90 1 2007 Ce CP
90 1 2007 Ce CP
ASHRAE ADDENDA
Energy Standard for
Buildings Except
Low-Rise
Residential Buildings
Approved by the ASHRAE Standards Committee on June 26, 2010; by the ASHRAE Board of Directors on
June 30, 2010; by the IES Board of Directors on June 23, 2010; and by the American National Standards Insti-
tute on July 1, 2010.
These addenda were approved by a Standing Standard Project Committee (SSPC) for which the Standards
Committee has established a documented program for regular publication of addenda or revisions, including
procedures for timely, documented, consensus action on requests for change to any part of the standard. The
change submittal form, instructions, and deadlines may be obtained in electronic form from the ASHRAE Web
site (www.ashrae.org) or in paper form from the Manager of Standards.
The latest edition of an ASHRAE Standard may be purchased on the ASHRAE Web site (www.ashrae.org) or
from ASHRAE Customer Service, 1791 Tullie Circle, NE, Atlanta, GA 30329-2305. E-mail:
orders@ashrae.org. Fax: 404-321-5478. Telephone: 404-636-8400 (worldwide), or toll free 1-800-527-4723
(for orders in US and Canada). For reprint permission, go to www.ashrae.org/permissions.
© Copyright 2010 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc.
ISSN 1041-2336
*Denotes members of voting status when the document was approved for publication.
© American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org).
For personal use only. Additional reproduction, distribution, or transmission in either print or
digital form is not permitted without ASHRAE's prior written permission.
SPECIAL NOTE
This American National Standard (ANS) is a national voluntary consensus standard developed under the auspices of the American
Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE). Consensus is defined by the American National Standards
Institute (ANSI), of which ASHRAE is a member and which has approved this standard as an ANS, as “substantial agreement reached by
directly and materially affected interest categories. This signifies the concurrence of more than a simple majority, but not necessarily unanimity.
Consensus requires that all views and objections be considered, and that an effort be made toward their resolution.” Compliance with this
standard is voluntary until and unless a legal jurisdiction makes compliance mandatory through legislation.
ASHRAE obtains consensus through participation of its national and international members, associated societies, and public review.
ASHRAE Standards are prepared by a Project Committee appointed specifically for the purpose of writing the Standard. The Project
Committee Chair and Vice-Chair must be members of ASHRAE; while other committee members may or may not be ASHRAE members, all
must be technically qualified in the subject area of the Standard. Every effort is made to balance the concerned interests on all Project
Committees.
The Manager of Standards of ASHRAE should be contacted for:
a. interpretation of the contents of this Standard,
b. participation in the next review of the Standard,
c. offering constructive criticism for improving the Standard, or
d. permission to reprint portions of the Standard.
DISCLAIMER
ASHRAE uses its best efforts to promulgate Standards and Guidelines for the benefit of the public in light of available information and
accepted industry practices. However, ASHRAE does not guarantee, certify, or assure the safety or performance of any products, components,
or systems tested, installed, or operated in accordance with ASHRAE’s Standards or Guidelines or that any tests conducted under its
Standards or Guidelines will be nonhazardous or free from risk.
(This foreword is not part of this standard. It is merely 2. conference, meeting rooms, and training rooms,
informative and does not contain requirements necessary 3. employee lunch and break rooms.,
for conformance to the standard. It has not been 4. storage and supply rooms between 50 ft2and 1000
processed according to the ANSI requirements for a ft2,
standard and may contain material that has not been 5. rooms used for document copying and printing,
subject to public review or a consensus process. 6. office spaces up to 250 ft2,
Unresolved objectors on informative material are not 7. restrooms
offered the right to appeal at ASHRAE or ANSI.) 8. dressing, locker, and fitting rooms.
9.4.1.2 Space Control. Each space enclosed by ceiling a. The controlled lighting shall have at least one control step
height partitions shall have at least one control device to inde- between 30% and 70% (inclusive) of full lighting power
pendently control the general lighting within the space. Each in addition to all off.
manual device shall be readily accessible and located so the Exception to 9.4.1.2 (a):
occupants can see the controlled lighting All controlled light- a. Lights in corridors, electrical/mechanical rooms,
ing shall meet the following requirements: public lobbies, restrooms, stairways, and storage
rooms
a. The controlled lighting shall have at least one control step b. Spaces with only one luminaire with rated input
between 30% and 70% (inclusive) of full lighting power power less than 100 W.
in addition to all off. c. Spaces types with allowed lighting power densities
Exception to 9.4.1.2 (a): allowance of less than 6 W/m2 (see table 9.6.1).
a. Lights in corridors, electrical/mechanical rooms,
public lobbies, restrooms, stairways, and storage a.b. An occupant sensor shall be installed that automatically
rooms turns lighting off within 30 minutes of all occupants leav-
b. Spaces with only one luminaire with rated input ing a space in
power less than 100 W. 1. classrooms and lecture halls,
c. Spaces types with allowed lighting power densities 2. conference, meeting rooms, and training rooms,
allowance of less than 0.6 W/ft2 (see table 9.6.1). 3. employee lunch and break rooms.,
4. storage and supply rooms up to 15.24 m2 and 304.8
a.b. An occupant sensor or a timer switch shall be installed m2,
that automatically turns lighting off within 30 minutes of 5. rooms used for document copying and printing,
all occupants leaving a space in
6. office spaces up to 76.2 m2,
1. classrooms and lecture halls, 7. restrooms
8. dressing, locker, and fitting rooms. d. Lighting required for 24-hour operation
Exceptions to 9.4.1.2 (ba):
b.c. For spaces not included in 9.4.1.2(b), each control device
a. Spaces with multi-scene lighting control systems
shall be activated either manually by an occupant or auto-
b. Shop and laboratory classrooms matically by sensing an occupant. Each control device
c. Spaces where an automatic shutoff would endanger shall control a maximum of 2500 ft2 area for a space
the safety or security of the room or building occu- 10,000 ft2 or less and a maximum of 10,000 ft2 area for a
pant(s) space greater than 10,000 ft2. The occupant shall be able
to override any time-of-day scheduled shutoff control for Heat Pumps with Heat Recovery capability; the EER and
no more than two hours. IEER values will be 0.2 lower due to the pressure drop in the
refrigerant system to achieve heat recovery operation. Higher
(This foreword is not part of this standard. It is merely IEER levels are being proposed as these products are primar-
informative and does not contain requirements necessary ily designed to operate in zoning applications and at part-load
for conformance to the standard. It has not been conditions. The first phase of IEER values is effective immedi-
processed according to the ANSI requirements for a ately, while the second phase will become effective on July 1,
standard and may contain material that has not been 2012.
subject to public review or a consensus process.
Note: In this addendum, changes to the current standard
Unresolved objectors on informative material are not
are indicated in the text by underlining (for additions) and
offered the right to appeal at ASHRAE or ANSI.)
strikethrough (for deletions) unless the instructions specifi-
FOREWORD cally mention some other means of indicating the changes.
TABLE 6.8.1M Electrically Operated Variable Refrigerant Flow Air-to-Air and Applied Heat Pumps— Minimum
Efficiency Requirements
TABLE 6.8.1M Electrically Operated Variable Refrigerant Flow Air-to-Air and Applied Heat Pumps— Minimum
Efficiency Requirements
TABLE 6.8.1M Electrically Operated Variable Refrigerant Flow Air-to-Air and Applied Heat Pumps— Minimum
Efficiency Requirements
<65,000 Btu/h
--- VRF Multi-split System 7.7 HSPF
(cooling capacity)
VRF Multi-split system
47ºF db/43ºF
3.3 COP
≥65,000 Btu/h and wb outdoor air
<135,000 Btu/h ---
(cooling capacity)
2.25 COP
VRF Air Cooled 17ºF db/15ºF wb out-
AHRI 1230
(heating mode) door air
VRF Multi-split System
47ºF db/43ºF
3.2 COP
wb outdoor air
≥135,000 Btu/h
---
(cooling capacity)
2.05 COP
17ºF db/15ºF wb out-
door air
<135,000 Btu/h VRF Multi-split System
--- 4.2 COP
VRF Water source (cooling capacity) 68ºF entering water
AHRI 1230
(heating mode) ≥135,000 Btu/h VRF Multi-split System
--- 3.9 COP
(cooling capacity) 68ºF entering water
<135,000 Btu/h VRF Multi-split System
VRF Groundwater --- 3.6 COP
(cooling capacity) 50ºF entering water
source AHRI 1230
(heating mode) ≥135,000 Btu/h VRF Multi-split System
--- 3.3 COP
(cooling capacity) 50ºF entering water
<135,000 Btu/h VRF Multi-split System
--- 3.1 COP
VRF Ground source (cooling capacity) 32ºF entering water
AHRI 1230
(heating mode) ≥135,000 Btu/h VRF Multi-split System
--- 2.8 COP
(cooling capacity) 32ºF entering water
Add the following reference to Section 12 (under Air- Add definition for VRF systems in Section 3 as follows:
Conditioning, Heating, and Refrigeration Institute)
Variable Refrigerant Flow (VRF) System. An engineered
Modify the Standard as follows (SI Units) direct expansion (DX) multi-split system incorporating at
least one variable capacity compressor distributing refrigerant h. Table 6.8.1 K-Heat Transfer Equipment
through a piping network to multiple indoor fan coil units each i. Table 6.8.1 L- Variable Refrigerant Flow Air Condition-
capable of individual zone temperature control, through inte- ers
gral zone temperature control devices and common commu-
nications network. Variable refrigerant flow utilizes three or j. Table 6.8.1 M- Variable Refrigerant Flow Air-to-Air and
more steps of control on common, inter-connecting piping. Applied Heat Pumps
TABLE 6.8.1M Electrically Operated Variable Refrigerant Flow Air-to-Air and Applied Heat Pumps — Minimum
Efficiency Requirements
TABLE 6.8.1M Electrically Operated Variable Refrigerant Flow Air-to-Air and Applied Heat Pumps — Minimum
Efficiency Requirements
VRF Multi-split
<19 kW All 3.81 SCOPC
System
3.22 COPC
Electric Resistance VRF Multi-split 3.60 ICOP
≥19 kW and <40 kW
(or none) System 3.78 ICOP (as of 7/1/
2012)
3.16 COPC
VRF Multi-split Sys-
Electric Resistance 3.55 ICOP
≥19 kW and <40 kW tem with Heat Recov-
(or none) 3.72 ICOP (as of 7/1/
ery
2012)
3.11 COPC
≥40 kW Btu/h and Electric Resistance VRF Multi-split 3.46 ICOP
VRF Air Cooled, <70 kW (or none) System 3.60 ICOP (as of 7/1/
AHRI 1230
(cooling mode) 2012)
3.05 COPC
VRF Multi-split
Electric Resistance 3.40 ICOP
≥40 kW and <70 kW System with Heat
(or none) 3.55 ICOP (as of 7/1/
Recovery
2012)
2.78 COPC
Electric Resistance VRF Multi-split 3.11 ICOP
≥70 kW
(or none) System 3.22 ICOP (as of 7/1/
2012)
2.73 COPC
VRF Multi-split Sys-
Electric Resistance 3.05 ICOP
≥70 kW tem with Heat
(or none) 3.16 ICOP (as of 7/1/
Recovery
2012)
VRF Multi-split
<19 kW All systems 3.52 COPC
30ºC entering water
VRF Multi-split sys-
tems with Heat
<19 kW All 3.46 COPC
Recovery
30ºC entering water
VRF Multi-split Sys-
≥19 kW and
All tem 3.52 COPC
<40 kW
30ºC entering water
VRF Water source
VRF Multi-split Sys- AHRI 1230
(cooling mode)
≥19 kW and tem with Heat
All 3.46 COPC
<40 kW Recovery
30ºC entering water
VRF Multi-split
≥40 kW All System 2.93 COPC
30ºC entering water
VRF Multi-split Sys-
tem with Heat
≥40 kW All 2.87 COPC
Recovery
30ºC entering water
TABLE 6.8.1M Electrically Operated Variable Refrigerant Flow Air-to-Air and Applied Heat Pumps — Minimum
Efficiency Requirements
VRF Multi-split
<40 kW All System 4.75 COPC
15ºC entering water
VRF Multi-split Sys-
tem with Heat
<40 kW All 4.69 COPC
Recovery
VRF Groundwater 15ºC entering water
source AHRI 1230
(cooling mode) VRF Multi-split
≥40 kW All System 4.04 COPC
15ºC entering water
VRF Multi-split Sys-
tem with Heat
≥40 kW All 3.98 COPC
Recovery
15ºC entering water
TABLE 6.8.1M Electrically Operated Variable Refrigerant Flow Air-to-Air and Applied Heat Pumps — Minimum
Efficiency Requirements
VRF Multi-split
<40 kW All System 3.93 COPC
25ºC entering water
VRF Multi-split Sys-
tem with Heat
<40 kW All 3.87 COPC
Recovery
VRF Ground source 25ºC entering water
AHRI 1230
(cooling mode) VRF Multi-split
≥40 kW All System 3.22 COPC
25ºC entering water
VRF Multi-split Sys-
tem with Heat
≥40 kW All 3.16 COPC
Recovery
25ºC entering water
<19 kW VRF Multi-split
--- 2.25 SCOPH
(cooling capacity) System
VRF Multi-split
system
8.3ºC db/6.1ºC 3.3 COPH
≥19 kW and
wb outdoor air
<40 kW ---
(cooling capacity)
2.25 COPH
VRF Air Cooled -8.3ºC db/
AHRI 1230
(heating mode) -9.4ºC wb outdoor air
VRF Multi-split
System
8.3ºC db/6.1ºC 3.2 COPH
≥40 kW wb outdoor air
---
(cooling capacity)
2.05 COPH
-8.3ºC db/
-9.4ºC wb outdoor air
VRF Multi-split
<40 kW (cooling
--- System 4.2 COPH
capacity)
VRF Water source 20ºC entering water
AHRI 1230
(heating mode) VRF Multi-split
≥40 kW (cooling
--- System 3.9 COPH
capacity)
20ºC entering water
VRF Multi-split Sys-
<40 kW (cooling
--- tem 3.6 COPH
VRF Groundwater capacity)
10ºC entering water
source AHRI 1230
VRF Multi-split Sys-
(heating mode) ≥40 kW (cooling
--- tem 3.3 COPH
capacity)
10ºC entering water
VRF Multi-split Sys-
<40 kW (cooling
--- tem 3.1 COPH
capacity)
VRF Ground source 0ºC entering water
AHRI 1230
(heating mode) VRF Multi-split Sys-
≥40 kW (cooling
--- tem 2.8 COPH
capacity)
0ºC entering water