Lucas Generator Out Put Control
Lucas Generator Out Put Control
a
i
TECHNECAT SERYICE
GENERATOR
OUTPUT CONTROI.
UNITS
OPERATI ON-CONSTRUCTI O N_SERYI CI N G
INTRODUCTION
The mention of any unit, or parts of a unit does not imply the
availability of either the complete unit or spare parts for service
purposes.
Page 3
C0NTEf.ITS
PART 1.
Why control of the generator outpttt is necessary.
The Principles of Voltage Control.
The construction of the control unit.
Voltage control in practice the voltage regulator.
The cutout. -
A theoretical constant voltage control charging circuit.
Compensated Voltage Control.
Why compensation is necessary.
The regulator series and load uindings.
The charging circuit employing the Lucas C.V.C. system'
Temperature com pensation.
Auxiliary circuits the complete colrtrol box.
-
PART 2.
Control Boxes: S1'mbols. T1'pcs :lnd Applications, Service Adjustments.
Symbols.
Features or tl:e R F.95 . 9(r, 97, RB. I 07, RB. I 08, RB. 1 06/ l. RB. I 06/2 control
boxes.
Reguletor nrc'chattical settings and contact cleaning.
Cut-,rri1 tnechanrcul settings and contact sets.
T llc ru'rlulrtlor poirit: resistor.
Frusr,' unils. FS5 -5lF and 4JF.
PAIIT 3.
Chccking the Charging System.
Conrplete test procedure for the charging system, comprising battery and
generirror tests. checking of the regulator, electrical setting; checking
crit-out operation. warning light, ammeter. Possible faults are indicated
at each stage.
I'AiiT ;1
@ Printed in England.
Page 4
PART ONE
Working Principles
o
2
Page 5
THE CONSTRUCTION OF THE CONTROL
UNIT (continued) terminal F connects to the insulated contact point (8).
On the vertical member of this armature a contact When at rest the two contact points will be closed,
point (7) is fixed to line up with a stationary contact thus completing the circuit between the generator
(8) insulated from the main bracket. Also on the armature and field.
vertical member of the armature is a spring blade The contact point assembly of the automatic cut-out
(9) and this blade lines up with an adjusting screw (10). switch (12) is of a generally similqr constructiori but
By means of this adjusting screw the pressure between a single opening and closing operation disconnects and
the two contact points may be varied. connects the generator from the battery. In the rest
The main D terminal of the generator connects position the cut-out points are open whereas the field
to the bracket as shown (11) and the generator field regulator points are closed.
Page 6
THE REGULATOR POINTS RESISTANCE THE CHARGING CIRCUIT
Unfortunately, however, to break the field circuit Let us now build-up a charging circuit from what
when a fairly heavy current is passing causes con- we have discussed so far. Al1 we need is an ammeter
siderable arcing across the contacts. Therefore a in series with our battery, and some sort of switch to
resistor must be placed in parallel with the contacts disconnect the battery from the generator when
to protect them against the heavy inductive surges charging stops. Otherwise the battery would dis-
which occur as they open. t charge itself through the generator windings.
When the regulator contacts are closed the resistance The switch is represented here by a pair of contacts,
is short circuited; it provides however an alternative on the right of the illustration below.
path between D and F when the contacts are open, Follow the circuit from the generator D terminal,
thus quickly limiting the induced field current. along the extended regulator frame, through the
switch and then through the ammeter to the battery.
The circuit is completed via the battery and generator
earths.
trr
GENERATOR FrELp CIRCU1I
VIA RESISTANCE
P.age 7
CHARGING CIRCUIT: "CONSTANT
VOLTAGE CONTROL"
The regulator and cut-out assembly, that is, the
control box, would now look like this. Follow the
circuit through, starting at the D terminal of the
generator, from there to the D terminal of the box
and then to the regulator frame, through the cut-out
when the contacts close, through the heavy series
winding on the cut-out and across to terminal A.
This telminal is connected via the ammeter to the
battery. The circuit is completed by the battery and
generator earths.
Unfortunately, this simple "constant voltage con'
lrol" system has one snag: it presupposes the use
of a generator of very great generating capacity.
Consider the case of a battery in a low state of charge,
its terminal voltage will be low. If, in addition, a
load is put on the battery, switch the headlamps on
for instance, the voltage will fall still lower. Under
such conditions, the generator will still endeavour to
maintain the pre-determined voltage set by the
regulator and consequently an extremely heavy
cuirent will flow in the charging circuit, owing to the
substantial difference between the battery and genera-
tor voltages. In practice this current would be
sufficient to burn out the armature of a standard
automobile generator.
Page 8
THE REGULATOR "LOAD TURNS"
If, when the battery is discharged, all the lights,
etc., are switched on, a further drop in the line voltage
will take place. To compensate for this. one or more
additional turns will be added to the series u'inding
and taken to a terminal marked A1 as shown. These
are called LOAD TURNS and only'become effective
rvhen the lights and any other external load are
switched on.
In appearance all the regulator units are similar and
mechanically this is so. Also with a very few excep-
tions the regulator settings are the sanle.
So, in order to make this standard unit universally
applicable to all types of generators and all models of
vehicles it is necessary to vary the number of turns
in the compensating and load windings. The com-
pensator windings must be made to suit the generator
and the load winding to suit the external loads, that is,
the lighting, etc., for different vehicle layouts.
Thus each type of control box has an identification
number which relates it to the correct generator and REGULATOR SPLIT SERIES WINDING
also the vehicle application. For this reason the
control units must not be interchanged except as
recommended in Lucas Interchangeability Lists.
Page 9
TEMPERATU RE COMPENSATION
The regulators themselves, in addition to having
compensating and load turns, are also TEMPERA-
TURE compensated. This, like the regulator setting,
is common to them all, but is not in any way adjustable.
Put in its simplest form, this temperature com-
pensation aims primarily to make the generator
voltage-setting follow the comparative battery voltage
BI.M EIAL
as it rises and falls due to marked temperature changes. srRr P,
As the charge proceeds, the generator will heat up
quickly. The temperature compensating feature
enables an extra high charge rate to be applied to the BI.METAL STRIP FITTED BEHIND
battery with a cold generator and be maintained until CONTACT TENSIONING SPRING
the generator reaches its maximum working tempera-
ture, when the generator voltage is automatically
reduced by the compensator and the charge proceeds the temperature falls. Having then applied such a
at a normal rate. combination of metals to the regulator adjusting
To this end, as shown in the illustration, a bi-metal spring, a spring tension is obtained which will vary
strip is fitted behind the contact tensioning spring. automatically with the temperature of the equipment.
This consists of two strips of metal with different The controlling voltage of the regulator will thus be
co-efficients of expansion welded together and the higher when it is cold than when it is hot.
combination, when heated, will give a differing degree Like the regulator, operation of the cut-out is
of expansion, causing the combination to bend as the temperature-controlled by means of a bi-metallic
temperature rises and resume its normal shape when tensioning spring.
AUXILIARY CIRCUITS
The regulator unit itself is now complete, but there
are other features of the control box which must be
considered.
On some control boxes, additional terminals are
provided to cater for accessories fltted on the vehicle,
such as trafficators, windscreen wipers, etc.
Extra terminals on this type of box are, flrst: the
A2 terminal. This, as you can see, is connected
from the Al terminal through a fuse marked "AUX"
(auxiliary). Any accessories connected to this ter-
minal will be fed from the battery via the ammeter
through the load turns on the regulator bobbin, with
a fuse in circuit.
Next, the ,A.3 and ,A.4 terminals. The A3 terminal is
fed from the ignition switch, and is thus "live"
only when the ignition switch is on. Both A4 terminals
are then fed through a fuse from A3. Thus auxiliaries
AUXILIARY IGNITION AND ACCESSORIES CIRCUIT connected to ,A.4 will only operate when the ignition
is switched on. The feed to the ignition switch itself
is from A1, i.e., through the LOAD turns.
REGULATOR LOCKNUT
ADJUSTING SCREW
FUSES
COMPENSATED VOLTAGE CONTROL REGULATOR
Page l0
PART TWO
Control Boxe Symbols, Types and Application
!F952 95' RBt07' RB108, RB105/1 AND R8106/2 THE RF96 CONTROL BOX
CONTROL BOXES This control box also has a moulded base assembly
We can now review the Control Boxes themselves. upon rvhich is mounted a similar LRT9 regulator and
In this particular section we will deal r.vith compensated cut-out. Again various split-series windings are
voltage control units only. employed.
To begin with, what are their characteristic features ? The 96 is a more recent design than the 95 and is
With the exception of the RF95/3, RBl07, RB108 and primarily intended for use with the heavier output
RB106i2 the LRT9 regulator is used with a variety of generators, in particular the RA5.
series windings, but the voltage settings are sometimes
The split-series winding generally has fewer turns
special for particular applications.
when used with the heavier output generators.
THE RF95 CONTROL BOX The simplified terminal board of the box is at once
noticeable. (See illustration below).
This control box comprises of a bakelite rnoulding
upon which is mounted the LRTS regulator and the Only terminals required by the regulator and cut-out
cut-out assenrbly. The heavy series turns on the are provided; commencing from the left.
regulator are divided into the main and load com- Al The supply for all external load; comes from
pensating windings. the load turns of the split-series winding.
Two 35 amp. fuses are provided lor the accessory A Comes from the main compensating turns of the
circuits. The one fuse (right) is fed through the ignition series winding.
switch. The second (left) has a direcr supply through F Wired to the generator f,eld terminal.
the load winding ol the regulator. D Wired to the generator main terminal.
The fleld points resistance are in the form of a E For the earth connexion from the LRT9
cartridge placed on the underside of the base.
assembly.
The terminal layout is indicated in the picture.
One or more independent fuse boxes can be fed
Later units of this type incorporate the RB built-in from the Al terminal according to car ffianufacturers'
regulator and are known as the RF95/3. requirements.
Page 11
THE REGULATOR SPLIT.SERIES WINDING
You may have noticed that the number of series
turns on the regulator bobbin varies considerably,
generally, the higher the output rating of the generator'
ihe fewer the series turns required. S'ith the RA5
for instance, the high output generator which was
used by Rolls Royce and Bentley. the regr-rlator split-
series winding has only I main turn. and 1 load turn.
At the other extreme, the regr'rlator used with the
fully enclosed, low output generator on the "Ford-
son" tractor has 6 main and 3 load turns.
Page 12
THE RBt06/1 CONTROL BOX
This control box is similar to tlie RF96, but was
designed for use with the higher output generators
C45PV5 and C39PV2. It may have a series com-
pensating u,inding consisting of only one main turn
and one load turn.
Neither the RBl06i I nor the RF96 are suitable for
use rvith tl.re lorver output, fully enclosed generators, as
the latter. in trying to maintain the regulation voltage
uith little series compensation. would be working out-
side their rated output and rvould thus over-heat.
On the other hand. if the older RF95 with more
series turns u,ere used with the high output generators,
their maxirnurn output would never be available.
This unit is mostly used for 12 volt u,orking but
u'as also available for special 6 volt applications. No
fuse positions are provided.
THE
REGULATOR
R8106/2
- CONTROL BOX
The illustration on the left shows the Iatest pattern
CUT_OUT AAJUSTING
A DJUSTING SCREW R8106/2 which is used on the majority of preserrt-day
SCREW cars. It has the same electrical operation as the
RB106/1.
The rnain difference lies in the mechanical arrange-
n-rentof the cutout and the voltage regulator. The
contacts are now fixed above the bobbins.
As shown, "Lucar" tenr-rinal blades are being
fitted in place of the grub screw type terminals
previously employed.
In addition, the regulator and cut-out electrical
setting adjusters are locked with a compression
spring located behind the head instead of with a
locking nut.
*Al One 17.5 amp. and one 35 amp. blade.
xA As for A1.
F One 17.5 amp. blade.
*D As for A1. The 17.5 amp. is for W/Light corlnex-
ion, the 35 amp. for main generator lead.
E One 17.5 amp. blade.
*Inhibitor tags are fitted in order to prevent crossed
AI AFDE connexions at these terminals. The inhibitor is
attached to the female portion on the wiring harness.
Page 13
CONTROL BOX MODEL RB1O8 On earlier units the cover was secured to the base by
This unit is fitted to tractors, motor cycles and means of four rivets and rolling over of the edge of the
stationary engines. Internally, it is identical with cover. On present day units the cover is rolled over the
control box model RF97 but externally, there are base edges.
differences in the methods of securing the cover and Because of the "rolled over" cover a new method of
of the mounting of the unit. Some units are fitted checking the O.C.V. was devised, see illustration
with the moulded rubber shockproof mounting studs. belou'.
Others are arranged for foot or bracket mounting, see
illustrations below.
FIEGULATOR REGULATOR CUT-OUT AAJUSIING FIXED CONTACT
SERIESWINOINGS ADJUSTING SCREW BLAOE
FROM BA-ITERY
AMMETER OR
LIGHTING SWITCH
TO
EARTH If the positive lead of test voltmeter can be fitted
with a suitable probe to enable it to be inserted into
the "A" terminal socket, then the open-circuit
voltage can be checked without having to remove the
cover, see illustration on left.
TO GENERATOR
If, of course, any mechanical or electrical adjustment
TERMINAL,D.
is necessary the cover will have to be removed.
Page 14
ADJUSTMENTS IN SERVICE
There is only a limited amount of service work (2) Oxidation of the points due to nortnal usage.
possible for the motor engineer who will usually (3) Incorrect air gaps invariably due to interference.
require to work with the components in situ. These faults can usually be corrected quite easily.
The perforn,ance of the regulator may be affected The voltage can be set with the aid of a good Moving
by three factors: Coil Voltmeter as detailed in Part 3. The air gaps
(1) Maladjustment of electrical setting, usually the can be checked and the regulator points cleaned, as
result of tinkering adjustments. detailed in the following paragraphs.
n1
ffi,1*
&#u:e ffi
#B
*p
ffi
ffi*
ffilcffi*s ffiffi
ffiw
ffi ffiffi
i@l
ffi WW
-# 'w
.5s#
ffiffi
Hffi
Page 15
THE REGULATOR VOLTAGE SETTING
Adjustment of the voltage setting is very easily
carried out by means of an adjusting screw, A, atrd
lock nut, B, on earlier units. (A spring loaded screw
is used on later production units).
This dangerously simple adjustment can only be
safely made with the control box connected to a
generator. A good quality moving coil voltmeter
should be used.
The operation as carried out in service is fully
dealt with in "Testing the Charging Systeur".
The regulator settings should always be checked
before any interference with the contact points and
alr gaps.
There are standard settings for all conditions of
working which will be outlined later.
CLEANING THE CONTACTS
L RT9 The contacts on the latest type ol control bor are
easily accessible, so that it is not necessary to adopi
RBr0612 any special procedure belore cleaning them.
Earlier control boxes. for instance. the RF95. RF96,
RF97 and RB106/l employed the LRT9 regulator, and
it is impossible to clean the regulator contacts. untii
the contact plate is swung ontu'ards.
The fixed contact plate is secured by trvo scre\\s.
These are both slackened. especially the upper screii'
(that is, the one farthest from the base plate). The
contact plate is then srvun-e outrvards.
Different materials are required lor cleaning the
regulator and cutout contacts. The regulator contacts
are made of tungsten. and should be cleaned uith
carborundum stone. or silicon carbide paper.
The cut-or.rt contacts are made of silver. and should
CLEANING OF CONTACTS be cleaned with fine glass paper.
A11 dust should be removed rvith a cloth soaked in
methylated spirits.
ARMATURE
@ FIXING SCREWS
REGULATOR @
FRAME ARMATURE
Page 16
o. o3o'-o.oro" n9r, ARMATU RE
CUT.OUT AIR GAP AND ELECTRICAL PRESSED AGAINST A\UGES
SETTTNGS (LRTg)
The cut-out switch seldom calls for any attention
ARMATURE FXING
rvhatsoever.
SCRE:WS
It should to 13.3 volts for the 12 volt
be close at 12.7
rnodel and 6.J to 6. / volts on the 6 volt model and
should re-open at betu'een 8.5 and l0 vglts on ,the,l2 o.ol4" @
voliEocl:l or 4.5 to 5 volts on the 6 volt model, with
a reverse current reading of between 3.5 and 5 amperes
in both cases.
SCRE\Y
The correct air gaps are as indicated in this illus- SECURING
tration:
FTXED CONTACT
A should be .014 inches.
B .0ll to .015 inches.
C .002 to .006 inches. @
D .030 to .034 inches. WITH O.O25 GAUGE BETWEEN ARM.ATURE SHIM
& coRE, CoNTACT cAP TO BE O.OO2: 0.006.
Page 17
R8107, RB108 AND RB105/2 CONTROL BOXES
AIR GAP AND ELECTRICAL
-CUT.OUT
SETTINGS
It is unlikely that the cut-out switch will require
any attention or adjustment, but for general infor-
mation the electrical settings are similar to those for
the LRT9 Units: SIOP PLATE
FIXED @NTAST
Page 18
PUSH-ON COVER
AUXILIARY
TERM INAL
Page l9
PART THREE
Checking the Charging System
SYSTEMATIC CHECKING
It must be understood that the circuit as a whole good tackling the job haphazardly. The fault must
rvill not function correctly unless each of the individr.ral be localised to a particular section, at the same time
units is in order. not forgettin-q of course the wiring verifying the rest ofthe charging circuit on the vehicle.
between them.
In checking for a fault on the charging systenl.
therefore, proceed according to a set plan; it is no
HYDROMETER TEST
First check the specific gravity of the electrolyte in
each cell. Remember, specific gravity is affected by
temperature variation and the figures quoted in the
table below are corrected to 80oF. (26.6"C.). Specific
gravity readings taken at electrolyte temperatures
other than this must be corrected before a true
indication of the state of charge, of battery under test.
can be determined.
I
Hone trade Climates
I
and climqres frequently
Cell lordinarilyl ot'er
belot' | 80't'
800F. I Q6.6'C.)
(26.6"C.)
Page 20
CHECKING THE DRIV!NG BELT AND
GENERATOR BEARINGS k: in.* lin. FRtt PLAY ilETWEIA
The first operation should always be to check the erilrnAT0R 1il0 Eil&lll[ PuLLEYl
driving belt. Atter all the generator can hardly be
expected to give of its best il it is not being driven
correctly. There should be about haif an inch move-
ment in the belt. tested at this point. And remernber
that a belt that is ercessively tight not only strains the
generator bearings. but is aiso liable to damage the
lvater pump gland. Make sure too that the belt is not
frayed or oily. as this will cause slipping when tl.re
generator is under any appreciable load.
One last point. the "V" belt must not be bottomin-u
in the pulley. If it is. either the pulley or the belt is
worn. A check should also be made at this stage for
side plal' or end float in the bearings. Make sure too
that the _senerator leads are tight at the terminals. T[$T Xtnr
Page 2l
CHECKING THE GENERATOR CABLES
If the generator is in order the next step is to check
lhe generator cables electrically, unless a complete
visual examination is possible. i{l'iix)*oei'ffif s
iwffi$pttt
** $
Repeat tl,e last two tests to prove both the D and F
cables as far as the control box.
First re-connect the cables at the generator and
disconnect them at the control box terminals.
The picture shows the first test, namely the volt- ,,t
r,
yneter between D and earth. If there is any doubt as /-!
to rvhich is the D and F cables, obviously this test will ,,u
-1
prove the point. Only one of the two leads should
give a voltage reading D lead. It will record
- the obtained,
trhe armature voltage previously if the lead
,::-...{:S3]
is intact.
At this point it should be stressed, that if the D and
F leads have been accidentally crossed, the regulator
contacts will show very obvious signs of having passed
excessive current. The points will be badly burnt and
in some cases welded together. So be careful when
:e-connecting the leads.
REG ULATOR
- STANDARD OPEN.CIRCU IT
VOLTAGE SETTINGS
Pre-Jarurury, 1956, v,ith .012" bi-metal strip Post-January, 1956, witlt .010" bi-metal strip
Antbient Temperature At 3,0N generator rev.f min. ll 3,000 generqtor rev.f min.
6 volt
l0oc. (50oF.)
*20oc. (68'F.)
t6.3
- 16.9 8.1
- 8.s 16.1
-16.7 I 8.05-8.4s
16.0
- 16.6 8.0
- 8.4 16.0-16.6 I 8.0
-8.4
- 16.5 I
30oc. (860F.) 15.7 16.3 7.9 8.3 5.9 1.95 8.35
40'c. (104'F.) 15.4 - 16.0 7.8 - 8.2
r
rs.8-16.4 I 7.9 -
- - -8.3
*Normal workshop temperature. Correction must be made if prevailing temperatures differ from the standard
Page 22
TO OPEN.CIRCUIT THE CONTROL UNIT-
REMOVE "A'' AND "AI" LEADS
The foregoing method of open circuiting the
regulator will provide an approximate idea of the v# a_ffi &tr ffi fl&{JL&T* ffi &*J U $Tffi r${y$
setting, but in order to get a true reading the following
procedure should be adopted.
The A and A1 lead should first be removed from
the terminals at the control box. This does two
things: it disconnects the battery from the generator
and puts the regulator load winding out of circuit.
In other words, as we are only making a voltage adjust-
ment, all we want in circuit is the voltage regulator
shunt (Voltage-Coil). Tll: series turns would affect
the voltage setting and must be out of circuit if an
accurate reading of the voltage setting is to be obtained.
The A and A1 leads rvill have to be twisted together
after detaching fron-r the control box terminals in order
to provide a feed from the battery to the ignition coil
to enable the en-eine to be run.
RUN GTTIERAT(}T AT
ADJUSTING THE REGULATOR SETTINGS
"q_[sguJ-I=E!g,_"g And now that the regulator is on open-circuit, its
adjustment is very simple.
Run the generator at charging speed. 3,000 rev./min.,
RIASI
. with the voltmeter already connected between regulator
N
frame (Gen. D) and earth. Turn the regulator adjust-
ing screw clockwise to increase the voltage, or anti-
clockwise to lower it, Reconnect A and Al leads.
Remove card from cut-out points.
Do not set the O/C voltage to exceed the maximum
$iInif,$t of the tolerbnce given in the table of settings and
temperatures.
''.
,;, * :
i,
1A
#
Se t
t
ffi
'''"qe8ti:lirilldrlli!l;riu$*ili$!$ise'--'
right off the scale, the most likely fault is a bad control
box earth.
There are two other less likely possibilities: an
open-circuit regulator shunt winding or a short
between the D and F terminals. In all three cases '$ *$$r"erfi*ijr{{}}
*!'$$ {t$l*tli& ,i.
ffiffiffi
#
there can be no regulation of the generator voltage. $i'tilffi wte&i** $:'
Regulation. you remember, depends on the shunt .
.' , '.', . '.......|i:,..1. l
?age 24
THE CHARGING CIRCUIT COMPLETE
-
And just to remind you what we have been checking,
here is a typical charging circuit.
The first check, you will remember, is made at the
battery: the hydrometer and high rate discharge tests.
A check is then made at the generator and the D
and F cables from it to the control box. First with a
voltmeter between D and earth which checked the
armature and brush circuit, and then an ammeter
was added between the D and F terminals to check
the field current. -
Then, at the control box, to check the regulator
open circuit setting. To adjust this setting, the Al
and A leads are disconnected and joined together. We
also made sure that the control box earth was good.
We then checked the operation of the cut-out and
finally the warning light and ammeter. Remember
too, the importance of good wiring and connexions
throughout the circuit. CHAPGING CIRCUIT
@craues
Page 25
PART FOUR
Current-Voltage Regulators (RB 310, 6GC & R8340)
CU RRENT-VOLTAGE CONTROL
The increasing number of electrical appliances now Current-voltage control of the generator rs more
being fitted to the modern vehicle, many of which positive because not only is the generator output
consume relatively heavy currents, has made necessary controlled at a safe maximum, but this maximum
the introduction of a system of regulation more output is used to full advantage, being available if
positive in its action than the compensated voltage necessary for a longer period at the beginning of the
system. charge.
C HARGI NG CHARACTERISTICS
Assume our battery to be discharged, as shown by
the broken line curve, with the Compensated Voltage TEO
Control System, charging commences at a relatively VOLT GE PEGULAIOR
high rate, but quickly begins to taper off, after which,
the charge steadily falls away as the battery voltage
r
rises and finally becomes reduced to a "trickle
charge". AMPERES CUFPEA T VOLTAGE
HOW THE CONTROL UNIT FUNCTIONS Let us study each component of the control
This control box comprises three components: individually after which it will be simple to follow out
the overall method of operation and understand how
(a) A cut-out switch to connect and disconnect the the components combine.
generator and battery automatically.
First let us examine the mechanical build-up of the
(b) A current regulator which allows the generator unit.
to give its maximum continuous output for about
one-third of the time necessary to recharge a
flat battery. YOLTAG€ REGUUTOR
OPERATING WINDINGS
THE REGULATOR AND CUT.OUT
The electro-magnetic relays which operate the
cut-out switch contacts (A) and the voltage regulator
contacts (B) are energised or "excited" by coils of
fine enamelled wire mounted on the respective bobbins
and permanently connected across the generator main
circuit, i.e., "in shunt".
When the generator "builds" a sufficiently high
voltage the current flowing in these windings induces
a magnetic field in the cores of sufficient strength to
pull down the armature and close the contact points,
in the case of the cut-out, and separate them in the
case of the voltage regulator.
Page 27
THE GENERATOR AND CUT.OUT CIRCUIT
The current path from the generator D terminal (or
armature) is taken direct to the frame of the voltage
regulator unit. From there a heavy gauge copper
r',ire is taken to the current regulator and a specified
number of turns of the conductor wound around the
current regulator bobbin. The conductor is then taken
to the cut-out bobbin where several turns are made
befbre it connects to the n-roving cut-out point. From
the fired cut-out point the conductor terminates at the
terminal (B) thus completing the current path from
generator to battery.
The turns of this series winding on the cut-out
bobbin are wound in the same direction as the
previously mentioned shunt winding and so increase
the pull, thus holding the contacts together tightly.
The shunt coil closes the cut-out points at between
12.1 and 13.3 volts on the 12 volt system and current
in the series winding holds them down.
When the generator ceases to charge and the voltage
flalls, these points should re-open at between 9.5 and I 1.0
volts. A reverse current rvill commence to flow back
from the battery into the generator windings. This
reverse current de-magnetises the core and immediately
r,hrows the armature off, thus opening the contact
points.
Page 28
GENERAL METHOD OF OPERATION
Assuming a flat battery in circuit.
Immediately the generator is run it builds up a
voltage. When this rises to between 12.7 and 13.3 in
the case ofthe 12 volt unit the shunt coil ofthe cut-out
is sufficiently energised to close the cut-out points (A)
against the pressure of the adjusting spring.
Current will then flow to the battery and increase
directly with generator speed. By the time the
generator output reaches the permissible uaximurn,
the current regulator coil (B) is sufficiently energised
to pull down the current regulator armature against
its spring setting and so open tl,e contact points.
breaking the field circuit. The generator voltage then
drops, the exciting current in the coil u'eakens and the
regulator points close again allou'in,s the voltage to
rebuild. This opening and closing cycle continues at
between 30 and 50 operations per second. thr"rs limiting increase in amplitude and keep the generator voltage
the total generaror output to a safe marimum. at a sale maximum.
By the time the battery is sornethin-u over one-third In this condition the difference between generator
fully charged its terminal voltage rr'ill l-rave risen, and battery voltage continues to become less and the
resulting in a general rise in the line voitaqe, i.e.. current from the generator is finally reduced to trickle
between generator and battery. When the line charge proportions.
voltage reaches the correct value the voltage regulator
coil (C) is sufficiently energised to pttll down its Frorn the moment that the voltage regulator points
armature against the spring setting. This set of come into operation, the current from the generator is
field contacts will open and ther.r be put into a state of so reduced that the current regulator will no longer
vibration which will reduce and limit the generator operate, and its contact points will remain closed.
voltage. As the battery, and consequently the line In practice. a changeover period often exists when
voltage, continues to rise, the field point vibration rvill both regulators are in operation.
Page 29
CONNECTING POINTS AND The current regulator has no temperature-com-
ADJUSTMENTS pensation.
Let us now examine some of the constructional Adjustment screws for the armature tensioning
details of the RB310 current-voltage regulator.
The first point to note is that there are only three
terminals: B, F and D, reading from left to right in
the picture. The earthing of the box is done through
the fixing screws to the metal base of the assembly.
The fixing holes are provided with rubber cushioning.
The 6GC is slightly different in this respect for it has
an extra terminal "R" provided for earthin_e the base
of the unit to the vehicle chassis. This is similar to the
RB340 covered later in this book, and is fitted because
the base assembly is normally insulated lrom the
vehicle chassis by means of rubber fixing posts.
springs, that is, for adjusting the electrical settings,
The cut-out is temperature-compensated by means are located in the usual position at the back of the
of a bi-metal strip attached to the back of the armature frames.
tensioning spring.
The mechanical settings for the two regulators are
The voltage regulator is also temperature-com- controlled by adjustment screws over the tops of the
pensated by means of a bi-metal strip. bobbins.
Page 30
LUCARTSED VERSION (RB3t0) CU RRENT AOJ USTMENT ScRE* VOLIAGE ADJU'IMElI SCRET'
Page 3l
TO CHECK AND ADJUST THE REGULATOR
opEN-crRculT voLTAGE (RB310 & 6GC)
We commence our adjustn.relrts at the voltage
regulator. First disconnect the lead from the control
box terminal "B" (marked "A" on earlier models) and
connect the voltmeter between "D" terminal (generator
armature) and earth. Then raise the generator speed
slowly to approximately 3,000 rev./min. (for C39PV,
C39PVR, C39Q, C40lt, C40L, C45PV, D5LF, GL45,
G524G,5A and GH45), 1,500 rev./min. (for C47. C48
and D5L), 2,000 rev.imin. (for G5 12). The voltage
should rise and steady itself with a slight flick. Accord-
ing to the temperature this reading should be as out-
lined in the table for voltage regulator electrical settings.
If any adjustment is required do not increase the
speed above 3,000 rev./min. Unlock the adjustment
screw on the back plate of the bracket and screw in-
wards to increase the voltage, and outwards to lower
the voltage, when corrected relock the adjustment a.'",--'---a,
?age 32
THE CUT-OUT SETTINGS
The cut-out should be adjusted next, for unless the
cut-out points close properly, it is impossible to adjust
the current regulator.
Leaving the voltmeter connected as in previous test,
insert an ammeter between terminal "B" and the "B"
cable. Switch on an electrical load, such as headlamps,
and slowly increase generator speed from zero. Closure
of the contacts, indicated by a slight drop in the volt-
meter reading should occur between the following
figures:
Cut-in Drop-olf
l-?
1.
Voltage Voltage
volts volts
l2 volts t2.7-13.3 i 9.5-11.0
6,. 6.3
- 6.7 i rs.o-23.0
4.8
24 26.s-21.0 - 5.s The drop-offvoltage can be checked by disconnecting
the lead from control box "B" terminal and connecting
the voltmeter between this and earth.
The cut-out is adjusted by means of the screrv at the
_ Run the engine up to 3,000 rev./min., then slowly
back. This is screrved inuards. That is to say clock- decelerate, noting the instant when the voltmeter drops
wise, to increase the voltage. and out$ards (or anti- to zero. This should occur between the limits given in
clockwise) to reduce it. the table.
volts I amps.
PY_2 t2 I l9+l
39P-2 . 12 I l0+++
C4OA 12 I r0+++
C4o-16iFan).: :: t2 I zz+t
C40-l (4t" Fan) t2 I
C4OAL t2 | 20+l
10+++
C4OL t2 I 2s+t
c40LQ t2|| 2s+1
c42 12 30+r+
c42 (EASTDRTVE) t2 | :s+ri
C45PV-5 t2I zz+r'
C45PV-6 t2 | 2s+l
c45PV-6 (EASTDRTVE) 12 I 30+1+
C45PVS_6 12 I 2s+1
c47 12 I 30+1+
c48 t2 l 3s+3
TO CHECK AND ADJUST THE CURRENT
REGULATOR
Finally the current regulator is adjusted. The volt-
age regulator contacts are short-circuited by means of a
The current setting is then checked against the
crocodile clip placed across the contact plate to the lgures given in the table for the appropriate generator
frame of the voltage regulator as shown. With the fitted to the vehicle.
battery still disconnected from the "B" terminal, the The output is then regulated by means of the screw
test ammeter is again connected between the lead and in the backplate. Once again, the setting is increased
the terminal, and again the complete load is switched by screwing inwards (or clockwise), and reduced by
on. The generator is then run to charging speed turning it outwards (or anti-clockwise).
approximately 4,500 rev./min. (4,000 rev./min. for Note.-Do not switch lights on after starting the
c48). engine otherwise the bulbs may burn out.
Page 33
MECHANICAL SETTINGS FOR RB31O & 6GC IXED CONTACT
ADJUSTMENT
Adjustment of Air Gap Settings SCREIV
Gauge Thicknesses BOBBIN CORE
Air gap settings are accurately adjusted during ARMATURE
SECURI NG
ASSEM BLY
SCREW.C,
assembly and should require no further attention.
If, however, an armature is removed for any reason, TENSION SPRING
care must be taken to obtain the correct setting on
re-assembly. When setting an armature-to-bobbin
core air gap, the correct size of gauge required is
determined by the thickness of the non-magnetic VOLTAGE ADJLi.STMENT SCREW
separation used in the gap and also, in the case of AND LOCKING NUT
voltage regulators, on the thickness of the bi-metal
spring located behind the tensioning spring of the ARMATURE
ASSEM B LY
armature. (nean vrail)
The above variable features are easy to identify SEPARATI ON ON
BOBB IN CORE
and are as follows:
0.015" separation is by means of a disc of copper.*
0.009" separation is by means of a square of copper.
O.Ol2" bi-metal springs are bright and unplated.
@D
Dlsc
@
SQUARE
Drsc
@
SQUARE
it is well clear of the armature tension spring.
Using a flat steel gauge of appropriate thickness
(see above) and wide enough to cover the bobbin core,
insert the gauge between the underside of the armature
ARMATURE and the copper discx or square. Take care not to
GAUGE turn up or damage the edge of the disc* or square.
DISC
sllE I
o.ors" I --i _.--+
/ Press the armature down squarely against the gauge
o'or8" /--t-;=== and re-tighten the two armature assembly securing
SQUARE
'tffi frrE screws. With the gauge still in position, screw in the
il fixed contact adjustment screw until it touches the
armature moving contact. Re-tighten the locking nut.
CURRENT REGULATOR Carry out the electrical settings.
Page 34
CUT.OUT RELAY MECHANICAL SETTINGS
Slacken the two armature assembly securing screws
so that the armature is loosely attached to the cut-out
frame. Slacken the adjustment screw locking nut and
unscrew the adjustment screw until it is wel-l clear of ARMATURE
the armature tension spring. ASSEM BLY BACK STOP
SECU R I NG
Press the armature down squarely against the core SCREIYS
face (copper sprayed in earlier units or fitted with a
CONTACT BLADE
square of copper in later units), and re-tighten the two
FRAME
armature assembly securing screws. No gauge is
necessary.
CORE
Press the armature down against the core face and ARMATURE
adjust the armature back stop so that a 0.018" gap is TENSION
obtained between the tip of the back stop and the SPRI NG F IXED
contact blade. CONTACT
POST
Insert a 0.010" thick flat steel gauge between the ADJUST HEIGHT BY
underside of the armature and the copper separation. STRAIGHTENING OR
The gauge should be inserted from the side of the core AD.JUSTMENT SCREW
BOWING LEGS
nearest the fixed contact post. The leading edge of AND LOCKING NUT
the gauge should not be inserted beyond the centre CONTACTS
line of the core face. Press the armature down against JUST TOUCHING
the gauge and check the cut-out contacts. These U
Page 35
THE RB34O CONTROL UNIT _ GENERAL
DESCRIPTION
The model RB340 control box rvill eventually super-
sede the model R83l0. Whilst the electrical functions
of the RB340 are the same as the RB3l0 and 6GC,
the mechanical arrangement of its regulators, and cut-
out unit is different.
Also, the base which was previously a box type
pressing now consists of a simple flat plate to which the
resistors and Lucar connectors are riveted (see illus-
tration). The contacts, which on the RB310 and 6GC
are positioned above the bobbin-cores, are, on the
RB340, situated parallel to the rear limb of their magnet
frames. The cut-out, voltage and current regulator
tensioning springs are riveted to the upper limb of the
armature. Another notable feature of the assembly The main service feature is the simplicity of making
are the toothed adjustment cams carried on the front mechanical and electrical adjustments. Simple
limb of each frame. With the aid of a special tool armature-to-bobbin-core air gap settings are the only
electrical adjustments are made by turning the cams to mechanical adjustments to be made. The three
vary the spring tension acting on the associated armatures are riveted to the rear limb of U-shaped
armature, except for the cut-out drop-offvoltage, which magnet frames thus their back air gap is fixed and non-
is effected by bending the fixed contact bracket. adjustable.
TEMPERATU RE COMPENSATIO N
As in the case of the RB3l0 and 6GC, the voltage
regulator and the cut-out of the RB340 are temperature
TTMPTRATURE compensated, by means of bi-metal strips. But, in
C(}MPENSATlof'J addition, tlie RB340 has a double swamp resistor. con-
nected in series with the two shunt coils.
The resistor has a higher resistance than the two
shunt coils, and it is made of an alloy, which is not
affected by changes in temperature. Thus, for all
practical purposes, the resistance ofthe shunt windings,
and the resistor will remain constant, although there
are considerable changes in temperature.
RESISTORS
SWAMP RESISTOR CONTACTS RESISTOR
As in the RB3l0 and 6GC, the resistors are posi-
tioned beneath the base. Contacts resistors and swamp
resistors are fltted to all units but an additional resistor,
the field parallel resistor, is fitted to units controlling FIELD PARALLEI.
C48 generators. RESISTOR
Page 36
Identifi-
Resistance cation
in ohms colour
Sw'amp Resistor (12-volt units)
Measured on unit betrveen
centre tag and base: 13.25-14.25
R eplacement resistor measured
between end ta_es before fitting
to unit: 53-57
Field Paraliel Resistor
As fitted in units controlling
model C48 generators: 95-105 Orange
Slunt Winditzgs ot 20oC. (68',F.)
Voltage regulator ( l2-volt !.el!:
UNT|L rN 1962, THE Vn. I *. MAGNET F&MEs WEFE LTNXEO 6y A CONN€CIOn THpMH Warca
units): r0.8-12.0 EARLY
(ril rHE coNi€rs cuoseo eosrror)rre FrELD oRRrNr pAssEo. vr^ rHa c.o, r qn. saRras
Cut-out Relal (12-volt r.rnits): 8.8- r 0.5 ttNotNcst lo TERMTNAL'D:
SYSTEMATIC CHECKING
As the R8340 is electrically similar to the R83l0 We will assume that both the battery and generator
& 6GC the instruntents and preliminary checks given have been tested, and have been found satisflactory.
on page 3l also applr'. ['e now proceed to adjust the control box.
Page 37
CUT.OUT SETTINGS AND ADJUSTMENT
Again as in the RB3l0 and 6GC the cut-out should
be adjusted nert. for unless the cut-out points close
properly, it is impossible to adjust the current regulator.
The voltmeter can be left connected between the
"D" terrninal and earth as in the open circuit test, and
the ammeter inserted between the "8" terminal and
tire "B" leads (these should be joined together if more
than one is fitted as shown).
Switch on an electrical load, such as the headlamps
and slowly increase the generator speed from zero.
Observe the voltmeter pointer, it should rise steadily,
as engine speed is increased and then drop slightly at
the instant of the contacts closing. The cutting-in
\--
volta-qe should occur between the following limits. '*
\
Generator Cutting-in Drop-o.fJ
Voltage Voltage Voltage
Page 38
CURRENT REGULATOR SETT!NGS
The current regulators should be set to the following Generalor Voltage Setting
values with the generator running at 4,500 rev./min.
(4,000 rev./min. for C48). volts amps.
C39PY.2 t2 19+ I
Unsteady readings are probably due to dirty c3sP-2 :: 12 l0+++
mechanical settings. C4OA 12 l02L+i
lf, however, the reading is steady, but is higher or C40-l (5" Fan) .. 12 22Ll
lower than the maximum rated output of the genera- C40-l (4j" Fan) 12 20+l
tor, the regulator setting must be altered, by turning C4OAL 12 10++i
the adjustment cam, with the special tool. C4OL 12 )s-L
When, for instance, the tool is turned in a clockwise c40LQ 12 ?{-!
direction, the setting is raised. On the other hand, C40T 12 18+
the setting is lowered, when the tool is turned anti- C4OT t2 )) -)-
clockwise. c42 t2 30* l1
c42 (EASTDRIVE) 12 35+t+
C45PV_5 t2 22+.1
C45PV_6 12 25+l
c4sPv-6 (EASTDRTVE) t2 30+ t+
C45PVS_6 t2 25+l
c47 t2 30+ l+
c48 t2 15-L I
or voltmeter.
MECHAN ICAL SETTI NGS: I NTRODUCTION In general, fluctuating readings are due to three
We have told you how the RB340 control box is factors:-
checked and regulated, while it is still in position on the (i) Oxidation of contacts.
vehicle. However, during the course of the tests, you (ii) Foreign matter in air-gaps.
may have obtained fluctuating readings on the ammeter (iii) Incorrect air-gap settings.
CLEANING THE CONTACTS wiped away by means of a fluffiess cloth, which has
We will first consider oxidised contacts. This is a been moistened with methylated spirits (de-natured
condition, which arises normally in service. Hence, all alcohol).
contacts should be cleaned periodically. Different The cut-out contacts are made of silver, and should
materials are required for cleaning the regulator and be cleaned with a piece of fine glass paper. All dust
cut-out contacts. The contacts for the voltage and should be removed with a cloth soaked in methylated
current regulators are made oftungsten, and so should spirits. On no account should carborundum stone or
be cleaned rn'ith fine carborundum stone or silicon emery paper be used for cleaning the cut-out contacts,
carbide paper. The dust and foreign matter should be or the silver contacts will be damaged.
CURRENT AND VOLTAGE REGULATORS: underneath the armature. Particular care must be
AIR-GAP SETTTNGS (EARLIER UNTTS) taken to avoid damaging the copper shim).
We will now consider how the air-gaps of the While the gauge is kept in position, you should
RB340 Current Voltage Control Box are set. press down the armature, and screw in the adjustable
Once again we must remind you that the air-gaps
contact, until it just touches the armature moving
and the fixed contact setting have been accurately set contact. The locking-nut is then retightened, and the
gauge is withdrawn.
during production. However, if the settings have been
disturbed in any way, they must be carefully reset.
Let us first describe the method for adjusting the
AIR GAP SETTING
regulator air-gaps. o 5'!O.O4g-
As we have already stated, the RB340 has toothed
adjustment cams, instead of the adjusting screws on
other control boxes. A special tool is, therefore,
needed, and the cams are turned as far as possible in
an anti-clockwise direction. (That is, to the point
giving minimum lift to the armature tensioning spring).
The adjustable contact is then screwed back, and a
gauge of .045" is inserted between the armature and
the copper separation on the core face. (The gauge
must be inserted, so that it reaches the two riyets CONTACT ADJUSTMENT
Page 39
REVISED AIR.GAP SETTINGS FOR LATER
UNITS
Later units manufactured since Decernber, 1963 do used to allou, for the space fonlerly occupied by
not have the copper separation in the top gap of the copper, the total gap measurement being unchanged.
voltage and current regulator. Therefore, when setting. To do this, the gauge thickness of 0.045" previously
the air-gaps of these units, a thicker -eauge must be given nTust be increased by .007" to 0.052".
Pa*ee 40