0% found this document useful (0 votes)
12 views1 page

LAPP2

The test certificate S256J25, dated 25-Oct-25, confirms the specifications and performance of the ÖLFLEX® UNIPLUS 1X1.5 GY product, including conductor type, insulation color, and various electrical and mechanical properties. All inspection parameters met or exceeded the specified requirements, indicating the product's compliance with relevant standards. The testing was conducted by Kunal Singh and reviewed by Vikash Jain at LAPP India Pvt, Ltd.

Uploaded by

info1.progrus
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
12 views1 page

LAPP2

The test certificate S256J25, dated 25-Oct-25, confirms the specifications and performance of the ÖLFLEX® UNIPLUS 1X1.5 GY product, including conductor type, insulation color, and various electrical and mechanical properties. All inspection parameters met or exceeded the specified requirements, indicating the product's compliance with relevant standards. The testing was conducted by Kunal Singh and reviewed by Vikash Jain at LAPP India Pvt, Ltd.

Uploaded by

info1.progrus
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

.

Test Certificate
No : S256J25
Date: 25-Oct-25

Work Order Number 250000308245


Article Number 4520061U
Product Description ÖLFLEX® UNIPLUS 1X1.5 GY

Sr. no. Inspection parameter Specification UOM Observations


1 Conductor Annealed Bare Copper - Annealed Bare Copper
2 Class of Conductor Class 5 Class 5
3 Insulation Color As per IS-694:2010 - GREY
4 Area of conductor 1.50 SQ.mm. 1.50
5 Max. Conductor Resistance at 20oC 13.3 Ώ / Km 13.17
6 Core Diameter Max. 3.4 mm 2.83
7 Nominal Wall Thickness 0.60 mm 0.66
8 Minimum Wall Thickness 0.44 mm 0.58
9 Spark Test (Online Test) As per IS-694:2010 Kv Withstood
10 Oxygen Index Test Min. 29 % 29.9
o
11 Temperature Index Min. 250 C 310
12 Tensile Strength Min . 10.0 N/mm 2 17.4
13 Elongation at Break Min. 150 % 236.0
14 Shrinkage Test Max. 6.0 % 1
15 Heat Shock Test No Sign of Cracks or Scales - No Cracks or Scale Observed
16 Hot Deformation Test Max. 65 % 32.3
17 Flame Test - Uncharred length from Top Min 50.0 mm 388
18 Period of burning Max. 60 Second 5.8
19 AC High Voltage Test in Water Bath shall withstand 3 KV/5 min KV / Min Withstood
20 Volume Resistivity at Ambient Temp. Min. 1x1012 Ώ - Cm 387.51 X 1012
21 Volume Resistivity at Rated Temp. Min. 1x10 9
Ώ - Cm 1603.27 X 109
22 IR Constant at Ambient Temp. Min. 3.67 MΏ - Km 1419.93
23 IR Constant at Rated Temp. Min. 0.004 MΏ - Km 5.87

AC Water Immersion Test after 24 hrs conditioning at


24 Shall Withstand with (A.C) 6KV/5 min. KV / Min Withstood
60+2oC

Insulation Type-D FR PVC

Tested By Reviewed By
Kunal Singh Vikash Jain

LAPP India Pvt, Ltd.


Plot No. E-16 to 19
AKVN Industrial Area
Village - Pilukhedi Tehsil Narsingarh
Dist. Rajgarh - 465667 India
Tel. : 07375 - 308100
www.lappindia.com