PCN0411B

Daikin offers various control devices for air conditioning systems, including interfaces compatible with BACnet and LONWORKS protocols for seamless integration with building management systems. The document outlines the RoHS Directive compliance, features of Daikin's A/C management system, and specifications for their interface units. Additionally, it highlights the importance of ISO 9001 and ISO 14001 certifications for quality and environmental management.

Uploaded by

adrian.cjwish
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
18 views8 pages

PCN0411B

Daikin offers various control devices for air conditioning systems, including interfaces compatible with BACnet and LONWORKS protocols for seamless integration with building management systems. The document outlines the RoHS Directive compliance, features of Daikin's A/C management system, and specifications for their interface units. Additionally, it highlights the importance of ISO 9001 and ISO 14001 certifications for quality and environmental management.

Uploaded by

adrian.cjwish
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 8

PCN0411B

Daikin also has various other control devices to suit the specific sizes and conditions of A/C systems.

E v o l u t i o n

The A/C management system that offers powerful


functions, yet still gives simple navigation for any user. DAM602B51 B52

Communication capabilities via a Web browser further


expand air conditioning control possibilities. DCS601C51

* RoHS Directive
The RoHS (Restriction of Hazardous Substances (in electrical and electronic equipment)) Directive is an environmental directive enacted
to regulate the use of designated chemical substances (lead, cadmium, hexavalent chromium, mercury, polybrominated biphenyls and
polybrominated diphenylether) in electrical equipment. All household products subject to this Directive and sold in Europe from July 1,
2006 are legally bound to comply with the RoHS Directive.

Using interface

1. Onc e a month, adjus t the c loc k of the interfac e.


2. Daikin’ s unique P.P.D. s ys tem es timates the power c ons umption of eac h individual indoor unit bas ed on data c ommunic ated from indoor units and
c ompared to the power c ons umption of an air c onditioning ins tallation with a s tandard s etup. Note that P.P.D. is not a “ gauge” adapted to the
methods
of meas uring power c ons umption in eac h c ountry. All c ountries differ in the ways tenant billing s ys tems are implemented depending on their
res pec tive legal s ys tems . Data obtained by P.P.D. is for referenc e only and s hould not be us ed for offic ial financ ial trans ac tions .
3. J MT (J oint Matc hing Tes t) is normally required before projec t exec ution.

DAIKIN is the first manufacturer (Vendor ID53: Nov 15, 1999) whose VRV System has been officially approved as BACnet® compatible equipment.
Catalog information is as of July 2007.
BACnet ® is a registered trademark of the American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE).
LONWORKS®, LON® and LonTalk® are registered tradmarks of Echelon Corporation.
Ethernet is a registered trademark of Xerox Corporation.

About ISO 9001 About ISO 14001


ISO 9001 is a plant certification system ISO 14001 is the standard defined by the
defined by the International Organization for International Organization for Standardization
Standardization (ISO) relating to quality (ISO) relating to environmental management
assurance. ISO 9001 certification covers systems. Our group has been acknowledged
quality assurance aspects related to the by an internationally accredited compliance
“ design, development, manufacture, organisation as having an appropriate
installation, and supplementary service” of programme of environmental protection
products manufactured at the plant. procedures and activities to meet the
JMI-0107 JQA-1452 requirements of ISO 14001.
The interface for connecting VRV to BACnet or L ONWORKS protocols
® ®

Dealer
Head Office:
Umeda Center Bldg., 2-4-12, Nakazaki-Nishi,
Kita-ku, Osaka, 530-8323 Japan
Tokyo Office:
JR Shinagawa East Bldg., 2-18-1, Konan,
Minato-ku, Tokyo, 108-0075 Japan
http://www.daikin.com/global_ac/
c All rights reserved
Printed in Japan 07/07/003 AD.HP.SW

Specifications, designs and other content appearing in this brochure are current as of July 2007 but subject to change without notice.
Connect VRV to your BMS via BACnet or LONWORKS - ® ®

Typical BACnet® application


using Daikin's integrated control system solutions.
® ®
B MS
C ompatible with B AC net and L ON W OR K S , the two leading open network c omunic ation protoc ols ,
the interfac es offered by Daikin provide a s eamles s c onnec tion between VR V and your B MS .

Outdoor
Dedicated interfaces make Daikin air conditioners Unit

freely compatible with open networks

B AC net®/E thernet
B MS DMS502B51
Local C ontroller
( Interfac e for us e in B AC net®)

PC

Indoor
Unit
HR V
P ower S upply
Fire Alarm S ecurity
Facility

E levator P ump Lighting, etc R emote C ontroller Daikin's A/C infras truc ture

Open network Building


Control
Network

BACnet ® LONWORKS ®
® ®

Daikin air conditioning and control systems


help you set up an open network.

Typical LONWORKS® application


Fire Alarm P ower S upply
Facility
B MS

E levator
P ump
D-B AC S S ecurity Lighting, etc
Interfac e Unit R
LonTalk

Outdoor
Unit

E thernet (TC /IP )


DMS504B51 Local C ontroller
( Interface for us e in L ON W OR K S ®)

R
Air conditioning control systems can be realized
realised with Providing flexible control and monitoring capability LonTalk Indoor
Unit
little equipment and lower costs. that features linked operation with other systems. HR V

LonP oint S ecurity LonP oint


Units can be added freely and easily to expand S ystem
Simple, direct connections make setup quick and easy. Fire Alarm S ystem R emote C ontroller
Daikin's A/C infras truc ture
the number of control points.

Other systems such as those for fire and crime prevention Building
Dedicated interfaces enhance VRV control. Control
can be easily interlocked with Daikin's unit.
Network

1 2
Connect VRV to your BMS via BACnet or LONWORKS - ® ®

Typical BACnet® application


using Daikin's integrated control system solutions.
® ®
B MS
C ompatible with B AC net and L ON W OR K S , the two leading open network c omunic ation protoc ols ,
the interfac es offered by Daikin provide a s eamles s c onnec tion between VR V and your B MS .

Outdoor
Dedicated interfaces make Daikin air conditioners Unit

freely compatible with open networks

B AC net®/E thernet
B MS DMS502B51
Local C ontroller
( Interfac e for us e in B AC net®)

PC

Indoor
Unit
HR V
P ower S upply
Fire Alarm S ecurity
Facility

E levator P ump Lighting, etc R emote C ontroller Daikin's A/C infras truc ture

Open network Building


Control
Network

BACnet ® LONWORKS ®
® ®

Daikin air conditioning and control systems


help you set up an open network.

Typical LONWORKS® application


Fire Alarm P ower S upply
Facility
B MS

E levator
P ump
D-B AC S S ecurity Lighting, etc
Interfac e Unit R
LonTalk

Outdoor
Unit

E thernet (TC /IP )


DMS504B51 Local C ontroller
( Interface for us e in L ON W OR K S ®)

R
Air conditioning control systems can be realized
realised with Providing flexible control and monitoring capability LonTalk Indoor
Unit
little equipment and lower costs. that features linked operation with other systems. HR V

LonP oint S ecurity LonP oint


Units can be added freely and easily to expand S ystem
Simple, direct connections make setup quick and easy. Fire Alarm S ystem R emote C ontroller
Daikin's A/C infras truc ture
the number of control points.

Other systems such as those for fire and crime prevention Building
Dedicated interfaces enhance VRV control. Control
can be easily interlocked with Daikin's unit.
Network

1 2
Product description

Seamless connection DMS502B51 Specification


Daikin's interface unit for B AC net® communicates with B AC net® clients via B AC net® over an ethernet.

between and BACnet


® This unit provides information for VR V through B AC net® s ervices .
C onformance C las s - 3 Data Link Layer Option - B AC net/IP

open network protocol. Specifications of Communication


Objects
Analog Input Analog Value B inary Input B inary Output
Functionality
M onitor C ommand Alarm
B inary Value M ultis tate Input M ultis tate Output
Functions of
operating system version 3.0 Monitoring and control of A/C
(Providing interface from BACnet to VRV.) ® The items to monitor and control air conditioners from B AC net® communication and des criptions of each item are lis ted below.
Function Des cription
BTL Certification NE W
ON/OFF Status Monitors ON/OFF s tatus of the res pective air conditioners .
High reliability product with B TL certification, the s ymbol of high quality. Alarm Sign Monitors whether air conditioners are operating normally and, if not, s ends out an alarm s ign.
*B TL(B AC net Tes ting Laboratory) was es tablis hed by B AC net International to s upport
Error Code Dis plays error code s pecified by the res pective manufacturer if an abnormality occurs in the s ys tem.
compliance tes ting and interoperability tes ting activities .
Operation Mode Monitors s tatus of cooling, heating and ventilation operation.
PPD data

Monitoring
Room Temperature Monitors room temperature and dis plays the actual room temperature.
VR V PPD (power proportional dis tribution) data can be trans mitted by Filter Limit C hecks the limit of filters in us e and monitors if there is a neces s ity to replace the filters .
B AC net communication for the B MS s ys tem.
Thermostat Status Monitors whether the thermos tat in the air conditioner is operating properly.
*Optional Di board (DAM412B 51) is required for the PPD s ys tem.
Compressor Status Monitors whether compres s ors in outdoor units that are connected to the indoor units are operating
ISO 16484-5 Indoor Fan Status properly.
S upports B AC net/IP in accordance with IS O16484-5 (B uilding automa- Heater Operation Status Monitors whether fans in the air conditioners are operating properly.
tion and control s ys tems . Data communication protocol) for B AC net.
PPD data Monitors whether heaters in the air conditioners are operating properly.
Note: Does not s upport IEEE802.3 protocol for B AC net.
ON/OFF Operation Total electric power (number of indoor units ) as an object of accumulator.

RoHS compliant Operation Mode Setting S tarts and s tops the res pective air conditioners and monitors control res ults .

Operation, S etting and Monitoring


W e have been making efforts to fac ilitate the trans ition to R oHS Room Temperature Setting S ets the operation mode (cooling, heating, ventilation or auto mode) and monitors the s etting res ults .
Direc tive c omplianc e. Filter Limit and Reset S ets room temperatures of the res pective air conditioners and monitors the s etting res ults .
*R efer to the back cover for details of the R oHS Directive. C hecks whether there is a us e limit for the res pective filters and then res ets the s ign as neces s ary.
Remote Control Operation Rejection
COV(Change of value) S ets the permis s ion/rejection function of remote controllers in order not to allow operation control, s uch
ON/OFF, operation mode and room temperature, from the remote controllers .
With the new O.S . a change of object can be automatically read by Sub Group Address Control as
Operation Rejection
the B MS without having to cons tantly s can regularly for any change. S ets the control permis s ion/rejection function of centralis ed devices (i.e., air conditioners in a s ub group
Airflow Rate Setting Operation addres s )
Property array index (Reading of objects) Air Direction Setting Operation connected on the D -NET.
This is used for objects such as the S chedule Object that use the Property System Forced OFF Setting Rejection S ets the airflow rate and monitors the s etting res ults .
Array included in the device object. The reason why this is sometimes re-
Forced Thermostat OFF Setting S ets the air direction and monitors the s etting res ults .
quired is so that registration of objects can be done automatically and man-
ual input is not necessary. Energy Efficiency Setting
The "Object_List" of the device can be read automatically with this index,
there by reducing engineering time of programming the indoor units into the Series and components
Segmented requests Hardware model name DMS502B51 DMS502B51+DAM411B51 (Optional D expansion kit)
This function trans mits two or more packets s eparately, when the
Max. number indoor units 128 256 per gateway
amount of data exceeds one packet s ize.
Max. number outdoor units 20 40 per gateway
If there are a large number of indoor units the res pons e is in the
"read property reques t" and the return data are s egmented. B MS Local P rocurement

Specifications
Typical BACnet® application Optional D expans ion kit
Item Des c ription Item Model name DAM411B51
Model name DMS 502B 51(Interfac e for us e in B AC net® )
B MS
B AC net®/IP DIII B oard D L ines 2
Trans mis s ion C onformanc e C las s 3 (AS HR AE 135- 1995)
Outdoor
Unit B - AS C (AS HR AE 135- 2001)
B A C ne t /E the rne t

Local C ontroller
R ated power s upply S ingle phas e AC 100 to 240 ±10% at 50/60 Hz Digital input port
DMS502B51
R ated power c ons umption Maximum 20 W
Di (Forced off) Imbedded in DMS 502B 51 4
Maximum of 10 outdoor units ±10% of the rated value
P ower s upply fluc tuation
®

Fire alarm S ecurity


Indoor – 10°C to 50°C Optional board
HR V Operable temperature range Di
P ower S upply Facility Unit 12
E levator P ump (kwh meter connection for P P D)(DAM412B 51) is required.
S torage temperature range – 15°C to 60°C
Lighting, etc Maximum of 64 groups
Operable ambient humidity 0 to 98% (No c ondens ation)
Building
R emote C ontroller
Control Ins ulation res is tanc e 50 MΩ or more by DC 500 megohmmeter Note: To achieve a s eamles s connection between both the B MS and
Network Daikin's B AC net interfaces , it is crucial that you contact us
Daikin's A/C infras truc ture Ins tallation E nc los ed in elec tric al panel
prior to any project cons ideration.
Dimens ions (W x H x D) 275 x 263 x 81.5 (mm) For a detailed lis t of B MS and compatibility s pecifications
BACnet ® is a registered trademark of the American Society of Heating, Refrigerating and
Air-Conditioning Engineers (ASHRAE). DMS502B51 W eight 3.0 kg pleas e contact your local dis tributor.

3 4
Product description

Seamless connection DMS502B51 Specification


Daikin's interface unit for B AC net® communicates with B AC net® clients via B AC net® over an ethernet.

between and BACnet


® This unit provides information for VR V through B AC net® s ervices .
C onformance C las s - 3 Data Link Layer Option - B AC net/IP

open network protocol. Specifications of Communication


Objects
Analog Input Analog Value B inary Input B inary Output
Functionality
M onitor C ommand Alarm
B inary Value M ultis tate Input M ultis tate Output
Functions of
operating system version 3.0 Monitoring and control of A/C
(Providing interface from BACnet to VRV.) ® The items to monitor and control air conditioners from B AC net® communication and des criptions of each item are lis ted below.
Function Des cription
BTL Certification NE W
ON/OFF Status Monitors ON/OFF s tatus of the res pective air conditioners .
High reliability product with B TL certification, the s ymbol of high quality. Alarm Sign Monitors whether air conditioners are operating normally and, if not, s ends out an alarm s ign.
*B TL(B AC net Tes ting Laboratory) was es tablis hed by B AC net International to s upport
Error Code Dis plays error code s pecified by the res pective manufacturer if an abnormality occurs in the s ys tem.
compliance tes ting and interoperability tes ting activities .
Operation Mode Monitors s tatus of cooling, heating and ventilation operation.
PPD data

Monitoring
Room Temperature Monitors room temperature and dis plays the actual room temperature.
VR V PPD (power proportional dis tribution) data can be trans mitted by Filter Limit C hecks the limit of filters in us e and monitors if there is a neces s ity to replace the filters .
B AC net communication for the B MS s ys tem.
Thermostat Status Monitors whether the thermos tat in the air conditioner is operating properly.
*Optional Di board (DAM412B 51) is required for the PPD s ys tem.
Compressor Status Monitors whether compres s ors in outdoor units that are connected to the indoor units are operating
ISO 16484-5 Indoor Fan Status properly.
S upports B AC net/IP in accordance with IS O16484-5 (B uilding automa- Heater Operation Status Monitors whether fans in the air conditioners are operating properly.
tion and control s ys tems . Data communication protocol) for B AC net.
PPD data Monitors whether heaters in the air conditioners are operating properly.
Note: Does not s upport IEEE802.3 protocol for B AC net.
ON/OFF Operation Total electric power (number of indoor units ) as an object of accumulator.

RoHS compliant Operation Mode Setting S tarts and s tops the res pective air conditioners and monitors control res ults .

Operation, S etting and Monitoring


W e have been making efforts to fac ilitate the trans ition to R oHS Room Temperature Setting S ets the operation mode (cooling, heating, ventilation or auto mode) and monitors the s etting res ults .
Direc tive c omplianc e. Filter Limit and Reset S ets room temperatures of the res pective air conditioners and monitors the s etting res ults .
*R efer to the back cover for details of the R oHS Directive. C hecks whether there is a us e limit for the res pective filters and then res ets the s ign as neces s ary.
Remote Control Operation Rejection
COV(Change of value) S ets the permis s ion/rejection function of remote controllers in order not to allow operation control, s uch
ON/OFF, operation mode and room temperature, from the remote controllers .
With the new O.S . a change of object can be automatically read by Sub Group Address Control as
Operation Rejection
the B MS without having to cons tantly s can regularly for any change. S ets the control permis s ion/rejection function of centralis ed devices (i.e., air conditioners in a s ub group
Airflow Rate Setting Operation addres s )
Property array index (Reading of objects) Air Direction Setting Operation connected on the D -NET.
This is used for objects such as the S chedule Object that use the Property System Forced OFF Setting Rejection S ets the airflow rate and monitors the s etting res ults .
Array included in the device object. The reason why this is sometimes re-
Forced Thermostat OFF Setting S ets the air direction and monitors the s etting res ults .
quired is so that registration of objects can be done automatically and man-
ual input is not necessary. Energy Efficiency Setting
The "Object_List" of the device can be read automatically with this index,
there by reducing engineering time of programming the indoor units into the Series and components
Segmented requests Hardware model name DMS502B51 DMS502B51+DAM411B51 (Optional D expansion kit)
This function trans mits two or more packets s eparately, when the
Max. number indoor units 128 256 per gateway
amount of data exceeds one packet s ize.
Max. number outdoor units 20 40 per gateway
If there are a large number of indoor units the res pons e is in the
"read property reques t" and the return data are s egmented. B MS Local P rocurement

Specifications
Typical BACnet® application Optional D expans ion kit
Item Des c ription Item Model name DAM411B51
Model name DMS 502B 51(Interfac e for us e in B AC net® )
B MS
B AC net®/IP DIII B oard D L ines 2
Trans mis s ion C onformanc e C las s 3 (AS HR AE 135- 1995)
Outdoor
Unit B - AS C (AS HR AE 135- 2001)
B A C ne t /E the rne t

Local C ontroller
R ated power s upply S ingle phas e AC 100 to 240 ±10% at 50/60 Hz Digital input port
DMS502B51
R ated power c ons umption Maximum 20 W
Di (Forced off) Imbedded in DMS 502B 51 4
Maximum of 10 outdoor units ±10% of the rated value
P ower s upply fluc tuation
®

Fire alarm S ecurity


Indoor – 10°C to 50°C Optional board
HR V Operable temperature range Di
P ower S upply Facility Unit 12
E levator P ump (kwh meter connection for P P D)(DAM412B 51) is required.
S torage temperature range – 15°C to 60°C
Lighting, etc Maximum of 64 groups
Operable ambient humidity 0 to 98% (No c ondens ation)
Building
R emote C ontroller
Control Ins ulation res is tanc e 50 MΩ or more by DC 500 megohmmeter Note: To achieve a s eamles s connection between both the B MS and
Network Daikin's B AC net interfaces , it is crucial that you contact us
Daikin's A/C infras truc ture Ins tallation E nc los ed in elec tric al panel
prior to any project cons ideration.
Dimens ions (W x H x D) 275 x 263 x 81.5 (mm) For a detailed lis t of B MS and compatibility s pecifications
BACnet ® is a registered trademark of the American Society of Heating, Refrigerating and
Air-Conditioning Engineers (ASHRAE). DMS502B51 W eight 3.0 kg pleas e contact your local dis tributor.

3 4
Product description

Facilitating the network DMS504B51 Specification


P rotocol: LonTalk ®

integration of
Trans mis s ion s peed: 78 kbps
Topology: Free topology
Trans mis s ion medium: Twis t pair

and LONWORKS
® Network parameters AC _nn (objec t id = 1- 64)
In parameter names, 'nn' refers to air-conditioning unit numbers 01
to 64. For 'NV' with 'nn' attached, a total of 64 NV has been pre- nvoOnOff_nn
nviOnOff_nn
SNVT_switch
SNVT_switch

Open network integration


pared (one for each object).
nvoHeatCool_nn
nviHeatCool_nn SNVT_hvac_mode

®
Network parameter chart SNVT_hvac_mode
nvoSetpoint_nn
A gateway for connection to L ON W OR KS network equipment D - NE T C ommon Objec ts SNVT_temp_p
nviSetpoint_nn
and building control s ys tem. SNVT_temp_p nvoSpaceTemp_nn
® SNVT_temp_p
L ON W OR KS networks are recognis ed worldwide as the de fac- G E NE R AL (objec t id = 65)
nviFanSpeed_nn nvoFanSpeed_nn
to s tandard in the building control indus try. SNVT_switch SNVT_switch
nviSystemOff nvoSystemOff
S ys tems are available for acces s control, energy manage- SNVT_switch SNVT_switch nvoFiltersign_nn
nviFSReset_nn
SNVT_switch
ment, fire/life, HVAC , lighting, and more. nviRejLC nvoRejLC SNVT_switch
SNVT_switch SNVT_switch nvoFailure_nn
nviRejOnOff_nn SNVT_switch

Reduction in engineering and


Configuration Properties SNVT_switch
nc49 Send Heartbeat nvoErrStatus_nn
nc52 Minimum Send Time SNVT_count
nviRejMode_nn
cost of wiring nc64 Send on Delta Temperature
nc111 Delay Start Up
nc20 Range Maximum
SNVT_switch nvoThermo_nn
SNVT_switch
nviRejSetpoint_nn
nvoRejOnOff_nn
The open protocol s pecification gives local s ys tem integrators SNVT_switch
SNVT_switch
complete des ign freedom. nvoRejMode_nn
Air C onditioner Objec ts nviThermoOff_nn
Plus , the ability to combine individual items of equipment into SNVT_switch SNVT_switch
®
This product features objects for a group of 64 indoor units. As shown below, the
a L ON W OR KS network reduces the engineering time and cos ts nvoRejSetpoint_nn
object name and the last "nn" in the "nv Name" correspond with the DIII-NET location SNVT_switch
required for wiring. Indoor Unit Location S etting Address A/C Object nv Name (E xample) nvoHvacExist_nn
1-00 - 1-15 AC_01 - AC_16 nviOnOff_01 - nviOnOff_16 SNVT_switch
2-00 - 2-15 AC_17 - AC_32 nviOnOff_17 - nviOnOff_32

Connectable to up to 64 groups
nvoThermoOff_nn
3-00 - 3-15 AC_33 - AC_48 nviOnOff_33 - nviOnOff_48 SNVT_switch
4-00 - 4-15 AC_49 - AC_64 NviOnOff_49 - nviOnOff_64

This unit can be connected to up to 64 groups .


(This figure depends on the number of control and monitoring Control and monitor fauction
functions us ed.)
Pleas e cons ult your Daikin repres entative for details . C ontrol items Monitor items
ON/OFF Command ON/OFF Status Report Remote Control Operation Mode Setting Rejection Report

RoHS-compliant hardware
Operation Mode Setting Operation Mode Status Report Remote Control Temperature Setting Operation Rejection Report
Temperature Setting Temperature Setting Report System Forced OFF Setting Report

We have been making efforts to facilitate the trans ition to Airflow Rate Setting Room Temperature Report Sub Group Address Control Operation Rejection Setting Report

R oHS Directive compliance. Filter Sign Reset Airflow Rate Setting Report A/C Communication Status Report

*R efer to the back cover for details of the R oHS Directive. Forced Thermostat OFF Setting Filter Sign Report Each item controlled or monitored by the control and monitoring
function is s ubject to a variety of res trictions that are not des cribed
Remote ON/OFF Control Rejection Error Status Report here due to s pace limitations . For details , contact your DAIKIN
dis tributor.
Remote Operation Mode Control Rejection Error Code Report
Remote Temperature Setting Control Rejection Thermostat Status Report
System Forced OFF Setting Forced Thermostat OFF Setting Status Report
Sub Group Address Control Rejection Setting Remote ON/OFF Operation Rejection Report

Specifications
Typical LONWORKS® application
Item Des c ription
B MS Model name DMS 504B 51 (Interfac e for us e in L ON W OR K S ® )

LonTalk
® L ON W OR K S ®
Trans mis s ion
F T - X1 (F ree topology 78 kbps )
Outdoor
E the rne t (T C P /IP )

Unit
R ated power s upply S ingle phas e AC 100 to 240 V 50/60 Hz
DMS504B51 Local C ontroller
R ated power c ons umption Maximum 5 W
C ontac t input U s e no voltage c ontac t ( F orc ed off ) minimum applic ation load DC 16 V and 10 mA
®
Maximum of 10 outdoor units
LonTalk Operable temperature range - 10 to +50°C
Indoor
Unit HR V S torage temperature range - 20 to +60°C
LonPoint S ecurity LonPoint Fire Alarm
S ystem S ystem Maximum of 64 groups Operable ambient humidity 0 to 95% ( No c ondens ation )
Building 50 MΩ or more by DC 500 megohmmeter
R emote C ontroller Ins ulation res is tanc e
Control
Network Ins tallation E nc los ed in elec tric al panel
Daikin's A/C infras truc ture
DMS504B51 Dimens ions (W x H x D) 168 x 260 x 50 (mm)
® ® ® W eight 1.5 kg
LONWORKS , LON and LonTalk are registered tradmarks of Echelon Corporation.

5 6
Product description

Facilitating the network DMS504B51 Specification


P rotocol: LonTalk ®

integration of
Trans mis s ion s peed: 78 kbps
Topology: Free topology
Trans mis s ion medium: Twis t pair

and LONWORKS
® Network parameters AC _nn (objec t id = 1- 64)
In parameter names, 'nn' refers to air-conditioning unit numbers 01
to 64. For 'NV' with 'nn' attached, a total of 64 NV has been pre- nvoOnOff_nn
nviOnOff_nn
SNVT_switch
SNVT_switch

Open network integration


pared (one for each object).
nvoHeatCool_nn
nviHeatCool_nn SNVT_hvac_mode

®
Network parameter chart SNVT_hvac_mode
nvoSetpoint_nn
A gateway for connection to L ON W OR KS network equipment D - NE T C ommon Objec ts SNVT_temp_p
nviSetpoint_nn
and building control s ys tem. SNVT_temp_p nvoSpaceTemp_nn
® SNVT_temp_p
L ON W OR KS networks are recognis ed worldwide as the de fac- G E NE R AL (objec t id = 65)
nviFanSpeed_nn nvoFanSpeed_nn
to s tandard in the building control indus try. SNVT_switch SNVT_switch
nviSystemOff nvoSystemOff
S ys tems are available for acces s control, energy manage- SNVT_switch SNVT_switch nvoFiltersign_nn
nviFSReset_nn
SNVT_switch
ment, fire/life, HVAC , lighting, and more. nviRejLC nvoRejLC SNVT_switch
SNVT_switch SNVT_switch nvoFailure_nn
nviRejOnOff_nn SNVT_switch

Reduction in engineering and


Configuration Properties SNVT_switch
nc49 Send Heartbeat nvoErrStatus_nn
nc52 Minimum Send Time SNVT_count
nviRejMode_nn
cost of wiring nc64 Send on Delta Temperature
nc111 Delay Start Up
nc20 Range Maximum
SNVT_switch nvoThermo_nn
SNVT_switch
nviRejSetpoint_nn
nvoRejOnOff_nn
The open protocol s pecification gives local s ys tem integrators SNVT_switch
SNVT_switch
complete des ign freedom. nvoRejMode_nn
Air C onditioner Objec ts nviThermoOff_nn
Plus , the ability to combine individual items of equipment into SNVT_switch SNVT_switch
®
This product features objects for a group of 64 indoor units. As shown below, the
a L ON W OR KS network reduces the engineering time and cos ts nvoRejSetpoint_nn
object name and the last "nn" in the "nv Name" correspond with the DIII-NET location SNVT_switch
required for wiring. Indoor Unit Location S etting Address A/C Object nv Name (E xample) nvoHvacExist_nn
1-00 - 1-15 AC_01 - AC_16 nviOnOff_01 - nviOnOff_16 SNVT_switch
2-00 - 2-15 AC_17 - AC_32 nviOnOff_17 - nviOnOff_32

Connectable to up to 64 groups
nvoThermoOff_nn
3-00 - 3-15 AC_33 - AC_48 nviOnOff_33 - nviOnOff_48 SNVT_switch
4-00 - 4-15 AC_49 - AC_64 NviOnOff_49 - nviOnOff_64

This unit can be connected to up to 64 groups .


(This figure depends on the number of control and monitoring Control and monitor fauction
functions us ed.)
Pleas e cons ult your Daikin repres entative for details . C ontrol items Monitor items
ON/OFF Command ON/OFF Status Report Remote Control Operation Mode Setting Rejection Report

RoHS-compliant hardware
Operation Mode Setting Operation Mode Status Report Remote Control Temperature Setting Operation Rejection Report
Temperature Setting Temperature Setting Report System Forced OFF Setting Report

We have been making efforts to facilitate the trans ition to Airflow Rate Setting Room Temperature Report Sub Group Address Control Operation Rejection Setting Report

R oHS Directive compliance. Filter Sign Reset Airflow Rate Setting Report A/C Communication Status Report

*R efer to the back cover for details of the R oHS Directive. Forced Thermostat OFF Setting Filter Sign Report Each item controlled or monitored by the control and monitoring
function is s ubject to a variety of res trictions that are not des cribed
Remote ON/OFF Control Rejection Error Status Report here due to s pace limitations . For details , contact your DAIKIN
dis tributor.
Remote Operation Mode Control Rejection Error Code Report
Remote Temperature Setting Control Rejection Thermostat Status Report
System Forced OFF Setting Forced Thermostat OFF Setting Status Report
Sub Group Address Control Rejection Setting Remote ON/OFF Operation Rejection Report

Specifications
Typical LONWORKS® application
Item Des c ription
B MS Model name DMS 504B 51 (Interfac e for us e in L ON W OR K S ® )

LonTalk
® L ON W OR K S ®
Trans mis s ion
F T - X1 (F ree topology 78 kbps )
Outdoor
E the rne t (T C P /IP )

Unit
R ated power s upply S ingle phas e AC 100 to 240 V 50/60 Hz
DMS504B51 Local C ontroller
R ated power c ons umption Maximum 5 W
C ontac t input U s e no voltage c ontac t ( F orc ed off ) minimum applic ation load DC 16 V and 10 mA
®
Maximum of 10 outdoor units
LonTalk Operable temperature range - 10 to +50°C
Indoor
Unit HR V S torage temperature range - 20 to +60°C
LonPoint S ecurity LonPoint Fire Alarm
S ystem S ystem Maximum of 64 groups Operable ambient humidity 0 to 95% ( No c ondens ation )
Building 50 MΩ or more by DC 500 megohmmeter
R emote C ontroller Ins ulation res is tanc e
Control
Network Ins tallation E nc los ed in elec tric al panel
Daikin's A/C infras truc ture
DMS504B51 Dimens ions (W x H x D) 168 x 260 x 50 (mm)
® ® ® W eight 1.5 kg
LONWORKS , LON and LonTalk are registered tradmarks of Echelon Corporation.

5 6
PCN0411B
Daikin also has various other control devices to suit the specific sizes and conditions of A/C systems.

E v o l u t i o n

The A/C management system that offers powerful


functions, yet still gives simple navigation for any user. DAM602B51 B52

Communication capabilities via a Web browser further


expand air conditioning control possibilities. DCS601C51

* RoHS Directive
The RoHS (Restriction of Hazardous Substances (in electrical and electronic equipment)) Directive is an environmental directive enacted
to regulate the use of designated chemical substances (lead, cadmium, hexavalent chromium, mercury, polybrominated biphenyls and
polybrominated diphenylether) in electrical equipment. All household products subject to this Directive and sold in Europe from July 1,
2006 are legally bound to comply with the RoHS Directive.

Using interface

1. Onc e a month, adjus t the c loc k of the interfac e.


2. Daikin’ s unique P.P.D. s ys tem es timates the power c ons umption of eac h individual indoor unit bas ed on data c ommunic ated from indoor units and
c ompared to the power c ons umption of an air c onditioning ins tallation with a s tandard s etup. Note that P.P.D. is not a “ gauge” adapted to the
methods
of meas uring power c ons umption in eac h c ountry. All c ountries differ in the ways tenant billing s ys tems are implemented depending on their
res pec tive legal s ys tems . Data obtained by P.P.D. is for referenc e only and s hould not be us ed for offic ial financ ial trans ac tions .
3. J MT (J oint Matc hing Tes t) is normally required before projec t exec ution.

DAIKIN is the first manufacturer (Vendor ID53: Nov 15, 1999) whose VRV System has been officially approved as BACnet® compatible equipment.
Catalog information is as of July 2007.
BACnet ® is a registered trademark of the American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE).
LONWORKS®, LON® and LonTalk® are registered tradmarks of Echelon Corporation.
Ethernet is a registered trademark of Xerox Corporation.

About ISO 9001 About ISO 14001


ISO 9001 is a plant certification system ISO 14001 is the standard defined by the
defined by the International Organization for International Organization for Standardization
Standardization (ISO) relating to quality (ISO) relating to environmental management
assurance. ISO 9001 certification covers systems. Our group has been acknowledged
quality assurance aspects related to the by an internationally accredited compliance
“ design, development, manufacture, organisation as having an appropriate
installation, and supplementary service” of programme of environmental protection
products manufactured at the plant. procedures and activities to meet the
JMI-0107 JQA-1452 requirements of ISO 14001.
The interface for connecting VRV to BACnet or L ONWORKS protocols
® ®

Dealer
Head Office:
Umeda Center Bldg., 2-4-12, Nakazaki-Nishi,
Kita-ku, Osaka, 530-8323 Japan
Tokyo Office:
JR Shinagawa East Bldg., 2-18-1, Konan,
Minato-ku, Tokyo, 108-0075 Japan
http://www.daikin.com/global_ac/