The document is a routine test report for a transformer (No: OQFB-N-0001/0001) conducted for Bharat Pet Products Pvt. Ltd. in Ankleshwar, Gujarat. It includes detailed measurements of winding resistance, load loss, no load loss, insulation resistance, and dielectric tests, confirming that the transformer meets the applicable standards. The testing engineer, Mr. Vikas Yadav, witnessed the tests, and the results indicate that the transformer is functioning correctly.
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF or read online on Scribd
0 ratings0% found this document useful (0 votes)
36 views2 pages
MFG Test Report of Transformer
The document is a routine test report for a transformer (No: OQFB-N-0001/0001) conducted for Bharat Pet Products Pvt. Ltd. in Ankleshwar, Gujarat. It includes detailed measurements of winding resistance, load loss, no load loss, insulation resistance, and dielectric tests, confirming that the transformer meets the applicable standards. The testing engineer, Mr. Vikas Yadav, witnessed the tests, and the results indicate that the transformer is functioning correctly.
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF or read online on Scribd
You are on page 1/ 2
UNIMAG Pt
niet
ER TRANSFORMER PVT LTD os,
26/A, Il PHASE, PEENYA INDUSTRIAL AREA, BANGALORE-INDIA,
fo“,
GE
‘Testing Engineer
For M/s. Bharat Pet Products Pvt.Ltd,
Ankleshwar, GUJARAT,
ROUTINE TEST REPORT FOR TRANSFORMER
Jcustomer _[M/s.BHARAT PET PRODUCTS PRIVATE LIMITED, Page No [tof
freansformer No: [OQFB-N-0001/0001 KA 3000 [Tested On 22.03.2025 | Std. Ref |
wag vous AMPERES coouns _[rrequencyivH2| vecrorcrour | 1s 2026
HY 22000 78.73 ‘ONAN 50 DYN
Ww. 433, 4000.12 Glass of insulation: A
1 MEASUREMENT OF WINDING RESISTANCE Ambient Temp: [Top Oil Temp.
1 HV Winding: 26 Deg. C. 26 Deg. C.
Tap no wav vw awau [Avge perph
5 1079 1.083 14056 1.609 [ohms
LL
1.2 LV. Winding
TAP 2U-2N 2V-2N 2W2N [Avge perph _|
02113 02118 02125 02119 [mii Ohms
[2 Measurement ofload loss and impedence: Supply to: HY Short LW
AMBIENT: 26 [bee c top oll temp: 26 |
POWER ANALYSER READING
‘Tap no Winding Voltage in Votts [current inamps Load Losses in KW
U-VPh 1496.45 7797 wi 9.08
5 v-wPh 1501.64 7885 we 692
100% LAD W-U Ph 1479.13 79.76 ws 847
Avg 149241 78.86 Wwiew2ews 2Aa7
[sMeasurement of no Load Lass and no Load Current Supply to Lv Open: HW
POWER ANALYSER READING Frequency: 49.97] ita
% of voltage Winding Voltage in Volts [Curent inamps No Load Losses in KW a
U-V Ph. 433.68 5.95 wi 1.014 4
ine V-WPh 34.89 4.05 we 0.608) g
W-UPh 432.26 639 wa: 0778 i]
Ave, 433.61, 5.73 wiewerws 2400 2
+. Measurement of Insulation resistance in G ohms ;
Megger used_| HV to LV (5000v) _ [uv to EARTH (5000¥] LV to EARTH(2500v] AMBIENT: 26)deg.c | &
4076 3246 266 |topoittemp: 26|dep.c |
5.1 Dielectric Tests for 60 Seconds
Winding [HV to EARTH Result [Lv to EARTH Result
‘Applied in kV 50 lwirnstoop 3 lwirnsroop q
[reste by “Tests Witnessed by
Name Signature
Mr.VIKAS YADAVFransformer No OQF-1-0001/0001 Taye Zot
5.2 Dioleti Tosts foro [evap beeen two 125mm a ash eco sett 2mm ap
Result: lwmasrooo Insulating Ol conforms to 15 335/166 296
5.3. induce Over Voltage Test Frequency 99:94[puravoninsee 60
Supplyto suv [Vottage applied sosly osu wimistooo
tums ratio test [rap RANGE: 5940-15 nsteps of 1.25%
Tap U-rHASE VeRHASE w-rtiase _[zvecor Group Test: [VECTOR GROUP
1 240 20 240 Supply to m7
2 0130 91.30 9130 Short 1u2N
3 90220 90.20 9020 uv wooly
4 39:10 39:10 58:10 av-iw 405
5 5800 58.00 800 1W-1U 403 |v
6 8690 8690 8690 Measured votage| Condition
7 85.80 8590 85.0 iwaw wor |v min
8 84.70 8470 8470 W-2v 403 |v Fqua
° 83.60 3.60 53.60 av-2w 403 |v equa
0 #250 250 3.50 1-20 a1 |v Ma,
it 140 e140 10 Results FOUND OK
2 8030 #030 8030
1B 7920 7920 7320
4 7810 7810 710
15 77.00 7.00 77.00 3
16 75.90 7590 7590 3
7 74.80 74.80 74.80 g
Ci
5
5-TeST RESULTS AT NORMAL TAP POSITION GTPVALE | Aetal Value
yTOTAL LOAD LOSSES AT75 sa0001sToL | 2749.72 [wats
5) NAME PLATE 9 IMPEDANCE AT'75 DEG. 62518TOL 379 _(
) NO LOAD LOSSES ATSOHe & RATED VOLTA 0001s To. | 240216 |wats
a) 9 OF EFFICIENCY @ 100% LOAD @ UPF v901 fe
=} Dio ENTIONS ARE. AS PER GADRG No jseasisno | FOUND oK
ACCEPTANCE CRITI
APPLICABLE STANDARDS
frestedby : —_SURESHA MAK “ests Witnssed by
Name Signature
MnVIKAS YADAV
Testing Engineer
For M/s. Bharat Pet Products PvtLtd.,
Ankleshwar , GUJARAT.