On/off Control HF Sensor
HC005S/IR
Super-compact Version
Applications
Occupancy detector with on/off control suitable for indoor use.
Suitable for building into the fixture:
Office / Commercial Lighting
Meeting rooms
Classroom
Use for new luminaire designs and installations
Features
Zero crossing detection circuit reduces in-rush current and prolongs relay life
Loop in
Loop out
Loop-in and loop-out terminal for efficient installation
5-year, Warranty
Technical Data
Input Characteristics Sensor Data
Model No. HC005S/IR Model No. HC005S/IR
Mains voltage 220 240VAC 50Hz Sensor principle High Frequency (microwave)
Stand-by power <0.5W Operation frequency 5.8GHz +/- 75MHz
Load ratings: Transmission power <0.2mW
Capacitive 400VA Detection range Max. ( Ø x H) 12m x 6m
Resistive 800W Detection angle O
30 ~ 150
O
Warming-up 20s Setting adjustments:
Sensitivity 10% / 30% / 50% / 75%/ 100%
Hold-time 5s ~ 30min (selectable)
Safety and EMC Daylight threshold 2 ~ 50 lux, disabled
EMC standard (EMC) EN55015, EN61000
Safety standard (LVD) EN60669-1/-2-1,
AS/NZS 60669-1/-2-1 Environment
O O
EN300440 EN301489, Operation temperature Ta: -20 C ~ +70 C
Radio Equipment (RED)
EN301489-3, EN62479 Case temperature (Max.) Tc: +80 C
O
Certification Semko, CB, CE , EMC, RED, RCM IP rating IP20
RED IP20
19 Hytronik Microwave motion sensor www.hytronik.com
Daylight sensor
Antenna module LED indication
36.5
Detection area
Hold-time
4.2
Daylight threshold
65
71.7
80.5
Power supply
26
220-240V out control
Detection Pattern
0 6
Loop in
Loop out
Hold-time 2~50Lux
6 5s~30min
Note: We recommend the mounting distance between sensors to be more than 2m to avoid sensors from being false-triggered.
Functions and Features
1 On/off Control with Lux Off Function
This sensor is a motion switch, which turns on the light upon detection of motion, and turns off after a pre-selected hold-time when
there is no movement.
Furthermore, a Hytronik specially designed IR photocell is also built in to switch on/off the light based upon ambient natural light
(infrared) lux level. It’s well known that LED lights have a totally different spectrum from natural light (infrared). Hytronik uses this
principle and comes up with this special IR photocell and sophisticated software algorithm to natural light (infrared) from behind the
fixture cover.
Our technology has no infringement to the existing patents in the market.
Settings on this demonstration:
Hold-time: 30min Daylight threshold: 50lux
Insufficient natural light (infrared) and motion Sufficient natural light (infrared) or no motion
detection: light ON after hold-time: light OFF
OR
With sufficient natural light, With insufficient natural light, The sensor switches off the light The sensor switches off the light
(infrared), the light does not (infrared), the sensor switches whenever natural light (infrared) after the hold-time when there is
switch on when presence is on the light when presence is exceeds pre-set daylight no motion detected.
detected. detected. threshold, even with presence.
Wiring Diagram
Control gear
Control gear
1 2 3 1 2 3 1 2 3
DP
0N
Control gear
www.hytronik.com Hytronik Microwave motion sensor 20
2 Zero-cross Relay Operation zero-cross point
Designed in the software, sensor switches on/off the
load right at the zero-cross point, to ensure that the
in-rush current is minimised, enabling the maximum
lifetime of the relay. Alternating current
3 Loop-in and Loop-out Terminal
Double L N terminal makes it easy for wire loop-in and loop-out, and saves the cost of terminal block and assembly time.
TM
4 SensorDIM Function
Working with Switch-dim. control gear (Excel ballast/driver, corridor function), this sensor can also achieve tri-level control.
Wiring Diagram
Switch-dim.
Control gear
Switch-dim.
1 2 3 1 2 3 1 2 3
DP
Control gear
Switch-dim.
0N
Control gear
Detection Pattern
0 6
9
Ceiling mounted height(m)
Wall mounted height (m)
10%
30%
50%
0
75%
10%
30%
50%
6 75%
Ceiling mounted detection pattern (m) Wall mounted detection pattern (m)
21 Hytronik Microwave motion sensor www.hytronik.com
DIP Switch Settings
1 2 3
I 100% I – 100%
1 Detection Range
II 75% II – 75%
Sensor sensitivity can be adjusted by selecting the combination on the DIP III 50% III – 50%
switches to fit precisely for each specific application. IV 30% IV – 30%
V 10% V – 10%
I – 5s
1 2 3
I 5s II – 30s
2 Hold Time II 30s III – 1min
III 1min
Select the DIP switch configuration for the light on-time after presence detection. IV 5min IV – 5min
This function is disabled when natural light is sufficient. V 10min V – 10min
VI 20min
VII 30min VI – 20min
VII – 30min
3 Daylight Threshold
1 2 3
Set the level according to the fixture and environment. The light will not turn on if I Disable I – Disable
ambient natural light (infrared) lux level exceeds the daylight threshold preset. II 50Lux II – 50 Lux
Please note that the ambient natural light (infrared) lux level refers to internal light reaching the III 20Lux III – 20 Lux
sensor. IV 5Lux IV – 5 Lux
V 2ux V – 2 Lux
Disabling the daylight sensor will put the sensor into occupancy detection only mode.
www.hytronik.com Hytronik Microwave motion sensor 22