FIRE ALARM SYSTEM SNAG
PENDING LIST BLOCK 02
                                                                                                    Pending
     Telephone 📞 jack is not working from 14th floor
   Parking Floor 2 - Telecom shaft is closed with gypsum
  board and there are multiple of modules and all circuit                                     Done \ Door pending
    joints inside the telecom shaft, it must be openable
                           always.
When the amplifier is turned on, there is a hemming sound                                           pending
     in the speakers from every floor. Please fix it.
Inside Fire Alarm Control Panel front cover not installed 1   #VALUE!                               Pending
                           Nos.
  The Annunciator Control Module ACM-24AT inside the                                                pending
             FACP panel is not functioning.
All occupancy certificate documents required for handing                            pending
               over the Fire Alarm System.
                                                 FIRE HYDRANT SNAG LIST
TERRACE - OHT buster pump required automation                                                       Pending
                    setup.
                                                                          #VALUE!
 TERRACE - Pressure gauge must be installed on all
riser as it will not be known how much kg pressure                                                  pending
is there at terrace.15/04/2025 Approved for gauge
                        installed
                                                                          #VALUE!
  All risers and line naming stickers need to be pasted.                                            Pending
    Block - 02 Booster pump not cover pending                                                       Pending
 Parking floor 1&2 -Water curtain deluge valve not                                            Done / Drain Pending
                 connected to FAS.
This butterfly valve on the terrace should always be                                                Pending
                        open.
  High zone ICV of sprinkler line pressure gauge
  required 15 kg pressure but is showing 17.5 kg                                                    Pending
    pressure, this is high pressure every time.
 High Zone Sprinkler ICV pressure gauge is faulty.                                                  Pending
  All pressure switch need to be set according to                                                   Pending
      sequence of fire pump operation board.
    Fire pump panel voltage required 415 Volts                                                      Pending
  Ramp area Hose box 1 - Female coupling of the                                                     Pending
          yard hydrant valve is loose.
Parking 1 - Female coupling of the Additional fire                                                  Pending
               shaft of block 02.
  Low Zone hydrant pressure gauge needs to be                                                       pending
    replaced because oil has dropped down.
                                                                          #VALUE!
Parking 1 should be relocate drain valve 25/35mm                                                    pending
                          FIRE ALARM SYSTEM SNAG LIST
                       Block 02
 Lift exhaust 03 fans on the terrace
        require automation.
  Parking Floor 2 - Telecom shaft is
closed with gypsum board and there
   are multiple of modules and all
   circuit joints inside the telecom
 shaft, it must be openable always.
                                               FIRE HYDRANT SNAG LIST
6th & 12th Floor - Hose reel 25
     mm ball valve leak
   Parking floor 1- External shaft light not
                  working.
   14 floor painting pending
Parking floor 2 - Water curtain
deluge valve not connected to
             FAS.
 Jubli clamp on the 2nd floor of
the hose reel drum needs to be
            replaced.
Both air cushion tank water is
          not filling.
 Low Zone Sprinkler pressure
    gauge need replace.
 FAS room door lock key not
         available
                    Completed
             Done
       Done \ Door pending
LIST
              Done
              Done
       Done
Done / Drain Pending
     work done
     work done
       Done
       Done