CRDXP
CRDXP
Front view
Features
3-Point control
Table of Contents
Page
1 Connection diagrams 2
2 Operation 3
3 Description of parameters 4
4 Control 8
5 Fan control 10
6 Defrosting 11
7 Error messages 13
8 Service connection 13
9 Installation 14
10 Accessories 15
11 Technical data 15
12 Software revisions and validity of documentation 16
1 Connection diagrams
CRD-XP
19 Bus L
8 defrost
9 sync.
17 0V
Power
10
11
12
7
5
6
1
3
2
-XP 9
CRD 8
VAC
In1
VAC
In2
230
230
Bus
F2
F1
2 Operation
Display
1 Set value adjustment enabled
1 2 Advanced level P00...P73
P 2
Defrost
Cool
Fan
Status LED Value/parameter number
Selecting parameters
1. Press the <P> key to display the parameter number.
The parameter number will appear in the display for as long as the key is depressed.
2. To select individual parameters with the <P> key depressed, press the ▲ or ▼ key.
When the key is released, the value corresponding to the parameter appears.
P P P P
P P
... ...
5 secs.
2. To return to the advanced level, press the <P> key again for 5 seconds.
If no key is pressed within 2 minutes, the display automatically returns to the standard level. The
return is always to the temperature display which is defined by parameter P60.
P P P P
5 Sek.
When changing the parameters, it is not necessary to re-enable access to make further set value
adjustments.
Actual values are only displayed, they cannot be adjusted even if the "Set value adjustment
enabled" LED is flashing.
4. To disable set value adjustment, press all three keys simultaneously again for 5 seconds.
If no key is pressed within 2 minutes, the display automatically returns to the standard level and
set value adjustment is disabled. The return is always to the temperature display which is defined
by parameter P60.
Set address
Fundamentally, one can proceed as described above to set the device address to Parameter P64. But
additionally, there is the possibility of changing directly to Parameter P64 with the help of the service
button arrayed behind the front plate. For this, the service button must be briefly actuated 3 times. The
advanced level is automatically released.
Service button
88:88
3 Description of parameters
Operating instructions
4 Control
Normal operation with 1 probe
In normal control operation, F1 is used to measure the regulating actual value. F2 serves as defrosting
limit probe. If the actual value exceeds the current setpoint by half the hysterisis amount, the cooling
relay is switched on. If the regulating actual value falls below the current setpoint by half the hysterisis
amount, the cooling relay is switched off again. To reduce the switching frequency of possible
compressors, you can enter a minimum run and standstill time (Æ P38/P39).
Initiation of defrosting is possible in this operation mode as well. If defrosting is not desired, the times
must be explicitly deleted. With forced air defrosting, there is no triggering of the defrosting output
(heat register). With electrical defrosting, the heating/defrosting output becomes active. F2 serves
here as a limit probe.
N Rundown time
N Rundown time
following cooling
following cooling
following cooling
P26 T Draining Time
P31 Fan beahaviour
LV Fan delay
P28 Fan controller
during defrost
Application
to cooling
to cooling
to cooling
examples
P32
P33
P34
P33
P34
Cool T Room
Defrost Circulation air defrost
ON Fan V N V N V N
Cool T Room
Defrost Circulation air defrost
ON Fan
6 Defrosting
Display during active defrost
During a defrost, the text "dEFr" (defrost) is
shown in place of the temperature value in the
P
standard level.
The text remains in the display in cold
locations with set values of > -15°C to
20 minutes and in cold locations with set
values of < -15°C to 30 minutes following the
end of defrost and draining time.
P P P
If several cold location controllers are connected via defrost synchronisation, the defrost operation is
triggered for all.
Terminating a defrost
1. Select parameter P09 "Manual defrost".
2. Enable set value adjustment.
3. Press the ▼ key. The controller defrost operation is terminated.
P P P
If several cold location controllers are connected via defrost synchronisation, the defrost operation
must be terminated for all, before the controllers switch back to cooling mode.
Timer-controlled defrost
Time-controlled defrost is only possible on operation in the BUS system. The time is transferred from
the Gateway to the controller.
6 defrost times are available, which can be set separately (P18 – P23). For these times to be effective,
the device must be programmed as MASTER via parameter P17 ("ON").
The required defrost times are deactivated by setting to '--:--'.
Synchronised defrost
To synchronise the defrosting of several controllers, they can be connected via terminals 8 and 9. A
maximum of 4 controllers can be coupled to each other.
Each device sends a signal to the terminals for the duration of its own defrost. If the Slave controller
detects that the Master controller is defrosting, it will start a defrost under the relevant conditions.
To prevent other devices triggering their own time-controlled defrost, the second device should be
programmed as the SLAVE via parameter P17 ("OFF"). On the other hand, additional times are
possible through the operation as additional master.
On completion of the individual defrost operations triggered by limit probe or time, all synchronised
devices wait until all thermometers have received their synchronous signal from the bus before
starting cooling. This means that the start of cooling as well as the start of defrosting is synchronised.
Cyclical defrost
If the defrost interval should be longer than 1 day, cyclical defrosting can be activated. The cycle time
in hours is set via parameter P27. It is effective when no individual defrost times are programmed or
the controller has been configured as slave.
If the controller does not request a cyclical defrost, the cycle time P27 must be set to "0".
Suppressing defrosts
Electric, hot gas or cold gas defrosts are not triggered if:
the limit probe temperature is higher than the set limit temperature
the limit probe is +5K warmer than the regulator set value and
the regulator actual value has exceeded the over-temperature threshold.
The limit probe malfunctions
7 Error messages
In the event of malfunction, the display flashes with the error code. Depiction of the error code is
suppressed in the advanced level (point in lower right flashes).
Display Cause of malfunction Monitoring function and emergency program
Short-circuit or incoming air Cooling command with defined operating time
F1 probe interrupted (Parameters P42, P43)
Short-circuit or limit probe With electric, hot gas or cold gas defrosting and a
F2 interrupted defect in the limit probe, defrosting does not take place.
Data error in non-volatile A power surge may destroy the set values. Operation
EE memory takes place with default settings.
Re-enter all memory locations!
Isolate thermostat!
Address collision on the bus The set address is already assigned.
COLL Set a different address for the device !
Bus error Check bus connection or set address to 0 (P64)
buS No bus
Cold room door open too long Close cold room door!
door
Alarm digital Input 1 Zero current principle,
AL alarm on loss of current at the input 1
Delayed alarm via input 1 Apply voltage to input 1,
dAL rectify external fault
Timer has invalid time on Restore bus connection to the gateway or enter time
Uhr address > 0 (P16) and set address to 0 (P64)
Over or under-temperature Thermostat is too warm or too cold.
-6 alarm of regulator actual value Check setting of over-temperature threshold P47 or
T flashing under-temperature threshold P48.
8 Service connection
For service and commissioning purposes, a laptop can be connected
directly to the cold location controller. The required connection
sockets for the communication bus are located to the left behind the
front plate. The CAN-PC901 – converter must be used for
communication with the computer.
9 Installation
158
120
61
72
120
28
75
62
33
12
65
10 Accessories
11 Technical data
CRD-XP cold location controller
Supply voltage 2 x 9V~ via transformer TR9-9-4
with plug connection
Power draw approx. 4VA
Digital inputs 2 x zero-potential multi-function inputs
Temperature probe 2 x TRK277plus
Output relay 1x ventilator/alarm – closer contact, 230V~ 4(2)A
1x cooling – closer contact , 230V~ 4(2)A
1x defrost – closer contact , 230~ 4(2)A
TR-9-9-4 - Transformer
Primary voltage 230V~, +10%/-20%
Power draw approx. 4VA
Fusing Max. 6A
Secondary voltage 2 x 9V~ for CRD-XP
with plug connection
Primary side connection 2 x AMP connection, 6.3mm
All software versions that are not listed are special solutions for individual projects and are not
documented in this description in detail.
The general technical guidelines must be observed!
This document will automatically become invalid when superseded by a new technical description of
the device.