REPUBLIC OF THE PHILIPPINES
D P W H
ELECTRICAL GENERAL NOTES : SCHEDULE OF LOADS AND DESIGN ANALYSIS: OFFICE OF THE BUILDING OFFICIALS
ALL WORKS SHALL COMPLY WITH THE PROVISION OF THE LATEST EDITION
OF THE PHILIPPINE ELECTRICAL CODE THE RULES
AND REGULATIONS OF THE LOCAL AUTHORITY CONCERNED IN THE ENFORCEMENT
OF ELECTRICAL LAWS AND ORDINANCES ELECTRICAL SYSTEM LEGEND :
AND WITH RULES AND REGULATIONS OF THE UTILITY COMPANY.
POWER SERVICE ENTRANCE FROM THE ELETRIC UTILITY COMPANY NEARBY
WORK SHALL NOT BE STARTED UNLESS A VALID WIRING PERMIT HAS BEEN SECURED. DISTRIBUTION TANSFORMER. RATED 230VAC, 2-WIRE+GROUND,1Ø , 60Hz.
1. SERVICES TO THE BUILDING SHALL BE 230 VOLTS, 3 PHASE, 3 - WIRES + GROUND ELECTRIC PANELBOARD
RP-REPTACLE PANELBOARD
PB-1
2. WIRING METHOD SHALL BE AS FOLLOWS:
PB CIRCUIT HOMERUN DESIGNATION:
a. POWER FEEDERS AND RISERS - SHALL BE IN RuPVC BOTTOM VALUE DENOTES CIRCUIT DESIGNATION AND,
1
UPPER VALUE DENOTES POWER SOURCE OF THE CIRCUIT OR PANELBOARD.
b. LIGHTING AND POWER RECEPTACLE BRANCH CIRCUIT-
POLYVINYL CHLORIDE CONDUIT (PVC) SCHEDULE 40 DUPLEX CONVENIENCE OUTLET, 11 WATTS PINLIGHT
3WIRE+G, 10A, 250VAC.
3. ALL LIGHTINGS CIRCUIT HOMERUN SHALL BE 3.5MM² THWN STRANDED
CU. ALL CONVENIENCE OUTLET CONDUCTORS WEATHER PROOF CONV. OUTLET 23 WATTS DROPLIGHT
SHALL BE 3.5MM THWN STRANDED
20mmØ x 3m COPPERCLAD
AIR CONDITIONING UNIT STEEL EARTH BAR
4. GENERAL USE RECEPTACLES SHALL BE RATED 16A., 250 VOLTS.
5. ALL LIGHT CONTROL SWITCHES SHALL BE RATED 16A., 120-277 VOLTS A.C. ONLY.
6. MOUNTING HEIGHTS SHALL BE AS FOLLOWS:
a. LIGHT CONTROL SWITCH - 1.40M. ABOVE FLOOR AT CENTER
b. CONVENIENCE OUTLET - 0.30M. ABOVE FLOOR AT CENTER,
FOR WEATHERPROOF OUTLET .
MOUNTING SHALL BE VERTICAL / HINGE ON TOP FOR NON WP OUTLET.
c. SPECIAL PURPOSE OUTLET - AS REQUIRED BY EQUIPMENT SERVED.
d. WALL TELEPHONE & TV OUTLET - 0.30M. ABOVE FLOOR AT CENTER
UNLESS OTHERWISE REQUIRED BY FIELD CONDITION.
THIS SITE
4.OM HIGH CONCRETE PEDESTAL
16MM DIA. OVAL EYE BOLT
SERVICE DROP CABLE
METALLIC SERVICE CAP
TELEPHONE AND CATV SERVICE
ENTRANCE CABLES
2x50mm DIA.PVC(1-SPARE)
SCHED.40PVC FOR SERVICE
ENTRANCE CABLES
2x32mm DIA.SCHED.40PVC
CONDUIT ENTIRE LENGTH
EMBEDED FOR TEL.AND
SHALL BE CONCRETE CATV
ENCASED
PROVISIONS
CONDUIT TO ONLY)
RESPECTIVE
PANELBOARD
FFL
CONCRETE PEDESTAL DETAIL
0.15
0.15
0.050
0.15
0.50
TO MDP
SITE DEVELOPMENT PLAN
APPROVED BY : SHEET CONTENTS : SHEET NO. :
RODEL D. DOSANO
PROFESSIONAL ELECTRICAL ENGINEER
PRC REG. NO. : 3757
TIN NO. : 919 280 601
PTR NO.: 9238412
PLACE: BTAC. NUEVO, ILOILO JAN. 06, 2024 OWNER