0% found this document useful (0 votes)
26 views2 pages

Instrumentation Datasheet

The document provides detailed specifications for two types of instrumentation cables compliant with BS EN 50288-7, including their construction, materials, and electrical parameters. Key features include copper conductors, XLPE insulation, and various protective layers such as PVC sheathing and steel wire armor. The cables are designed for rated voltages of 0.5 kV and 300/500 V, with specific resistance and capacitance values outlined for performance assessment.

Uploaded by

Ahmed Hussain
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
26 views2 pages

Instrumentation Datasheet

The document provides detailed specifications for two types of instrumentation cables compliant with BS EN 50288-7, including their construction, materials, and electrical parameters. Key features include copper conductors, XLPE insulation, and various protective layers such as PVC sheathing and steel wire armor. The cables are designed for rated voltages of 0.5 kV and 300/500 V, with specific resistance and capacitance values outlined for performance assessment.

Uploaded by

Ahmed Hussain
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

DATA SHEET

INSTRUMENTATION CABLE AS PER BS EN 50288-7

C
SL
ITEM NO 1
#
0.5 KV CU (CL2)XLPE/OS/SWA/PVCBK UNIT 1PX1.5
Product Standard BS EN 50288-7
Performance Standard(Flame / Fire - Test) IEC 60332-1
Rated Voltage SOLID 0.5
1 Circular Stranded Copper Class 2 Conductor
Number of Pair(s) Nos 1
Nominal cross-sectional area mm² 1.5
Approx. Diameter of Conductor mm 1.4
2 Insulation - XLPE
Color(s) BK, WH
Nominal Thickness mm 0.6
Approx. Diameter over Insulation mm 2.7
3 2 Cores Laid up
Approx. Diameter over Laid Up mm 5.5
4 Overall metalic screen
Aluminium/Polyester laminated tape applied over the laid up
with Metalic side down in electric contact with Drain wire
Type of Drain Wire SOLID
Area of Drain wire mm² 0.5
Overlap % % 25
5 Extruded PVC Bedding
Nominal Thickness mm 0.9
Approx. Diameter over bedding mm 8.2
6 Armour-Type: Round Galvanised Steel Wire
Nominal Diameter of Wire mm 0.9
Approx. Diameter over armour mm 9.9
7 Extruded PVC Outer Sheath (BLACK)
Nominal Thickness mm 1.3
Approx. Diameter over outer sheath mm 12.3
Approx. Weight of complete cable kg/km 310
8 Electrical Parameters
Min.Insulation Resistance at 20°C Mohm/km 1000
Max. DC Resistance of Conductor at 20°C ohm/km 12.342
Voltage Test(For 1 min) KV 2
Approx AC Resistance of conductor at 90 degree ohm/km 15.737
approx mutual capacitance nF/km 150
Maximum L / R Ratio μH/Ω 40
9 Installation parameters
Minimum Bending Radius mm 74
Page1

ELECTRICWAY | Data Sheet - TEL +971-04-48170777 | FAX +971-04-8825700 |


www.electricway.com
DATA SHEET INSTRUMENTATION CABLE AS PER BS EN 50288-7

SL
ITEM No 2
#
2PX
Cu (Cl2)/XLPE/IS+OS/PVC/SWA/PVC-BLACK TO BSEN 50288 - 7 UNIT
1.5mm²
1 Rated voltage (Uo/U) V 300/500
2 Conductor
Number of Pair(s) Nos 2
Stranded Copper Conductor : Class 2 -
Nominal cross sectional area mm2 1.5
Conductor diameter mm 1.44
3 Insulation
.(Core color black and white, with number printing on white core ) - XLPE
Nominal thickness mm 0.6
Diameter Over Insulation mm 2.74
4 Pair
Makeup: 2 cores twisted together with a suitable lay-length to form a
Pair
5 Individual Screen
Each Pair shall have Aluminium / Polyester laminated tape applied with
Metallic side down in electric contact with the Drain wire
Over-lap % 25
Drain wire cross section area ( SOLID ) mm2 0.5
6 Overall Screen
Aluminium / Polyester laminated tape applied Over the Laid up Pair with
Metallic side down in electric contact with the Drain wire
Over-lap % 25
Drain wire cross section area ( SOLID ) mm2 0.5
7 Extruded PVC Bedding
Nominal Thickness mm 1.1
Diameter Over Bedding mm 13.04
8 Single Layer (Steel ) Wire Armour
Nominal Diameter mm 0.9
Diameter Over Armour mm 14.78
9 Extruded PVC Outer Sheath ( BLACK with Anti-termite)
Nominal Thickness mm 1.5
Overall diameter of cable mm 18
10 Weight of complete cable kg / km 549
11 Electrical Characteristics
Voltage Test (For 1 min as per BSEN 50288 - 7 kV 1
Minimum Insulation resistance at 20°C MW/km 1000
Maximum D.C. resistance of conductor at 20°C W/km 12.342
A.C.resistance of conductor at 90°C W/km 15.7
Maximum Mutual Capacitance at 1kHz pF/m < 150
Maximum L / R Ratio mH / W 40
Page2

12 Minimum bending radius of cable (6X OD) 108

ELECTRICWAY | Data Sheet TEL +971-04-48170777 | FAX +971-04-8825700 |