InstallationGuide MS60

The installation guide for the MS Series HMI outlines essential safety precautions, installation instructions, and specifications for proper operation. It emphasizes the importance of grounding, using qualified personnel, and adhering to environmental conditions during installation. Additionally, it provides detailed information on the product's features, wiring, and communication ports.

Uploaded by

Anand Kumar
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
86 views1 page

InstallationGuide MS60

The installation guide for the MS Series HMI outlines essential safety precautions, installation instructions, and specifications for proper operation. It emphasizes the importance of grounding, using qualified personnel, and adhering to environmental conditions during installation. Additionally, it provides detailed information on the product's features, wiring, and communication ports.

Uploaded by

Anand Kumar
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

Installation Guide

1 Safety Precautions Dismantling and Scrapping 4 Grounding 6 External and Cut-out Dimensions
– The MS Series HMI or parts thereof shall be recycled according to local regulations.
Both the installer, the owner, and the operator of this MS Series HMI must read and understand this instal- Make sure that the MS Series HMI works properly. To prevent it from radiating radio frequency noise, the
lation manual. – The following components contain substances that might be hazardous to health and the environment: MS Series HMI must be connected to earth ground.
lithium battery, electrolytic capacitor and display..
General – Without grounding, the MS Series HMI may be severely affected by excess noise. Make sure that the
– Only qualified personnel may install or operate the MS Series HMI. Note: grounding is done properly from the power connector at the rear side of the MS Series HMI. When
Indicated loss of life, severe personal injury, or substantial property damage power is connected, make sure that the wire is grounded.
– The MS Series HMI must be installed according to the installation instructions. ! will result if proper precautions are not taken.
– Use a cable of at least 2 mm2 (AWG 14) to ground the MS Series HMI. Ground resistance must be less
– The MS Series HMI is designed for stationary installation on a plane surface, where the following con-
ditions are fulfilled: than 100 Ohms (class3). Note that the ground cable must not be connected to the same ground point as
the power circuit.
• no high explosive risks
• no strong magnetic fields 2 Package Contents
• no direct sunlight 5 Power Supply and Wiring
• no large, sudden temperature changes
The MS Series HMI must use a power supply with 24 V DC and the power consumption is 20W.
• for use in Pollution Degree 2 Environment
• for use on the flat surface of a Type 1 enclosure Warning:
– Never allow fluids, metal filings or wiring debris to enter any openings in the MS Series HMI. This To avoid an electric shock, be sure to switch off the power before connecting the communica-
may cause fire or electrical shock. tion/download cable to the MS Series HMI.
– The MS Series HMI fulfills the requirements of article 4 of EMC directive 2004/108/EC.
– Storing the MS Series HMI where the temperature is lower/higher than recommended in this manual Steps to wire
can cause the LCD display liquid to congeal/become isotopic. 1. Unplug the power connector and unscrew the screws.
– The LCD display liquid contains a powerful irritant. In case of skin contact, wash immediately with MS-6 0
2. Strip about 7-8mm of insulation. Insert the wire all the way into the power connector and then turn
plenty of water. In case of eye contact, hold the eye open, flush with plenty of water and get medical the screws tight.
attention.
– The supplier is not responsible for modified, altered or reconstructed equipment. 3. Plug in the connector to the power input of the MS Series HMI.
– Use only parts and accessories manufactured according to specifications of the supplier. Note:
– Peripheral equipment must be appropriate for the application and location. Power connector is already plugged in the power input of the MS Series HMI when the package MS-6 0

– The figures in this manual serves an illustrative purpose. Because of the many variables associated with 3 Mounting Procedure is first opened.
any particular installation, the supplier cannot assume responsibility for actual use based on the figures. 1. Cut out the control front panel to match the dimensions (mm) specified under the External and Cut-
– The supplier neither guarantees that the MS Series HMI is suitable for your particular application, nor out dimensions chapter.
assumes responsibility for your product design, installation or operation.
2. Mount the MS Series HMI into the cut-out. Insert the fixtures to the holes on the unit and fasten the
Power Source screws into the front panel. Do not tighten the screws with too much or uneven force, or it may cause
– The MS Series HMI is equipped with a 24 V DC input. Supply power other than 24 V DC ± 15% will deformation of the MS Series HMI.
severely damage the MS Series HMI. Thus, check the power supply supporting the DC power regular-
ly. Step 1 Step 2 Step 3
– To avoid electric shock, be sure the power cable is unplugged from the power input when connecting
the cable to the MS Series HMI.
Installation
-

+
– Communication cables must be separated from the power cables for operational circuits. Use shielded FG
cables or it may cause unpredictable problems. 90º
DC 24V
During Use 135º
135º

y
– Emergency stop and other safety functions may not be controlled from the MS Series HMI. Use Copper Conductors Only, 60/75

la
sp
Di
– Do not use force or sharp objects when touching the keys, display etc.
Service and Maintenance
Wire Gauge
– Only qualified personnel should carry out repairs. Max torque: 0.6~0.7 Nm (5.31~6.2 lb-in) Type Stripped Length Torque
(AWG)
– Before carrying out any cleaning or maintenance operations, disconnect the equipment from the elec- 0º
trical supply. Display Solid 28-12 7-8 mm 4.5 lb-in
– Clean the display and surrounding front cover with a soft cloth and mild detergent. Stranded 30-12 7-8 mm 4.5 lb-in
– Replacing the battery incorrectly may result in explosion. Use batteries recommended by the supplier. 3. The MS Series HMI must be installed within an angle of 0° to 135° as shown above.

7 Description of Parts 8 Product Specifications 9 Communication Ports 10 Dip Switches


– COM 1 is a 9-pin female connector used to connect a controller and the MS Series HMI via RS232 or
Item MS60C-E MS60T-C MS60T-Pe MS60B-Pe MS60B-C MS60B-E RS485 Dip Switches Function
– COM 2 is a 25-pin female connector used to connect a controller and the MS Series HMI via RS232,
Display Type Color STN TFT LCD TFT LCD Mono STN LCD RS422 or RS485 SW 1 Reserved
LCD SW 2 Reserved
Please make sure that the connection is in accordance with the setting of the dip switches. (For example, ,
Display Color 256 colors 64K colors 16 shades of blue RS485 with SW9 and SW10=ON). SW 3 SW 4 Operation Mode
Display size 5.7” For illustration on the connection between the MS Series HMI and a controller, please consult the informa- ON ON Runs user application
Active area of display 117.2 x 88.4 mm tion on the controller.
ON OFF Runs burn-in test program
Display resolution 320 x 240, Number of 8 x 8 characters displayable 40 x 30 OFF ON Updates BIOS
Display adjustment Via touch panel & VR on the back OFF OFF Runs bench test program
COM 1 COM 2
Back light CCFT, Life- CCFT, Lifetime 60,000 hours CCFT, Lifetime 50,000 hours @ 25 °C SW 5 Communication Parameters
time 50,000 @ 25°C 13 12 11 10 9 8 7 6 5 4 3 2 1
hours @ 25°C 5 4 3 2 1 ON The MS Series HMI uses parameters defined on the Configuration Screen for controller
25 24 23 22 21 20 19 18 17 16 15 14 communications
Touch Screen Analog 9 8 7 6
OFF The MS Series HMI uses parameters defined in MS Designer for controller communications
Keypad 1 Menu key and 5 user-defined Function keys (F1-F5)
SW 6 Password
Keypad pressure 350±50 gf operating force, lifetime is over 1 million activations
and lifetime
PIN Function PIN Function ON The MS Series HMI asks the operator to enter a password after power-on self-test

Input Power 24 V DC +-15%, less than 20W 1 RS485+ 1 N/A OFF No password is required to start the MS Series HMI

Flash ROM 4 Mb 2 RS232 RXD 2 RS232 TXD SW 7 System Menu


RAM 512 K byte 3 RS232 TXD 3 RS232 RXD ON The MS Series HMI displays System Menu
0 OFF The MS Series HMI runs user application without displaying System Menu
-6 CPU 32 bits RISC 4 N/A 4 RS232 RTS
S
M Battery backed mem- 512 K byte 5 Signal ground 5 RS232 CTS SW 8 Default user level
ory 6 RS485- 6 N/A ON The default user level is set to 1 if the MS Series HMI requires no password to start its
RTC YES (rechargeable lithium battery) operation
7 RS232 RTS 7 Signal ground
Data/Recipe - 512 K byte - OFF The default user level is set to 9 if the MS Series HMI requires no password to start its
8 RS232 CTS 8 Optional +5 V @ 100mA output operation
COM1 9-pin female connector, RS232 and RS485 9 Optional +5 V @ 100mA output 9 N/A
SW 9 COM 1 Port
COM2 25-pin female connector, RS232,RS422 and RS485 10 N/A ON For RS485 this switch has to be set ON
Multi-functional port - 26-pin con- - 26-pin connector to printer - 11 N/A
nector to or 64 keys SW 10 COM 2 Port
12 RS422 CTS+
printer or 64 ON For RS485 this switch has to be set ON
keys 13 RS422 CTS- OFF For RS422 this switch has to be set OFF
Ethernet - Yes Yes - 14 RS422 TX+ (RS485+)
Front Panel seal IP65 15 RS422 TX- (RS485-) Document name: Installation manual for MS-60
Ambient 0° - 50°C 16 RS422 RX+ Document no: PD-2002-507
temperature 17 RS422 RX-
Storage -10° - 60°C 18 N/A

Mitsubishi Electric India Pvt.Ltd.


temperature
19 N/A
Ambient humidity 20-90% (non-condensing)
20 N/A
Vibration endurance 0.5 mm displacement, 10-55 Hz, 2 hours per X, Y, Z axis directions
Shock endurance 10 G, 11 ms three times in each direction of X, Y, Z axes
21 N/A
Factory Automation And Industrial Division
22 N/A
CE EN61000-6-4,EN61000-6-2
23 RS422 RTS+
External dimensions 195.0 x 145.0 x 59.1 mm
24 RS422 RTS- Emerald House, EL -3 , J Block ,
Cut-out dimensions 185.8 x 135.8 mm MIDC, Bhosari , PUNE – 411 026. INDIA
25 N/A
Weight 0.81 kg Tel. – (+91) –020 – 2710 2000
Cooling Natural cooling Fax. – (+91) –020 –2710 2100
Email – marketing.FA2@mei-india.com
Web - www.MitsubishiElectric.in

Note:
When using the MS Series HMI for the first time, remember to reset Real Time Clock (RTC).