mP20 II-om Eng
mP20 II-om Eng
mP20 II
INSTRUCTION MANUAL
GB
© UNIFLAIR 2001
CONTENTS
Page
Program Identification 4
Display information with unit OFF 4
Unit start up conditions 5
Start up and Shut down of Unit 5
Display information with unit ON 6
Manual override of switching on / switching off 7
Visualisation of the Unit state. 8
Program Versions 12
#
Special Functions 12
nd
Addressing of 2 level alarm 32
Alarm Readings 32
Default Values 37
Appendix - Screen flow chart 38
PROGRAM IDENTIFICATION
This manual describes the standard regulation characteristics for air conditioning units. Some characteristics of
special-order units may be different from those described in this manual.
…… v .. EN .. / .. / 2001 LAN
A 12:30 31/05/00
INITIATING ... B Temperature 23.5°C
PLEASE WAIT C C
When the unit is connected to the power supply but not running, three TO START UNIT
fields are active on the user terminal display: PRESS ON KEY
1.
A. Time and date (only in units with clock circuit);
WARNING: STOPPED
BY REMOTE CONTROL
B. Room temperature; 2.
If the unit is programmed in the setback mode the following message appears WARNING: UNIT
at regular intervals in field C: IN SETBACK MODE
• The operator must press the OFF button so that the green terminal LED switches on;
• In the event of remote control command (see screens 130a or 130b), the digital input ID1 must be in the closed
contact position;
• the unit must be switched on by the supervisor in the event that it is connected to the unit and the unit is set (see
screens 130a or 130b);
• in the event of daily or weekly time bands, they must enable control switching on.
The display and the green light on the "ON/OFF" button inform the user of the system state.
ON
ON
LOCALLY: the unit is controlled by the OFF button (on pressing the button OFF
once the unit starts up, on pressing the button a second time the unit switches
off). Pressure placed on the ON/OFF button is confirmed by an acoustic 12:30 31/05/00
signal. Temperature 23.5 °C
In direct expansion units the control commands the start up of the START DELAY
compressor in such a way that continuous start up cycles and unit shut down PLEASE WAIT …
is not possible (a maximum of 6 start’s each hour). Start up of the compressor
therefore can be delayed after the ON/OFF button push.
The assumed unit state is memorised; on regaining power the unit assumes ON
the previous state before power loss, the unit will restart if it was already OFF
operating. Re-starting the unit can be delayed by a period of time equal to the
"power on delay" value (see screen 80). 12:45 31/05/00
Shut down of the unit fans is delayed by 10 seconds after the ON/OFF button Temperature 22.4 °C
push. SWICTHING OFF
PLEASE WAIT …
Automatic MODE: the control is set in such a way that the unit switches on and shuts down due to the following:
1. a remote ON/OFF contact (see screens 130a or 130b);
2. a supervision system (only possible in units provided with serial board);
3. automatically programmed time bands (not only unit equipped with a clock circuit);
4. automatic inversion cycle of the base unit.
If programmed in the set back function, the unit switches on automatically also when the set thermo-hygrometric
limits are exceeded.
ON
PLEASE NOTE: in the automatic functioning mode the OFF button can be used only by forcing the switch on or
shut down through inserting the password "SETTINGS" (see paragraph "MANUAL START-UP /SHUT DOWN ").
A. The time (only in the units equipped with a clock circuit), room
temperature, room humidity (only with humidity sensors); MAN REMOTE ALARM LAN 01
B. Current operation: according to the working conditions, the following FORCE SUPERV. SERV. LAN 02
indications are provided:
• "COOLING"/"HEATING"/"DEHUMIDIFICATION"; WATCH CYCLE
• "REHEATING"/"HUMIDIFICATION"
TIMED
C. Manual override with regard to the automatic cycle:
• “MAN” in the operating mode with manual commands;
• “FORCE” if the unit is turned on by manual override;
• “WATCH” when the unit enters the "setback mode" to maintain the
thermohygrometric parameters within the established limits.
F. Indication of the unit, identified by "LAN 01", "LAN 02", …. with more than one connected unit connected in LAN
that are shown as a shared terminal.
P
In this case by pressing the and buttons at the same time it is possible to move from one unit to the
next, following the order with which they were addressed.
OFF
• Contact ON/OFF remote; SWITCH ON/OFF
• Supervision system; MANUAL OVERRIDE
PLEASE TYPE IN
• Automatic inversion of unit in stand-by; PASSWORD: _ 00000
• Automatic time band function. (screen 201)
ON
……
By pressing the OFF button, the display automatically shows screen 201 with any
manual overrides of the automatic function mode.
To access the subroutine, enter the SETTING password found in the envelope
IMPORTANT: On entering three incorrect key words the alarm state is activated
and memorised (see paragraph "ALARM READINGS").
• if the unit is overridden and turned off, in field C of the display appears the
message “ UNIT TURNED OFF - PRESS THE ON/OFF KEY ”;
……
• if the unit is overridden and turned on, in field C of the STATUS SCREEN
appears the message “FORCE”.
UNIT MANUALLY OFF
TO GO BACK TO
(∗)
PRESS ON/OFF KEY
EXITING MANUAL OVERRIDE (screen 204)
To exit from manual override, shown in field C of the STATUS SCREEN with the
ON
UNIT MANUALLY ON
TO GO BACK TO
message “FORCE”, press the button and enter the SETTING password.
OFF
(∗)
If the unit is turned off, screen 204 appears. PRESS ON/OFF KEY
(screen 205)
If the unit is turned on, screen 205 appears.
The line with the asterisk (∗) shows the system commanding the unit. ON
OFF
Having exited from manual override, the message “FORCE” disappears from field
C of the STATUS SCREEN.
The functioning parameters of the unit (temperature, humidity, …) are readable by pressing the button and
scrolling the screens using the and buttons. At the end of the reading cycle the STATUS SCREEN
appears.
Information on the display is shown in the SCREEN FLOW CHART in the appendix; however it is to be noted that
only the information or data relative to the chosen configuration appears:
- time and date appear only in the controls with base circuit supplied with clock circuits;
- temperature sensors which are not present are shown as "NC" in the place of the corresponding reading.
1. ACCESS TO THE CONSULTATION (READ ONLY): possibility to consult data yet without the possibility to
perform any modifications;
2. ACCESS TO PROGRAMME MODE (READING AND WRITING) possibility to vary memorised data and
requires:
P
2.a. pressure on the button for one second (until hearing the acoustic signal);
I/O
2.b. immediate pressure on one of the following buttons: , , , , , ;
2.c. entry of the PASSWORD found in the sealed envelope attached to this manual and addressed to the
maintenance manager (see paragraph "ACCESS LEVELS").
The yellow LED associated to each button has the following function:
- LED on: access to the screens for reading only ;
- LED flashing: access to the screens for programming (by pushing the selected button immediately after the “P”
button)
To move from one screen to another press one of the vertical scrolling buttons or ; any direction (up or
down) you may choose, you will return to the first screen of the SUBROUTINE. To move the cursor to the wanted
From any consultation or programming screen it is possible to return to the unit STATE field by pressing the
. button
IMPORTANT: entry an incorrect password is pointed out by a brief acoustic signal. After entering three incorrect
passwords, the alarm state is activated (see paragraph "ALARMS READING").
ACCESS LEVELS
In the APPENDIX "SCREEN FLOW CHART" is shown with reference and programming screens.
Screens which are displayed directly refer to the chosen configuration (ex.: screens relative to the timer operations
of the electric heaters do not appear if the unit is not provided with this feature).
User interaction with the microprocessor is developed on 3 levels:
1. CONSULTATION METHOD: visualisation of the parameters and reading of the following data:
• Time and date (if the system is equipped with the clock circuit);
• Environmental conditions;
• Measured values of the sensors connected to the system;
• set point of functional parameters;
• memorised and past alarms (with past time and dates only if the system is equipped with the clock circuit).
2. PROGRAMMING METHOD of the OPERATIVE PARAMETERS : to modify the set values of:
• : the working hours threshold of each component to signal the maintenance intervention request;
• : remote command parameters, the local network, supervision and rotation between units.
3. PROGRAMMING METHOD of the CONFIGURATION PARAMETERS and MANUAL COMANDS that allow the
manual start-up of various unit components, independent to the environmental conditions and following
operations:
I/O
• : configuration of unit type, devices password modification and operations on all data present in the
microprocessor memory;
this level is accessible only through using the password "CONFIGURATIONS"/"SERVICE" found in the
closed envelope attached to this instruction manual and addressed to the maintenance manager.
VARIATION OF PARAMETERS
Modification of set parameters and/or configuration in a subroutine (set point, differential…), is as follows:
2. select with the or buttons the screen that shows the parameter (see "SCREEN FLOW CHART"); the
cursor ( _) flashes in the top left corner;
4. to vary the parameter value – this may be numerical or Boolean (YES/NO) – with the or button
(numeric values can be varied only within the set control limits);
• To return to the STATUS screen press the button. In the unit hardware configuration, pressing the
button however returns to the initial "Hardware Configuration" (screen 50);
• To modify parameters in other screens press the button until the cursor is at the start of the first line;
12:30 31/05/00
Temperature 23.5°C
TO START UNIT
PRESS ON KEY
ACCESS
TO SETTINGS
P + ENTER PASSWORD: ……
***** 220
12:30 31/05/00
REMOTE
PROGRAM VERSION
SPECIAL FUNCTIONS
#
In a few program versions, by pressing the button it is possible to visualise a
few special functions, personalised on the clients request.
Possible special functions are illustrated in the APPENDIX.
P +
ACCESS
TO SETTINGS
P ENTER PASSWORD
+
_00000
(screen 210)
/
AIR FILTER
TOT. RUN HOURS 00000
ALARM LIMIT H 20000
RESET --
(screen 13)
……
The steam cylinder needs to be periodically cleaned of the build up of lime; before
removing the cylinder for cleaning or substitution it is necessary to drain completely
the water from the boiler.
To complete this operation it is necessary access to the hourmeter screen in ……
programming mode:
Humidifier Cilinder
- the cursor will appear on the third row of the display (---); Maintenance
_ ---
(screen 19a)
- press the (or ) button to visualise the command "_SWITCH OFF AND
- press the button; the command "SWITCH OFF AND EMPTY" will be
confirmed by a brief acoustic signal and the message "Please wait…" will appear
on the display;
Humidifier Cilinder
Maintenance
- wait about 2 minutes;
Please Wait…
(screen 19b)
- a brief acoustic signal confirms that the draining process is complete and the
message "EMPTY CILINDER" appears on the display; ……(after 2 minutes)
Humidifier Cilinder
- open the humidifier magnetothermal switch and complete cylinder Maintenance
cleaning/replacement; Press Enter to ESC
EMPTY CILINDER
(screen 19c)
- only after all the maintenance operations on the cylinder have been carried out
press the button to restore normal functioning of the humidifier. To restore humidifier functioning
press
I/O
(screen 48)
When a sensor is added or an optional sensor connected to the board is added, it is necessary to carry out the
"HARDWARE SET-UP" command or to set the optional sensors in screen 70, so that the boards registers the
inputs and outputs. Serial boards RS485 or RS422 and the clock circuit are exceptions.
P + I/O
HARDWARE CONFIGURATION
……
P _ Hardware Config.
Access to the unit configuration is possible by pressing the programming Delay Settings
Manual Control
I/O
button until hearing a brief signal and by then pressing the button.
(screen 50)
After introducing the password (screen 220) screen 50 is shown containing three
options: move the cursor vertically to the chosen line with the button and
HARDWARE CONFIGURATION
The unit regulation program needs to be “configured”, that is adapted to the unit in which it is installed; in this phase
it is necessary to define all the elements of the unit and that the microprocessor must control.
As a rule this intervention is only required when the control is installed inside the unit and therefore is carried out in
the factory during final inspections; it can however be necessary to intervene due to further unit modifications.
The screens that refer to configuration are in the English language and are reserved for technicians.
* * * * *: Introduce the password "SERVICE" ("CONFIGURATION PASSWORD") found in the envelope attached to this manual.
Depending on the type of unit (CW, DX, ES, TC) only a few of the screens from 61a to 63 are shown.
ON Fans
OFF
"Summer Temp."
T closed water circuit
(default = 28°C)
6°C
"Summer Temp."
T closed water circuit
(default = 28°C)
6°C
Compressori
differenziale
fisso: 3°C
Electric heater
differential
fixed: 5°C
OPTIONAL SENSORS
At the first start of the board, during the configuration phase carried out in the
factory, the control automatically researches all the devices and sensors /
connected to the terminals, through analysis of the analogue and digital inputs. CL. FILTER P-STAT N
Whatever is inserted – by the installer – an optional sensor (dirty filer pressostat, FLOOD DETECTOR N
flood detector, fire/smoke detector or temperature and humidity sensors), it is SMOKE/FIRE-STAT N
T+H INSTRUMENTS N
necessary to specify this in screen 70. (see also screen 72a – command (screen 70)
"HARDWARE SET UP")
NOTE: the digital and analogue inputs for connection of the optional sensors are
specified in the unit electrical diagram.
SET-UP PASSWORD
Screen 71 permits the possibility to change the password for access:
- to the settings ("SETTINGS" password). See paragraph "ACCESS LEVELS", /
point 2.; SET-UP PASSWORDS
- to the configuration ("CONFIGURATIONS" password or "SERVICE" password). FOR ACCESSING TO:
SETTINGS 00000
See paragraph " ACCESS LEVELS ", point 3. SERVICE 00000
(screens 71)
Since access to the HARDWARE menu is denied if the correct password is not
introduced, it is advised to note down the new password before changing the old
password.
to the unit HARDWARE configuration); where all the set point values reset (screens 72a)
automatically (see paragraph "DEFAULT VALUES").
After this operation it is necessary to re-configure the control and to proceed to the /
setting of the set-point when different from those of the default.
PROGRAM SET-UP NO
AL. PAGE CLEAR-UP NO
IMPORTANT: when modified also if only a parameter of the configuration (and HARDWARE SET UP NO
therefore also for EPROM substitution) it is necessary to empty also the RAM Please Wait…
(screen 72b)
memory by cutting off the power to the control for a few seconds.
AL. PAGE CLEAR-UP. La historical alarms cleaning permits to cancel the last 30
alarm event saved in the memory.
To carry out default factory settings and other memory data (with the exception of "Hardware Configuration"
P
parameters) press both the and buttons at the same time for at least 5 seconds.
A brief signal sounding will confirm that the operation has been carried out correctly.
EPROM SUBTITUTION.
In the event of EPROM substitution control automatically performs all the
operations listed above: memory clear-up, re-setting of the factory defaults,
cleaning of the historical alarms, re-reading of the devices:
- proceed to the configuration and setting of parameters different to that of the
default.;
- cut off power to the control for a few seconds;
- restore power to the control;.
In the event of problems, carry out manually the command program set-up and
repeat the sequence of operations.
DELAY SETTINGS
ACCESS TO ACCESS TO
CONFIGURATION MENU CONFIGURATION MENU
P I/O
ENTER PASSWORD …… ENTER PASSWORD
+
_00000 _* * * * *
(screen 220) (screen 220)
* * * * *: Insert the key word "SERVICE" ("CONFIGURATION PASSWORD") that youm find in the envelope attached to this
manual.
screen 50 Screen 50
Screen 80 manages the behaviour in the initial transitori and the possibilty to set:
• units re-start delay after power loss (‘POWER ON DELAY’); serve to prevent
simultaneous starting in multiple installations;
In the units in LAN there is the automatic progressive re-start sequence (unit 1, Power On Delay s 000
unit 2, …) with intervals of 5 seconds between one unit and the next. LP-Stat Delay s 180
Start Trans. s 60
• (only DX, TC, ES units) the initial period – from the start of the compressor - T+H Al. Delay min 15
during which there is no reading of the low pressure pressostat (‘LP-STAT (screens 80)
DELAY’); permits the start up of the compressor also at tough temperatures
• The period of time that between the start up of the unit and the start of regulation /
(‘START TRANS.’); is the starting period deemed necessary to obtain control Anti-Hunting Time
system stability. Constant of Room
In this period also the reading of the air fluxostat FS is ignored; this permits – Temp. Control min 01
mostly in units with a motorised damper – start-up of the unit without an alarm (screens 81)
signal "Loss of air flow".
• The signal of ambient alarms delay since the unit first starting (‘T+H AL.
DELAY’).
In the next screen 81 there is the setting of the ‘ANTI HUNTING CONSTAT OF
ROOM TEMP. CONTROL’ to avoid excessive thermal excursion. The value has to
be as high as bigger is the thermal inertia in the conditioned room.
MANUAL CONTROL
During normal operation all unit components are controlled automatically, however the simplify maintenance and
regulation operations or in emergency conditions it is possible to force manually– and independent to the
reguklation process the start up of each component.
• Unit fans (Unit start-Up);
• Compressor 1/2;
• (CW units) analogue output 0/1 (Y0/Y1Ramp %);
• Dehumidification;
• Reheating 1 ;
• Reheating 2;
• Forces the analogic output 0/1 in DX, TC, ES units(Y0/Y1Ramp);
The security devices are active also during manual functioning.
To modify the parameter values it is necessary to access to the subroutine "MANUAL CONTROL" from the
"HARDWARE" menu until reaching screen 220 where the password is requested password.
ACCESS TO ACCESS TO
CONFIGURATION MENU CONFIGURATION MENU
P I/O
ENTER PASSWORD …… ENTER PASSWORD
+
_00000 _* * * * *
(screen 220) (screen 220)
* * * * *: Introduce the password "SERVICE" ("CONFIGURATION PASSWORD") found in the envelope attached to this maunual.
screen 50 screen 50
/
MANUAL OVERRIDE
Y0 RAMP % 000
Y1 RAMP % 000
P +
ON/OFF FROM REMOTE: unit start up is managed by the closure of a remote contact N.O. without tension
connected to the board (see electrical diagram). For units with standard regulation program the digital input is: ID1.
SUPERVISION SYSTEM
A supervision system exchanges data via a serial cable with the board of the unit that is commanded and controlled
from remote: for this purpose an optional Serial card is available which permits the interface to a net RS422/RS485
for the transmission of data (see Supervision System manual).
ACCESS TO
CONFIGURATION MENU
P ENTER PASSWORD
+
_00000
(screen 210)
Screens 130a/130b determine if the unit is managed by remote by tele control and
you can set:
• remote start-up/shut down from free contact (‘I/O via Contact’);
• remote start-up/shut down by a supervision system – via serial RS422 or RS485 I/O via Contact N
- (‘I/O via Serial’); if "I/O via Serial YES" is set the possibility to select "I/O via I/O via Serial N
Id# 001 Speed 1200
Contact" is excluded automatically;
• the serial address of the unit connected to the supervision serial network (must (screen 130a)
be the same as the serial address set in the supervision program); the speed of
data transmission (‘Speed.’): 1200, 2400, 4800 for RS422 or 1200, 2400, 4800, I/O via Contact N
I/O via Serial N
9600 and 19200 for RS485. Id# 001 Speed 1200
LAN: UNIT NUMBER 00
(screen 130b)
By selecting 'AUTOM.SWITCH-OVER OF STD-BY UNIT: Yes' in screen 131b it is possible to verify the following
functioning modes:
• one functioning unit; second unit in stand-by;
• Start-up of the reserve unit in the event of the break down of the first unit; the alarm states that activate this
ND
function are those defined in the paragraph "ADDRESSING OF 2 LEVEL ALARM", including the loss of tension in
the working unit
If in screen 131b "1 UNIT ON LIMIT: No' is set, following an alarm situation on the functioning unit the reserve
unit is started and both unit continue to work until the operator intervenes. Only by pressing the button for 5
seconds the alarm is reset and the unit is disactivated.
• Rotation on a temporary basis between the two units; this operation allows the division of the work load onto
two units at intervals of time which are pre-set (see screen 131b "CYCLE TIME");
• It is possible to start-up the stand-by unit as a substitute of the already working unit or in addition. The additional
unit may be useful, for example, in the event of an alarm caused by a high room temperature due to thermal
overloading, however if the available electrical power is sufficient for only one unit it is possible limit the operation
to just one unit.
SCREEN 131b
It does not appear in units not suitable for the LAN connection.
Provides the possibility to control two units of which one is functioning and one is in P +
stand-by by selecting: ……
• The possibility of this management (Yes/No);
Autom. Switch-Over
• the length of the automatic cycle between one inversion and the next (‘Cycle Base / Std-by Pair Y
Time’), within 1 and 999 hours; Cycle Time h 000
1 Unit On Limit N
• the possibility to have only one working unit ('1 Unit ON Limit'), for example with
(screen 131b)
the intention to avoid overloading on a supply line unable to support both units
(eg. UPS).
As an alternative to the control of two units as described above it is possible to manage a local network at the
condition that the board is provided with LAN card and EPROM able to manage the LAN (see next paragraph).
Management of more than two units always requires connection to a local network (see specific instruction
manual).
Screen 133, displayed only if the local network is is set, gives the possibility to
control unit operation with a mean temperature measured in the room or with the
"local" value measured the sensor inside the unit:
- Mode: Local Unit control is made by the temperature and humidity values read
by the sensors in the unit.
- Mode: Mean Unit control is affidato to the mean temperature and humidity
values read by the sensors in the active connected units in the local network.
Whatever the difference between the mean value and the sensor reading exceeds
the value "MEAN/LOC.DIFF." (default equal to 2°C), the control automatically
exchanges from the "MEAN" mode to the "LOCAL" mode.
P +
The set points and other set parameters can be read by pressing the button (it is not possible however to vary
the parameters).
To modify the values it is necessary to access the programming mode and insert the password "SETTINGS"
(screen 210).
ACCESSO TO
SETTINGS
P + ENTER PASSWORD
_00000
(screen 210)
• COOL. SET P.: cooling set point (reference only); (screen 111)
• HEAT. SET P. (°C): heating set point;
• SENSITIVITY (°C): heating proportional band. /
Cool. Set P. °C 23.0
Room High T. °C 30
TEMPERATURE ALARMS (SCREEN 112) Heat. Set P. °C 23.0
Setting of the minimum and maximum room temperatures, when reached a Room Low T. °C 10
(screen 112)
specific alarm signal is switched on (from an internal sensor).
• COOL. SET P. (°C): cooling set point (reference only);
• ROOM HIGH T. (°C): threshold of high room temperature limit alarm;
• HEAT. SET P. (°C): heating set point (reference only);
• ROOM LOW T. (°C): threshold of low room temperature limit alarm.
N.B. the last two lines only appear if the unit is provided with at least one
dedicated heating device.
P +
P +
To change
move to screen 103, otherwise press the button. Press Key "ENTER"
(screen 102)
By using screen 103 (moving from screen 102 by pressing the button) it is
possible to change the classification of the seven days to come, including the PROGRAM. LU 13/10/97
actual day that is shown on the first line of the screen. MO TU WE TH FR SA SU
N N >F N >P >F F
Under each day there is a memorised classification (N or P or F) that can be (screen 103)
by pressing the button the set classification is confirmed and the next day is
selected. If the classification differs from the standard the symbol > appears
automatically before the classification.
The selected time bands will be the same as days of same classification.
The selection of the time bands is cancelled automatically once the day for which it was activated has passed.
To exit from the time-calendar and time bands screens press the button.
P +
ALARM READINGS
ACTIVE ALARMS
By pressing the button the alarm buzzer is silenced and a description of the alarm is shown in the display.
If the cause of the alarm has been eliminated, the last alarm message can be reset by holding the button
down for a few seconds; by doing this the red light on the button switches off immediately.
If the cause of the alarm has not been eliminated, the buzzer is activated again.
All the memorised alarms can be read in order by pressing the button starting from the STATUS MEMORY.
CLOGGED FILTERS
Service time limits overcoming are not memorised and therefore can not be read ("SERV.").
In the sequence the first event shown corresponds to the last alarm.
In microprocessor fitted with clock circuits (optional) during each alarm event the date and ime is shown.
ALARM Signal only. Can be delayed during the unit start-up phase (15 minute default delay).
ROOM TEMPERATURE
ABOVE MAX. LIMIT
ALARM Signal only. Can be delayed during unit start-up phase (15 minutes default delay).
ROOM TEMPERATURE
BELOW MIN. LIMIT
ALARM Signal only. Can be delayed during unit start-up phase (15 minutes default delay).
ROOM REL. HUMIDITY
ABOVE MAX. LIMIT
ALARM Signal only. Can be delayed during unit start-up phase (15 minutes default delay).
ROOM REL. HUMIDITY
BELOW MIN. LIMIT
ALARM Detected by the flood control module, causes the unit to shut down only if selected from
FLOOD ALARM
CHECK WATER the second level alarms..
CONNECTIONS
ALARM Detected by the fire/smoke sensors, causes the unit to shut down only if selected from
PRESENCE OF
SMOKE/FIRE the second level alarms.
Alarms relative to the air conditioning unit components and that are caused by the intervention of a protection
device.
ALARM Only TC units: causes the switching from chilled water (CW) functioning to direct
CW VALVE FAILURE OR
WATER FLOW TOO LOW expansion (DX) stage. Shown also when room temperature sensor detects exceeds for
the first time the set limits.
ALARM Only CW units. When the water flow gauge signals a flow loss in the chilled water circuit.
FLOOD ALARM
CHECK WATER
CONNECTIONS
ALARM CW units (Signal only). Detected by the chilled water temperature sensor when the "Set
WATER TOO WARM TO
GET DEHUMIDIFICATION Point" value set in screen 63 is not reached within 15 minutes after the dehumidification
CHECK CHILLER GROUP call.
ALARM Only CW units. Detected by the chilled water temperature sensors when it exceeds the
HIGH CHILLED WATER
TEMPERATURE: limit "High Temp." set in screen 63.
CHECK CHILLER GROUP
ALARM Fan alarms: Detected by the air flow differential pressostat. Causes the shut down of all
LOSS OF AIR FLOW
CHECK FAN/SWITCH devices (compressors, electric heaters, humidifier, fans).
ALARM Detected by the dirty filter differential pressostat (PFS), causes a single alarm signal,
CLOGGED FILTERS
CLEAN OR REPLACE without affecting the unit functioning. Indicates that the air filter must be cleaned or
FILTER ELEMENT replaced.
ALARM Only DX, ES, TC units. Causes the displayed circuit compressors (1 or 2) to shut down.
COMPR.1 HIGH PRESS.
CHECK REFRIG. CIRCUIT
AND/OR CONDENSER
ALARM Only DX, ES, TC units. Causes the shut down of the displayed circuit compressors (1 o
COMPR.1 LOW PRESSURE
CHECK REFRIG. CIRCUIT 2).
/REFRIGERANT CHARGE
ALARM Alarm detected by the safety thermostat, causes the electric heaters to shut down.
HEATERS OVERHEATING
CHECK AIR FLOW
AND/OR SAFETY SWITCH
HUMIDIFIER ALARMS
SENSOR ALARMS
Relative to the malfunction or the incorrect connection of the sensors to the basic board.
Whenever one of these alarms is activated, verify the accuracy of the set configuration, the presence of the sensor,
the exact connection of the sensor, the functional characteristics of the sensor.
ALARM Disable a unit function according to the sensor signalling
(*****)
SENSOR
FAILED/DISCONNECTED
(*****)
Causes the shut down of the compressors and the electric heaters keeping only the fans
ROOM TEMP.
running.
Disables the free-cooling function control (only ES units) and forces the RAD COOLER
WATER IN T.SENSOR
to work at 100%.
SERVICE NOTES
These report the set service time limits overcoming of the described component refer to signal (cfr. HOURMETER
OPERATION).
As already mentionned, this type of alarms continues until the hourmeter is reset, however it is not memorised in
the historical series of alarms.
SERVICE ALARM Signal only. Can refer to: "UNIT", "Air FILTER", "COMPRESSOR 1", "COMPRESSOR 2",
(* * * * *)
EXCEEDED XXXXX RUN "COMPRESSOR 3", "COMPRESSOR 4", "EL. HEATER 1", "EL. HEATER 2", "HUMIDIFIER".
HOURS
To reset the alarm it is necessary to reset the hourmeter (see paragraph "HOURMETER
READING AND PROGRAMMING").
ALARM Indicates communication problems between the LAN unit and specifies which units are
LAN INTERRUPTED,
DISCONNECTED UNITS not connected. Can be due to a power loss, a malfunction of the serial circuits or an
………………………. interruption in the electrical connections.
The alarm appears on the units which bear the lowest LAN address both just before and
after the disconnection.
SYSTEM ALARMS
ALARM Indicates errors in the EEPROM memory, probably due to the exceeding erasing /
EEPROM FAILURE:
REPLACE CONTROL writing cycles. It is necessary to replace the control board.
BOARD
ACCESS ALARMS
ALARM Refers to an attempt to access the setting screen or configuration with the wrong
ATTEMPT TO ACCESS
WITH WRONG (MIN. 3 OC- password three times in a row.
CURRENCES) PASSWORD
To reset the alarm proceed as follows:
- Enter into the "Hardware Config." Menu and insert the correct password;
- Use the "AL. PAGE CLEAR-UP" command (screen 72a) to cancel the alarms in the
memory;
- Keep the button pressed for 5 seconds until the red light switches off.
DEFAULT VALUES
Please wait … 48
19b
…… SEQUENTIAL DISPLAY OF
ANALOGUE OUTPUT
Humidifier Cilinder
Maintenance
Press Enter to ESC
EMPTY CILINDER
19c
DX, DX-S TC ES CW
Anti-Hunting Time Manual Override
Closed Circuit Setup Closed Circuit Setup Chilled Water Setup Constant of Room Unit star-up
Temp. E.S. °C 08.0 Dehum. Cycle Start Temp. Control min 00 Y0 Ramp %
Set Point. °C 28.0 Summer Temp. °C 28.0 Set Point °C 07.0 Y1 Ramp %
Rad-Cooler On-Off / Modul. Rad-Cooler On-Off / Modul. High Temp. °C 15.0
81 91
61a 61b 63
Manual Override
Dehumidification
DX, DX-S TC ES CW
Reheating 1
Closed Circuit Setup Reheating 2
92
Chilled Water Activ.
Set Point °C 07.0
62 Manual Override
Y0 Ramp %
Y1 Ramp %
93
Hot Water Reheat Si Hot Water Reheat Si
Hot Gas Coil No
"PASSWORD External Dehumid. No External Dehumid. No
External Humidif. No External Humidif. No
64a 64b
64c
Offset Adj.
SENSORE
Read value °C 00.0
Adjustment °C 0.0
66-69
Set-up Of Passwords
For Accessing To:
Settings 00000
Service *****
Heat. Set P. °C 00.0
s 00:00 Programm Versi
Sensitivity °C 0.0
00/00/00
00 mP20
111
120
Cool.. Set P. °C 00.0
Cycle
Room High T. °C 00
on-off Daily
Heat. Set P. °C 00.0
ycles)
Room Low T. °C 00
N/Y
112
SI
Relative Humidity Relative Humidity
Programmed Cycle:
Dehumid. Control: N Dehumid. Control: Y
Dehum. Set P. rH% 00
To change
Deh. Prop. Band. rH% 00
Press Key "ENTER"
113a 113b
102
PROGRAM. 00/00/00
MO TU WE TH FR SA SU
Humidification
N N N N N P F
Humid. Set P. rH% 00
Hum. Prop. Band. rH% 00
103 Programme
MODE
114
Humidifier Setting
Maximum Steam
Production kg/h 00.0
(30-100 % Nom. Cap.) P
115
"SETTINGS" P
Dehum. Set P. rh% 00
High Rel. Hum. rh% 00
Hum. Set Point rh% 00
Low Rel. Hum. rh% 00 I/O via Contact N I/O
116 I/O via Serial N I/O
Id# 001 Speed 1200 Id#
LA
130a 130
Setback Mode N/Y Setback Mode Y
Min. Temp. °C 00.0 Min. Temp °C 00.0
Max. Temp. °C 00.0 Max. Temp °C 00.0
Autom. Switch-Over Au
Base / Std-by Pair N of
117a 117b Cy
N°
131a 13
Setback Mode
Min. Rel Hum. rH% 00
Max. Rel Hum. rH% 00
Autom. Switch-Over
118 Base / Std-by Pair Y M
Cycle Time h 000
1 Unit On Limit N Me
INSTRUCTION MANUAL