Analogue Panel Instruments
We offer a comprehensive range of analogue and panel
instruments for use in control and instrumentation systems.
The range includes moving-iron and moving-coil mechanisms in
a variety of formats, scales and sizes. All our panel meters are
robust, accurate and constructed from high-quality materials to
give a long service life. Ammeters, voltmeters and power
meters are available with a large range of scales and can be
further customised for special applications.
Application Features
Ÿ HV and LV switchgear panels Ÿ Range of standard front panel sizes: 48x48, 72x72 and
Ÿ Control and relay panels 96x96 mm
Ÿ Power control centre (PCC) panels Ÿ Range of scales: quadrant (90°), circular (240°) and
Ÿ Motor control centre (MCC) panels edgewise
Ÿ Test benches Ÿ Options for different mounting positions: horizontal,
Ÿ Laboratory equipment vertical or angled
Ÿ Optional protective coatings and materials for use in
tropical environments
Ÿ Ingress protection rating IP 54 across the range (option
Benefits for IP 65)
Ÿ Easy to install, with snap-in mounting Ÿ Wide temperature range: -25 °C to +50 °C
Ÿ Well proven instrument designs for high quality and Ÿ Adjustable red markers for meters with quadrant scales
reliability Ÿ Models available for AC or DC measurement
Ÿ Complete product range for a wide range of applications Ÿ Measured parameters:
Ÿ Low power consumption Ÿ Current
Ÿ No need for additional magnetic shielding Ÿ Voltage
Ÿ Frequency
Ÿ Power (active or reactive)
Ÿ Power factor
Ÿ Maximum demand (current)
Ÿ Synchronisation (pointer synchroscope, twin voltmeter or
twin frequency meter)
Analogue Panel Instruments
Technical specifications
Moving Iron Instruments: AC Ammeters and Voltmeters
Scale type Quadrant (90°)
Front panel size 48x48, 72x72 or 96x96 mm
Linearity From 20% to 100% of full range
Frequency 50 to 60 Hz (default)
Measuring ranges 13 models cover 250 mA to 60 A (plus 1 A or 5 A via current transformer)
13 models cover 6 V to 800 V (plus 100 V or 110 V via voltage transformer)
Overload capability 1.2x Un continuously, 2x Un for 5 s, 2x In continuously, 10x In for 10 s
CT-operated ammeter: 50x In for 1 s
Moving Coil Instruments: DC Ammeters and Voltmeters
Scale type Quadrant (90°), circular (240°) or edgewise (70°)
Front panel size 48x48, 72x72 or 96x96 mm (quadrant or circular scale)
48x24, 72x24 or 96x48 mm (edgewise scale)
Linearity Full range
Frequency 50 to 60 Hz (default)
Measuring ranges
Quadrant scale 30 models cover 100 µA to 25 A | 22 models cover 60 mV to 600 V
Circular scale 26 models cover 600 mA to 25 A | 22 models cover 60 mV to 600 V
Edgewise scale 23 models cover 100 µA to 1 A | 16 models cover 1 V to 600 V
Overload capability 1.2x Un continuously, 2x Un for 5 s, 2x In continuously, 10x In for 10 s
Moving Coil Instruments: AC Ammeters and Voltmeters
Scale type Quadrant (90°), circular (240°) or edgewise (70°)
Front panel size 48x48, 72x72 or 96x96 mm (quadrant or circular scale)
Linearity Full range
Frequency 50 to 60 Hz (default)
Measuring ranges
Quadrant scale 18 models cover 400 mA to 1 A (plus 1 A or 5 A via current transformer)
12 models cover 6 V to 600 V (plus 110 V via voltage transformer)
Circular scale 16 models cover 1 mA to 1 A (plus 1 A or 5 A via current transformer)
12 models cover 6 V to 600 V (plus 110 V via voltage transformer)
Overload capability 1.2x Un continuously, 2x Un for 5 s, 2x In continuously, 10 In for 10 s
Maximum Demand Ammeter with Bimetallic Movements (With or Without Moving-iron Ammeter)
Scale type Quadrant (90°)
Front panel size 48x48, 72x72 or 96x96 mm
Setting time 15/8 minutes
Frequency 15 to 100 Hz
Measuring range 25 models cover 0-6 A to 0-4.8 kA (via 1 A or 5 A current transformer)
Power Meters (Active and Reactive) and Power Factor Meters
Specifications are subject to change without prior notice
Scale type Quadrant (90°) or circular (240°)
Front panel size 96x96 mm
Frequency 40 to 65 Hz
Measuring range Input current: 1, 2, 5 or 10 A (power meters only)
Input voltage: 100, 110, 230, 400 or 500 V
Frequency Meters
Scale type Quadrant (90°)
Front panel size 72x72 or 96x96 mm
Voltage 110, 230 or 400 V
Measuring range 46-54 Hz, 56-64 Hz or 375-425 Hz