0% found this document useful (0 votes)
12 views5 pages

Qap Barc

The document outlines a Quality Assurance Plan for a Fire Alarm System for the Department of Atomic Energy, detailing various components and their respective testing methods, acceptance criteria, and documentation references. It specifies checks for items such as fire alarm control panels, detectors, and sounders, with a focus on visual inspections and functional tests. The plan includes a comprehensive list of components with defined testing extents and acceptance norms to ensure compliance and quality assurance.

Uploaded by

Bhavesh Patel
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
12 views5 pages

Qap Barc

The document outlines a Quality Assurance Plan for a Fire Alarm System for the Department of Atomic Energy, detailing various components and their respective testing methods, acceptance criteria, and documentation references. It specifies checks for items such as fire alarm control panels, detectors, and sounders, with a focus on visual inspections and functional tests. The plan includes a comprehensive list of components with defined testing extents and acceptance norms to ensure compliance and quality assurance.

Uploaded by

Bhavesh Patel
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 5

Address : Unit C-2, Model Indl. Colony,(Vikas Indl. Estate), Vishweshwar Nagar, Rd.

No 2, Off
TECHNOCRATS SECURITY Arey Road, Goregaon (East), Mumbai – 400 063, India.

SYSTEMS PVT. LTD. Web : www.technocrat.asia,www.technocratss.net

QUALITY ASSURANCE PLAN FOR FIRE


TITLE P.O. REF NO. BARC/TSD/96/2016-17/17/953
ALARM SYSTEM
PROJECT DEPARTMENT OF ATOMIC ENERGY P.O. DATE 30th March 2017
OWNER DEPARTMENT OF ATOMIC ENERGY
1 FOR APPROVAL AW BP AK 18/04/2017 BIDDER TECHNOCRATS SECURITY SYSTEMS PVT. LTD.

REV DESCRIPTION PBY CBY ABY DATE DOC. NO. TSS/BARC/FAS/01

Quality Assurance Plan

Sr. Component/ Characteristic Checked Method of Extent of Ref. Accepta Format Of Agency Remar
no. Operation Check(testing and Check Documen nce Record k
commissioning) t/ Spec. Norms (P) (W) (V)
sec. No.
1. Fire alarm a. Appearance a. Visual 100% Datasheet Model MTC/ 2 1&3 1
system Control b. Dimensions b. As per / as per No./ Datasheet/
panel c. Power on check instructions by spec. Article Catalogue
d. mode selection manufacturer No.,
check for c. Verifications Sr.No. /
commissioning and d. Measurements Plate No
operator mode e. Loop and CPU
e. CPU redundancy redundancy will
f. Loop redundancy be shown
Page 1 of 5
physically
during
commissioning
2 Power supply a. appearance a. visual 100% Datasheet Model MTC/ 2 1&3 1
b. rating b. verifications / as per No./ Datasheet/
c. power on check c. as per spec Article Catalogue
instructions by No.,
manufacturer Sr.No. /
Plate No
3 Fire alarm a. Appearance a. Visual(LED for 100% Datasheet Model MTC/ 2 1& 1
system b. Dimensions power ,Fire / as per No./ Datasheet/ 3
repeater panel c. Power on check ,Fault and spec. Article Catalogue
d. mode selection bypass No.,
check for indication) Sr.No. /
commissioning and b. Programmable Plate No
operator mode panel
c. Verifications
d. measurements
4 Optical Smoke a. appearance a. Visual(green led 10% Datasheet Model MTC/ 2 1& 1
Detector b. Model no. label blinking and / as per No./ Datasheet/ 3
and lot no. etc. RED LED spec. Article Catalogue
c. Functional check indication on No.,
alarm Sr.No. /
conditions) Plate No
b. Verifications

5 Multisensor a. appearance a.Visual(green led 10% Datasheet Model MTC/ 2 1& 1


Smoke b. model no. label blinking and RED / as per No./ Datasheet/ 3
detector and lot no. etc. LED indication on spec. Article Catalogue
c. Functional check alarm) No.,
c. verifications Sr.No. /
Plate No
6 Heat Detector a. appearance a. Visual(Green 10% Datasheet Model MTC/ 2 1& 1
b. model no. label LED blinking and / as per No./ Datasheet/ 3
and lot no. etc. RED LED spec. Article Catalogue
c. Functional check indication fire No.,
condition) Sr.No. /

Page 2 of 5
b. Verifications Plate No
7 Beam Detector a. appearance a. Visual(LED 10% Datasheet Model MTC/ 2 1& 1
b. model no. label blinking at / as per No./ Datasheet/ 3
and lot no. etc. Transmitter and spec. Article Catalogue
c. Power on check receiver end) No.,
d. Operational check( b. Verifications Sr.No. /
without integration c. Operation as Plate No
with FAP) per
manufacturers
Instruction

8 Duct Detector a. appearance a. Visual(Green 10% Datasheet Model MTC/ 2 1& 1


b. model no. label LED indication / as per No./ Datasheet/ 3
and lot no. etc. on Detector) spec. Article Catalogue
c. Functional check b. Verification No.,
Sr.No. /
Plate No
9 Manual Call a. appearance a. Visual(RED LED 10% Datasheet Model MTC/ 2 1& 1
Point b. model no. label indication on / as per No./ Datasheet/ 3
and lot no. etc. FIRE it can be spec. Article Catalogue
shown on No.,
testing) Sr.No. /
b. Verification Plate No

10 Sounders a. appearance a. Visual(Activatio 10% Datasheet Model MTC/ 2 1& 1


b. model no. label n) / as per No./ Datasheet/ 3
and lot no. etc. b. Auto addressing spec. Article Catalogue
can be done No.,
and connected Sr.No. /
in loop Plate No
c. Verification

11 Beacon a. appearance a. Visual(Activatio 10% Datasheet Model MTC/ 2 1& 1


b. model no. label n) / as per No./ Datasheet/ 3
and lot no. etc. b. Auto addressing spec. Article Catalogue
can be done No.,
and connected Sr.No. /

Page 3 of 5
in loop Plate No
c. Verification

12 Response a. appearance a. Visual(LED 10% Datasheet Model MTC/ 2 1& 1


Indicator b. model no. label indication / as per No./ Datasheet/ 3
and lot no. etc. during fire) spec. Article Catalogue
b. Verification No.,
Sr.No. /
Plate No
13 PC based a. Appearance a. Visual 100% Datasheet Model MTC/ 2 1& 1
graphical user b. Model no. label b. Verification No./ Datasheet/ 3
interface and lot no. etc. c. Actual working Article Catalogue/
hardware& c. software CD will be at site. No., software CD/
software /license Sr.No. / License of the
Plate No software
14 Linear Heat a. Appearance a. Visual(Heat 10% Datasheet Model MTC/ 2 1& 1
Sensing Cable b. Model no. label testing will be / as per No./ Datasheet/ 3
and lot no. etc. done on site spec. Article Catalogue
c. Functional check after No.,
for the demo commissioning) Sr.No. /
piece. b. Verification Plate No
c. As per
manufacturer
testing
guidelines
15 Control relay a. appearance a. Visual 10% Datasheet Model MTC/ 2 1& 1
Module b. model no. label b. Verification No./ Datasheet/ 3
and lot no. etc. Article Catalogue
No.,
Sr.No. /
Plate No
16 Armored Cable a. appearance a. Visual 10% As per As per MTC/ 2 1& 1
b. model no. label b. Verification spec. spec./ Datasheet/ 3
and lot no. etc. approve Catalogue
d test
certifica
Page 4 of 5
te.
15 Final Testing a. External a. Measurement 100% Datasheet MTC/ 3 1&3 1
Of the System Appearance b. Operation , Datasheet/
b. Over all c. Testing of all Warranty Catalogue,
dimensions the equipment’s Cert./ Internal Test
c. Functionality which is Type of reports/
included in approval Functional Test
BOM. Cert./ Report
Lists of
Internal
Check

LEGENDS:-

P- Performance W- Witness V- Verification

1 Purchaser 2 Manufacturer 3 Vendor(TSSPL)