Cfas-Cfae Catalog
Cfas-Cfae Catalog
One-way fan coil cassettes with AC fan motor technology - model CFAS
One-way fan coil cassettes with EC fan motor technology - model CFAE
Sizes 16-26-36
UNT-PRC017-E4
Contents
Introduction 3
Model number 5
Dimensions 6
General data 10
Sound spectrum 15
Water pressure drop 16
Options 18
Standalone controls 26
Group controls 32
Building Management Controls 36
Accessories 37
2 UNT-PRC017-E4
Introduction
UNT-PRC017-E4 3
Introduction
6 000 AC
EC motor Watt.hour
5 000
4 000 67%
3 000 energy savings
2 000
1 000 EC
0
4 UNT-PRC017-E4
Model number
Table 1
DIGIT Description
1 Unit type C = Cassette
2 Unit type F = Fan Coil
3 Major Design Sequence A=A
4 Motor Type S = AC fan motor
E = EC fan motor
5+6 Unit size 16 = 1.6 kW at speed 5 total capacity
26 = 2.6 kW at speed 5 total capacity
36 = 3.6 kW at speed 5 total capacity
7 Application A = 2-pipe cooling only
B = 2-pipe heating only (on request)
C = 2-pipe changeover
D = 4-pipe
8 Coil size 3 = Standard 3 rows
4 = High efficiency 4 rows
5 = High efficiency heating 3 rows plus 2 rows
9 Minor Design Sequence B
10 Water valves and controls access sides G = Water valves on the left, controls on the right
D = Water valves on the right, controls on the left
11 Raise X = Standard / drain outlet height 100 mm from ceiling
R = Raised / drain outlet height 160 mm from ceiling
12 Filter X = Standard G0
3 = EU3
13 Electric heater(1) X = Without
1 = 350 W - size 16
2 = 550 W - size 16
3 = 700 W - size 26
4 = 1150 W - size 26
5 = 900 W - size 36
6 = 1400 W - size 36
14 Controls type X = Without for wall mount thermostat interface or customer field-mounted controls
A = Group control Modbus for wall-mounted thermostat or infrared controller
B = ZN Zone for wall-mounted thermostat or return air control
C = ZN Cascade for wall-mounted thermostat or return + supply air control
D = Free issued control
15 Free issued control factory-mounted W = Large empty control box
X = Without
16 Valve type X = Without
A = 2-way thermal On/Off
B = 3-way thermal On/Off
C = 2-way modulating 3 points
D = 3-way modulating 3 points
17 Condensate pump X = Without
A = Mounted
18 Fan speed selection 1 = Standard 1-2-4 (refer to table page 18)
2 = Up 2-4-5 (refer to table page 18)
19 Special X = Without
S = With
(1)
Electric heater sizes 1 and 2 correspond to fan coil size 16.
Electric heater sizes 3 and 4 correspond to fan coil size 26.
Eledtric heater sizes 5 and 6 correspond to fan coil size 36.
UNT-PRC017-E4 5
Dimensions
SIZE 16 SIZE 26
SIZE 36
Dimensions (mm)
Unit size A E F
16 592 454 78
26 970 884 43
36 1192 1099 46.5
6 UNT-PRC017-E4
Dimensions
Dimensions (mm)
Unit size A E F
16 592 454 78
26 970 884 43
36 1192 1099 46.5
UNT-PRC017-E4 7
Dimensions
30 Min
306
Raised height version
30 Min
366
Packaging
Standard height/raised height version
A
B
8 UNT-PRC017-E4
Dimensions
* 4 pipe units have 2 coils. The main coil for cooling has the same cooling performance as the
2 pipe coil for the same number of rows. The additional coil (+1 or +2) is the heating coil with 1 or
2 rows.
Note: The 2 row heating coil provides higher heating performance and is designed to provide
higher heating capacities for utilization with heat pump chillers, providing lower hot water
temperatures than boilers.
UNT-PRC017-E4 9
General data
2-pipe units
The following standard rating conditions are used:
COOLING
Entering air temperature +27°C d.b. +19°C w.b.
Water temperature +7/12°C
HEATING
Entering air temperature +20°C
Entering water temperature +50°C
water flow rate as for the cooling conditions
Table 2 - CFAS standard efficiency 3 row
16 26 36
Speed Standard 1 2 3 4 5 6 1 2 3 4 5 6 1 2 3 4 5 6
Speed Up 2-4-5 1 2 3 4 5 6 1 2 3 4 5 6 1 2 3 4 5 6
Air Flow m3/h 140 180 220 245 280 310 190 230 290 360 445 530 275 335 420 505 600 650
Cooling total emission kW 0.88 1.06 1.26 1.35 1.50 1.60 1.37 1.62 1.97 2.37 2.81 3.23 1.97 2.37 2.84 3.34 3.75 4.05
Cooling sensible emission kW 0.66 0.81 0.98 1.06 1.18 1.27 1 1.19 1.47 1.77 2.13 2.47 1.44 1.74 2.11 2.51 2.83 3.07
Heating kW 1.08 1.33 1.59 1.73 1.93 2.08 1.6 1.91 2.35 2.86 3.43 3.95 2.30 2.79 3.37 4.02 4.53 4.88
∆P Cooling kPa 2.4 3.3 4.5 5.1 6.1 6.8 2.9 3.9 5.5 7.6 10.3 13.1 6.4 8.8 12.1 16.2 19.8 22.7
∆P Heating kPa 1.8 2.6 3.5 4.0 4.9 5.6 2.3 3.1 4.5 6.3 8.4 10.8 5.2 7.3 9.8 13.4 16.3 18.6
Power consumption W 16 22 32 38 49 66 24 27 34 44 57 71 38 46 57 69 78 88
Fan amps A 0.07 0.10 0.14 0.17 0.22 0.30 0.11 0.12 0.15 0.20 0.26 0.32 0.12 0.15 0.19 0.27 0.33 0.38
NR level dB(A) 22 27 31 34 38 41 17 18 25 33 40 43 17 24 30 37 40 42
NC level dB(A) 20 25 30 33 36 39 15 16 23 31 38 41 15 22 28 35 38 41
Speed 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5
Selected speeds Min Med Max Min Med Max Min Med Max
Air Flow m /h
3
130 165 205 250 295 215 295 370 450 540 275 345 430 525 620
Cooling total emission kW 0.82 1 1.18 1.37 1.56 1.46 1.92 2.31 2.74 3.16 1.87 2.31 2.78 3.28 3.75
Cooling sensible emission kW 0.62 0.76 0.91 1.07 1.24 1.07 1.42 1.73 2.07 2.41 1.37 1.7 2.06 2.45 2.83
Heating kW 1.02 1.25 1.5 1.75 2.02 1.72 2.28 2.79 3.33 3.85 2.19 2.72 3.3 3.93 4.54
∆P Cooling kPa 2.1 3 4 5.2 6.5 3.2 5.2 7.3 9.8 12.6 5.8 8.4 11.7 15.7 19.8
∆P Heating kPa 1.7 2.4 3.3 4.3 5.3 2.6 4.2 6 8 10.4 4.7 6.9 9.4 12.9 16.6
Power consumption W 8 11 14 21 29 8 11 16 24 37 10 13 19 29 42
Fan amps 0.04 0.05 0.07 0.1 0.14 0.04 0.05 0.08 0.12 0.18 0.05 0.06 0.09 0.14 0.2
NR level dB(A) 22 27 32 37 41 18 22 30 37 42 18 25 33 39 44
NC level dB(A) 21 26 30 35 39 17 21 28 35 40 16 24 31 38 42
10 UNT-PRC017-E4
General data
Speed Standard 1 2 3 4 5 6 1 2 3 4 5 6 1 2 3 4 5 6
Speed Up 2-4-5 1 2 3 4 5 6 1 2 3 4 5 6 1 2 3 4 5 6
Air Flow m3/h 140 180 220 245 280 310 190 230 290 360 445 530 275 335 420 505 600 650
Cooling total emission kW 0.97 1.19 1.44 1.55 1.74 1.87 1.44 1.72 2.12 2.57 3.09 3.58 2.05 2.49 3.00 3.56 4.02 4.36
Cooling sensible emission kW 0.71 0.88 1.07 1.17 1.31 1.42 1.04 1.24 1.54 1.88 2.28 2.67 1.48 1.81 2.20 2.63 2.98 3.25
Heating kW 1.14 1.42 1.72 1.88 2.10 2.27 1.69 2.03 2.54 3.12 3.79 4.44 2.38 2.90 3.51 4.20 4.77 5.20
∆P Cooling kPa 4.7 6.7 9.2 10.6 12.9 14.6 4.4 6.0 8.6 12.1 16.8 21.7 4.7 6.7 9.3 12.6 15.5 17.9
∆P Heating kPa 3.7 5.4 7.6 8.8 10.7 12.3 3.5 4.8 7.1 10.2 13.6 17.9 3.9 5.5 7.3 10.0 12.6 14.6
Power consumption W 16 22 32 38 49 66 24 27 34 44 57 71 38 46 57 69 78 88
Fan amps A 0.07 0.10 0.14 0.17 0.22 0.30 0.11 0.12 0.15 0.20 0.26 0.32 0.12 0.15 0.19 0.27 0.33 0.38
NR level dB(A) 22 27 31 34 38 41 17 18 25 33 40 43 17 24 30 37 40 42
NC level dB(A) 20 25 30 33 36 39 15 16 23 31 38 41 15 22 28 35 38 41
Speed 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5
Selected speeds Min Med Max Min Med Max Min Med Max
Air Flow m3/h 130 165 205 250 295 215 295 370 450 540 275 345 430 525 620
Cooling total emission kW 0.91 1.12 1.34 1.58 1.81 1.55 2.06 2.51 3 3.5 1.95 2.42 2.94 3.49 4.02
Cooling sensible emission kW 0.66 0.82 0.99 1.18 1.38 1.11 1.49 1.84 2.21 2.6 1.41 1.76 2.15 2.57 2.98
Heating kW 1.07 1.32 1.6 1.9 2.2 1.82 2.46 3.03 3.68 4.32 2.25 2.82 3.44 4.12 4.78
∆P Cooling kPa 4.1 5.9 8.1 10.9 13.9 5 8.2 11.6 15.9 20.8 4.3 6.4 8.9 12.1 15.5
∆P Heating kPa 3.3 4.8 6.6 9 11.6 4.1 6.7 9.4 13.2 17.1 3.5 5.2 7.4 10 13
Power consumption W 8 11 14 21 29 8 11 16 24 37 10 13 19 29 42
NR level dB(A) 22 27 32 37 41 18 22 30 37 42 18 25 33 39 44
NC level dB(A) 21 26 30 35 39 17 21 28 35 40 16 24 31 38 42
UNT-PRC017-E4 11
General data
COOLING
Entering air temperature +27°C d.b. +19°C w.b.
Water temperature +7/12°C
HEATING
Entering air temperature +20°C
Water temperature: +70/60°C
Speed 1 2 3 4 5 6 1 2 3 4 5 6 1 2 3 4 5 6
Selected speeds 6 5 4 3 2 1 6 5 4 3 2 1 6 5 4 3 2 1
Air Flow m3/h 140 180 220 245 280 310 190 230 290 360 445 530 275 335 420 505 600 650
Cooling total emission kW 0.88 1.06 1.26 1.35 1.50 1.60 1.37 1.62 1.97 2.37 2.81 3.23 1.97 2.37 2.84 3.34 3.75 4.05
Cooling sensible emission kW 0.66 0.81 0.98 1.06 1.18 1.27 1 1.19 1.47 1.77 2.13 2.47 1.44 1.74 2.11 2.51 2.83 3.07
Heating kW 0.92 1.08 1.25 1.34 1.47 1.56 1.49 1.71 2.02 2.35 2.73 3.07 2.12 2.47 2.87 3.30 3.64 3.89
∆P Cooling kPa 2.4 3.3 4.5 5.1 6.1 6.8 2.9 3.9 5.5 7.6 10.3 13.1 6.4 8.8 12.1 16.2 19.8 22.7
∆P Heating kPa 1.6 2.1 2.7 3.1 3.6 4.0 0.9 1.2 1.6 2 2.6 3.2 2.0 2.6 3.4 4.3 5.1 5.8
Power consumption W 16 22 32 38 49 66 24 27 34 44 57 71 38 46 57 69 78 88
Fan amps A 0.07 0.10 0.14 0.17 0.22 0.30 0.11 0.12 0.15 0.20 0.26 0.32 0.12 0.15 0.19 0.27 0.33 0.38
NR level dB(A) 22 27 31 34 38 41 17 18 25 33 40 43 17 24 30 37 40 42
NC level dB(A) 20 25 30 33 36 39 15 16 23 31 38 41 15 22 28 35 38 41
Speed 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5
Selected speeds Min Med Max Min Med Max Min Med Max
Air Flow m3/h 130 165 205 250 295 215 295 370 450 540 275 345 430 525 620
Cooling total emission kW 0.82 1 1.18 1.37 1.56 1.46 1.92 2.31 2.74 3.16 1.87 2.31 2.78 3.28 3.75
Cooling sensible emission kW 0.62 0.76 0.91 1.07 1.24 1.07 1.42 1.73 2.07 2.41 1.37 1.7 2.06 2.45 2.83
Heating kW 0.87 1.03 1.18 1.35 1.52 1.58 1.97 2.31 2.66 3.01 2.04 2.42 2.82 3.24 3.64
∆P Cooling kPa 2.1 3 4 5.2 6.5 3.2 5.2 7.3 9.8 12.6 5.8 8.4 11.7 15.7 19.8
∆P Heating kPa 1.4 1.9 2.5 3.1 3.8 1 1.5 2 2.5 3.1 1.8 2.5 3.3 4.2 5.1
Power consumption W 8 11 14 21 29 8 11 16 24 37 10 13 19 29 42
NR level dB(A) 22 27 32 37 41 18 22 30 37 42 18 25 33 39 44
NC level dB(A) 21 26 30 35 39 17 21 28 35 40 16 24 31 38 42
12 UNT-PRC017-E4
General data
COOLING
Entering air temperature +27°C d.b. +19°C w.b.
Water temperature +7/12°C
HEATING
Entering air temperature +20°C
Water temperature: +60/50°C
Table 8
CFAS high efficiency heating 16 26 36
coil
Speed 1 2 3 4 5 6 1 2 3 4 5 6 1 2 3 4 5 6
Selected speeds 6 5 4 3 2 1 6 5 4 3 2 1 6 5 4 3 2 1
Air Flow m3/h 140 180 220 245 280 310 190 230 290 360 445 530 275 335 420 505 600 650
Cooling total emission kW 0.88 1.06 1.26 1.35 1.50 1.60 1.37 1.62 1.97 2.37 2.81 3.23 1.97 2.37 2.84 3.34 3.75 4.05
Cooling sensible emission kW 0.66 0.81 0.98 1.06 1.18 1.27 1 1.19 1.47 1.77 2.13 2.47 1.44 1.74 2.11 2.51 2.83 3.07
Heating kW 1.16 1.38 1.63 1.75 1.92 2.05 1.79 2.11 2.55 3 3.53 4.03 2.57 3.07 3.65 4.22 4.70 5.06
∆P Cooling kPa 2.4 3.3 4.5 5.1 6.1 6.8 2.9 3.9 5.5 7.6 10.3 13.1 6.4 8.8 12.1 16.2 19.8 22.7
∆P Heating kPa 4.5 6.0 8.1 9.1 10.8 12.2 2.4 3.2 4.5 6 8 10 5.4 7.4 10.0 12.9 15.6 17.8
Power consumption W 16 22 32 38 49 66 24 27 34 44 57 71 38 46 57 69 78 88
Fan amps A 0.07 0.10 0.14 0.17 0.22 0.30 0.11 0.12 0.15 0.20 0.26 0.32 0.12 0.15 0.19 0.27 0.33 0.38
NR level dB(A) 22 27 31 34 38 41 17 18 25 33 40 43 17 24 30 37 40 42
NC level dB(A) 20 25 30 33 36 39 15 16 23 31 38 41 15 22 28 35 38 41
Sensible capacity
To be used based on Eurovent cooling rating conditions 27°C/19°C and 50% RH ambient temperature and 12/7°C cooling water
temperatures.
UNT-PRC017-E4 13
General data
Operating limits
Maximum entering water temperature: +80°C.
Minimum water temperature without glycol: +5°C.
For lower water temperatures please contact your local sales office.
Maximum water operating pressure: 1000 kPa (10 bars).
Water flow cooling coil
Size 16 26 36
Minimum 100 150 150
3-row
Maximum 500 1000 1500
Minimum 100 150 200
4-row
Maximum 750 1000 2000
Electrical motor
maximum power
input AC fan motor 16 26 36
W 66 71 84
A 0.30 0.32 0.38
230/1/50
EC fan motor
W 29 37 42
16 26 36
Speed 1 2 3 4 5 6 1 2 3 4 5 6 1 2 3 4 5 6
Throw (L) Heating 3.8 4.5 5.8 6.3 6.8 7.2 4.0 5.0 6.1 7.0 8.0 9.0 4.5 5.2 6.3 7.5 8.8 9.5
(m) Cooling 3.0 3.6 4.6 5.0 5.4 5.7 3.2 4.0 4.8 5.6 6.0 7.2 3.6 4.1 5.0 6.0 7.0 7.6
14 UNT-PRC017-E4
Sound spectrum
Table 9 - CFAS
Sound Power level Frequency octave band LWA Sound Pressure
Speed m3/h 125 250 500 1000 2000 4000 8000 Glob (*) Lp (*) NC NR NC
Table 10 - CFAE
Sound Power level Frequency octave band LWA Sound Pressure
Volt Speed m /h
3
125 250 500 1000 2000 4000 8000 Glob (*) Lp (*) NC NR
7.5 4 250 33.8 43.1 46.9 45.5 41.4 34.3 24.2 50.9 42 37 35
7.5 4 450 37.6 45.2 47.9 45.6 42.8 33.5 25.9 52.0 43 37 35
7.5 4 525 39.8 47.3 50.1 47.8 43.1 33.3 24.5 54.0 45 39 38
(*)Note: The sound pressure levels Lp and NC are determined with the following assumptions:
- a room absorption of 9 dB(A) for a room of 100 m with a reverbering time of 0,5 sec
- units complete of filter, coil and fan sections
UNT-PRC017-E4 15
Water pressure drop
1 = 3-row coil
2 = 4-row coil
3 = Additional row +1
4 = Additional row +2
16 UNT-PRC017-E4
Water pressure drop
(1)
Available only as an accessory for field mounting
UNT-PRC017-E4 17
Options
Options
Access side configuration
The unit can be delivered with the water valve package on the right or left hand side. The
control box is always mounted on the opposite side of the water valve package. There are 2
precut circles in the sheet metal for fresh air intake, one each side of the unit. The one to be
used is opposite side of the control box, same side as the water valve package.
Electrical
Electrical
connections side
connections
side
Water
Water connections
side
connections
side
Unit size 16 26 36
Row Speed 1 2 3 4 5 6 1 2 3 4 5 6 1 2 3 4 5 6
Standard 1-2-4 x x x x x x x x x
3
Up 2-4-5 x x x x x x x x x
Standard 1-2-4 x x x x x x x x x
4
Up 2-4-5 x x x x x x x x x
Standard 1-2-4 x x x x x x x x x
3+1
Up 2-4-5 x x x x x x x x x
Standard 1-2-4 x x x x x x x x x
4+1
Up 2-4-5 x x x x x x x x x
Standard 1-2-4 x x x x x x x x x
3+2
Up 2-4-5 x x x x x x x x x
18 UNT-PRC017-E4
Options
Filter
Two options available easy removable
without any tool, the standard version
is classified G0 made of polypropylene
honeycomb design. It is washable. A
factory-mounted optional filter class EU3
made of 8 mm thick polyester media
mounted on a metallic frame is also available
Valve
Unit size DN Diameter (inches) Kvs
Cooling coil 16-26 15 1/2” 1.6
36 20 3/4” 2.5
Heating coil all 15 1/2” 1.6
UNT-PRC017-E4 19
Options
163
119
27
32
163
123
32
361
27
321
302
262
229
101
120
163
163 20 25
123
25
361
321
302
262
120
163
20 UNT-PRC017-E4
Options
223
179
163
27 32
123
32
361
27
321
302
262
229
160
180
223
223
20 25
183
25
361
321
302
262
180
223
UNT-PRC017-E4 21
Options
M
M
II I
R R
III
V
16-26 15 35169809-001
Cooling
2 way 36 20 35169810-001 Yes
16-26 15 35169806-001
Cooling
3 way 36 20 35169807-001 Yes
16-26 15 35169803-001
Cooling
3 way lockshield 36 20 35169804-001 No
22 UNT-PRC017-E4
Options
UNT-PRC017-E4 23
Control options
2 pipe 4 pipes
Wall thermostat
N x x Manual Manual manu x
(wires)
Unit controller
+ wall
BMS ZN523 x auto (WT) auto (SP) auto (WT) auto (SP) x x
thermostat
(bus)
Unit controller
+ wall
BMS ZN525 x auto (WT) auto (SP) auto (WT) auto (SP) x x
thermostat
(bus)
24 UNT-PRC017-E4
Control options
Control
Return air Time Control
Installation
Control
Architecture Accessory Type
capability
temperature MHW
Economy Window Remote
of day external
type (number overide contact on/off
sensor scheduler equipment
of units)
Wall thermostat
N Relay card REL03 wires
(wires)
10
Wall thermostat
P Relay card REL03 wires
(wires)
Wall thermostat
R Relay card REL03 wires 10 x
Standalone (wires)
Wall thermostat
T Relay card REL03 wires 10 x
(wires)
AC fan
motor Propri-
Unit controller + wall
U Relay card REL02 etary 10 x x
LCD thermostat (bus)
RS485
Mod-
Unit controller + wall
Standalone T-EC Relay card REL04 Bus 16 x x x
thermostat (bus)
RS485
UNT-PRC017-E4 25
Standalone controls
Figure 1 - Thermostat N
Main characteristics:
- On/off switch.
- Manual speed switch.
- Manual Summer/Winter switch.
- Temperature setting
Operation:
- 1-step heating
- 1-step cooling
- Controls one water valve ON-OFF for
cooling
- Controls one electric heater or one water
valve ON-OFF for heating
- Fan runs continuously regardless of water
valve operation when the thermostat is
turned ON.
26 UNT-PRC017-E4
Standalone controls
(Accessory 35169831-001)
Figure 2 - Thermostat P
Main characteristics:
- On/off switch.
- Manual speed switch.
- Automatic Summer/Winter change-over.
- Temperature setting
Operation:
- 2-step heating
- 1-step cooling
- Controls one water valve ON-OFF for
cooling
- Controls one water valve ON-OFF for
heating
- Controls one electric heater as second
step heating
- Fan runs continuously regardless of water
valve operation when the thermostat is
turned ON.
UNT-PRC017-E4 27
Standalone controls
(Accessory 35169833-001)
Main characteristics:
- On/off switch.
- Manual speed switch.
- Manual change mode switch.
- Temperature setting
- Water temperature sensor to avoid cold
air drafts in heating mode.
Operation:
- 1-step heating
- 1-step cooling
- Controls one water valve ON/OFF for
cooling
- Controls one water valve ON/OFF or one
electric heater for heating
- Fan runs continuously regardless of water
valve operation when the thermostat is
turned ON.
- With the water temperature sensor
accessory MHW, cold air drafts are
avoided in cases where the hot water
temperature is lower than 38°C.
28 UNT-PRC017-E4
Standalone controls
(Accessory 35169834-001)
Main characteristics:
Same characteristics as the R control,
adding:
- Manual or automatic speed switch.
- Electronic thermostat for fan control
(on/off).
- Electronic thermostat for valve(s) control
(on/off).
- Simultaneous thermostatic control on the
valves and fan (on/off).
- It allows installation of the Summer/
Winter switch centralized and remote, or
to control it with an automatic change-
over fitted on the water pipe (for 2 pipe
installations only). The last case needs
the adjustment of the jumper on the
control board (see the instruction leaflet
supplied with the control).
UNT-PRC017-E4 29
Standalone controls
30 UNT-PRC017-E4
Standalone controls
(Accessory 35169835-001)
Main characteristics:
- Manual or automatic speed switch.
- Manual or automatic Summer/Winter
switch.
- Electronic thermostat for fan control
(on/off).
- Electronic thermostat for valve(s) control
(on/off).
- It allows to control the minimum water
temperature sensor (MWT).
- It allows to control the chilled water
valve (on/off) and the electric resistance
in the CWS-E version.
- It allows to control the fan and the
heating electric resistance.
- It allows to control up to 10 units with
the REL02 relay board.
UNT-PRC017-E4 31
Group controls
System configuration
More over, the TODS centralized controller is capable to pilot up to 8 external devices like a
chiller or an air handler using the external control card ECC. Each external device can provide
the state of operation to the TODS controller to provide a diagnosis about the installation.
Such the MB control using ModBus communication protocol is a powerful device than can
operate a small building in a system configuration.
32 UNT-PRC017-E4
Group controls
T-MB thermostat
(Accessory 35169876-001)
The T-MB thermostat and the Modbus The T-MB wall-mounted thermostat is used
controller suit all types of system with the Modbus controller fitted on the
applications. cassette. The Modbus controller is factory-
- 2 or 4 pipe configured for the customer’s application.
- 2-pipe with auto changeover The T-MB thermostat is configured by
- 2-step heating with electric heater default to control air ambient temperature
- Fan operation with continuous or based on the temperature sensor of the
alternate with destratification. thermostat. In the case that return air
temperature is used, it can be configured
It is connected to the factory-mounted using the dipswitch 2 in position ON during
unit controller MB and configured for the installation.
customer’s requirements. The MB controller
can be connected in a Master/Slave
configuration with up to 20 units.
J1
Exernal devices: window contact, cold air
draft protection with T3 sensor. 7
6
JP3 5
3
2
M1
1
J5
7 6 5
JUMPER
MC2
UNT-PRC017-E4 33
Group controls
IR
REMOTE
CONTROL
34 UNT-PRC017-E4
Group controls
1. Clock : 24 hours
2. Timer : the program switches the device on and off
3. Displays the temperature setpoint
4. Fan speed setting: 3 speed plus automatic selection
5. Operating mode: heat, cool, fan only plus and automatic mode selection.
UNT-PRC017-E4 35
Building Management Controls
Intelligent LonTalk® ZN523 The intelligent control offers the following • Filter timer for preventive maintenance
benefits: • Adjustable local set point max - min
control for AC fan motor • Intelligent management of valve position limits.
The Tracer® ZN unit controller is a micro- and fan speeds. Valve is fully open • Built-in electrical protection.
processor based direct digital controller before changing the fan speed (acoustic • 2 operating modes in stand-alone
that is dedicated to the control and the comfort optimization). application: comfort and reduce.
optimization of the units. It is designed to • Control algorithms based on ambient and • After a power up in the building, units
provide improved comfort with minimum discharge air temperatures. automatically staggered from 5 to 32
energy consumption through the use of • Discharge air temperature (low and high seconds.
custom proportional integral derivative (PID) limit control). • Built-in adjustable timed override
control algorithms as well as intelligent • Automatic intelligent changeover function.
fan speed and set point control strategies. based on ambient air - entering water • Built-in condensate overflow protection.
It is factory installed, pre-commissioned temperatures differential (+/-%2.5K). • Built-in output test capability.
and tested, resulting in a highly integrated • Automatic intelligent changeover with • Built-in diagnostic indicator.
product, reduced installation and sampling function for 2-way valves use.
commissioning time.
1. Control output
2. Unoccupied heating setpoint
3. Occupied standby heating setpoint
4. Occupied heating setpoint
5. Dead band
6. Local setpoint
7. Occupied cooling setpoint
8. Occupied standby cooling setpoint
9. Unoccupied cooling setpoint
10. Temperature
For more details about the LonTalk® ZN
control, please refer to the controller’s
manual.
36 UNT-PRC017-E4
Accessories
Condensate pump
Accessory 35169826-001
A condensate pump kit is available for field
installation, it has the same performances
than the factory-mounted version, see
page 31.
UNT-PRC017-E4 37
Accessories
Thermostat T-EC
(accessory 35169884-001)
Thermostat for CFAE for installation on the
job site. It can control up to 16 units.
38 UNT-PRC017-E4
Accessories
R1
- ACCORDING TO APPLICATION
Y1
Y2
III
II
I
N N
7 8 9 10 11 12 7 8 9 10 11 12
REL3 = REPEATER
FCT = FAN COIL TERMINALS
REL-3 REL-3
R1 = RESISTANCE (OPTION)
Y2 = HOT WATER VALVE (OPTION)
Y1 = COLD WATER VALVE (OPTION)
= TRANE WIRING
230Vac
50Hz
230Vac
50Hz
= EXTERNAL CONNECTION RESPONSABILITY OF
L N 1 2 3 4 5 6 L N 1 2 3 4 5 6 THE INSTALLER
L L
PE PE
FCT FCT
PE L N 4 5 6 7 8 9 10 11 12 13 14 15 PE L N 4 5 6 7 8 9 10 11 12 13 14 15
R1
- ACCORDING TO APPLICATION
Y1
III
II
I
N N
7 8 9 10 11 12 7 8 9 10 11 12
REL-3 REL-3
230Vac 230Vac
50Hz 50Hz
L N 1 2 3 4 5 6 L N 1 2 3 4 5 6
L L
PE PE
FCT FCT
PE L N 4 5 6 7 8 9 10 11 12 13 14 15 PE L N 4 5 6 7 8 9 10 11 12 13 14 15
UNT-PRC017-E4 39
Accessories
AL AL
SEC1 Y SEC1 Y
SB SB
N PE L N PE L
REL 2 TR REL 2
TR
R POWER
UNIT
REL2 for U
40 UNT-PRC017-E4
Accessories
UNT-PRC017-E4 41
Accessories
42 UNT-PRC017-E4
Notes
UNT-PRC017-E4 43
Trane optimizes the performance of homes and buildings around the world. A business of Ingersoll Rand,
the leader in creating and sustaining safe, comfortable and energy efficient environments, Trane offers
a broad portfolio of advanced controls and HVAC systems, comprehensive building services, and parts.
For more information, visit www.Trane.com.
Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice.
© 2012 Trane All rights reserved Produced on post-consumer recycled paper, using environmentally
UNT-PRC017-E4_1112 friendly print practices that reduce waste.
Supersedes UNT-PRC017-E4_0512