Pss Srd998 1
Pss Srd998 1
Product Specifications
PSS EVE0108
SRD998 Intelligent Positioner with HART Communication
The intelligent positioner SRD998 is designed to operate pneumatic valve actuators and can be operated
from control systems (e.g. the I/A Series System and Evo™), controllers or PC-based configuration and
operation tools such as the FDT/DTMs VALcare™. The positioner is available with HART 7 Communication
Protocol. The extra large multi-lingual full text graphical-LCD, in conjunction with the rotary selector, allows
a comfortable and easy local configuration and operation. For installations in contact with explosive
atmospheres certificates are available.
FEATURES
Auto-start with self-calibration Stroke 8 to 260 mm (0.3 to 10.2 in) with standard
Self diagnostics, status and diagnostic lever; larger stroke with special lever
messages Angle range up to 95° (up to 120° on request)
DTM for valve diagnostics and predictive Mounting onto any linear or rotary actuator
maintenance Supply air pressure up to 10 bar (145 psig)
Easy local operation with the rotary selector Single or double acting
Extra large multi-lingual full text graphical LCD. Protection class IP 66
SRD998 AD model with backlight.
Explosion protection: Intrinsic Safety according
With HART 7 communication to ATEX/IECEx, INMETRO, NEPSI, PESO,
CNS, EAC, KCs, and TIIS
DESIGN
Figure 1. Design
Using the modular concept of the SRD998, the Single-acting pneumatics have versions B0S, B1S
positioner can be optimally adapted to the and B2S that differ in air flow. For the double-acting
application. In addition to connection manifolds with pneumatics, there are the versions C0S, C1S and
various threads, mounting kits for each drive and C3S, which differ in the air performance.
extensive accessories, these also include integrated
For drives with increased air output, a
pneumatic amplifiers in various performance
correspondingly powerful supply air station is
classes.
required.
Pneumatic Amplifiers
Depending on the actuator, a single or double-acting
pneumatic amplifier is used.
Codes Bxx - Single Acting
Codes Cxx - Double Acting
PSS EVE0108
TECHNICAL DATA Page 3
T E C H N I C A L D ATA
USABILITY
P N E U M AT I C P ER F O R M A N C E - A I R F L O W
Pneumatic Code B1S (Single Acting - Standard Flow, High Performance Pneumatic)
to pressurize actuator 7000 Nl/h
to vent actuator 5000 Nl/h
Pneumatic Code B2S (Single Acting - High Flow, High Performance Pneumatic) Cv 0.58
to pressurize actuator 21500 Nl/h
to vent actuator 15000 Nl/h
Pneumatic Code C1S (Double Acting - Standard Flow, High Performance Pneumatic)
to pressurize actuator 7000 Nl/h
to vent actuator 7000 Nl/h
Pneumatic Code C3S (Double Acting - Very High Flow, High Performance Pneumatic) Cv 0.85
to pressurize actuator 33500 Nl/h
to vent actuator 33500 Nl/h
P N EU M AT I C PE R F O R M AN C E - A I R C ON S U M P T I O N [ N L / H] (3 )
Pneumatic Code
B0S (Single Acting - Standard Flow) 250 Nl/h
B1S (Single Acting - Standard Flow, High Performance Pneumatic) 400 Nl/h
B2S (Single Acting - High Flow, High Performance Pneumatic) 400 Nl/h
C0S (Double Acting - Standard Flow) 335 Nl/h
C1S (Double Acting - Standard Flow, High Performance Pneumatic) 400 Nl/h
C3S (Double Acting - Very High Flow, High Performance Pneumatic) 400 Nl/h
B O O S T E R S F OR I N C R E A S E D A I R F L O W
VBS200/VBS201
Volume boosters with Cv1.4 and pneumatic connection 1/2”
Optional with Exhaust Collector or Silencer
Figure 2. VBS201 Directly Flanged to the Positioner, Optional with Silencer
VBS300/VBS310
Volume boosters with Cv 7 and pneumatic connection 1” for remote mounting.
Figure 5. VBS300 in Aluminum, VBS310 in Stainless Steel 316
FRS923
PSS EVE0108
FUNCTIONAL SPECIFICATIONS Page 9
F U N C T I O N A L S P E C I F I C AT I O N S
DIAGNOSTIC
To monitor the high performance of the positioner, see Table 2.
Basic Advanced
Type Diagnostics Diagnostics
Configuration data surveillance Yes Yes
Input current adjustment surveillance Yes Yes
A/D converter surveillance Yes Yes
Position value surveillance Yes Yes
Connection to I/P converter surveillance Yes Yes
Potentiometer surveillance Yes Yes
Angle adjustment surveillance Yes Yes
Surveillance of reaching the set point in a specific time Yes Yes
Temperature limit min or max surveillance Yes Yes
Autostart surveillance Yes Yes
Custom Characterization Yes
Auto diagnostic Yes
Alarm Management Yes
Alarm Output for Switching (with Option board) Yes
Status List according to NE107 Yes
Position History Yes
Response History Yes
Step Response Analyze Yes
PHYSICAL SPECIFICATIONS (COMMON DATA FOR PSS EVE0108
ALL VERSIONS) Page 11
P H Y S I C A L S PE CI F I C AT I O N S ( C O M M O N D ATA F O R A L L V E R S I O N S )
Mounting Materials
Attachment to Stroke Actuators Housing and covers Aluminum Alloy No. 230 (GD-
AlSi12) Polyester Powder
For casting yoke according to IEC 534-6 coated
(NAMUR) with attachment kit EBZG –H or –H1 Sealings between Silicone elastomer and silicone
For pillar yoke according to IEC 534-6 (NAMUR) covers core with Ag/Cu particles
with attachment kit EBZG –K or –K1 LCD Window Polycarbonate,U.V. stabilized
Stroke range with feedback lever: External Screws Stainless Steel V2A 1.4301
Motherboard Coated with protective resin
Standard (EBZG-A) - 8 to 80 mm/0.31 to 3.15 in
Extended (EBZG-B) - 60 to 120 mm/2.36 to All moving parts of 1.4306/1.4571/1.4104
feedback system
4.72 in (e.g. shaft)
Extended (EBZG-A1) - 110 to 260 mm/4.33 to
Attachment kits V4A 1.4401 or (depending upon
10.24 in version). Aluminum Alloy
Larger stroke ranges can be realized with special No. 230 (GD-AlSi12) finished
with DD varnish
levers.
Mounting bracket Aluminum Alloy No. 230
Attachment to Rotary Actuators according to (GD-AlSi12)
VDI/VDE 3845 Pneumatic VMQ, PVMQ (Silicone
diaphragms Elastomer, suitable for use in
With Attachment Kit - EBZG -R the paint industry)
(depending upon version)
Further Attachment kits, see “MODEL CODE
ACCESSORIES” Weight
With pneumatic
B0S - approximately 2.1 kg (4.7 lbs)
B1S/B2S - approximately 2.2 kg (4.9 lbs)
C0S - approximately 2.3 kg (5.1 lbs)
C1S/C3S - approximately 2.2 kg (4.9 lbs)
PSS EVE0108 PHYSICAL SPECIFICATIONS (COMMON DATA FOR
Page 12 ALL VERSIONS)
E L E C T R I C A L C ERT I F I C AT I O N S ( 4 ) ( 5)
These positioners have been designed to meet the electrical safety descriptions listed in the following table.
For detailed information or status of testing laboratory approvals/certifications, contact Global Customer
Support.
Model Code
Certification Option
Intrinsically Safe according to ATEX/IECEx A1
II 2G Ex ia IIC T6...T4 Gb; II 1D Ex ia IIIC (a) or IIIB (b) T100°C Da
Intrinsically Safe according to ATEX/IECEx A2
II 2G Ex ib IIC T6...T4 Gb; II 2D Ex ib IIIC (a) or IIIB (b) T100°C Db
Intrinsically Safe according to ATEX/IECEx A3
II 3G Ex ic IIC T6...T4 Gc; II 3D Ex ic IIIC (a) or IIIB (b) T100°C Dc
INMETRO: Ex ia IIC T4/T6 Gb, Ex ia IIIC T100°C Da, IP66 (a) B1
INMETRO: Ex ib IIC T4/T6 Gb, Ex ib IIIC T100°C Db, IP66 (a) B2
INMETRO: Ex ic IIC T4/T6 Gc, Ex ic IIIC T100°C Dc, IP66 (a) B3
NEPSI: Ex ia IIC T4/T6 Ga, Ex iaD 20 T100 Da, IP66 (a) N1
NEPSI: Ex ib IIC T4/T6 Gb, Ex ibD 21 T100 Db, IP66 (a) N2
NEPSI: Ex ic IIC T4/T6 Gc, Ex icD 22 T100 Dc, IP66 (a) N3
EAC: 1 Ex ia IIC T4/T6 Gb X, Ex ia IIIC T100°C Da (a) G1
EAC: 1 Ex ib IIC T4/T6 Gb X, Ex ib IIIC T100°C Db (a) G2
EAC: 2 Ex ic IIC T4/T6 Gc X, Ex ic IIIC T100°C Dc (a) G3
KCs (Korean Certificate Safety): II 2G Ex ia IIC T4/T6 Gb, II 1D Ex ia IIIC T100°C Da, K1
IP66 (a)
KCs (Korean Certificate Safety): II 2G Ex ib IIC T4/T6 Gb, II 2D Ex ib IIIC T100°C Db, K2
IP66 (a)
KCs (Korean Certificate Safety): II 3G Ex ic IIC T4/T6 Gc, II 3D Ex ic IIIC T100°C Dc, K3
IP66 (a)
CNS certification: The SRD998 has the CNS certificate for usage in Taiwan. (a)
PESO certification: The SRD998 has the PESO certificate for usage in India. (a)
a. For Model BD.
b. For Model AD.
For use in hazardous areas in certified safe circuits with the following maximum values for Model SRD998
BD (Certification number: IBExU15ATEX1109X):
Pi Ui Ii T4 T6
900 mW 30 V 130 mA –40°C to 80°C
660 mW 28.1 V 130 mA –40°C to 80°C –40°C to 44°C
630 mW 25.7 V 130 mA –40°C to 80°C –40°C to 46°C
590 mW 25.3 V 130 mA –40°C to 80°C –40°C to 48°C
510 mW 26 V 130 mA –40°C to 80°C –40°C to 52°C
Li = < 10 μH
Ci = < 2.5 nF
IP degree according to IEC 60529 - IP 66
For use in hazardous areas in certified safe circuits with the following maximum values for Model SRD998
AD (Certification number: IBExU20ATEX1044X):
Supply and sensor circuit in protection type intrinsic safety Ex ia IIC (Terminal + 11/-12)
Ui 30 V / Ii 130 mA
Pi (T4) 0.9 W / Pi (T6) 0.515 W
Ci 25 nF / Li 1 μH
UNI-I/O module circuit in protection type intrinsic safety Ex ia IIC (channel 1: + 13 /-14 and channel 2
(position feedback): + 15 /-16)
Ui 30 V / Ii 130 mA
Pi (T4) 0.9 W (channel 1) or 0.66 W (channel 2)
Pi (T6) 0.550 W (channel 1) or 0.386 W (channel 2)
Ci 28 nF / Li 2 μH
S R D 9 9 8 W I T H H A RT C O M M U N I C AT I O N
F U N C T I O N A L D E S I G N AT I O N S
Figure 8. Functional Designations
Terminals
+11
-12
+13
-14
+15
-16
ADDITIONAL EQUIPMENT
Remote Potentiometer: –Code V, W, Y For more information about remote mounting, see
PSS EVE0118.
The remote potentiometer is used in applications
where high temperatures or vibration are present NOTE
and can result in negative influences to the control. It The functionality and certifications are only
can also be used in places not easy to reach, to help ensured with our RMU998.
ensure easier handling of the unit, or for cylinders
Electrical Classification ATEX/IECEx
with large strokes. The positioner SRD998, is
mounted far away from the valve or cylinder in a safe For electrical ATEX/IECEx classification, see
environment. “ELECTRICAL CERTIFICATIONS” on page 13.
The Potentiometer unit is mounted on the valve or RMU998 is approved for use with SRD998 (a)(b)
cylinder. The Potentiometer unit can be made by under the following certifications:
RMU998 or by an external potentiometer.
a) EU-Type Certificate of Conformity
The external potentiometer unit must support a IBExU15ATEX1109X and IECEx Certificate of
3-wire system with approximately 5 kOhm Conformity IECEx IBE 15.0028X;
resistance.
b) EU-Type Certificate of Conformity
If the following requirements are fulfilled, the set up IBExU20ATEX1044X and IECEx Certificate of
is insensitive to electrical disturbances caused by Conformity IECEx IBE 20.0005X
high electromagnetic fields, EMC, and HF radiation.
For use in hazardous areas, the remote
Cable length maximum: Model BD 3m (9 ft), potentiometer interface is certified as Intrinsically
AD 10m (32 ft) Safe with the following maximum values:
Cable Specifications:
3-wire twisted pair, shielded Uo = 6 V
Shield needs to be connected on both ends to the Io = 130 mA
internal ground Po = 0.9 W
Shield endings need to be kept very short when
connected to Ground The maximum length of the cable between the
An HF cable gland is not required remote potentiometer and positioner is 3m (for
Model BD) and 10m (for Model AD).
M O DE L C O D E S R D 9 9 8
Intelligent Positioner SRD998 Model
Communication
HART H
Diagnostics Performance
Basic Diagnostics BD
Advanced Diagnostics AD
Electrical In-Out Option
No In-Out Option 0
Universal In-Out Option 1
Version
Single Acting B
Double Acting C
Pneumatic Performance
Standard Pneumatic (6 bar max air supply) 0
Standard Flow - High Performance Pneumatic (10 bar max air supply) 1
High Flow - High Performance Pneumatic (Cv 0.58 – 10 bar max air supply) 2
Very High Flow - High Performance Pneumatic (Cv 0.85 – 10 bar max air supply) 3
Fail in case of loss of power
Fail safe S
Housing
Aluminum 1
Mounting
Standard S
Direct mounting T
Remote Mounting of positioner with side mounting potentiometer unit V
Remote Mounting of positioner with top mounting potentiometer unit W
Remote Mounting of positioner w/o potentiometer unit (order potentiometer separately) Y
Pneumatic Connection
1/4 NPT A
1/4 G B
Gauges
Without gauge 0
With 2 standard gauges for single acting (a) 1
With 2 Nickel plated gauges connection for single acting (a) 2
With 3 standard gauges for double acting (b) 3
With 3 Nickel plated gauges connection for double acting (b) 4
Electrical Connection
M20x1.5 7
1/2 NPT (made with an adaptor) 8
PSS EVE0108
Page 22 MODEL CODE SRD998
M O D E L C OD E S RD 9 9 8 ( C ON T I N U E D )
Intelligent Positioner SRD998 Model
Electrical Certification
without certification ZZ
ATEX/IECEx: II 2G Ex ia IIC T6...T4 Gb; II 1D Ex ia IIIC (c) or IIIB (d) T100°C Da A1
ATEX/IECEx: II 2G Ex ib IIC T6...T4 Gb; II 2D Ex ib IIIC (c) or IIIB (d) T100°C Db A2
ATEX/IECEx: II 3G Ex ic IIC T6...T4 Gc; II 3D Ex ic IIIC (c) or IIIB (d) T100°C Dc A3
INMETRO: Ex ia IIC T4/T6 Gb, Ex ia IIIC T100°C Da, IP66 (c) B1
INMETRO: Ex ib IIC T4/T6 Gb, Ex ib IIIC T100°C Db, IP66 (c) B2
INMETRO: Ex ic IIC T4/T6 Gc, Ex ic IIIC T100°C Dc, IP66 (c) B3
NEPSI: Ex ia IIC T4/T6 Ga, Ex iaD 20 T100 Da, IP66 (c) N1
NEPSI: Ex ib IIC T4/T6 Gb, Ex ibD 21 T100 Db, IP66 (c) N2
NEPSI: Ex ic IIC T4/T6 Gc, Ex icD 22 T100 Dc, IP66 (c) N3
EAC: 1 Ex ia IIC T4/T6 Gb X, Ex ia IIIC T100°C Da (c) G1
EAC: 1 Ex ib IIC T4/T6 Gb X, Ex ib IIIC T100°C Db (c) G2
EAC: 2 Ex ic IIC T4/T6 Gc X, Ex ic IIIC T100°C Dc (c) G3
CNS certification IS (c) (d)
PESO certification IS (c) (e)
KCs (Korean Certificate Safety): II 2G Ex ia IIC T4/T6 Gb, II 1D Ex ia IIIC T100°C Da (c) K1
KCs (Korean Certificate Safety): II 2G Ex ib IIC T4/T6 Gb, II 2D Ex ib IIIC T100°C Db (c) K2
KCs (Korean Certificate Safety): II 3G Ex ic IIC T4/T6 Gc, II 3D Ex ic IIIC T100°C Dc (c) K3
Options
Stainless Steel Label, fixed with wire -L
a. Only to be ordered with single acting model code Version B.
b. Only to be ordered with double acting model code Version C.
c. For Model BD.
d. The SRD998 has a CNS certificate for usage in Taiwan. Please order with ATEX/IECEx model code.
e. The SRD998 has a PESO certificate for usage in India. Please order with ATEX/IECEx model code.
PSS EVE0108
ACCESSORIES FOR ALL BASIC DEVICES Page 23
A CC ES SO R I ES F O R A L L B AS I C DE V I C ES
Figure 11. Accessories for all Basic Devices
no threads
O ring
with filter
#$"%&
'()%**&%&+
!
"
no threads
(
Connection manifold for
single acting positioner %/
with pressure gauges for
supply air s and output y
"
no threads ,
,
-
. ..%
PSS EVE0108
Page 24 MODEL CODE ACCESSORIES
M O D E L C OD E A C C E S S O RI E S ( C O N T I N U E D )
Accessories for SRD998 Model
Couple Lever EBZG
Standard (stroke max. 80 mm) A
Extended (stroke max. 260 mm) -A1
Reduced (stroke < 8 mm) -A2
Fold feedback lever (stroke 8 to 70 mm) -A3
Short stroke (stroke 8 to 35 mm) -A4
Couple Lever Folded (stroke special) -A5
Extended (stroke max. 120 mm) -B
Carrier bolt SRXG
Carrier bolt extra short 23 mm -A
Adjustable carrier bolt 20 to 37 mm -B
Carrier bolt 38 mm -C
Carrier bolt 47 mm -D
Carrier bolt 57 mm -E
Carrier bolt 65 mm -F
Adjustable carrier bolt with fixing system for stem diameter up to 21 mm -G
Adjustable carrier bolt with fixing system for stem diameter up to 34 mm -H
Carrier Bolt 80 mm -I
Adjustable carrier bolt for thread 3/8” -J
Adjustable carrier bolt for thread 5/16” -K
Extension for carrier bolt -L
Adjustable carrier bolt with fixing system centered for stem diameter up to 64 mm -M
Adjustable carrier bolt with fixing system centered for stem diameter up to 21 mm -G1
Adjustable carrier bolt with fixing system centered with extension up to 80 mm for stem diameter up to
21 mm -G2
PSS EVE0108
Page 26 MOUNTING TO LINEAR ACTUATORS
M OU N T I N G T O L I N E A R A C T U AT OR S
Figure 12. Attachment to Stroke Actuators according to IEC 534-6 (NAMUR), Left Hand
Figure 14. Attachment to Stroke Actuators according to IEC 534-6 (NAMUR), Right Hand, Mounting Bracket EBZG-K
EBZG-K
Figure 15. Compact Stainless Steel Attachment Kit with Mounting Bracket EBZG-H6
EBZG-H6
PSS EVE0108
Page 28 MOUNTING TO ROTARY ACTUATORS
M O U N T I N G T O R OTARY A C T U AT O R S
Figure 16. Delivery of Bracket by Manufacturer of Actuator
PSS EVE0108
DIMENSIONS Page 29
DIMENSIONS
Figure 17. Attachment to Rotary Actuator
Linking piece
PSS EVE0108
Page 30 DIMENSIONS
T Y P I C AL M O U N T I N G
Figure 21. SRD998 with Remote Mounting Unit RMU998-V
Figure 22. SRD998 with Booster VBS201, Directly Flanged to SRD998 with Connection to an Exhaust Collecting System
PSS EVE0108
Page 34 NOTES
NO T ES
PSS EVE0108
NOTES Page 35
PSS EVE0108
Page 36
A D D I T I O N A L P RO D U C T S
These product lines offer a broad range of measurement and
instrument products, including solutions for pressure, flow,
analytical, temperature, positioning, and controlling.
For a list of these offerings, visit our web site at:
www.se.com
Schneider Electric Systems USA, Inc. Global Customer Support Copyright 2010-2020 Schneider Electric
70 Mechanic Street Inside U.S.: 1-866-746-6477 Systems USA, Inc. All rights reserved.
Foxboro, MA 02035 Outside U.S.:1-508-549-2424
United States of America https://pasupport.schneider-electric.com The Schneider Electric brand and any
http://www.se.com trademarks of Schneider Electric SE or its
subsidiaries are the property of Schneider
Electric SE or its subsidiaries. All other
trademarks are the property of their respective
owners.
1120