TP04P PLC Instruction

The Delta TP04P is a text panel PLC that supports 16 to 32 inputs and outputs, featuring a shared program download port and various graphical programming objects. It requires specific Delta power supply modules and includes safety precautions for installation and wiring. The document provides detailed specifications, installation instructions, and electrical requirements for the TP04P model.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
51 views8 pages

TP04P PLC Instruction

The Delta TP04P is a text panel PLC that supports 16 to 32 inputs and outputs, featuring a shared program download port and various graphical programming objects. It requires specific Delta power supply modules and includes safety precautions for installation and wiring. The document provides detailed specifications, installation instructions, and electrical requirements for the TP04P model.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 8

ENGLISH

Thank you for choosing Delta TP series products. TP04P is a text panel PLC supporting
16~32 inputs and outputs, various instructions, and 8k steps SRAM for programming.
TP04P features the same program download port shared by both PLC and TP editing
software: WPLSoft and TPEditor. It also offers various graphical objects for developing
the program. The user can also obtain higher efficiency by purchasing additional
extension cards, which increase the program portability and save the program download
time. Please ensure to use TP series with Delta power supply module, DVPPS01 and
DVPPS02.
Please read this instruction carefully before use. This instruction sheet only provides
introductory information on electrical specifications, general specifications,
installation and wiring. For detailed information on programming and instructions,
please refer to “DVP-ES2/EX2/SS2/SA2/SX2/SE Operation Manual—Programming”.
For information about optional peripherals, please see individual product instruction
sheet enclosed with TP04P.
Switch off the power before wiring. DO NOT touch any terminal when the power is
switched on. DO NOT touch any internal circuit in 1 minute after the power is
switched off.
DO NOT connect AC input power to any of the input/output terminals, otherwise
serious damage may occur. Check all the wiring again before switching on the
power.
Make sure the ground terminal is correctly grounded in order to prevent
electromagnetic interference.
The display panels of TP04P series products are waterproof. However, please
prevent grease, corrosive liquids and sharp objects from contacting TP04P series
products.
Please use the fixed supports which are packed in the product package. Tighten the
cables or screws according to the specified torque, otherwise serious damage may
occur.

Product Outline and Dimensions


Front Panel
U ser -def ined key

P ow er indic ator E sc ape /Exit ke y


A larm indic ato r

D is play area Le ft /R ig ht k eys

F un ct io n/N em e ric k eys E nt er k ey

U p/D ow n ke ys

Back Panel
Input/output terminal bl ocks

Input/output Program uplaod/download


terminal blocks communication port (USB)

Program copy DC power suppl y


card interface
RS485 communic ati on
Run/Stop swtich

-1-
Front View and Right Side View (Units: mm, [ ]: inch)
175.8 [6.921]

59.2 Figure1
[2.331]

Mounting Dimensions (Units: mm, [ ]: Top View (Units: mm, [ ]: inch)


inch)

162.2
[6.386]
162.7~164.0 [6.4055~6.4567] Figure3
Thickness Range 0.5~5mm
Figure2

Model Name and Serial Number


T P0 4P - 3 2 T P 1 R
S eries name
P LC m ode
N umber of inp ut/output po in ts
Input /o utp ut f unction
Ou tpu t type

Function Specifications
Model
TP04P series
Spec.
Screen type/Display
STN-LCD/Monochromatic
color
Driver Delta automation products
Function/Numeric
0~9, ESC, F, Enter and Up/Down/Left/Right keys
keys
Alarm LED indicator Power indication (Blinking for three times)/Communication error
(Red) alarm/User program indication
Automatically turning off the backlight: 1~99 minutes (0: The backlight
is not turned off.)
Backlight
(The life span of the backlight is about 50,000 hours at a temperature
of 25°C)
Contrast adjustment Set by software, 10 levels of adjustment
ASCII: (Code page 850) Alphanumeric code (including European
characters)
Language/Font
Taiwan: Traditional Chinese fonts
China: Simplified Chinese fonts
Resolution 192 × 64 dots
Display range 101.8 mm (W) × 35.24 mm (H); 4.1” (diagonal)
Font size ASCII: 5 × 8, 8 × 8, 8 × 12, 8 × 16

-2-
Model
TP04P series
Spec.
5×8 dots: 38 characters × 8 rows 8×12 dots: 24 characters × 5 rows
Display text
8×8 dots: 24 characters × 8 rows 8×16 dots: 24 characters × 4 rows
Program Transmission method: Virtual communication port
upload/download Data length: 7 or 8 bits, Stop bits: 1 or 2 bits, Parity: None/Odd/Even
communication port Baud rate: 9,600 bps~115,200 bps
USB (COM1) USB: USB (Type B) terminal
Extension Asynchronous transmission method: RS-485
communication port Data length: 7 or 8 bits, Stop bits: 1 or 2 bits, Parity: None/Odd/Even
RS485 (COM2) Baud rate: 9,600 bps~115,200 bps
RS485 (COM3) RS-485: 8 PIN-removable terminal block
Battery cover DC 3V battery
Monitoring method Download program to TP through virtual COM port
Extension interface Slot for a program copy card

Panel component Explanation


Status 1: When power is ON, LED will start to blink slowly
Alarm LED indicator
(Red) Status 2: When the user-defined conditions are met, LED will blink for
one second repeatedly along with an alarm sound.
Power LED indicator
When the power is connected to the product, LED will be ON.
(Green)
Display area LCM display area. It is used to display current program status.
0~9: They function as constants. Users can also define the keys by
Numeric keys
themselves.
Function keys Users can define the keys by themselves
If the input value is correct, users can press the key. Users can define
Enter key
the key in the user page.
Up: increase the value or move up one page.
Down: decrease the value or move down one page.
Up/Down/Left/Right Left: Left direction key. Can be used to select the position of the
keys value.
Right: Right direction key. Can be used to select the position of the
value.

Electrical Specifications
Model
TP04P-16TP1R TP04P-32TP1R
Spec.
CPU LPC1787FBD208
Program memory 1 MB-flash memory
RAM of the system 64K Bytes
24VDC (-15% ~ 20%) (With counter-connection protection on the
Power supply voltage
polarity of DC input power)
Power consumption 3.2W 5.2W
With counter-connection protection on the polarity of DC input
Power protection
power
Insulation resistance >5M (all I/O point-to-ground insulation resistance: 500 VDC)
ESD (IEC 61131-2, IEC 61000-4-2): 8KV Air Discharge
EFT (IEC 61131-2, IEC 61000-4-4): Power Line: 2KV, Digital I/O:
1KV,
Noise immunity
Analog & Communication I/O: 1KV
Damped-Oscillatory Wave: Power Line: 1KV, Digital I/O: 1KV
RS (IEC 61131-2, IEC 61000-4-3): 26MHz~1GHz, 10V/m
The diameter of ground cannot be less than the diameter of the
Ground power cable. (If severla PLCs are used, they should be grounded
directly.)
Operating temperature
0°C~50°C: Relative humidity: 20%-90% RH (non-condensing)
for hardware

-3-
Model
TP04P-16TP1R TP04P-32TP1R
Spec.
Storage temperature for
-20°C~60°C
hardware
Waterproof class of the
IP66/NEMA4
front panel
Vibration/Shock International standards IEC61131-2, IEC 68-2-6 (TEST Fc)/
resistance IEC61131-2 & IEC 68-2-27 (TEST Ea)
Weight 420g 444g
Dimensions 175.8 × 108.6 × 59.2 mm (Width(W) × Height(H) × Deep(D))
Cooling method Natural air cooling

Model Input terminal


Item 24VDC (-15% ~ 20%) single common terminal
Input number X0, X1 X2~X7, X10~X17
Input type DC (Sinking or soucing)
Input voltage (±10%) 24VDC, 5mA
Input impedance 4.7k ohm
Maximum frequency 10KHz 60Hz
Off On > 16.5 VDC
Action level
On Off < 8 VDC
Response Off On <20us
10ms
time On Off <50us

Model Output terminal


Item Relay
Current specifications 2A/1 point (5A/COM)
Voltage specifications 250VAC, < 30VDC
Resistive 1.5A /1 point (5A/COM)
Current #1
Inductive
specifications
Bulb 20WDC/100WAC
Response time
Approximately 10 ms
Off On
#1: Life curves
120VAC Resistive
3,000
30VDC Inductive(t=7ms)
2,000
240VAC Inductive(cos =0.4)
1,000
120VAC Inductive(cos =0.4)
500
300
200

100
30VDC
Inductive
50
(t=40ms)
30
20 Contact
0.1 0.2 0.3 0.5 0.7 1 2 Current(A) Figure 4

I/O Configuration

-4-
Input Output I/O Configuration
Model
Point Type Point Type 32TP1R 16TP1R
S/S0 C0
X0 Y0
X1 Y1
X2 Y2
TP04P-32TP1R 16 16 X3 Y3
X4 Y4 S/S0 C0
X5 Y5 X0 Y0
X6 Y6 X1 Y1
X7 Y7 X2 Y2
DC X3 Y3
Relay X4 Y4
(Sink or Source) S/S1 C1
Y5
X10 Y10 X5
Y11 X6 Y6
X11
X12 Y12 X7 Y7
TP04P-16TP1R 8 8 X13 Y13
X14 Y14
X15 Y15
X16 Y16
X17 Y17

Installation
Insert TP04P into the opening hole on the panel, and then tighten the screws. If it needs to be
mounted firmly, please use the mounting fixed supports and screws in the accessory package
which is packed with TP04P. Insert the hooks of the fixed supports into the fixing holes on the
back, and then tighten the screws. Please refer to figure 5 and figure 6 below for more
information.
( The torque exerted on a screw should be 4.75 (kg-cm). Please tighten the screws
according to the specifications, otherwise the product may be damaged. If the fixed supports
are not installed well, Delta will not guarantee the waterproof rating.) The cover of the mounting
panel should be waterproof/dust proof or meet the related specifications (IP66/NEMA4).
Do not install TP04P in the following environment.
A location full of Airborne dust, metallic particles, oily smoke, corrosive or flammable
gases and liquids
High-temperature and humid environment
A location in which the product may be shocked and vibrated directly

Figure5 Figure6

Wiring
1. Please use single-core cables or twin-core cables. The
diameters of the cables used should be within the range 22-16AW G
between 16 AWG and 22 AWG (1.5mm). The torque applied
to the screw terminals should be 1.90 kg-cm (1.65 in-lbs).
Please use copper conducting wires. The temperature of the
copper conducting wires should be 60/75 C. < 1.5mm

2. DO NOT wire the empty terminal. DO NOT put the input signal cables and the output signal
cables in the same wiring.
3. DO NOT drop any tiny metallic conductor into the PLC while you are tightening screw and
wiring the PLC. After the wiring is complete, you have to ensure that heat can radiate from the
PLC.
Power Supply
The power input of TP04P is DC. When you operates TP04P, please note the following
points:
1. The power is connected to two terminals, 24 VDC and 0 V, and the range of power is
20.4 to 28.8 VDC. If the power voltage is less than 20.4VDC, TP04P will stop running,
all outputs will be Off, and the ERROR indicator will start to blink.
2. If a power failure lasts for less than 10 ms, the operation of TP04P will not stop.
-5-
However, if a power failure lasts for long, or the power voltage decreases, TP04P will
stop running, and all outputs will be off. After the power returns to the normal status,
TP04P will automatically resume the operation. (Users have to note that TP04P is
equipped with latched auxiliary relays and registers when they write a program.)
Safety Wiring
Since TP04P is only compatible with DC power supply, Delta’s power supply modules
(DVPPS01/DVPPS02) are suitable for it. t is suggested that you shoudl install a
protection circuit at the power supply terminal to protect DVPPS01 or DVPPS02. See
the figure below.

Figure 7

AC power supply:100 ~ 240VAC, 50/60Hz Breaker


Emergency stop: The emergency stop button can be used to cut off the power when an
emergency occurs.
Power indicator AC power supply load
Power supply circuit protection fuse (2A) DVPPS01/DVPPS02
DC power supply output: 24VDC, 500mA DVP series PLC (main processing unit)
Digital I/O module

Input Point Wiring


There are 2 types of DC inputs, SINK and SOURCE. (See the figures below)
SINK Mode SOURCE Mode

+24V 0V S/S X0 X1 X2 +24V 0V S/S X0 X1 X2


DC Power Supply DC Power Supply
Sink mode Source mode

Figure 8 Figure 9

Relay (R) output circuit wiring (Sink)

Figure 10

-6-
P LC Rela y P LC Rela y
output out put La rger power and
S mal ler p ower f requent on/of f
Y Y

R V DC R V DC
D D ZD
C0 C0
D: 1N4001 diode or equi valent com ponent D: 1N4001 diode or equi valent com ponen t
ZD: 9V Z ener, 5W
F i gur e11 F i gur e 12
P LC Rela y
out put
A C loa d
Y
R: 100~ 120
C: 0. 1~0. 24uF
R

R C
C1 F i gur e 13
1 Emergency stop: An external switch is
2
DC power supply
used.
3 Fuse: To protect the output circuit, a fuse having a breaking capacity within the range
between 5 A and 10 A is connected to the common terminal.
4 Transient voltage suppressor: It increases the life span of the terminal.
1. Diode suppression of the DC load: It will be used if the power is small. (See figure 11.)
2. Diode + Zener suppression of the DC load: It is used when the power is large, and
TP04P is turned on and off frequently. (See figure 12.)
5 Incandescent light (resistive load) 6 AC power supply

7 Mutually exclusive output: Y4 controls the clockwise rotation of the motor, and Y5
controls the counterclockwise rotation of the motor. The interlock circuit which is formed,
and the program in the PLC ensure that there are protective measures if an abnormal
condition occurs.
8 Incandescent bulb: Neon light
9 Absorber: It reduces the interference from the AC load. (See figure 13)

RS-485 Wiring
1 D+ D- 2 D+ D- D+ D- 2

3 3
Figure 14

Master station Slave station Terminal resistor


Note: 1. The terminal resistor should be connected to the master station and the last slave
station. The resistance of the terminal resistor should be 120 .
2. To ensure communication quality, it is suggested that users should use double shielded
twisted pair cables (20AWG) for wiring.

Communication Connection
TP04P may connect to a PC by using USB adaptor cable.
Please use an AM/BM USB adaptor cable.

Figure15

Battery’s Life
Temperature (°C) -20 0 20 60
Life (Year) 2.0 2.5 2.7 2.8

Precision of the Real Time Clock


(Second/Month)
Temperature (°C/°F) 0/32 25/77 55/131

Maximum error (Second) -117 52 -132

-7-