming to IS: 1520. Suitable HP, SQ cage
induction motor TEFC type synchronous speed 2900RPM suitable for
78 operation on 415 volts, 3 phase 50 Hz. AC with IP 55 protection for 1 Nos. 40890.00 40890.00
enclosure, vertical mounted type with class 'F' insulation, conforming to
IS: 325. M.S.fabricated common base plate, coupling, coupling guard,
foundation bolts etc. as required.suitable cement concrete foundation duly
plastered with anti vibration pads as required (A) 7.5 HP (SUITABLE
HEAD AND LPM)
79 Do… do… (B) 10 HP (SUITABLE HEAD AND LPM) 1 Nos. 54340.00 54340.00
80 Do… do… (C) 12.5 HP (SUITABLE HEAD AND LPM) 1 Nos. 62050.00 62050.00
81 Do… do… (D) 15 HP (SUITABLE HEAD AND LPM) 1 Nos. 17165.00 17165.00
82 Do… do… (E) 20 HP (SUITABLE HEAD AND LPM) 1 Nos. 81270.00 81270.00
Supply, Installation, Testing and Commissioning of DIESEL DRIVEN
PUMP(Stand By) fire pump suitable for automatic operation and
consisting of following: complete in all respect as required. a) Horizontal,
centrifugal, end suction pump to ensure a minimum pressure of 3.5 kg /
cm². at highest and farthest outlet at specified flow AND lpm at mtr. head
conforming to IS standards. The installation shall be complete with
flexible coupling and coupling guard as required.b) Diesel engine of 2000
RPM water cooled type with radiator conforming to relevant BS & IS
standard complete with auto starting mechanism, 12 volts/24 volts electric
starting equipment, Diesel tank, exhaust pipe extended up to 1 mtr outside
pump house duly insulated with 50 mm. thick glass wool with 1.0 mm.
thick aluminium sheet cladding, residential silencer, instruments and
protection as per specification, stop solenoid for auto stop in the event of
1 Nos. 334650.00 334650.00
fault with audio indications, painted with post office red colour etc. as
required.c) 1 no. 8 hours capacity day diesel storage tank fabricated from
3 mm thick M.s plates. Tank shall be provided with inlet, outlet, overflow,
air vent, drain connections, filling connection and magnetic level
indicator. Tank shall be mounted on a suitable steel structure (painted with
2 coats of red oxide paint). tank shall be provided with epoxy coat from
83 inside & two or more coats of synthetic enamel paint outside over two
coats of red oxide primer. d) 24 volts 180 AH lead acid battery (24 volts- 2
Nos) with boost/trickle charger for starting the engine automatically
complete as required.
ITEM
ITEM DESCRIPTION QTY UNIT RATE AMOUNT
NO
e) Suitable cement concrete foundation with cement concrete plaster
complete with anti-vibration arrangement of cushy foot mountings shall be
in scope of contractor. Common Base plat for Pump and Engine and
coupling, coupling guard and other accessories as required for complete
installation of pump set.The supply & Installation of J-Type bolt for Pump
fixing in vendor scope. The pump should be tested for bench mark at
factory & Test certifcate submit to client . & The all requrie Technical
specification & Test certificate shall be submit for Local fire Authority
approval.).Casing - Cast Iron to IS:210, Gr. FG260. Impeller - Bronze
IS:318 Br. LTB 2. (BS 1400 GR. LG2) Shaft & Sleeve - ASTM A276
Gr. 410 (A) 39 BHP (SUITABLE HEAD AND LPM)
84 Do…do…. (B) 56 BHP (SUITABLE HEAD AND LPM) 1 Nos. 460000.00 460000.00
85 Do…do…. (C) 76 BHP (SUITABLE HEAD AND LPM) 1 Nos. 611800.00 611800.00
86 Do…do…. (D) 102 BHP (SUITABLE HEAD AND LPM) 1 Nos. 692300.00 692300.00
Supply Installation, assembly, connection, testing and commissioning of FIRE
PUMP CONTROL PANEL as per Drawing, Specification, Technical Data
sheet & IS.Panel shall be manufactured CPRI approved panel manufacturer
with inhouse 7 tank process and painting facility.The unit rate for each item
shall include Testing of panels as per specifications at manufacturer's works in
presence of clients representative and/or consultant.Supply & delivery of the
panels at the site.Assembly and wiring of component supplied
separately.Installation of panels as per lcoation arranged by site engineer in
charge including removing packing.'Shifting of panels from site store to the
suitable location.(If applicable).Installation of panels as per lcoation arranged
by site engineer in charge including removing packing.Earthing all
components, frame etc. to a common internal earth bar.Supply & fixing all
accessories and supporting structure.'Toching of body with poweder coating for
demaged parts. All the nuts bolts & joints exposed to the air shall be covered
87 1 Nos. 12650.00 12650.00
with suitable anti-oxidant material or as directed by the Engineer incharge.To
carry out the insulation test at site and all the readings shall be submitted in
duplicate to the consultant or engineer-in-charge.To prepare submission
drawing and to take approval of consultant at each stage.For panel MS angle
stand required. ( Size MS angle & height of stand as per Panel Weight & size
of cable termination requirement to be calculate by panel vendor, need to
confirm with desing Consultant). Checking of Internal connection and wiring,
operation of switches, starter, MCCB, MCB, relays, contactors etc.Supply of
necessary tools, hardware, testing hardware, testing equipment etc.To prepare
& submit as-built drawing and handing over document to end user. Approval
from consultant required before fabrication of panel. (A) 7.5 HP
103 Single Loop Card for series, capacity of 242 devices 1 Nos. 25000.00 25000.00
104 Dual Loop Card, capacity of 484 devices 1 Nos. 35000.00 35000.00
RS485 Network Card for GST200 series panel and GST-NRP00,
105 1 Nos. 10000.00 10000.00
Maximum 1200 meters, Class A Connection
RS485 Network Card for series panel, Maximum 1200 meters, Class A
106 1 Nos. 10000.00 10000.00
Connection
Supply, Installation,testing & Commissing of Active Repeater with Full
Function Control, 144 character capacity LCD disply 15 LEDs in
107 displying imotant information, repeater panel networking via RS-485, 1 Nos. 30000.00 30000.00
Password protect access levels, Flush-mount or Surface-mount structure.
(Aprroved by LPCB & EN54)
Supply, Installation,testing & Commissing Intelligent Photoelectric Smoke
+ Heat Multi Detector, With Remote Indicator Output, Magnetic Test
108 Function, Built-in microprocessor stores 14 history data, 2-level 1 Nos. 1800.00 1800.00
sensitivities, LED for 360° vision and Removable innovative sensing
chamber. (Aprroved by LPCB & EN54)