0% found this document useful (0 votes)
15 views45 pages

30SS3 报告

The report details the testing of equipment according to EN 12601 standards, confirming that all tests were successfully passed. It includes specific test item particulars, safety requirements, and the results for various components, indicating compliance with relevant standards. The report emphasizes that the results pertain only to the tested object and cannot be reproduced without permission from the testing laboratory.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
15 views45 pages

30SS3 报告

The report details the testing of equipment according to EN 12601 standards, confirming that all tests were successfully passed. It includes specific test item particulars, safety requirements, and the results for various components, indicating compliance with relevant standards. The report emphasizes that the results pertain only to the tested object and cannot be reproduced without permission from the testing laboratory.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 45

Page 2 of 45 Report No.

JSH107110340-001

Copy of nameplate

Label

Summary of testing:

All tests are carried out in according to the EN 12601 and the test results meet the requirements specified in
the above-mentioned standard.

TRF No. EN12601B


Page 3 of 45 Report No. JSH107110340-001

Test item particulars:


Equipment mobility ................................................ : stationary
Operating condition................................................ : Continuous
Supply connection ................................................. : N.A.
Mass of appliance ................................................. : 960Kg
Output type ............................................................ : Neutral floating
IP number .............................................................. : IP23
Possible test case verdicts:

- test case does not apply to the test object ................. : N/A

- test object does meet the requirement....................... : P(Pass)

- test object does not meet the requirement ................ : F(Fail)

Testing ......................................................................... :

Date of receipt of test item............................................ : 6 November 2007

Date (s) of performance of tests................................... : 6 November 2007–26 November 2007

General remarks:

The test results presented in this report relate only to the object tested.

This report shall not be reproduced, except in full, without the written approval of the Issuing testing laboratory.
"(see Enclosure #)" refers to additional information appended to the report.

"(see appended table)" refers to a table appended to the report.


Throughout this report a comma is used as the decimal separator.

Determination of the test results include consideration of measurement uncertainty from the test equipment
and methods.

TRF No. EN12601B


Page 4 of 45 Report No. JSH107110340-001

Main components list


object/part No. manufac- type/model technical data standard mark(s) of
turer/trademark conformity1)
AC Circuit- Wenzhou Baishibao BSB1- 30 250V~, 16A EN 60934: 2001 TUV
breaker for single Electric Appliance /50074490
phase socket Co., Ltd.
Single phase Zhangjiagang B-012 250V~ 16A DIN VDE 0620- TUV
Youguang Electric IP44 1/04.05 /50069654
Socket
Manufacture Co.,
Ltd.
AC Circuit- ABB Xinhui Low Isomax AC 690V 50Hz EN 60947- TUV

breaker for main Voltage Switchgear S2N 40A 4 Poles 2:1996+A1+A2 /50031304

circuit Co., Ltd.


Residual current ABB SACE SPA RC212/2 3/N 50…500V EN 60947-1 CE
detection devices 50Hz EN 60947-2 declaration
EN 50081-1 by ABB
Fuse for battery Suzhou Littelfuse 215 250V~, 10A EN 60127- VDE
charging circuit OVS Ltd. 1:1991+A1:1999+A2 /40013521
:2003
EN 60127-
2:2003+A3:2003
Class II Thai Lin Radio Coil TCL30S- Input 230V, 50Hz EN 61558-1: TUV
transformer in Manufactory Ltd 100-260 Output 10V 1997+A1+A11 /50044062
control circuit 260mA EN 61558-2-6: 1997
EN 60950:2000
Indicator ABB Automation CL-523G AC 230V EN 60947-1: 2004 CE
Technologies AB EN 60947-5-1: 2004 declaration
by ABB
Emergency stop ABB Automation CE4T-12- 300V 5A EN 60947-1: 2004 CE
Technologies AB 11 EN 60947-5-1: 2004 declaration
EN 60947-5-5: 1997 by ABB
Internal wire Wuxi Xinhongye BVV 0,5mm² EN 12601: 2001 Tested in
1,5mm²
Wire & Cable CO., appliance
10mm²
LTD.
Diesel Engine WUXI KIPOR POWER KD493G 23,2KW, EN 12601: 2001 Tested in
CO.,LTD 1500/min appliance

TRF No. EN12601B


Page 5 of 45 Report No. JSH107110340-001

Generator WUXI KIPOR POWER KDE30SS3 230/415V~ 50Hz EN 60034: 2004 Tested in
CO.,LTD 24KW Class 130 ISO 8528-3: 2005 appliance
Resistance of AC
winding
RAC=0,252Ω
(between phases)
(18,6°C)
1) an asterisk indicates a mark which assures the agreed level of surveillance

TRF No. EN12601B


Page 6 of 45 Report No. JSH107110340-001
EN 12601: 2001
Clause Requirement - Test Result - Remark Verdict

6 Safety requirements
6.1 Starting system
Starting systems shall meet the requirements of 6.1 12V dc electric starting device P
of EN 1679-1:1998. provided
6.2 Normal stopping

All generating sets shall have a normal stopping Manually operated stopping P
device which can be manually or automatically switch provided, operate by
actuated. Stopping control shall remain in the stop cutting off starting circuit.
position when operated. This shall operate by cutting
off the fuel or ignition (for spark ignition engines)
supply. This device may include an air supply cut-off.

6.3 Emergency stopping


Emergency stopping devices are only required for P
remote controlled generating sets and generating
sets with an enclosure accessible by persons. For
low power generating sets no emergency stopping
device is necessary.
Emergency stopping devices can be actuated manually and automatically P
manually or automatically. The emergency stopping
shall operate by cutting off the fuel or ignition (for
spark ignition engines) supply. It may include an air
supply cut-off.
6.3.1 Manually actuated
The generating set shall be provided with a manually P
actuated emergency stopping device if this can be
actuated or reacts quicker than the normal stopping
device. According to EN 418 the reset of the stop
function shall not initiate a restart or any hazardous
conditions.
Manually actuated emergency stopping device shall P
meet the requirements of EN 418, category 0.
In the case of generating sets operating in a N/A
housing, which is accessible to persons a manually
actuated emergency stopping device shall be
located inside and outside the housing.
6.3.2 Automatically actuated

TRF No. EN12601B


Page 7 of 45 Report No. JSH107110340-001
EN 12601: 2001
Clause Requirement - Test Result - Remark Verdict

The generating set shall be provided with an P


automatically actuated emergency stopping device if
the normal stop control is not accessible to persons
working on or around the generating set.
This device monitors one or more signals of the P
generating set and if these signals are out of the
permissible range it triggers the automatic stop.
The main signals that might be used to actuate P
automatic stopping are e.g.
a) for the RIC engine overspeed , low lubricating oil P
- overspeed (see ISO 3046-6) pressure,
- low lubricating oil pressure high coolant temperature, low
- high coolant temperature coolant level
- low coolant level
b) for the generator excessive overvoltage function P
-excessive overvoltage And overload condition
-earth-fault current
Which of these or other measures that should be P
specified depends on the application.
6.4 Control devices

6.4.1 Design, safety and mechanical strength


Control devices on generating sets shall comply with P
6.4 of EN 1679-1:1998.
For control devices on electrical equipment 10.1 and P
10.2 of EN 60204-1:1997 with the exception as given
in B.10 shall apply.

6.4.2 Identification
The requirements of 6.4.2 of EN 1679-1:1998 shall P
apply.
For control devices on electrical equipment 10.1 and P
10.2 of EN 60204-1:1997 with the exception as given
in B.10 shall apply.

6.4.3 Accessibility
The requirements of 6.4.3 of EN 1679-1:1998 shall P
apply.
6.5 Monitoring devices

TRF No. EN12601B


Page 8 of 45 Report No. JSH107110340-001
EN 12601: 2001
Clause Requirement - Test Result - Remark Verdict

The instruments for the monitoring of the generating P


set shall comply with the requirements in 6.5 of EN
1679-1:1998

Devices for electrical equipment shall comply with P


10.3 of EN 60204-1:1997

6.6 Warning devices

Warning mark provided P


Warning devices, signs, markings and colours shall
meet the requirements of EN 61310-1 and EN 981. Yellow for caution and red for
prohibition

6.7 Guarding

Persons shall be protected against hazards within All doors with lock, which shall P
the safety distances specified in EN 294 and EN be open by key
811. The safety distance depends on the generating
set installation. For fixed installed generating sets
the need of guarding shall be agreed between
generating set manufacturer and installer
considering that the persons shall be protected
during operating and routine servicing.

Because it is not possible to envisage the layout of N/A


fixed installation the overall requirements for this
situation are not dealt with in this standard. The
following clauses give the requirements for the
specific hazards and these principles shall be
followed for any installation.

6.7.1 Guarding against mechanical hazards


Moving parts are covered P
Moving parts at generating sets e.g. fan, belt, chains
appropriately. All doors with
etc. shall be so arranged or enclosed as to prevent
lock, which shall be open by
direct involuntary access during normal use.
key
6.7.2 Guarding against hot surfaces
The hazard a hot surface presents depends on the P
surface temperature, its location and if a person is
likely to touch it. A guard shall be provided to prevent
accidental contact with any engine exhaust
component during normal operation; any surface
below 10 cm needs not be guarded.
2

TRF No. EN12601B


Page 9 of 45 Report No. JSH107110340-001
EN 12601: 2001
Clause Requirement - Test Result - Remark Verdict

To decide if there is a measure needed, EN 563 P


should be used as a guide for evaluating the limit
temperature of the hot surfaces. The guards used
shall not exceed the permissible temperatures as
defined in EN 563 under normal operating
conditions, which are at continuous power according
to ISO 8528-1.
In order to define the surfaces which may need a P
guard, the following described test procedure shall
be used.

The generating set shall be operated at its rated


speed until the surface temperatures stabilize. The
test shall be conducted in the shade. If the test is
conducted at an ambient temperature outside of the
nominal 20 C±3 C the reported temperatures shall
o o

be determined by correcting the observed


temperature by adding the difference between the 20
o
C and the actual test ambient temperature. When
the distance between the identified hot area and the
nearest control is in excess of 100 mm, cone A as
shown in figure 1 shall be used. For distances less
than 100 mm between the identified hot area and the
nearest control, cone B as shown in figure 1 shall be
used. For cone A with the axis of the cone anywhere
0 and 180 to the horizontal and with the point of the
o o

cone in a downward to horizontal direction, move the


cone towards the hot surface. The cone shall not be
moved in an upwards direction. When moving the
cone, determine if contact is made with the hot
surface area(s) with the cone tip or conical surface
of the cone. Cone B shall be moved in any direction.
Any surface that cannot be reached by the cones is P
considered out of reach for the operator.
For low power generating sets 6.4 of ISO 8528- Not low power generating sets N/A
8:1995 shall apply
6.7.3 Guarding against electrical shock by enclosures
The requirements of 6.2.2 of EN 60204–1:1997 shall IP23 P
be met.
6.8 Guard design
The requirements for guarding and guard device laid P
down in 6.8 of EN 1679-1:1998 shall apply.

TRF No. EN12601B


Page 10 of 45 Report No. JSH107110340-001
EN 12601: 2001
Clause Requirement - Test Result - Remark Verdict

It shall only be possible for the fixed guards to be P


removed using tools (6.3.2 of ISO 8528-8:1995).
Movable guards shall be interlocked according to EN N/A
1088.
6.9 Lighting
If the generating set manufacturer supplies a Light on the control box, P
generating set that includes lighting, the area around powered by battery
the control levers, monitoring devices and
corresponding walkways shall be illuminated with an
intensity of at least 20 lux.

6.10 Handling

Generating sets shall have provisions for lifting Provided the lifting P
attachments to attach lifting devices to lift the attachments
generating set or parts of it according to the Tested with 1,5 times of the
manufacturers instructions. The lifting attachments product mass
shall be designed to withstand at least 1,5 times the
mass lifted divided by the number of lifting
attachments.

The lifting attachments and their location shall Comply with 6.10 of EN 1679- P
comply with 6.10 of EN 1679-1:1998. For mobile 1:1998
used low power generating sets the mechanical
stability to prevent tip-over shall comply with 6.2 of
ISO 8528-8:1995.

Generating sets intended for transportation by N/A


persons (below 140 kg) shall have carrying handles
or an adequate frame design to transport it
according to the manufacturers manual. The
handles shall be designed to withstand at least 2,5
times the mass lifted divided by the number of
carrying handles.

Because individual generating sets are either N/A


designed with handles or use the frame for carrying
purposes it is not possible to prescribe the exact
number or layout of handles. As a basis for providing
means of carrying the generating set it is considered
that a 140 kg set should be provided with the means
of carrying by 4 Persons.

6.11 Fire protection

TRF No. EN12601B


Page 11 of 45 Report No. JSH107110340-001
EN 12601: 2001
Clause Requirement - Test Result - Remark Verdict

The design has to consider hazards from flammable In addition, plastic material P
liquids or gases with regard to routing of pipes, used to support electric
location of reservoir, leakage, filling and draining. connection or the close to
The possibility of contact with energy sources that such connection with 3 mm, is
could result in a hazard should be minimized. tested with the glow wire test
of 850°C

For the engine, the basic requirements of ISO 6826 P


shall be met. The orifices and the filling devices of
the generating set shall meet the requirements of 6.2
of ISO 6826:1997 the piping for flammable liquids
the requirements of 7.3 of ISO 6826:1997 and the
draining valves the requirements of 7.6 of ISO
6826:1997.
For fuel tanks the following additional requirements P
apply.
- Fuel tanks shall be designed as to ensure that no
leaks develop under normal operating conditions.
-Leaking fuel from the vent holes of the tanks of
reciprocating internal combustion engines during
start-up and operation is permissible as long as it
has been ensured that there is no subsequent
danger of fire.
- Filler necks in fuel tanks shall be arranged and
designed in such a way as to ensure that fuel cans
or other devices with spouts can be directly inserted
and no fuel can come into contact with hot parts.
-The tank shall be secured to withstand normal
handling.
- The tank shall be strong enough to withstand
impact during normal handling or be protected from
impact.

For low power generating sets, the test in 6.1.1 of N/A


ISO 8528-8:1995, satisfies these last two
requirements.

For low power generating sets the following N/A


additional requirement applies.

- Any parts of the generating set which are in direct N/A


contact with the flat supporting surface shall not
exceed a temperature of 90 °C.

TRF No. EN12601B


Page 12 of 45 Report No. JSH107110340-001
EN 12601: 2001
Clause Requirement - Test Result - Remark Verdict

6.12 Hoses, pipes and electrical harnesses of the RIC engine

Requirements for these components laid down in P


6.14 of EN 1679-1:1998.

6.13 Electrical equipment

6.13.1 Generators

Generators shall meet the requirements of ISO See Appendix IEC60034 and P
8528-3. Generators for low power generating sets Appendix ISO 8528-3
shall meet the requirements of 6.6.2 of ISO 8528-
8:1995.

The IP-degree of protection of the generators shall IP23 P


correspond to the requirements of the operational
conditions. Generators for low power generating sets
shall at least comply with IP 23 when operating.

The increase of temperature of generators when N/A


operating in low power generating sets, shall
correspond, under normal operational conditions, to
6.8 of ISO 8528-8:1995, and, when operating under
overload, to 6.10 of ISO 8528-8:1995.

In case the generator supplies electrical equipment N/A


of machinery the design of the generator has to be
agreed between generating set installer and
manufacturer according to 4.3.1 of EN 60204-
1:1997.

6.13.2 Other electrical equipment


Electrical equipment used to operate the generating P
See Annex B
set shall meet the requirements of Annex B.
6.14 Noise

6.14.1 Noise reduction at the design stage


When designing the generating set the available P
information and technical measures to control noise
at source shall be taken into account, see for
example EN ISO 11688-1. The main sources of
airborne noise on generating sets include:
-the engine;
- the cooling system fan if provided;
- the exhaust system.

6.14.2 Noise measurement and declaration

TRF No. EN12601B


Page 13 of 45 Report No. JSH107110340-001
EN 12601: 2001
Clause Requirement - Test Result - Remark Verdict

Airborne noise shall be measured as specified in LpA: 74,7 dB(A) P


ISO 8528-10 at 75 % of rated power (PRP) and
LwA: 90,9 dB(A)
determined according to clause 13 for the sound
power level and according to clause 14 for the
emission sound pressure level.
6.15 Access systems (e.g. operator platforms, walkways, etc.)

Surfaces of all access system (e.g. walkways and Generating set is floor N/A
platforms, etc.), if required, shall be slip resistant supported
under the expected use to minimize the possibility of
foot slippage.
Access system shall be level and free from N/A
obstructions and protrusions to prevent injury.
The structure shall be sufficiently sturdy and stable N/A
to support any expected load without undue
deformation.
Access systems if required shall be designed N/A
according to prEN 12437-2:1996.
6.16 Access to service points

Moving parts and hot surfaces bigger than 10cm 2


No service needs to be done N/A
which are closer than 300mm to the service point with the generating set
and/or operator access path shall be guarded if running.
servicing has to be done with the generating set
running.
Openings intended for maintenance purposes shall No such openings N/A
comply with EN 547-2.
6.17 Gaseous and particulate exhaust emissions
The exhaust directed away P
The exhaust shall be directed away from the
from the generator set control
generating set control panel.
panel
If required exhaust emissions shall be determined as N/A
specified in EN ISO 8178-1, EN ISO 8178-2, EN ISO
8178-4, EN ISO 8178-5, EN ISO 8178-6 and ISO
8178-3, ISO 8178-7 and ISO 8178-8.
For generating sets used indoors, the installer has to Stated in the manual: not used N/A
assure that the exhaust is directed outside. in doors

6.18 Drainage

TRF No. EN12601B


Page 14 of 45 Report No. JSH107110340-001
EN 12601: 2001
Clause Requirement - Test Result - Remark Verdict

Provisions shall be made to allow drainage of fuel, P


coolant and lubrication oil without any spillage.
This can be achieved by:
- permanently installed pipework to a collection point
or
- providing access for collection tanks to allow direct
drainage, or
-access to drain plugs without the need to remove
guards.
7 Operating and maintenance instructions
Operating and maintenance instruction shall comply P
with clause 5 of EN 292-2:1991 and shall provide
adequate information to enable the generating set to
be operated safely and give clear advice concerning
its installation, use and maintenance.
Extensive use should be made of photographs P
and/or diagrams.
The operating and maintenance instructions shall P
include, but not be limited to the following:
a) General description, in particular description of the P
generating set nameplate, and explanation of the
adjustment points that shall not be modified.
b) General information concerning the toxicity of P
exhaust gases, fuel, oil.
c) Information concerning the limitation of use in P
ambient where the risk of fire may be high.
d) Filling with fuel and oil. P

e) Starting and stopping. P

f) Correct use of batteries. P


g) Indications about the hot surfaces and eventually
P
of their guards.
h) Routine maintenance instructions. P

i) Correct disposal of residual fluids. P


j) Indication that the installation and major repair P
work shall be carried out only by specifically trained
personnel.

TRF No. EN12601B


Page 15 of 45 Report No. JSH107110340-001
EN 12601: 2001
Clause Requirement - Test Result - Remark Verdict

k) Information on installation precautions e.g. P


exhaust system, intake system, cooling system,
drainage, fueling, electrical connection, noise and
access.
l) Advice on the need of personal protection P
equipment, e. g. hearing protection where the
application is known.

TRF No. EN12601B


Page 16 of 45 Report No. JSH107110340-001
EN 12601: 2001
Clause Requirement - Test Result - Remark Verdict

m) A declaration concerning the airborne noise P


emission as required by 1.7.4.f) of EN 292-2:1991/A
1:1995, based upon measurements made in
accordance with the method specified in 6.14.2. The
declaration shall be accompanied by a statement of
the measuring method used, operating condition
applied during the test and values for the uncertainty,
K, using the dual-number form of presentation given
e.g. in EN ISO 4871. The declared values shall
consider uncertainties due to production variation
and measurement procedures.
For example, for a sound power level LWA = 98 dB
(measured value). Uncertainty K = x dB for
measurements made in accordance with ISO 8528-
10.
If the accuracy of declared noise emission values is
to be verified, measurements shall be made using
the same method, the same operating conditions
and the same arrangement of microphone positions.
The noise declaration shall be accompanied by the
following statement:
"The figures quoted are emission levels and are not
necessarily safe working levels. Whilst there is a
correlation between the emission and exposure
levels, this cannot be used reliably to determine
whether or not further precautions are required.
Factors that influence the actual level of exposure of
work-force include the characteristics of the work
room, the other sources of noise, etc. i.e. the
number of machines and other adjacent processes,
and the length of time for which an operator is
exposed to the noise. Also the permissible
exposure level can vary from country. This
information, however, will enable the user of the
machine to make a better evaluation of the hazard
and risk".
In the case of generating sets provided for use by P
laymen as defined in 3.1 of ISO 8528-8:1995 the
supplied instructions have to meet the requirements
as defined in 8.2 and 9 of ISO 8528-8:1995.

8 Special requirements

TRF No. EN12601B


Page 17 of 45 Report No. JSH107110340-001
EN 12601: 2001
Clause Requirement - Test Result - Remark Verdict

Some application might require that the generating N/A


set is designed to meet special requirements. The
customer of the generating set shall specify the
requirements to be met (see also ISO 8528-7).

9 Marking
Generating sets shall be marked legibly and indelibly According to ISO 8528-5 P
according to ISO 8528-5 or ISO 8528-8 whichever is
applicable.

10 Verification of the safety requirements and/or measures


Verification of the safety requirements and/or P
measures shall be carried out either on the complete
generating set or by documentation provided by the
component manufacturer

- Visual inspection particularly related to safety P


measures.

- Functional tests of safety devices. P


- Insulating resistance test or voltage test according Insulating resistance >200MΩ P
to 19.3 or 19.4 of EN 60204-1:1997.
1000V applied between live
parts and enclosure
- Function of the protective bonding circuit according Measured value below the limit P
to 19.2 of EN 60204-1:1997.
- Function of the protection measure against indirect P
by calculation
contact (verification either by calculation or by tests).

TRF No. EN12601B


Page 18 of 45 Report No. JSH107110340-001
EN 12601: 2001
Clause Requirement - Test Result - Remark Verdict

Annex A List of hazards P

Annex B Application of EN 60204-1 for generating sets

Introduction
Generating sets are considered as machines as P
defined in the machinery directive. For this reason,
the basic standard EN 60204-1 shall be used for
the subject electric equipment. In the introduction of
this standard reference is being made to its
application, when preparing product standards for
the various product families.
The following list shows which subclauses of EN P
60204-1 are either not applicable to generating sets
or supplements are necessary. If different
requirements to those of EN 60204-1 have to be
met, they are given in the following list. In those
cases the complete subclauses of EN 60204-1 are
substituted and not valid.
Those clauses of EN 60204-1 which are not P
mentioned in the following list are applicable and
have to be met.
1 SCOPE
The equipment, which is covered by the following P
requirements as well as the requirements of EN
60204-1, commences for generating sets at the
output terminals of the generator.
If generating sets, operating standby-to mains or N/A
parallel to mains, and the equipment of generating
sets is supplied with power supply from the main
supply net, those requirements commences at the
point of connection of the supply.

4 General Requirements

4.1 General considerations P

4.2 Selection of equipment See main components list P


4.3 Contrary to EN 60204-1 the following requirements P
apply to generating sets:

TRF No. EN12601B


Page 19 of 45 Report No. JSH107110340-001
EN 12601: 2001
Clause Requirement - Test Result - Remark Verdict

Electrical equipment of generating sets, which is Class G1 P


supplied by the generator of the generating sets
see attached table “Operating
itself, shall work without any failure under the rated
characteristics”
conditions of the generating sets according to
clause 7 of ISO 8528-1:1993 and clause 16 of ISO
8528-5:1993. For low power generating sets clause
7 of ISO 8528-8:1995 applies.
If not otherwise agreed the electrical equipment No such equipment N/A
which is not supplied by the generator of the
generating set has to meet the requirements
according to 4.3 of EN 60204-1:1997.
In case the generator supplies electrical equipment N/A
of machinery the supply requirements according to
4.3.1 of EN 60204-1:1997 apply. The requirements
have to be agreed between user and manufacturer
especially in view of the transient behaviour during
load changes.

4.4 Physical environment and operating conditions P

4.4.1 General P

4.4.2 Electromagnetic compatibility (EMC) N/A

4.4.3 Ambient air temperature -15°C to 40°C P


4.4.4 Instead of the values given in EN 60204-1 25°C, 100kPa, 30% P
generating sets shall meet the limit values
according to clauses 10 and 11 of ISO 8528-
1:1993.

TRF No. EN12601B


Page 20 of 45 Report No. JSH107110340-001
EN 12601: 2001
Clause Requirement - Test Result - Remark Verdict

Low power generating sets shall meet the limit N/A


values according to clause 7 of ISO 8528-8:1995.
Deviations from those values shall be agreed N/A
between manufacturer and user.
4.4.5 Altitude 1000m P

4.4.6 Contamination IP23 P

4.4.7 Ionizing and non-ionizing radiation N/A

4.4.8 Vibration, shock and bump P

4.5 Transportation and storage P

4.6 Provision for handling P

4.7 Installation and operation P


5 Supply Conductor Terminations and Devices for Disconnection and Switch
Off

5.1 Supply Conductor Terminations on generating sets


Contrary to EN 60204-1 for generating sets, N/A
dependent from the demanded protection measure,
a connection between neutral conductor and
protective bonding circuit may be required.
If generating sets are used as standby-to-mains- N/A
units a safety and an interlocking system is
necessary to avoid parallel operation (see ISO
8528-4). If generating sets are operating parallel to
the mains or other generating sets additional
equipment for synchronising and protection is
needed (see ISO 8528-4).
5.2 The generating sets shall have a terminal for the Equipotential earthing used, P
connection of an external protective conductor the total system is isolated from
and/or a functional grounding near the associated earth.
phase conductor terminal, or on a suitable place at
the generating set frame. The requirements for this
terminal shall be according to 5.2 of EN 60204-
1:1997. If the use of this terminal at delivery of the
generating sets is unknown, it has to be delivered
and marked with the symbol 417-IEC-5019
Contrary to EN 60204-1 the following requirements P
5.3
apply to generating sets:

TRF No. EN12601B


Page 21 of 45 Report No. JSH107110340-001
EN 12601: 2001
Clause Requirement - Test Result - Remark Verdict

For generating sets in single operation, which P


provide power supply to various electrical
equipment through a plug-type device, the electrical
disconnection through the plug-type device up to 32
A or a protection switch above 32 A at the
generating sets with manual operation is permitted.
For generating sets in single operation, standby-to N/A
mains operation or parallel-to mains operation,
which provides power to a consumer net, 5.1 of ISO
8528-4:1993 applies.
Electrical equipment which is necessary for the N/A
operation of the generating set and which is not only
supplied by the generator has to be equipped with a
separate disconnecting device.
5.4 Devices for switching off for prevention of unexpected start-up
Such devices are only necessary for generating P
sets with a remote starting device or an automatic
starting device if there is any danger of an
unexpected start. An emergency stop button may
be used as such a device.
Devices provided for disconnecting (isolating) P
5.5
electrical equipment
Protection against unauthorized, inadvertent and/or P
5.6
mistaken connection
6 Protection against electric shock

6.1 General P

6.2 Protection against direct contact P

6.3 Protection on indirect contact. P


Supplement: For low power generating sets See Appendix ISO 8528-8 N/A
exclusively protection measures according to 6.7.2
and 6.7.3 of ISO 8528-8:1995 shall used.
6.3.1 General P
6.3.2 Measures to prevent the occurrence of a N/A
hazardous touch voltage
6.3.3 Protection by automatic disconnection of supply Circuit breaker with residual P
current detection to initiate
automatic disconnection used,
distribute 3L/N, which set
disconnecting time 0,5s

TRF No. EN12601B


Page 22 of 45 Report No. JSH107110340-001
EN 12601: 2001
Clause Requirement - Test Result - Remark Verdict

Supplement: If the automatic disconnection should P


be done by over-current release the dimension of
the over-current protection device, the impedance
of the generator and the short circuit behaviour of
the generating sets shall be taken into account.
Earth fault protection devices shall correspond to N/A
7.2.7 of ISO 8528-4:1993.
6.4 Protection by use of PELV N/A

7 Protection of equipment

7.1 General P

7.2 Over-current protection P


Supplement: For low power generating sets Overcurrent protector provided N/A
according to ISO 8528-8 no over-current protection in AC circuit
devices are necessary, if current, occuring in the
worst case, does not exceed the rating of any
component or the current carrying capacity of the
conductors.
7.2.1 General P

7.2.2 Supply conductors P

7.2.3 Power circuits P

7.2.4 Control circuits P

7.2.5 Socket outlets and their associated conductors P


7.2.6 Lighting circuits Light powered by battery, circuit P
with fuse

7.2.7 Transformers P

7.2.8 Location of protective devices P


7.2.9 Overcurrent protective devices P

7.3 Overcurrent protection of motors P

7.4 Abnormal temperature protection P


Protection against supply interruption or voltage N/A
7.5
reduction and subsequent restoration
7.6 Motor overspeed protection N/A

7.7 Earth fault / residual current protection N/A

7.8 Phase sequence protection N/A

TRF No. EN12601B


Page 23 of 45 Report No. JSH107110340-001
EN 12601: 2001
Clause Requirement - Test Result - Remark Verdict

Protection against overvoltages due to lightning N/A


7.9
strike or switching surges
8 Equipotential Bonding

8.1 General P

8.2 Protective bonding circuit P

8.3 Bonding for operational purpose P

8.3.1 General P

8.3.2 Bonding to the protective circuit N/A

8.3.3 Bonding to a common reference potential P

9 Control circuits and control functions


9.1 Control circuits N/A
9.2 Control functions N/A
9.3 Protection interlocks N/A

9.4 Control function in the event of failure P

9.4.1 General requirements P

9.4.2 Measures to minimize in the event of failure P


Protection against maloperation due to earth faults, N/A
9.4.3
voltage interruptions and loss of circuit continuity
10 Operator interface and machine mounted control devices
10.1 General P
10.1.1 General device requirement P
10.1.2 Location and mounting P
10.1.3 Operator interface and machine mounted control P
devices shall withstand the stresses of the expected
use declared by the manufacturer. A minimum
degree of protection of IP 33 according to IEC 529
is sufficient.
10.1.4 Position sensors N/A

10.1.5 Portable and pendant control stations N/A

10.2 Push-buttons P

10.3 Indicator lights and displays P

10.4 Illuminated push-buttons N/A

TRF No. EN12601B


Page 24 of 45 Report No. JSH107110340-001
EN 12601: 2001
Clause Requirement - Test Result - Remark Verdict

10.5 Rotary control devices N/A

10.6 Start devices N/A


Only applicable if an emergency stopping is P
10.7
provided.
10.8 Devices for emergency switching off N/A

12 Electronic equipment

12.1 General N/A

12.2 Basic requirement N/A

12.3 Programmable equipment N/A

12.3.1 Programmable controllers N/A

12.3.2 Memory retention and protection N/A

12.3.3 Programming equipment N/A

12.3.4 Software verification N/A

12.3.5 Use in safety-related functions N/A

13 Controlgear: Location, mounting and enclosures


13.1 General requirements P
13.2 Location and mounting P
13.3 Control- and switchgear shall withstand the stresses Generating sets IP23 P
of the expected use declared by the manufacturer.
For generators of generating sets the degree of
protection IP 23 applies. For control- and
switchgear in electrical operating areas the degree
of protection IP 41 is sufficient.
13.4 Enclosures doors and openings P
14 Conductor and cables P

15 Wiring practices

15.1 Connections and routing P

15.2 Identification of conductors P

15.3 Wiring inside enclosures P


Flame-retardant cable ducts are generally not P
required.
15.4 Wiring outside enclosures N/A

TRF No. EN12601B


Page 25 of 45 Report No. JSH107110340-001
EN 12601: 2001
Clause Requirement - Test Result - Remark Verdict

15.5 Ducts, connection boxes and other boxes P

15.5.1 General requirements P


Degree of protection for ducts > IP 33 according to N/A
EN 60529 is generally not required.
15.5.2 Percentage fill of ducts N/A

15.5.3 Rigid metal conduit and fittings N/A

15.5.4 Flexible metal conduit and fittings N/A

15.5.5 Flexible non-metallic conduit and fittings P

15.5.6 Cable trunking system N/A

15.5.7 Machine compartments and cable trunking system N/A

15.5.8 Connection boxes and other boxes P

15.5.9 Motor connection boxes N/A

16 Electric motors and associated equipment See Appendix IEC 60034-1 P

17 Accessory and lighting N/A

18 Warning signs and item destinations

(see also 9a) of ISO 8528-8:1995) P

19 Technical documentation

Not applicable (see clause 7) P

20 Testing
The requirements of clause 10 of this standard P
apply

TRF No. EN12601B


Page 26 of 45 Report No. JSH107110340-001
EN 12601: 2001
Clause Requirement - Test Result - Remark Verdict

Appended Table: Operating characteristics


Frequency behaviour (steady-state, Dynamic)
No load frequency, fi,r (Hz)............................... : 51,8
Load frequency, farb (Hz).................................. : 50,3
Undershoot frequency in case of increasing load,
fd,min (Hz) ......................................................... : 49,12
Rate frequency, fr (Hz)..................................... : 50
Overshoot frequency in case of decreasing load,
fd,max (Hz) ......................................................... : 54,42
Frequency droop, δfst 3,6% Limit < 8%
Transient frequency 100% sudden power Limit < - (15+δfst)%
-2,3%
difference from initial increase
frequency δfd Sudden power decrease 8,2% Limit < +18%
Transient frequency 100% sudden power Limit < - 15%
-2,4%
difference from rated increase
frequency δfdyn Sudden power decrease 8,2% Limit < +18%
Steady-state voltage behaviour
Rated voltage (V) 230
Steady condition, Maximum voltage (V) 231,0

for all power between


no-load and rated output Minimum voltage (V) 230,7
at rated power factor
Steady-state voltage deviation δUst ±0,1% Limit ≤ ± 10%

TRF No. EN12601B


Page 27 of 45 Report No. JSH107110340-001
EN 12601: 2001
Appendix IEC 60034-1:2004
Clause Requirement - Test Result - Remark Verdict

3. DEFINITIONS
3.10 Duty dype of the motor .................................... : S1 P
3.17 Cooling method ............................................... : for generator,Primary coolant: P
air, Secondary coolant: water

4. Duty
4.1 Declaration of duty
Purchasers declaration of duty N/A
If duty not declared, S1 S1 P
4.2 Duty types
4.2.1 Duty type S1 – Continuous running duty P

5. Rating
5.1 Assignment of rating P
Rating assigned by manufacturer P
5.2 Classes of rating
5.2.1 Rating for continuous running duty S1 P
5.3 Selection of a class of rating
General purpose machine has rating for S1 P
continuous running duty
5.4 Allocation of outputs to class of rating
For duty S1 to S8, specified value(s) of constant S1, constant load P
load(s) is rated output(s)
For duty S9 and S10, reference value of load N/A
based on S1 taken as rated output
5.5 Rated output
5.5.1 DC generators
Output at terminals (W) …………………………..:. N/A
5.5.2 AC generators
Apparent power at the terminals (VA)…………: See copy of nameplate P

Power factor………………………………………..: 0,8 P


The rated power factor for synchronous 0,8 P
generators shall be 0,8 lagging (over-excited),
usless otherwise specified by the purchaser (A2:
1999)
5.5.3 Motors
Mechanical power at shaft (kW) …………….. ..: N/A
5.5.4
Synchronous condensers
Reactive Power at terminals (var)……………….: N/A

TRF No. EN12601B


Page 28 of 45 Report No. JSH107110340-001
EN 12601: 2001
Appendix IEC 60034-1:2004
Clause Requirement - Test Result - Remark Verdict

5.6
Rated voltage
5.6.1
DC generators
For relatively small range of voltage, rated output N/A
and current applied at the highest voltage of the
range
unless otherwise specified (see also 6.3) N/A

5.6.2
AC generators
For a relatively small range of voltage, rated P
output and power factor applied at any voltage
within the range,
Unless otherwise specified (see also 7.3) N/A
5.7 Coordination of voltages and outputs
For machines with rated voltages above 1 kV, N/A
preferred rated voltages are selected according
to rated output as stated in table 1
5.8 Machines with more than one rating N/A

6. Site operating conditions


6.1 General
Unless otherwise specified machines shall be P
suitable for the following site operation
conditions. For site operating conditions deviating
from those values, corrections are given in clause
8
6.2 Altitude
Not exceed 1000 m above sea level. P
6.3 Maximum ambient air temperature
Not exceed 40 °C P
6.4 Minimum ambient air temperature
Not be less than –15 °C for any machine P
Not less than 0°C if one or more exceptions apply N/A
6.5 Water coolant temperature
Not exceeding +25°C and not less than + 5°C P
6.6 Storage and transport
Minimum specified temperature if different form N/A
that in 6.4(°C)
6.7 Purity of hydrogen coolant
Operation at hydrogen content ≥ 95% N/A

TRF No. EN12601B


Page 29 of 45 Report No. JSH107110340-001
EN 12601: 2001
Appendix IEC 60034-1:2004
Clause Requirement - Test Result - Remark Verdict

7. Electrical operating conditions


7.1 Electrical supply
Rated voltage of three-phase machines derived N/A
from IEC 60038
7.2 For and symmetry of voltages and currents
7.2.1 AC motors N/A
7.2.2 AC generators
Three-phase AC generators P
7.2.3 Three-phase synchronous machines
Maximum I2/IN value for continuous operation N/A
7.2.4 DC motors supplied from static power converters
Complying with requirements N/A
7.3 Voltage and frequency variations during operation
Figure 11 for generators and synchronous P
condensers
Figure 12 for motors N/A
Zones A and B apply only to voltages when d.c. N/A
machines directly connected to a normally
constant d.c. bus
Machine capable of performing its primary N/A
function within Zone A
Machine capable of performing its primary N/A
function with Zone B with deviations.
7.4 Three-phase a.c. machines operating on unearthed systems N/A
7.5 Voltage (peak and gradient) withstand levels N/A

8. Thermal performance and tests


8.1 Thermal class
A thermal class in accordance with IEC 62114 Class 130 P
shall be assigned to the insulation systems used
in machines
It is the responsibility of the manufacturer of the P
machine to interpret the results obtained by
thermal endurance testing according to the
appropriate part of IEC 60034-18
8.2 Reference coolant
The referemce coolant for a given method of cooling the machine is specified in
Table 4
Primary coolant Air
Method of cooling Indirect

TRF No. EN12601B


Page 30 of 45 Report No. JSH107110340-001
EN 12601: 2001
Appendix IEC 60034-1:2004
Clause Requirement - Test Result - Remark Verdict

Secondary coolant water


Table number 7
Table referred to in column 5 specifies limits of
Reference coolant
If a third collant is used, temperature rise shall be N/A
measured above the temperature of the primary
or secondary coolant as specified in Table 3.
8.3 Conditions for thermal tests
8.3.1 Electrical supply
Comply with requirements N/A
8.3.2 Temperature of machine before test
If the temperature of a winding is to be P
determined from the increase of resistance, the
temperature of the winding measured by
thermometer, when the resistance is measured
before the thermal test, shall be practically that of
the coolant at the time
When a machine is to be tested on a short-time N/A
rating (duty type S2) its temperature at the
beginning of the thermal test shall be within 5 K
of the temperature of the coolant
8.3.3 Temperature of coolant
A machine may be tested at any convenient value N/A
of coolant temperature.
Table 11 for indirect cooled windings P
Table 14 for direct cooled windings N/A
Temperature of primary coolant (ºC) 15
Temperature of secondary coolant (ºC) 15
8.3.4 Measurement of coolant temperature during test
Mean of the readings of the temperature P
detectors taken at equal intervals of time during
the last quarter of duration of the test
To reduce errors due to the time lag of the P
change of temperature of large machines
following variations in the temperture of the
coolant, all reasonable precautons shall be taken
to minimize such variations
8.3.4.1 Open machines or closed machines without heat exchangers (cooled by
surrounding ambient air or gas)

TRF No. EN12601B


Page 31 of 45 Report No. JSH107110340-001
EN 12601: 2001
Appendix IEC 60034-1:2004
Clause Requirement - Test Result - Remark Verdict

Several detectors placed at different points P


around and halfway up the machine at 1 m to 2 m
from it.
Each detector shall be protected from radiant P
heat and draughts
8.3.4.2 Machines cooled by air or gas from a remote source though ventilation ducts and
machines with separately mounted heat exchangers
Temperature of primary coolant measured where N/A
it enters the machine
8.3.4.3 Closed machines with machine-mounted or internal heat exchangers
Temperature of primary coolant measured where N/A
it enters the machine; for machines having water-
cooled or air-cooled heat exchangers,
temperature of secondary coolant measured
where it enters the heat exchanger
8.4 Temperature rise of a part of a machine
The temperature rise, ∆θ, of a part of a machine P
is the difference between the temperature of that
part measured by the appropriate method in
accordance with 8.5, and the temperature of the
coolant measured in accordance with 8.3.4
For comparison with the limits of temperature rise Table 7 P
(see Table 7 or Table 8) or of temperature (see
Table 12)
When possible, the temperature shall be N/A
measured immediately before the machine is
shut down at the end of the thermal test, as
described in clause 8.7
When this is not possible, e.g. when using the P
direct measurement of resistance method, see
8.6.2.3
For machines tested on actual periodic duty (duty N/A
types S3 to S8) the temperature at the end of the
test shall be taken as that at the middle of the
period causing the greatest heating in the last
cycle of operation 9but see also 8.7.3)
8.5 Methods of measurement of temperature
8.5.1 General
Recognized method used………………………….: Resistance method used P
8.5.2 Resistance method

TRF No. EN12601B


Page 32 of 45 Report No. JSH107110340-001
EN 12601: 2001
Appendix IEC 60034-1:2004
Clause Requirement - Test Result - Remark Verdict

The temperature of the windings is determined P


from the increase of the resistance of the
windings
8.5.3 Embedded temperature detector (ETD) method N/A
8.5.4 Thermometer method N/A
8.6 Determination of winding temperature
8.6.1 Choice of method
Rated output (P0) (W or VA)……………………..: 24KVA
In general, resistance method in accordance with P
7.5.1 applied
For P0 ≥ 5000 kW (or kVA), the ETD method N/A
shall be used unless otherwise agreed
For 200 kW (kVA) < P0 < 5000 kW (kVA), the N/A
resistance method used, unless the ETD method
is agreed
For P0 ≤ 200kW (kVA) the resistance method Resistance method used P
used, unless the superposition method is agreed
For P0 ≤ 600 W (VA), when the windings are non- N/A
uniform or severe complications are involved in
making the necessary connections, the
temperature may be determined by means of
thermometers. Temperature rise limits in
accordance with Table 7 shall apply
The thermometer method is recognized in the following cases:
a) when not practicable to determine the P
temperature rise by the resistance method;

b) Single layer windings, rotating or stationary; N/A

c) During routine tests on machines N/A


manufactured in large numbers

For a.c. stator windings having only one coil-side N/A


per slot, the ETD method shall not be used for
verifying compliance with this standard: the
resistance method shall be used
For other windings having one coil-side per slot N/A
and for end windings the ETD method shall not
be used for verifying compliance with tis standard

TRF No. EN12601B


Page 33 of 45 Report No. JSH107110340-001
EN 12601: 2001
Appendix IEC 60034-1:2004
Clause Requirement - Test Result - Remark Verdict

For windings of armatures having commutators N/A


and for field windings, except for field windings in
cylindrical rotors of synchronous machines, the
resistance method and the thermometer method
are recognized. The resistance method is
preferred but for stationary field windings of d.c.
machines having more than one layer the ETD
method may be used
8.6.2 Determination by resistance method
8.6.2.1 Measurement
One of the following methods shall be used P
Direct measurement at the beginning and the end N/A
of the test, using an instrument having a suitable
range
Measurement by d.c. current/voltage in the d.c N/A
windings, by measuring the current in and the
voltage across the winding, using an instrument
having a suitable range
Measurement by d.c. current/voltage in the a.c P
windings by injecting direct current into the
windings when de-energized
Superposition method N/A
8.6.2.2 Calculation See appended table P
Temperature (θ1) of winding (cold) at moment of
initial resistance measurement (ºC)………………:
Temperature (θa) of coolant at the end of test
(hot) (ºC)……………………………….……………:
Resistance (R1) of winding (cold) at temperature
θ1 (Ω)
Resistance (R2) of winding (hot) at temperature
θa (Ω)…………………………………………………:
Reciprocal of temperature coefficient (K)………..:
The temperature rise, θ2-θa, may be obtained P
from the equation:
θ2-θa=(R2 - R1) x (k + θ1)/ R1 + θ1 - θa
8.6.2.3 Correction for stopping time
8.6.2.3.1 General
Direct measurement resistance method requires P
a quick shutdown
8.6.2.3.2 Short stopping time

TRF No. EN12601B


Page 34 of 45 Report No. JSH107110340-001
EN 12601: 2001
Appendix IEC 60034-1:2004
Clause Requirement - Test Result - Remark Verdict

Initial reading obtained within time interval <30s P


specified in table 5…………………………………:
8.6.2.3.3 Extended stopping time
Initial reading obtained within twice the time N/A
interval specified in table 5……………………….:
8.6.2.3.4 Windings with one coil-side per slot
Direct measurement only used if machine comes N/A
to stop within time interval specified in table 5..
8.6.3 Determination by ETD method N/A
8.6.4 Determination by the thermometer method N/A
8.7 Duration of thermal test
8.7.1 Rating for continuous running duty
The test shall be continued until thermal P
equilibrium has been reached
8.7.2 Rating for short-time duty N/A
8.7.3 Rating for periodic duty N/A
8.7.4 Rating for non-periodic duty and for duty with N/A
discrete constant loads
8.8 Determination fo the thermal equivalent time N/A
constan for machines of duty type S9
8.9 Measurement of bearing temperature
Either the thermometer method or the ETD Thermometer method P
method may be used
The measuring point shall be as near as possible Ball bearing with inside P
to one of the two locations specified in Table 6 diameter less than 150mm
The thermal resistance between the temperature Air gaps are packed with P
detector and object whose temperature is to be thermally conducting paste
measured shall be minimized
8.10 Limits of temperature and of temperature rise
Limits given for operation under site operating P
conditions specified in clause 6 and at rating for
continuous running duty (reference conditions),
followed by rules for the adjustment of those
limits when operatng at site under other
conditions and on other ratngs.
Further rules give adjustments to the limits during P
thermal testing when conditions at the test site
differ from those at the operating site
The limits are stated relative to the reference P
coolant specified in Table 4

TRF No. EN12601B


Page 35 of 45 Report No. JSH107110340-001
EN 12601: 2001
Appendix IEC 60034-1:2004
Clause Requirement - Test Result - Remark Verdict

A rule is given to allow for the purity of hydrogen N/A


coolant
8.10.1 Indirect cooled windings
Temperature rises not exceed the limits given in Table 7 P
Table 7 (air coolant) or Table 8 (hydrogen
coolant)
temperature rise limit according to Table 7 or 8 Limit 80K (Class 130) P
(K) ……………………………………………:
Measured/calculated temperature rise according See appended table P
to 8.6 (K) ……………………………………………:
For other operating site conditions, for ratings N/A
other than continuous running duty, and for rated
voltages greater than 12000 V, the limits shall be
adjusted according to Table 9.
In the case of thermometer readings made in N/A
accordance with 8.6.1, the limit of temperature
rise shall be according to Table 7
If, for windings indirectly cooled by air, conditions N/A
at the test site differ form those at the operating
site, the adjusted limits given in Table 11 shall
apply at the test site
If the adjusted limits given in Table 11 lead to N/A
permissible temperatures at the test site which
the manufacturer considers to be excessive, the
testing procedure and the limits shall be agreed
No adjustments at the test site are given for N/A
windings indirectly cooled by hydrogen, because
it is very unlikely that they will be tested at rated
load anywhere other than at ehe operating site
8.10.2 Direct cooled windings
Temperatures not exceeding limits of table 12 N/A
For other operating site conditions limits adjusted N/A
according to table 13
For test site conditions differing from operating N/A
site conditions, limits adjusted according to table
14
If the adjusted limits given in table 14 lead to N/A
temperatures at the site which the manufacture
considers to be excessive, the testing procedure
and the limits shall be agreed
8.10.3 Adjustments to take account of hydrogen purity on test

TRF No. EN12601B


Page 36 of 45 Report No. JSH107110340-001
EN 12601: 2001
Appendix IEC 60034-1:2004
Clause Requirement - Test Result - Remark Verdict

Hydrogen content between 95 – 100 % N/A


8.10.4 Permanently short-circuited windings, magnetic cores and all structural
components (other than bearings) whether or not in contact with insulation
Temperature rise/temperature not be detrimental N/A
to the insulation of that part or to any other part
adjacent to it
8.10.5 Commutators and sliprings, open or enclosed and their brushes and brushgear
Temperature rise or temperature not be P
detrimental to the insulation of that part or any
adjacent part
The temperature rise or temperature not exceed P
that at which combination of brush grade and
commutator or slipring material can handle
current over full operating range

9. Other performance and tests


9.1 Routine tests N/A
9.2 Withstand voltage test
A test voltage applied between the windings P
under test and the frame of the machine, with the
core and the windings not under test connected
to the frame.
The withstand voltage test be carried out P
immediately after thermal test
Tests applied only to a new and completed P
machine with all its parts in place under
conditions equivalent to normal working
conditions
Tests shall be carried out at the manufacturer’s P
works or after erection on site
Polyphase machines with rated voltage above 1 P
kV having both ends of each phase individually
accessible, the test voltage be applied between
each phase and the frame, with the core and the
other phases and windings not under test
connected to the frame
The test voltage shall be of power frequency and P
as near as possible to a sine wave form.
The final value of the voltage shall be in See appended table P
accordance with Table 16.

TRF No. EN12601B


Page 37 of 45 Report No. JSH107110340-001
EN 12601: 2001
Appendix IEC 60034-1:2004
Clause Requirement - Test Result - Remark Verdict

However, for machines with a rated voltage 6 kV P


or greater, when power frequency equipment is
not available, then by agreement a d.c. test may
be carried out at voltage 1,7 times the r.m.s.
value given in Table 16
The test shall be commenced at a voltage not P
exceeding half of the full test voltage. The voltage
shall then be increased to the full value, steadily
or in steps of not more than 5% of the full value,
the time allowed for the voltage increase from
half to full value being not less than 10 s. The full
test voltage shall then be maintained for 1 min in
accordance with the value as specified in Table
16. There shall be no failure (see IEC 60060-1)
during this period
During the routine testing of quantity produced machines, the one-minute test
may be replaced:
for machines up to 200 kW (or kVA) and rated N/A
for UN<1 kV, by a test of approximately 1 s at
120% of the normal test voltage in Table 16

The high-voltage test at full voltage made on the N/A


windings on acceptance shall not be repeated.

Second test is made at the request of the N/A


purchaser, after further drying if considered
necessary, the test voltage shall be 80% of the
voltage specified in Table 16

To determine the test voltage from Table 16 for N/A


d.c. motors supplied by static power converters,
te direct voltage of the motor or the r.m.s. phase
to phase value of the rated alternating voltage at
the input terminals of the static power converter
shall be used, whichever is the greater
Completely rewound windings shall be tested at N/A
the full test voltage for new machines
When a user and a repair contractor have agreed to carry out withstand voltage
tests in cases where windings have been partially rewound or in the case of an
overhauled machine, the following procedure is recommended:

TRF No. EN12601B


Page 38 of 45 Report No. JSH107110340-001
EN 12601: 2001
Appendix IEC 60034-1:2004
Clause Requirement - Test Result - Remark Verdict

a) Partially rewound windings are tested at 75% N/A


of the test voltage for a new machine. Before the
test, the old part of the winding shall be carefully
cleaned and dried;

b) Overhauled machines, after cleaning and N/A


drying, are subjected to a test at a voltage equal
to 1,5 times the rated voltage, with a minimum of
1000V if the rated voltage is equal to or greater
than 100 V and a minimum of 500 V if the rated
voltage is less than 100 V
9.3 Occasional excess current
9.3.1 General
9.3.2 Generators
AC generators having rated outputs not Withstanding a current equal P
exceeding 1200 MVA shall be capable of to 1,5 times the rated current
withstanding a current equal to 1,5 times the for 60 s
rated current for not less than 30 s 52A
AC generators with rated outputs above 1200 N/A
MVA capable of withstanding a current equal to
1,5 times the rated current for at least 15s or a
period agreed.
9.3.3 AC motors (except commutator motors and permanent magnet motors) N/A
9.3.4 Commutator machines N/A
9.4 Momentary excess torque for motors
9.4.1 Polyphase induction motors and DC motors N/A
9.4.2 Polyphase synchronous motors N/A
9.4.3 Other motors N/A
9.5 Pull-up torque for motors N/A
9.6 Safe operating speed of cage induction motors N/A
9.7 Overspeed
Machines shall be disigned to withstand the Test with the engine, set the P
speeds specified in Table 18 engine speed at 1,2 times of
rated for 2 min
An over speed test is not normally considered P
necessary but can be performed when this is
specified and has been agreed. (For turbine-type
a.c. generators, see also IEC 60034-3.)

TRF No. EN12601B


Page 39 of 45 Report No. JSH107110340-001
EN 12601: 2001
Appendix IEC 60034-1:2004
Clause Requirement - Test Result - Remark Verdict

And overspeed test shall be considered as P


satisfactory if no permanent abnormal
deformation is apparent subsequently, and no
other weakness is detected which would prevent
the machine from operating normally, and
provided the rotor windings after the test comply
with the required dielectric tests.
The duration of any overspeed test shall be 2 min P
Due to settling of laminated rotor rims, laminated P
poles held by wedges or by bolts etc., a minute
permanent increase in the diameter is natural,
and not to be considered as an abnormal
deformation indicating that the machine is not
suitable for normal operation
During commissioning of a hydraulic-turbine N/A
driven synchronous generator, the machine shall
be driven at the speed it can reach with the
overspeed protection operating, so as to
ascertain that the balance is satisfactory up to
that speed
9.8 Short-circuit current for synchronous machines
Peak value of the short-circuit current (including r.m.s value of the short P
turbine-type machines not covered by IEC 60034- current:
3), in the case of short circuit on all phases between phase conductors
during operation at rated voltage, not exceed 15 168,7A
times the peak value or 21 times the r.m.s. value between phase conductor and
of the rated current neutral conductor: 112,8A
Verification may be carried out by calculation or Test at a voltage of the rated P
by means of a test at a voltage of 0,5 times the voltage
rated voltage or above
Rated torque(Nm)…………………………………..:
Excess torque (Nm)………………………………..:
9.9 Short-circuit withstand test for synchronous machines
Requested by purchaser N/A
Machine running on no-load with excitation N/A
corresponding to rated voltage, short circuit
maintained for 3s
No harmful deformation, dielectric strength test N/A
not resulting in breakdown.
9.10 Commutation test for commutator machines N/A
9.11 Total harmonic Distortion (THD) for synchronous machines

TRF No. EN12601B


Page 40 of 45 Report No. JSH107110340-001
EN 12601: 2001
Appendix IEC 60034-1:2004
Clause Requirement - Test Result - Remark Verdict

9.11.1 General
The requirement of this subclause apply only to <300kW P
synchronous machines having rated output of
300 kW (or kVA) or more, intended for
connection to power networks operating at
nominal frequencies of 16.67 Hz to 100 Hz
inclusive, with a view to minimizing interference
between power lines and adjacent circuits
9.11.2 Limits N/A
9.11.3 Tests N/A
THD limit (%) ……………………………………….: 5%
THD measured (%) ……………………………….:

10. Rating plates The generator is associated N/A


with relevant generating set

11. Miscellaneous requirements


11.1 Earthing of machines
Machine be provided with an earthing terminal or P
other device to permit the connection of
protective conductor or an earthing conductor
The symbol or legend shall identify P
Machine shall neither be earthed nor be provided with terminal when
1) Fitted with supplementary insulation, or N/A
2) Intended for assembly in apparatus having N/A
supplementary insulation, or;
3) Rated voltges up to 50 V a.c. and are intended N/A
for use on SELV (Safety Extra Low Voltage)
circuits.
In the case of machines having rated voltages P
greater than 50 V a.c. or 120 V d.c., but not
exceeding 1000 V a.c. or 1500 V d.c., the
terminal for the earth conductor shall be situated
in the vicinity of the terminals for the line
conductors being placed in the terminal box, if
one is provided
Machines having rated outputs in excess of 100 N/A
kW (or kVA) shall have in addition an earth
terminal fitted on the frame

TRF No. EN12601B


Page 41 of 45 Report No. JSH107110340-001
EN 12601: 2001
Appendix IEC 60034-1:2004
Clause Requirement - Test Result - Remark Verdict

Machines for rated voltages greater than 1000 V N/A


a.c. or 1500 V d.c. shall have an earth terminal
on the frame, for example an iron strap, and in
addition, a means inside the terminal box for
connecting a conducting cable sheath, if any
The earth terminal shall be designed to ensure a P
good connection with the earth conductor without
any damage to the conductor or terminal.
Accessible conducting parts which are not part of N/A
the operating circuit shall have a good electrically
conducting connection with each other and with
the earth terminal
When all bearings and the rotor winding of a N/A
machine are insulated, the shaft shall be
electrically connected to the earth terminal,
unless the manufacturer and the purchaser agree
to alternative means of protection
When an earth terminal is provided in the P
terminal box, it shall be assumed that the earth
conductor is made of the same metal as the live
conductors
When an earth terminal is provided on the frame, N/A
the earth conductor may, by agreement, be made
of another metal (e.g. steel). In this case, in
designing the terminal, proper consideration shall
be given to the conductivity of the conductor
The earth terminal shall be designed to P
accommodate an earth conductor of cross-
sectional area in accordance with Table 19
If an earth conductor larger than the size given in N/A
the table is used, it is recommended that it should
correspond as nearly as possible to one of the
other sizes listed
For other cross-sectional areas of live conductors, the earth or protective
conductor shall have a cross-sectional area at least equivalent to :

that of the live conductor for cross-sectional P


2
areas less than 25 mm ;
2
25 mm for cross-sectional areas between 25 N/A
2 2
mm and 50 mm ;

TRF No. EN12601B


Page 42 of 45 Report No. JSH107110340-001
EN 12601: 2001
Appendix IEC 60034-1:2004
Clause Requirement - Test Result - Remark Verdict

50% of that of the live conductor for cross- N/A


2
sectional areas exceeding 50 mm

The earth terminal shall be identified in P


accordance with IEC 60445
11.2 Shaft-end key(s)
When a machine shaft end is provided with one Associated with the output N/A
or more keyways, each shall be provided with a shaft of engine driven
full key of normal shape and length.

12. Tolerances
Tolerances shall be as specified in Table 20 P

13. Electromagnetic compatibility (EMC) Generating sets N/A

14. Safety
14.1 Rotating complying with the requirements of IEC P
60204-1 or IEC 60204-11
In the case of rotating machines incorporated in N/A
household and similar electrical appliances, IEC
60335-1
Unless otherwise specified in this standard, and N/A
be designed and constructed as far as possible in
accordance with internationally accepted best
design practice, appropriate to the application

TRF No. EN12601B


Page 43 of 45 Report No. JSH107110340-001
EN 12601: 2001
Appendix IEC 60034-1:2004
Clause Requirement - Test Result - Remark Verdict

8.6 Appended Table: temperature rise measurements


t1 (°C) ............................................................. : 16,0
t2 (°C) ............................................................. : 15,7
L1-N................................................................. : 231,0V 33,39A
L2-N................................................................. : 224,9V 33,11A
L3-N................................................................. : 228,1V 33,987A
Output.............................................................. : 19,35KW
Frequency........................................................ : 50,3Hz
operating period (min) .................................... : Steady condition >60min
temperature rise dT of part/at: dT (K) Required dT (K)
Control panel 2,7 35
Generator housing 13,6 ---
Internal wire 3,9 50
Muffler protective frame 38,7°C ≤ 90°C
Circuit breaker 2,2 ---
Generator winding temperature rise measurements:
temperature rise dT of winding: R1 (Ω) R2 (Ω) dT (K) allowed dT Insulation
(K) class
AC winding(L-L) 0,470 0,566 51,5 80 130

9.2 TABLE: withstand voltage test P


test voltage applied between: test voltage (V) Breakdown
Basic insulation (between the windings under test and frame of 1800 No
the machine, with the core and the windings not under test
connected to the frame)

TRF No. EN12601B


Page 44 of 45 Report No. JSH107110340-001
EN 12601: 2001
Appendix ISO 8528-3: 2005
Clause Requirement - Test Result - Remark Verdict

4. Other requirements and additional regulations P


5 Rating
5.1 General
The generator rating class shall be specified in P
accordance with the requirements of IEC 60034-
1
In case of generators for RIC engine driven S1 P
generating sets, the continuous rating (duty type
S1) or rating with discrete constant loads (duty
type S10) shall be specified.
5.2 Basic continuous rating (BR)
For the purposes of this part of ISO 8528, the P
maximum continuous rating based on duty type
S1 is called the basic continuous rating (BR).
5.3 Peak continuous rating (PR) N/A
6 Limits of temperature and temperature rise
6.1 Basic continuous rating
The generator shall be capable of delivering its See Appendix IEC 60034-1 P
BR over the whole range of operating conditions
(e.g. minimum to maximum coolant temperature
with total temperature) not exceeding 40°C plus
the temperature rises specified in Table 1 of IEC
60034-1
6.2 Peak continuous rating N/A
7 Rated power and speed characteristics P
8 Voltage characteristics P
9 Parallel operation N/A
10 Special load condition See Appendix IEC 60034-1 P
11 Effect of electromechanical frequency of N/A
vibrations when sets operate in parallel
12 Asynchronous generators with excitation N/A
equipment
13 Operating limit values
Four performance classes are defined to G1 P
describe the generator characteristics
Rated range of voltage setting Limit: ±5% N/A
Steady-state voltage deviation Limit: ±5% P
Transient voltage deviation on load increase Limit: -30% P
Transient voltage deviation on load decrease Limit: 35% P
Voltage recovery time <2,5s P
Voltage unbalance Limit: 1% P

TRF No. EN12601B


Page 45 of 45 Report No. JSH107110340-001
EN 12601: 2001
Appendix ISO 8528-3: 2005
Clause Requirement - Test Result - Remark Verdict

14 Rating plate The generator is associated N/A


with relevant generating set

TRF No. EN12601B

You might also like