VCB 1
VCB 1
Instruction manual
Types 3AH3 and 3AHc vacuum circuit
breaker operator modules
4.16 kV to 38 kV
www.usa.siemens.com/mvswitchgear
Hazardous voltages and high-speed moving parts.
The contents of this instruction manual shall not become part of or modify any prior or
existing agreement, commitment or relationship. The sales contract contains the entire
obligation of Siemens Industry, Inc. The warranty contained in the contract between the
parties is the sole warranty of Siemens Industry, Inc. Any statements contained herein
do not create new warranties or modify the existing warranty.
Table of Contents
Introductions 04 – 05
Maintenance 28 – 41
Overhaul 42 – 46
Introduction
4
3AH3 & 3AHc Vacuum Circuit Breaker Operator Modules | Instruction Manual
5
3AH3 & 3AHc Vacuum Circuit Breaker Operator Modules | Instruction Manual
Heavy weight.
Improper lifting or hoisting can result in death, serious injury or
property damage.
Obtain the services of a qualified rigger prior to hoisting the circuit
breaker to assure adequate safety margins in the hoisting equipment
and procedures to avoid damage.
3. Any visible damage must be noted on the Note: Shipments are not released from the
delivery receipt and acknowledged with factory without a clear bill of lading.
the driver’s signature. The damage should Approved methods are employed for
be detailed as much as possible. It is preparation, loading, blocking and tarping
essential that a notation "possible of the equipment before it leaves the
internal damage, subject to inspection" Siemens factory. Any determination as to
be included on the delivery receipt. If the whether the equipment was properly loaded
driver will not sign the delivery receipt or properly prepared by shipper for over-the-
with the damage noted, the shipment road travel cannot be made at the
should not be signed for by the destination. If the equipment is received in a
consignee or their agent. damaged condition, this damage to the
equipment has to have occurred while en
4. Notify Siemens medium-voltage
route due to conditions beyond Siemens‘
customer service immediately of any
control. If the procedure outlined above is
damage, at 1-800-333-7421 or 1-423-
not followed by the consignee, purchaser or
262-5700 outside the U.S.
their agent, Siemens cannot be held liable
5. Arrange for a carrier inspection of the for repairs. Siemens will not be held liable
damage immediately. for repairs in any case where repair work
was performed prior to authorization from
Important: Do not move the equipment
Siemens.
from the place it was set when unloading.
Also, do not remove or disturb packaging or Handling procedure
wrapping material prior to carrier damage 1. Carefully remove the shipping carton
inspection. Equipment must be inspected by from the circuit breaker. Keep the
carrier prior to handling after receipt. This shipping pallet for later use if the circuit
eliminates loss due to claims by carrier that breaker is to be stored prior to its
the equipment was damaged or further installation.
damaged on site after unloading.
2. Inspect for concealed damage.
6. Be sure the equipment is properly Notification to carrier must take place
protected from any further damage by within 15 days to assure prompt
covering it properly after unloading. claim resolution.
7. If practical, make further inspection for 3. Each circuit breaker should be lifted
possible concealed damage while the appropriately to avoid crushing the side
carrier’s inspector is on site. If inspection panels of the circuit breaker, or
for concealed damage is not practical at damaging the primary disconnect
the time the carrier’s inspector is assemblies.
present, it must be done within 15 days
Type 3AH3 vacuum circuit breaker
of receipt of the equipment. If concealed
operator modules weigh between 165
damage is found, the carrier must again
and 408 lbs (75-185 kg), plus an
be notified and inspection made prior to
additional 100 lbs (45 kg) for packaging
taking any corrective action to repair.
and pallet. Refer to Table 13 for more
Also notify Siemens immediately at
information.
1-800-333-7421 or 1-423-262-5700
outside the U.S. Type 3AHc vacuum circuit breaker
operator modules are not furnished
8. Obtain the original carrier inspection
separately, but are supplied as a
report and forward it with a copy of the
component of a complete drawout
noted delivery receipt to Siemens.
circuit breaker. Weights and lifting
Approval must be obtained by Siemens
details are provided in the circuit breaker
from the carrier before any repair work
manuals.
can be performed.
4. The palleted circuit breaker can be
Before approval can be obtained, Siemens
moved using a properly rated fork-lift
must have the documents referenced in
vehicle. The pallets are designed for
the paragraph above. The carrier
movement by a standard fork-lift vehicle.
inspection report and/or driver’s signature
on the delivery receipt does not constitute
approval to repair.
7
3AH3 & 3AHc Vacuum Circuit Breaker Operator Modules | Instruction Manual
Figure 1: Front panel controls of circuit breaker and manual charging of closing spring Storage procedure
1. Whenever possible, install the circuit
breaker operator module in its assigned
switchgear enclosure or end location for
storage.
2. When the circuit breaker operator
G
module needs to be placed on its pallet
for storage, be sure the unit is securely
bolted to the pallet and covered with
polyethylene film at least 10 mils thick.
A E
Indoor storage
Whenever possible, store the circuit breaker
operator module indoors. The storage
environment must be clean, dry and free of
B F
such items as construction dust, corrosive
atmosphere, mechanical abuse and rapid
temperature variations.
C
Outdoor storage
D Outdoor storage is not recommended. When
no other option is available, the circuit
breaker operator module must be
completely covered and protected from rain,
snow, dirt and all other contaminants.
Space heating
Space heating must be used for both indoor
and outdoor storage to prevent
condensation and corrosion. When the
circuit breaker operator module is stored
outdoors, 250 watts per circuit breaker of
space heating is recommended. If the circuit
Item Description Item Description breaker operator module is stored inside the
A Manual spring-charging port E Manual close pushbutton switchgear enclosure, and the switchgear is
B CHARGED/DISCHARGED indicator F Manual open pushbutton equipped with space heaters, energize the
space heaters.
C OPEN/CLOSED indicator
G Rating plate
D Operation counter
8
3AH3 & 3AHc Vacuum Circuit Breaker Operator Modules | Instruction Manual
9
3AH3 & 3AHc Vacuum Circuit Breaker Operator Modules | Instruction Manual
10
3AH3 & 3AHc Vacuum Circuit Breaker Operator Modules | Instruction Manual
Vacuum interrupter/
operator
N
M
T N
C
R
D
S
Q
E H P
K
B
A G M
R J F
O V
S
F C D
Q
G O
H U
P
J
I L
J
K
11
3AH3 & 3AHc Vacuum Circuit Breaker Operator Modules | Instruction Manual
Figure 4: Vacuum circuit breaker operator module This section describes the operation of each
Figure 3: Vacuum interrupter cut-
away view major subassembly as an aid in the
1
operation, installation, maintenance and
repair of the circuit breaker.
Vacuum interrupters
2 The operating principle of the vacuum
interrupter is simple. Figure 3 is a section
view of a typical vacuum interrupter. The
4
entire assembly is sealed after a vacuum is
3 established.
5
3AH3 operator mechanism
The vacuum interrupter stationary contact is
connected to the upper pole head of the
3AH vacuum circuit breaker operator circuit breaker. The vacuum interrupter
6 movable contact is connected to the pole
7 bottom and driving mechanism of the circuit
breaker.
8
3AHc operator mechanism
The vacuum interrupter stationary contact is
9
connected to the lower pole head of the
circuit breaker. The vacuum interrupter
Item Description movable contact is connected to the upper
pole head (pole bottom) and drive
Fixed contact-current
1
connection
mechanism of the circuit breaker.
12
3AH3 & 3AHc Vacuum Circuit Breaker Operator Modules | Instruction Manual
Phase barriers (if applicable) The energy-storing mechanism and all the
Plates of glass-polyester insulating material control and actuating devices are installed
are attached to the circuit breaker and in the operator housing. The mechanism is
provide suitable electrical insulation of the spring stored-energy type and is
between the vacuum interrupter and mechanically and electrically trip-free.
primary conductors and the cubicle.
The close-open indicator, closing spring-
Stored-energy operating mechanism charge indicator and the operation counter
The stored-energy operating mechanism of are located on the front of the operator
the circuit breaker is an integrated housing.
arrangement of springs, coils and
The control connector for the control and
mechanical devices designed to provide a
signalling cables is a multi-contact plug in
number of critical functions. The energy
most designs, although direct connection to
necessary to close and open the contacts of
the switchgear is used for certain products.
the vacuum interrupters is stored in
powerful opening and closing springs. The Circuit breaker pole (refer to Figure 2)
closing springs are normally charged The vacuum interrupter is bolted to the
automatically, but there are provisions for upper pole head and the upper pole head is
manual charging. The operating mechanism rigidly connected to the operator housing by
that controls charging, closing and tripping the post insulator. The moving contact end
functions is fully trip-free. “Trip-free” of the vacuum interrupter is stabilized
requires that the tripping function prevail against lateral forces by a centering ring on
over the closing function as specified in the pole bottom. The external forces due to
ANSI/IEEE C37.04. switching operations and the contact
pressure are absorbed by the struts.
Vacuum interrupter/operator module
The vacuum interrupter/operator module Current-path assembly (refer to Figure 2)
consists of the three poles, each with its The current-path assembly consists of the
vacuum interrupters and primary insulators, pole head, the stationary contact and the
mounted on the common operating moving contact, that is connected to the
mechanism housing. This module is shown pole bottom by a terminal clamp and a
in Figure 4. flexible connector.
Construction (Refer to Figures 1, 2, 5 and Vacuum interrupter (refer to Figure 2)
6) (3AH only) The moving-contact motion is aligned and
This description covers the type 3AH stabilized by a guide bushing. The metal
operator. The type 3AHc differs in bellows follows the travel of the contact and
arrangement but the fundamental seals the vacuum interrupter against the
discussion of operation applies. surrounding atmosphere.
Each of the circuit breaker poles are fixed to Switching operation (refer to Figures 2
the rear of the operating mechanism and 5)
housing by two cast-resin insulators. The When a closing command is initiated, the
insulators also connect to the upper and closing spring (62.0), that was previously
lower pole supports that in turn support the charged by hand or by the motor, actuates
ends of the vacuum interrupter. the moving contact through the jack shaft
(63.0), lever, contact pressure spring (49.0),
The pole supports are aluminum castings
insulating coupler (48.0) and angled lever.
(most 1,200 A, all 2,000 A and some
3,000 A), copper castings (some 3,000 A) or The forces that occur when the action of the
sheet steel (some 1,200 A). For type 3AH insulating coupler (48.0) is converted into
operators, primary disconnect stud the vertical action of the moving contact are
extensions may be attached directly to the absorbed by the guide link, that pivots on
upper and lower pole connection pads. the pole bottom and the eye bolt.
13
3AH3 & 3AHc Vacuum Circuit Breaker Operator Modules | Instruction Manual
14
3AH3 & 3AHc Vacuum Circuit Breaker Operator Modules | Instruction Manual
Figure 5: Stored-energy operating mechanism (circuit breaker shown in OPEN position) (straight linkage shown)
62.5
55.2 62.3
62.1 50.3
62.5.2
62.2
68.0
53.0
50.5 62.6
50.2
55.1
53.1
62.0 54.1
50.4.1
55.0 54.0
50.4
64.0
68.1
58.0
63.0 63.1
63.5
61.8
59.0
60.0
Item Description Item Description Footnote:
50.2 Charging mechanism gear box 62.1 Charging shaft For certain applications, the straight
1.
15
3AH3 & 3AHc Vacuum Circuit Breaker Operator Modules | Instruction Manual
Figure 6: Stored-energy operating mechanism (circuit breaker shown in CLOSED position) Closing (refer to Figures 5, 7-10)
(Drawout trip-free linkage shown) If the circuit breaker is to be closed
manually, the closing spring is released by
Item Description
pressing the Close button (53.0). In the case
54.0 Open pushbutton of remote electrical control, the close coil
62.8 Trip-free coupling rod1 62.8.1 52SRC (53.1) unlatches the closing spring
62.8.1 Spring-return latch1 (62.0).
Trip-free coupling link 62.8.2 As the closing spring discharges, the
62.8.2
(draw bar)1 62.8 charging shaft (62.1) is turned by crank
64.0
64.0 Opening spring 54.0 (62.2).
64.2 Trip-latch pawl (not visible) The cam disc (62.3) at the other end of the
64.3 Lever charging shaft actuates the drive lever
64.3.1 Pawl roller 64.3.1 (62.6), with the result that jack shaft (63.0)
is turned by lever (63.5) via the coupling rod
64.3 (62.8). At the same time, the levers (63.1),
(63.5) and (63.7) fixed on the jack shaft
operate the three insulated couplers (48.0)
Footnote: (refer to Figure 2) for the circuit breaker
1.
For type SDV6 and some fixed-mounted circuit breakers, trip-free coupling rod (62.8) is
poles. Lever (63.7) changes the OPEN/CLOSE
replaced with a straight coupling rod, and other parts associated with drawout
interlocking are eliminated. indicator (58.0) over to CLOSED. Lever
(63.5) charges the opening spring (64.0)
during closing, and the circuit breaker is
When the charging mechanism is actuated latched in the closed position by lever (64.3)
by hand with a hand crank (refer to Figures with pawl roller (64.3.1) and by pawl (64.2).
12 and 13) or by a motor (50.4), the flange Lever (63.1) actuates the auxiliary switch
(50.3) turns until the driver (50.3.1) locates (68.0) through the linkage (68.1).
itself in the cutaway part of the cam disc
The crank (62.2) on the charging shaft
(62.3), thus causing the charging shaft to
(62.1) moves the linkage (55.1) by acting
follow. The crank (62.2) charges the closing
on the control lever (55.2). The closing
spring (62.0). When the closing spring has
spring charged indication is thus canceled,
been fully charged, the crank actuates the
and the limit switches (50.4.1) switch in the
linkage (55.1) via the control lever (55.2)
control supply to cause the closing spring to
for the closing spring CHARGED indicator
recharge immediately.
(55.0), and actuates the limit switches
(50.4.1) for interrupting the motor supply. Trip-free operation
At the same time, the lever (62.5) at the (refer to Figures 5 and 6)
other end of the charging shaft is securely Trip-free for all drawout circuit breakers
locked by the close latch pawl (62.5.2). and some fixed-mounted circuit breakers
When the closing spring is being charged, The trip coupling rod (62.8 together with
the cam disc (62.3) follows along, and it is 62.8.1 and 62.8.2) permits the immediate
brought into position for closing when the de-coupling of the drive lever (62.6) and the
closing spring is fully charged. jack shaft (63.0) to override closing action
by trip command or by means of the racking
interlocks.
The trip-free coupling rod (62.8) forms a
link between the drive lever (62.6) and the
jack shaft (63.0). The rigidity of this link
depends upon a spring-return latch (62.8.1)
carried within the coupling rod. The latch
pivots within the coupling rod and is
normally positioned to maintain the rigidity
of the coupling rod.
16
3AH3 & 3AHc Vacuum Circuit Breaker Operator Modules | Instruction Manual
17
3AH3 & 3AHc Vacuum Circuit Breaker Operator Modules | Instruction Manual
Figure 7: Operating mechanism section diagram (drawout trip-free linkage shown) mechanism OPEN, closing spring DISCHARGED
Item Description
48.0 Insulating coupler
50.3 Charging flange
50.3.1 Driver
53.0 Close pushbutton
62.5.1†
62.5 53.1 Close coil 52SRC
62.1 54.0 Open pushbutton
62.3† 50.3
54.1 Trip coil 52T
62.2†
50.3.1 62.1 Charging shaft
62.2 Crank
62.5.2†
53.0 62.2.2 Closing-spring mounting
62.3 Cam disc
62.5 Lever
62.5.1 Pawl roller
64.5* 62.6
53.1 62.2.2 62.5.2 Close latch pawl
Footnotes:
* Items moved from position shown in Figure 9: Operating mechanism section diagram (drawout trip-free linkage shown) mechanism
CLOSED, closing spring DISCHARGED on trip operation.
† Items moved from position shown in Figure 8: Operating mechanism section diagram (drawout trip-free linkage shown) mechanism OPEN,
closing spring DISCHARGED on closed spring discharge operation.
1.
For type SDV6 and some fixed-mounted circuit breakers, trip-free coupling rod (62.8) is replaced with a straight coupling rod, and other parts
associated with drawout interlocking are eliminated.
18
3AH3 & 3AHc Vacuum Circuit Breaker Operator Modules | Instruction Manual
Figure 8: Operating mechanism section diagram (drawout trip-free linkage shown) mechanism OPEN, closing spring DISCHARGED
.
Item Description
48.0 Insulating coupler
50.3 Charging flange
50.3.1 Driver
53.0 Close pushbutton
53.1 Close coil 52SRC
54.0 Open pushbutton 62.2†
50.3.1†
54.1 Trip coil 52T
62.1† 62.3†
62.1 Charging shaft 50.3†
Footnotes:
* Items moved from position shown in Figure 10: Operating mechanism section diagram (drawout trip-free linkage shown) mechanism
CLOSED, closing spring CHARGED on trip operation.
† Items moved from position shown in Figure 7: Operating mechanism section diagram (drawout trip-free linkage shown) mechanism
OPEN, closing spring DISCHARGED on closed spring discharge operation.
1.
For type SDV6 and some fixed-mounted circuit breakers, trip-free coupling rod (62.8) is replaced with a straight coupling rod, and other parts
associated with drawout interlocking are eliminated.
19
3AH3 & 3AHc Vacuum Circuit Breaker Operator Modules | Instruction Manual
Figure 9: Operating mechanism section diagram (drawout trip-free linkage shown) mechanism CLOSED, closing spring DISCHARGED
Item Description
48.0 Insulating coupler
53.0 Close pushbutton
53.1 Close coil 52SRC
62.1 Charging shaft
62.2 Crank
62.2.2 Closing-spring mounting
62.3 Cam disc
62.5 Lever
62.5.1
62.5.1 Pawl roller
62.5 62.5.2 Close latch pawl
62.1 62.6 Driver lever
62.8
64.5
63.7
63.5
63.1
63.0
48.0
63.5
Footnotes:
* Numbered items moved from position shown in Figure 8: Operating mechanism section diagram (drawout trip-free linkage shown)
mechanism OPEN, closing spring DISCHARGED.
1.
For type SDV6 and some fixed-mounted circuit breakers, trip-free coupling rod (62.8) is replaced with a straight coupling rod, and other parts
associated with drawout interlocking are eliminated.
20
3AH3 & 3AHc Vacuum Circuit Breaker Operator Modules | Instruction Manual
Figure 10: Operating mechanism section diagram (drawout trip-free linkage shown) mechanism CLOSED, closing spring CHARGED
Item Description
50.3 Charging flange
50.3.1 Driver
62.1 Charging shaft
62.2 Crank
62.2.2 Closing-spring mounting
62.3 Cam disc
62.5 Lever
62.5.1 Pawl roller
62.2
50.3.1
62.3
62.1
62.5 50.3
62.5.1
62.2.2
Footnotes:
* Numbered items moved from position shown in Figure 9: Operating mechanism section diagram (drawout trip-free linkage shown)
mechanism CLOSED, closing spring DISCHARGED.
1.
For type SDV6 and some fixed-mounted circuit breakers, trip-free coupling rod (62.8) is replaced with a straight coupling rod, and other parts
associated with drawout interlocking are eliminated.
21
3AH3 & 3AHc Vacuum Circuit Breaker Operator Modules | Instruction Manual
Closing Closed
voltage applied. Anti-pumping feature (52Y) assures a continuously applied closing command does not cause
the circuit breaker to reclose automatically after it has tripped out on a fault.
Closing spring is
fully charged.
Close coil (52SRC)
unlatches the closing
LS21 and LS22 LS9 closes close
L3 opens in series LS41 closes to spring and the circuit
operate to circuit only when
with anti-pump signal closing spring breaker closes.
de-energize spring- closing spring is
relay (52Y). is charged.
charging motor. fully charged.
Motor cutoff switches
LS21, LS22 and LS3 are
Circuit Circuit closed because the
breaker breaker closing spring is
No action! Open is closed. Close coil is
is open. discharged.
52b in series with Closing actuated through
close coil (52SRC) command the closed 52b
blocks closing when contacts and the Before the spring-
spring-release. two normally closed charge motor has
Closing contacts of the anti- recharged the closing
spring is pump relay (52Y). spring and opened LS3,
not charged. anti-pump relay (52Y)
No action! Anti- picks up and seals in.
pump relay (52Y)
The closing spring is The opening spring
picks up through
unlatched. is charged. The anti-pump relay
the closed LS3
contact and opens. (52Y) opens two
contacts in series with
LS21 and LS22 close the close coil (52SRC).
52a contacts in
Circuit breaker to energize motor
series with the trip
auxiliary contacts The circuit breaker (88). LS3 closes and
coil (52T) close to
52a and 52b change closes. LS9 opens to cancel The close coil (52SRC)
enable a trip
state. closing spring is now blocked and
operation.
signal. cannot be activated
until springs are fully-
Rapid auto-reclosing. The closing spring is automatically recharged as described above. charged and close
Therefore, when the circuit breaker is closed both of its springs are charged. The closing command is removed.
spring charges the opening spring during closing. As a result, the circuit breaker is capable of
an O-0.3s-CO-3 min-CO operating cycle. The dashed line shows the operating sequence
Footnote:
initiated by the closing command. 1.
Optional items.
Tripping
Trip
command.
22
3AH3 & 3AHc Vacuum Circuit Breaker Operator Modules | Instruction Manual
50.5
50.6
50.0
Item Description
50.0 Hand crank
50.5 Manual spring-charging port
50.6 Over-running coupling
23
3AH3 & 3AHc Vacuum Circuit Breaker Operator Modules | Instruction Manual
(+)
01
01 T
C
SD16 SD13
W 21 G R
LS21 41
22 52b
42
SD3 SD4 SD1
22 21 14
Motor 88 52Y LS3 52Y
21 22 13
13 31 24
LS41 31 52b 52a
DC supply 14 52Y 32 23
21 32
LS22
22 A1 A1 A1
52SRC 52Y 52T
22 22 A2 A2 SD14 A2
MI1 MI2 34
21 21 13 LS9
52a
33
TB 14
1 SD2
2
3
4
5
SD15 6
(-)
Standard:
Fuses in close circuit. Slugs in trip circuit (fuses optional).
Shown with springs discharged, trip-latch reset, circuit breaker open, connect or withdrawn position.
24
3AH3 & 3AHc Vacuum Circuit Breaker Operator Modules | Instruction Manual
Indirect releases - secondary shunt Figure 15: Construction of secondary shunt release (shown charged)
release (dual trip) (52T1) or undervoltage
(27.0)
The indirect release provides for the
conversion of modest control signals into
33.0
powerful mechanical-energy impulses. It is 23.0
primarily used to open medium-voltage 31.0
25.0 27.0
circuit breakers while functioning as a 21.0
secondary shunt-release (dual trip) or 11.0
13.0 7.0
undervoltage device.
9.0 1.0
These releases are mechanical energy- 15.0
storage devices. Their internal springs are
charged as a consequence of the circuit
6.0
breaker mechanism operation. This energy
is released upon application or removal (as 3.0
appropriate) of applicable control voltages
(refer to Figures 15, 16 and 17).
Item Description Item Description
The secondary shunt-release and 1.0 Magnet core 15.0 Tripping pin
undervoltage release mounts to the
3.0 Housing 21.0 Locking pin
immediate right of the trip coil (54.1).
6.0 Mounting holes 23.0 Striker pin
Secondary shunt-release (52T1) (refer to 7.0 Magnet coil 25.0 Latch
Figure 15)
9.0 Magnet armature 27.0 Spring
A secondary shunt-release (extra-trip coil)
(3AX1101) is used for electrical opening of 11.0 Tension spring 31.0 Striker-pin spring
the circuit breaker by protective relays or 13.0 Adjusting screw (factory set) for 11.0 33.0 Terminal block
manual control devices when more than
one trip coil is required. The second trip coil
Figure 16: Latch details (shown charged)
is generally connected to a separate
auxiliary supply (dc or ac) from the control
supply used for the normal trip coil.
Undervoltage release (27.0) (refer to
Figures 16 and 17) 29.0
The undervoltage release (3AX1103) is used
for continuous monitoring of the tripping
supply voltage. If this supply voltage falls
excessively, the undervoltage release will 23.0
provide for automatic tripping of the circuit
breaker.
The undervoltage device may be used for
manual or relay tripping by employing a 25.0 27.0
contact in series with undervoltage device
holding coil. Relay tripping may also be
achieved by employing a normally open 21.0
contact in parallel with the holding coil. If
this scheme is used, a resistor must be
provided to limit current when the normally
open contact is closed.
Secondary shunt and undervoltage releases Item Description Item Description
are available for all standard ANSI/IEEE 21.0 Locking pin 25.0 Latch
control voltages. 23.0 Striker pin Undervoltage enable/disable set-
29.0
25.0 Latch ting screw (undervoltage only)
25
3AH3 & 3AHc Vacuum Circuit Breaker Operator Modules | Instruction Manual
26
3AH3 & 3AHc Vacuum Circuit Breaker Operator Modules | Instruction Manual
27
3AH3 & 3AHc Vacuum Circuit Breaker Operator Modules | Instruction Manual
Maintenance
28
3AH3 & 3AHc Vacuum Circuit Breaker Operator Modules | Instruction Manual
Failure to maintain the equipment can result in death, serious injury, property damage or product
failure, and can prevent successful functioning of connected apparatus.
The instructions contained herein should be carefully reviewed, understood and followed.
29
3AH3 & 3AHc Vacuum Circuit Breaker Operator Modules | Instruction Manual
The use of unauthorized parts in the repair of the equipment, or tampering by unqualified personnel
can result in hazardous conditions, that can result in death, serious injury or property damage.
30
3AH3 & 3AHc Vacuum Circuit Breaker Operator Modules | Instruction Manual
31
3AH3 & 3AHc Vacuum Circuit Breaker Operator Modules | Instruction Manual
32
3AH3 & 3AHc Vacuum Circuit Breaker Operator Modules | Instruction Manual
Stay clear of circuit breaker components that are subject to sudden, high-
speed movement.
Figure 21: Contact-erosion check mark dot circled in The contact-erosion check procedure is:
orange (shown with circuit breaker OPEN)
a) Be sure the circuit breaker primary
contacts are CLOSED.
b) Observe the white contact-erosion
mark (refer to Figure 20) of each pole.
When any part of the white contact-
erosion mark is visible, contact wear
is within acceptable limits.
4. Press the red Open pushbutton after
completing the contact-erosion check.
Visually verify the Discharged condition
of the closing spring and that the circuit
breaker contacts are OPEN.
5. Press the black Close pushbutton.
Nothing should happen. The manual-
spring check should demonstrate
smooth operation of the operating
mechanism.
Electrical control checks
The electrical controls of the circuit breaker
should be checked during inspections to
verify absence of any mechanical damage,
and proper operation of the automatic
spring-charging and Close and Trip circuits.
Unless otherwise noted, all of these tests
are performed without any control power
applied to the circuit breaker.
33
3AH3 & 3AHc Vacuum Circuit Breaker Operator Modules | Instruction Manual
Check of the wiring and terminals Electrical close and trip check (control
1. Physically check all of the circuit breaker power required)
wiring for evidence of abrasion, cuts, A check of the circuit breaker control circuits
burning or mechanical damage. shall be performed. This check is made with
the circuit breaker energized by control
2. Check all terminals to be certain they are
power either from the switchgear or an
solidly attached to their respective
external control-power source.
device.
1. Once the circuit breaker springs are
Automatic spring-charging check (control
charged, move the switchgear-mounted
power required)
Close/Trip switch to the Close position.
Repeat the automatic spring-charging check
Verify by both the sound of the circuit
described in the section describing the
breaker closing and by the main contact
installation check and initial functional tests
status indicator that the circuit breaker
(refer to pages 9-10).
contacts are CLOSED.
Primary tasks of this check are:
2. As soon as the circuit breaker has closed,
1. The circuit breaker must be energized the automatic spring-charging process is
with control power for this check. repeated.
2. Energize the control-power source. 3. After a satisfactory close operation is
verified, move the switchgear-mounted
3. When control power is connected to the
Close/Trip switch to the Trip position.
circuit breaker, the closing spring should
Verify by both the sound of the circuit
automatically charge. Visually verify that
breaker opening and by the main
the closing spring is charged.
contact status indicator that the circuit
Note: A temporary source of control power breaker contacts are OPEN.
and test leads may be required if the
4. After a satisfactory open operation is
control-power source has not been
verified, hold the circuit breaker manual
connected to the switchgear or circuit
Trip button and apply and maintain an
breaker. When control power is connected
electrical close signal. The circuit breaker
to the circuit breaker, the closing spring
should close, immediately trip, the close
should automatically charge.
spring should charge, and the circuit
breaker should not attempt to close
again.
Completion of these checks demonstrates
satisfactory operation of auxiliary switches,
internal relays and open and close coils.
34
3AH3 & 3AHc Vacuum Circuit Breaker Operator Modules | Instruction Manual
Footnote:
1.
Maximum symmetrical interrupting current rating of circuit breaker (refer to Tables 11 and 12).
35
3AH3 & 3AHc Vacuum Circuit Breaker Operator Modules | Instruction Manual
100,000
50,000
20,000
10,000
5,000
2,000
1,000
500
200
100
50
20
C A E
10
1 2 5 10 20 25 31.5 40 50 100
36
3AH3 & 3AHc Vacuum Circuit Breaker Operator Modules | Instruction Manual
100,000
50,000
20,000
10,000
5,000
2,000
1,000
500
200
100
50
20
D BF
10
1 2 5 10 20 40 50 63 100
37
3AH3 & 3AHc Vacuum Circuit Breaker Operator Modules | Instruction Manual
38
3AH3 & 3AHc Vacuum Circuit Breaker Operator Modules | Instruction Manual
Keep personnel more than six feet away from a circuit breaker under test.
39
3AH3 & 3AHc Vacuum Circuit Breaker Operator Modules | Instruction Manual
40
3AH3 & 3AHc Vacuum Circuit Breaker Operator Modules | Instruction Manual
Insulation and contact-resistance test Inspection and cleaning of circuit breaker Table 5: Maximum contact-resistance
procedure insulation
1. Observe safety precaution listed in the 1. Perform the spring-discharge check Contact
Current rating
resistance
danger and warning advisories for the (refer to page 9) on the circuit breaker A
Micro-Ohms
vacuum integrity check tests (refer to after all control power is removed. The
pages 38-39). spring-discharge check consists of: 1,200 35
2. Close the circuit breaker. Ground the a) Pressing the red Open pushbutton 2,000 30
frame of the circuit breaker, and ground
b) Pressing the black Close pushbutton 3,000 30
each pole not under test. Use manual
charging, closing and tripping c) Pressing again the red Open
procedures. pushbutton.
3. Apply the proper ac or dc (refer to Table All of these controls are on the circuit
4) high-potential test voltage between a breaker front panel (refer to Figure 1).
primary conductor of the pole and Visually verify the Discharged condition
ground for one minute. of the springs.
4. If no disruptive discharge occurs, the 2. Remove any inter-phase and outer-phase
insulation system is satisfactory. barriers if furnished (applicable for
certain types only).
5. After test, ground both ends and the
middle of each vacuum interrupter to 3. Clean barriers and post insulators using
dissipate any static charge. clean cloth dipped in isopropyl alcohol.
6. For drawout applications, connect all 4. Replace all barriers. Check all visible
points of the secondary disconnect with fasteners again for condition and
a shorting wire. For stationary tightness.
applications, disconnect secondary
Note: Do not use any cleaning compounds
circuits for the operating mechanism by
containing chlorinated hydrocarbons, such
disconnecting the multiple pin-plug at
as: trichlorethylene, perchlorethylene or
the upper right corner of the operator,
carbon tetrachloride.
and connect all pins on the operator side
with a shorting wire. Connect the These compounds will damage the
shorting wire to the high-potential lead phenylene ether copolymer material used in
of the high-voltage tester, and ground the barriers and other insulation on the
the circuit breaker housing. Starting circuit breaker.
with zero voltage, gradually increase the
Functional tests
test voltage to 1,500 volts rms, 60 Hz.
Refer to the installation checklist in the
Maintain test voltage for one minute.
installation checks and initial functional
Alternatively, the test may be conducted
tests section of this instruction manual
at 1,800 volts rms for one second.
(refer to pages 9-10). Functional tests
7. If no disruptive discharge occurs, the consist of performing at least three manual
secondary control insulation level is spring-charging checks and three automatic
satisfactory. spring-charging checks. After these tests are
complete, and the springs are fully
8. Disconnect the shorting wire, and
discharged, all fasteners and connections
reattach the multiple pin-plug (if
are checked again for tightness and
applicable).
condition.
9. Perform contact-resistance tests of the
primary contacts. The resistance should
be read between the lower and upper
connection pads (refer to Figure 22).
Contact resistance should not exceed
the values listed in Table 5.
41
3AH3 & 3AHc Vacuum Circuit Breaker Operator Modules | Instruction Manual
Overhaul
Table 6: Overhaul schedule Introduction b) Remove two M4 hex-head screws and
The following procedures along with the remove solenoid.
Circuit Closing troubleshooting charts in this instruction
breaker type operations
c) Install replacement coils with new M4
manual (refer to pages 47-51), provide
x 10 hex-head screws (Siemens part #
maintenance personnel with a guide to
10,000 00-000-443-820) and new lock
SDV6 identifying and correcting possible
operations washers for M4 (Siemens part #
malfunctions of the circuit breaker.
10,000 00-000-288-316).
All others
operations Circuit breaker overhaul
d) The coil-mounting screws must be
Table 6 gives the recommended overhaul
installed using thread locking
schedule type 3AH operating mechanisms.
adhesive (Loctite #222, Siemens part
These intervals assume that the circuit
15-133-281-007) and primer (Loctite
breaker is operated under “usual service
primer T (#7471), Siemens part
conditions” as discussed in ANSI/IEEE
15-133-281-005).
C37.20.2 (for drawout circuit breakers) or
ANSI/IEEE C37.04 and elaborated in ANSI/ e) Connect wires to coils with new wire
IEEE C37.010 (for outdoor distribution terminals (Siemens part #
circuit breakers). If the circuit breaker is 15-171-600-002).
operated frequently, the overhaul interval in
3. Motor interlock
Table 6 may coincide with the maintenance
interval in Table 2. a) Remove wire connections
Replacement at overhaul b) Remove two 6-32 x 1.00 screws and
The following components are replaced dismount switch
during an overhaul of the circuit breaker,
c) Install replacement MI switch with
when required:
new 6-32 x 1.00 screws (Siemens part #
Vacuum interrupters as determined by 00-615-471-132), new lockwasher
vacuum integrity test, contact erosion or (Siemens part # 00-655-007-059)
according to overhaul schedule (refer to
d) Apply a thread locking adhesive to
Table 6)
screws using locking adhesive (see
Close coil, 52SRC above)
Trip coil, 52T e) Reconnect wires.
Trip-free drive bar mechanism (if 4. Lubricate operating mechanism
applicable) according to maintenance and lubrication
information (refer to page 32).
Motor interlock (MI) (if applicable).
5. When work is finished, operate circuit
When these parts are changed, locking
breaker and close and open several
devices must also be removed and replaced.
times, and check that all screw
These include lock washers, retaining rings,
connections are tight.
retaining clips, spring pins, cotter pins, etc.
Replacement of vacuum interrupters
1. Replace vacuum interrupter; instructions
It is recommended that vacuum interrupters
follow.
be replaced only by a qualified Siemens field
2. Close coil (52SRC) and trip coil (52T). service representative. The information in
the following sections is provided to aid in
a) Remove two “push on” terminal
understanding the replacement procedures.
connections
42
3AH3 & 3AHc Vacuum Circuit Breaker Operator Modules | Instruction Manual
Vacuum interrupters for type 3AH rated 1.1 Before starting work, the circuit
63 kA interrupting or rated 3,000 A breaker should be isolated from all
continuous current and all type 3AHc primary and control-power sources and
operators require special expertise for all stored energy discharged by
replacement and must be replaced only by a opening, closing and opening the
qualified Siemens field service circuit breaker by hand. Discharge any
representative. Accordingly, detailed static charge by grounding both ends
instructions for replacement vacuum and the middle of each vacuum
interrupters for these ratings are not interrupter. Carefully remove outer-
provided in this instruction manual. phase and inter-phase barriers.
Replacement vacuum interrupters are 1.2 Loosen the lateral bolt(s) on terminal
furnished as a complete assembly. They clamp (29.2). Employ the illustrated
have been completely tested and procedure to loosen clamp hardware
dielectrically and mechanically conditioned. (refer to Figure 25).
It is recommended that one vacuum 1.3 Withdraw pin (48.5) from insulating
interrupter be removed and replaced coupler (48.0) and levers (48.6).
completely rather than removing two or
1.4 Remove coupling pin from the eye bolt
more vacuum interrupters at a time.
(36.3).
The following procedure in check list format
1.5 Free struts (28.0) from the pole head
describes the procedure for removing and
(20.0). Loosen the strut hardware on
replacing a vacuum interrupter. Components
the pole bottom (40.0) and swing the
may be identified by reference to Figures 23
struts forward and downward.
and 24.
1.6 Loosen screws fastening the centering
Instructions herein apply for replacement of
ring (28.1).
all vacuum interrupters except type
VS-17085 vacuum interrupters, and 1.7 Remove bolt (31.2), lock washer and
interrupters on 3,000 A circuit breakers large washer at the stationary contact
having the flexible connector (refer to 29.1 of the vacuum interrupter (18 mm or
in Figure 23) electron-beam welded to the 24 mm socket with extension).
moving terminal (refer to 36.1 in Figure 23)
1.8 Using a 24 mm socket with an
of the vacuum interrupter. These
extension, loosen and remove hex-cap
interrupters must be replaced by factory-
screw fastening the pole head to the
trained personnel. Contact Siemens medium-
post insulator. Completely remove the
voltage customer service at 1-800- 333-
pole head and set aside.
7421 or 1-423-262-5700 outside the U.S.
1.9 Grasp the vacuum interrupter (30.0)
1. Removing the vacuum interrupter
and withdraw vertically. Assistance
may be required to work the terminal
Note: Special care needs to be exercised in clamp off the movable stem of the
removal or installation of hardware around vacuum interrupter. DO NOT USE
the bottom, or movable contact end, of the UNDUE FORCE OR TWISTING
vacuum interrupter. MOTION. If the terminal clamp (29.2)
cannot be easily removed, STOP!, check
The movable contact uses a metal bellows
to be certain hardware is loose, and
to maintain the vacuum seal while still
that the terminal clamp (29.2) is not
permitting up and down motion of the
binding.
contact. The bellows is rugged and reliable,
and is designed to withstand years of 2. Installing a vacuum interrupter
vertical movement. However, care should be
Note: Replacement vacuum interrupter
exercised to avoid subjecting the bellows to
(30.0) will be received from the factory with
excessive torque during removal and
an eye bolt (36.3) in place, adjusted and
replacement. Twisting the bellows through
torqued to specific requirements. DO NOT
careless bolt removal or tightening may
ALTER THE ADAPTER (EYE-BOLT)SETTING.
damage the vacuum interrupter, resulting in
loss of vacuum integrity.
43
3AH3 & 3AHc Vacuum Circuit Breaker Operator Modules | Instruction Manual
Item Description
20.0 Upper pole-support (pole head)
28.0 Strut
28.1 Centering ring
20.0
29.1 Flexible connector
31.2
29.2 Terminal clamp
29.3 Spacer (or shoulder)
30.0 Vacuum interrupter
31.2 Upper terminal bolt
36.1 Moving terminal
36.3 Eye bolt (or adapter)
40.0 Lower pole-support
48.0 Insulating coupler
48.5 Pin
28.0
48.6 Angled lever
48.9 Drive link
30.0
28.1
29.3
36.1
29.1 29.2
36.3
48.0
40.0 48.9
48.6
48.5
44
3AH3 & 3AHc Vacuum Circuit Breaker Operator Modules | Instruction Manual
Figure 25: Illustration showing required technique for fastening terminal-clamp hardware
Item Description
A Moving contact (36.1)
B Spacer (shoulder) (29.3)
C Torque wrench
D Direction of force (P)
E Terminal clamp (29.2)
F Holding wrench
G
G Vacuum interrupter
F
A
B
2.1 Inspect all silver-plated connection 2.6 Couple levers (48.6) and drive link
surfaces for cleanliness. Clean only (48.9) to the eye bolt (36.3), using the
with a cloth and solvent. Do not pin supplied. Apply retaining clips.
abrade, as this will damage the silver Appropriate pin is modestly chamfered,
plating. not to be confused with pin for the
insulating coupler.
2.2 Insert vacuum interrupter (30.0) into
the lower pole-support (40.0). Slip 2.7 Raise the terminal clamp (29.2) against
terminal clamp (29.2) into position on the step or the spacer (if applicable) of
the movable stem. the moving contact (36.1) of the
vacuum interrupter (30.0) so that the
2.3 Align vacuum interrupter and fasten
radius of the movable contact faces the
“finger tight” using heavy flat washer,
connecting surface of the flexible
lock washer and bolt (31.2).
connector (29.1). Employ technique
2.4 Fasten the pole head to the post illustrated to fasten terminal clamp
insulator (16.1) “finger tight” using (refer to Figure 25). Note opposing
hex-head bolt, lock washer and flat wrenches. Tighten the bolt(s) of the
washer. terminal clamp to a torque of 40 Nm
(30 ft-lb), taking care to see that the
2.5 Attach struts (28.0) to the upper pole-
terminal of the vacuum interrupter is
support (20.0), replace hardware
not subjected to excessive bending
(M10), but do not tighten at this time.
movement.
45
3AH3 & 3AHc Vacuum Circuit Breaker Operator Modules | Instruction Manual
Note: Excessive bending movement exerted 3.4 Connect the insulating coupler (48.0)
while fastening the terminal clamp will using pin (48.5) and the retaining clips
damage the vacuum interrupter. provided.
2.8 Align pole head (20.0) correctly and 3.5 Repeat the measurement described in
tighten bolt fastening it to the post step 3.3 again with care to maximize
insulator. Torque M16 bolt to 130 Nm accuracy. Record your result.
(96 ft-lb). Fasten securely all bolts
3.6 Determine difference between the
associated with struts (28.0).
measurements made under steps 3.3
2.9 Tighten vacuum interrupter fastening and 3.5. Your results should be per
bolt (31.2) on the pole head (20.0) Table 7.
holding the vacuum interrupter firmly
3.7 If you fail to achieve the listed results,
by its upper insulator and operate
carefully repeat the entire procedure
levers (48.6), by hand, to see whether
making certain of your measurements.
the movable contact moves freely. If
any binding or lack of freedom is 3.8 Loosen eye bolt locking nut on
noted, loosen bolt (31.2) and adjust insulating coupler (48.0), and retain
the vacuum interrupter in pole head by position of the eye. Make adjustments
turning and moving it slightly. Torque in one-half turn increments. After
M12 bolt to 60 Nm (44 ft-lb) and M16 adjustment is completed, tighten eye
bolt to 130 Nm (96 ft-lb). bolt locking nut to 26-34 ft-lb. (35-45
Nm).
2.10 The centering ring (28.1) has been
loose and “floating” during installation 4. After eye bolt is tightened to proper
of the vacuum interrupter. Check that torque, repeat all measurement
the movable contact is free to move procedures, making certain they are in
vertically without binding, and then agreement with values indicated in
tighten the hardware which secures step 3.6.
the centering ring. Recheck that the
5. Complete all other maintenance
movable contact is free to move
procedures. Completely reassembled
vertically without binding.
circuit breaker should pass the high-
2.11 Attach insulating coupler (48.0) and potential test before it is ready for
lever (48.6) together, using pin (48.5). service.
Apply retaining clips. Correct pin has
Hydraulic shock absorber
ends that have been generously
The mechanism is equipped with a hydraulic
chamfered.
shock-absorber that functions when the
2.12 Open and close circuit breaker several circuit breaker opens (refer to item 61.8 in
times and then check to see that all Figure 6). The shock absorber should require
bolted joints and devices are tight. no adjustment. However, at maintenance
checks, the shock absorber should be
3. Checking the contact stroke
examined for evidence of leaking. If
3.1 Open the circuit breaker. evidence of fluid leakage is found, the shock
absorber must be replaced to prevent
3.2 Free insulating coupler (48.0) by
damage to the vacuum interrupter bellows.
removing pin (48.5). The vacuum
interrupter contacts must now close
automatically as a consequence of
atmospheric pressure.
3.3 Observe the terminal clamp (29.2)
through the openings on each side of
the pole bottom (40.0). Using vernier
calipers, measure the distance from the
bottom surface of the terminal clamp
to the bottom edge of the cutout
opening. Measure carefully and record
your result.
46
3AH3 & 3AHc Vacuum Circuit Breaker Operator Modules | Instruction Manual
47
3AH3 & 3AHc Vacuum Circuit Breaker Operator Modules | Instruction Manual
Table 8: Troubleshooting
Circuit breaker fails to close. 2. No closing signal to secondary disconnect pin A2.
Check for continuity and correct protective relay
logic.
48
3AH3 & 3AHc Vacuum Circuit Breaker Operator Modules | Instruction Manual
49
3AH3 & 3AHc Vacuum Circuit Breaker Operator Modules | Instruction Manual
Footnotes:
1.
Current at nominal voltage
2.
Capacitor trip
3.
Value preceding slash (/) is the current for the standard trip coil with standard rating interrupting time. Value
following (/) is current for optional trip coil with three-cycle interrupting time.
4. --------------
means this selection is not available at this voltage.
Non-
10 10 5 10/301 9.6 4.8
inductive
Inductive 10 6 3 10 6 3
Footnotes:
1.
Two contacts in series.
2.
All switches are non-convertible.
50
3AH3 & 3AHc Vacuum Circuit Breaker Operator Modules | Instruction Manual
Table 11: Type 3AH vacuum circuit breaker ratings ("constant kA" ratings basis)
Maximum
Withstand voltage Continuous Short-circuit
These ratings are in
design accordance with:
Voltage levels current7 (I)3,4
voltage (V)1
Circuit breaker range ANSI/IEEE C37.04
type factor Lightning
Power Standard for Ratings and
(K)2 impulse
kV rms frequency A rms kA rms sym Requirements for AC High-
(BIL)
kV rms
kV crest Voltage Circuit Breakers
with Rated Maximum
5-3AH-31.5 4.76 1.0 19 60 1,200, 2,000 31.5
Voltages above 1000 V
1,200, 2,000, ANSI/IEEE C37.09
5-3AH-40 4.76 1.0 19 60 40
3,000 Standard Test Procedure
5-3AH-50 4.76 1.0 19 60
1,200, 2,000,
50
for AC High-Voltage Circuit
3,000 Breakers with Rated
1,200, 2,000, Maximum Voltage above
5-3AH-63 4.76 1.0 19 60 63
3,000 1000 V
1,200, 2,000,
7-3AH-40 8.25 1.0 36 95 40 ANSI/IEEE C37.010
3,000
Guide for AC High-Voltage
15-3AH-20 15.0 1.0 36 95 1,200, 2,000 20 Circuit Breakers > 1000 Vac
Rated on a Symmetrical
15-3AH-25 15.0 1.0 36 95 1,200, 2,000 25 Current Basis.
1,200, 2,000,
38-3AH-31.5 38.0 1.0 80 150/2006 31.5
3,000
1,200, 2,000,
38-3AH-40 38.0 1.0 80 150/2006 40
3,000
51
3AH3 & 3AHc Vacuum Circuit Breaker Operator Modules | Instruction Manual
Table 11: Type 3AH vacuum circuit breaker ratings (new "constant kA" ratings basis) (continued)
Permissible
Interrupting Max. sym. % dc Short-time
tripping delay Closing and latching (momentary)
time5 interrupting (I) component current (I) (3 s)
Circuit breaker (y)
type Asymmetrical Peak
ms/cycles s kA rms sym % kA rms (1.55 x I) (2.6 x I)
kA rms kA peak
15-3AH-20 83/5 2 20 47 20 31 52
15-3AH-25 83/5 2 25 47 25 39 65
15.5-3AH-20 83/5 2 20 47 20 31 52
15.5-3AH-25 83/5 2 25 47 25 39 65
27-3AH-20 83/5 2 20 47 20 31 52
27-3AH-25 83/5 2 25 47 25 39 65
38-3AH-20 83/5 2 20 47 20 31 52
38-3AH-25 83/5 2 25 47 25 39 65
52
3AH3 & 3AHc Vacuum Circuit Breaker Operator Modules | Instruction Manual
Table 12:Type 3AH vacuum circuit breaker ratings (historic "constant MVA" ratings basis)
Nominal
These ratings are in
Maximum Voltage accordance with:
Nominal three-
design Continuous range Withstand voltage
voltage phase
voltage current11 factor levels ANSI/IEEE C37.04-1979
class MVA
Circuit class7
(V)1 (K)2 Standard Rating Structure
breaker type for AC High-Voltage Circuit
Lightning Breakers Rated on a
Power
kV MVA kV rms A rms ---- frequency
impulse Symmetrical Current Basis
(BIL)
kV rms ANSI C37.06-1987
kV crest
AC High-Voltage Circuit
5-3AH-250,
4.16 250 4.76 1,200, 2,000 1.24 19 60 Breakers Rated on a
5-3AHc-250 Symmetrical Current Basis -
Preferred Ratings and
5-3AH-350, 1,200, Related Required
4.16 350 4.76 1.19 19 60
5-3AHc-350 2,000, 3,000 Capabilities
ANSI/IEEE C37.09-1979
1,200, Standard Test Procedure for
7-3AH-500 7.2 500 8.25 1.25 36 95
2,000, 3,000
AC High-Voltage Circuit
Breakers Rated on a
1,200, Symmetrical Current Basis
15-3AH-500 13.8 500 15.0 1.30 36 95
2,000, 3,000
ANSI/IEEE C37.010-1979
Application Guide for AC
1,200,
15-3AH-750 13.8 750 15.0
2,000, 3,000
1.30 36 95 High-Voltage Circuit
Breakers Rated on a
Symmetrical Current Basis.
1,200,
15-3AH-1000 13.8 1000 15.0 1.30 36 95
2,000, 3,000
Footnotes: 4.
Within the limitations stated in 10.
High close and latch
1.
Maximum design voltage for which the circuit ANSI/IEEE C37.04-1979, all values apply to (momentary) rating available for
breaker is designed and the upper limit for polyphase and line-to-line faults. For single special application.
operation. phase-to-ground faults, the specific conditions 11.
Continuous current may be
2.
K is the ratio of the rated maximum design stated in clause 5.10.2.3 of increased by the use of forced-
voltage to the lower limit of the range of ANSI/IEEE C37.04-1979 apply. cooling (fan-cooling) in the
operating voltage in which the required 5.
Current values in this row are not to be exceeded switchgear, together with
symmetrical and asymmetrical interrupting even for operating voltage below 1/K times rated increased bus bar capacity.
capabilities vary in inverse proportion to the maximum design voltage. For operating voltages
operating voltage. between rated maximum design voltage and 1/K
3.
To obtain the required symmetrical interrupting times rated maximum design voltage, follow
capability of a circuit breaker at an operating Footnote 5.
voltage between 1/K times rated maximum 6.
Current values in this row are independent of
design voltage and rated maximum design operating voltage up to and including rated
voltage, the following formula shall be used: maximum voltage.
Required symmetrical interrupting capability = 7.
"Nominal three-phase MVA class" is included for
rated short-circuit current (I) x [(rated maximum reference only. This information is not listed in
design voltage)/(operating voltage)]. For ANSI C37.06-1987.
operating voltages below 1/K times maximum 8.
Standard duty cycle is O - 15 s - CO.
design voltage, the required symmetrical 9.
Standard rating interrupting time is five-cycles
interrupting capability of the circuit breaker shall (83 ms). Optional rated interrupting time of
be equal to K times rated short-circuit current. three-cycles (50 ms) is available (except with
24 Vdc tripping).
53
3AH3 & 3AHc Vacuum Circuit Breaker Operator Modules | Instruction Manual
Table 12:Type 3AH vacuum circuit breaker ratings (historic "constant MVA" ratings basis) (continued)
Short-circuit Rated
(at rated maximum Maximum Short-time
Permissible
maximum Interrupting design symmetrical current (I) Closing and latching
tripping delay
design time9 voltage (V) interrupting (three (momentary)
(y)
Circuit breaker voltage) divided by K (K x I)5 seconds)
type (I)3, 4, 8 (= V/K)
Asymmetrical Peak
(1.6 x (2.7 x
kA rms sym ms / cycles Sec kA rms kA rms sym kA rms
K x I)6 K x I)6
kA rms kA peak
5-3AH-250,
29 83 / 5 2 3.85 36 36 58/7810 97/13210
5-3AHc-250
5-3AH-350,
41 83 / 5 2 4.0 49 49 78 132
5-3AHc-350
54
3AH3 & 3AHc Vacuum Circuit Breaker Operator Modules | Instruction Manual
Table 13: Type 3AH3 vacuum circuit breaker weight in lbs (kg) (circuit breaker operator only)2
Up to 15.5 kV ≤ 55 ms
Close time from energizing close coil at rated
Over 15.5 kV up to 27.6 kV ≤ 65 ms
control voltage to contact touch (last pole)
Over 27.6 kV up to 38 kV ≤ 70 ms
Up to 15.5 kV ≤ 56 ms
5-cycle interrupting time
Over 15.5 kV up to 27.6 kV ≤ 56 ms
(83 ms)
Over 27.6 kV up to 38 kV ≤ 56 ms
Opening time from
Up to 15.5 kV ≤ 43 ms
energization trip coil at
3.5-cycle interrupting time
rated control voltage to Over 15.5 kV up to 27.6 kV ≤ 43 ms
(58 ms)
contact part (last pole),
Over 27.6 kV up to 38 kV ≤ 43 ms
not including arcing time
Up to 15.5 kV ≤ 38 ms
3-cycle interrupting time
Over 15.5 kV up to 27.6 kV ≤ 38 ms
(50 ms)
Over 27.6 kV up to 38 kV ≤ 38 ms
55
Siemens Industry, Inc.
7000 Siemens Road
Wendell, NC 27591
www.usa.siemens.com/mvswitchgear